Instrument Transformer, Div of GE 2VT460 Data Sheet

GE
Energy Connections
3 Phase Voltage Transformer
Frequency
60 Hz.
Standard Secondary Voltage
120 Volts
Insulation Level
600 Volt, 10 kV BIL full wave.
Accuracy Class: (Per Phase)
0.6 W, 1.2 X
Thermal Rating: (Per Phase)
150 VA at 30 oC. amb., 100 VA at 55
Terminals are brass screws No. 8-32 with one lockwasher and flatwasher.
Approximate weight 15.5 lbs.
Clear Plastic Cover
oC. amb.
Model 2VT460
The Core and coil assembly is encased in a thermoplastic shell and filled with resin.
Transformers are designed for open delta connection.
Primary fuses are type CC rejection style. It is desirable to use a 1.6 amp BBS type or equal fuse in secondary to protect the transformer.
Models designed specifically for 50 Hz operation are available with reduced performance. Consult factory for details.
This page contains a circle diagram for the estimation of the errors or other than rated burdens.
Grid-AIS-L4-ITI_Model_2VT460-1409-2017_05-EN. © Copyright 2017. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.