![](/html/bd/bd1f/bd1f1ca35acf425e754c3bbc22bef7aaf2f5d4a158e323215c7813dbd0ba07fa/bg1.png)
GE
Energy Connections
Model 3VT472
3 Phase Voltage Transformer
Frequency
60 Hz.
Standard Secondary Voltage
120 Volts line-to-line
Insulation level
600 Volt, 10 kV BIL full wave.
Accuracy Class: (Per Phase)
± 1% @ 5 VA
Thermal Rating: (Per Phase)
40 VA at 30oC. amb., 27 VA at 55oC. amb.
Terminals are brass screws No. 8-32 with
one lockwasher and flatwasher.
Approximate weight 8 lbs.
Clear Plastic Cover
![](/html/bd/bd1f/bd1f1ca35acf425e754c3bbc22bef7aaf2f5d4a158e323215c7813dbd0ba07fa/bg2.png)
Model 3VT472
The core and coil assembly is encased in a thermoplastic shell and filled with resin.
Only ground XO/HO terminals if source is 3 phase, 4 wire effectively grounded.
These transformers are designed for application to Y connected systems.
Model 3VT472 available with primary and/or secondary fuses
Primary fuses are type CC rejection style. Secondary fuses are type BBS
Dimension tolerance + 0.050
Each transformer has a clear plastic cover.
Grid-AIS-L4-ITI_Model_3VT472-1569-2017_05-EN. © Copyright 2017. General Electric Company
and Instrument Transformers LLC reserve the right to change specifications of described
products at any time without notice and without obligation to notify any person of such changes.