Model 3VT468
3 Phase Voltage Transformer
Frequency
60 Hz.
Standard Secondary Voltage
120 Volts
Insulation Level
600 Volt, 10 kV BIL full wave.
Accuracy Class: (Per Phase)
± 0.6% @ 7.5 VA
Thermal Rating: (Per Phase)
75 VA at 30 °C. amb., 50 VA at 55 °C. amb.
Terminals are brass screws No. 8-32 with
one lockwasher and flatwasher.
Approximate weight 8 lbs.
Clear Plastic Cover
![](/html/ce/ced1/ced1f0cf31efd1b78b92288965c17908a9551b4f9277983082ede23d0dc39c09/bg2.png)
Model 3V Model 3VT468
The core and coil assembly is encased in a thermoplastic shell and filled with resin.
These transformers are designed for application to Y connected systems.
Only ground XO/HO terminals if source is 3 phase, 4 wire effectively grounded.
Primary fuses are type CC rejection style.
It is desirable to use a 0.80 amp BBS type or equal fuse in the secondary to protect the transformer.
Models designed specifically for 50 Hz operation are available with reduced performance. Consult factory for details.
Supplied with a clear plastic cover.