Instrument Transformer, Div of GE 3VTL460 Data Sheet

GE
Grid Solutions
Model 3VTL460
3-Phase Voltage Transformer For Line-to-Line Connection
Frequency
60 Hz.
Standard Secondary Voltage
120 Volts line-to-line
Insulation Level
600 Volt, 10 kV BIL full wave.
Accuracy Class: (Per Phase)
0.6 W, 1.2 X at 60 Hz.
Thermal Rating: (Per Phase)
The primary and secondary terminals are No. 8-32 screws into 1/2” deep brass inserts and fitted with one lockwasher and flatwasher.
Approximate weight 24 lbs.
Clear Plastic Cover
REGULATORY AGENCY APPROVALS
Manufactured to meet the requirements of ANSI/IEEE C57.13. Classified by U.L. in accordance with IEC 44-1
Model 3VTL460
© Copyright 2017. General Electric Company
Model 3VTL460 is an assembly of three transformers in one case.
The core and coil assembly is encased in a thermoplastic shell and filled with resin
These transformers are designed for operation line to line. All terminals are accessible.
Spacing between live parts per U.L. 1558.
See page 7 of this section for a circle diagram for the estimation of the errors for other than rated burdens. See page 27 in this section
for a description of its use.
The transformer has a clear plastic cover.
Connection Diagram
ITI-Model-3VTL460-Flyer-EN-2017-11-Grid-AIS-1411.
and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.