GE
Grid Solutions
Model 2VT469
3-Phase Voltage Transformer
Frequency
60 Hz.
Standard Secondary Voltage
120 Volts
Insulation Level
600 Volt, 10 kV BIL full wave.
Accuracy Class
+ 1% at all burdens up to 5 VA at 1.0
and 0.95 P.F.
Thermal Rating: (Per Phase)
40 VA at 30oC. amb., 27 VA at 55oC. amb.
Terminals are No. 6-32 screws with one
lockwasher and one flatwasher.
Approximate weight 4.5 lbs.
REGULATORY AGENCY APPROVALS
Manufactured to meet the requirements of ANSI/IEEE C57.13.
Classified by U.L. in accordance with IEC 44-1

These transformers are designed for operation line-to-line. They
Model 2VT469
and Instrument Transformers LLC reserve the right to change specifications of described products at
Characteristics
The core and coil assembly is encased in a thermoplastic shell
and filled with resin.
may also be operated line-to-ground or line-to-neutral at
reduced voltage voltage, (58% of rated volts). It is desirable to
use a 0.40 amp fuse in the secondary to protect the
transformer.
With two exceptions these transformer are ANSI C57.13
group 1. Those marked * are group 2.
Models designed specifically for 50 Hz operation are available
with reduced performance. Please consult factory for details.
Model 2VT469 is an assembly of two transformers in one case
with all terminals accessible, for open delta connection.
Each transformer has a clear plastic cover.
Connection Diagram
ITI_Model_2VT469-Flyer-EN-2017-11-Grid-AIS-1567. © Copyright 2017. General Electric Company
any time without notice and without obligation to notify any person of such changes.