Model 200WP Wound Primary &
Model 200X Auxiliary Transformer
Current Transformers
Frequency
50-400 Hz.
Insulation Level
0.6 kV, BIL 10 kV full wave.
Continuous Thermal
Current Rating Factor
1.33 at 30°C. amb., 1.0 at 55 °C. amb.
Terminals are brass screws No. 10-32
with one flatwasher, lockwasher and
regular nut, for ratios up to 25:5 and 1/420 studs for higher ratios.
Approximate weight 46 lbs.
The Model 200WP is a low ratio wound primary current transformer, suitable for primary
currents up to 50 amperes. The table lists the most common current ratings. Other ratios are available.
* 1/4-20 stud terminals
Model 200WP Wound Primary & Model 200X Auxiliary Transformer
ANSI Metering Class: 0.3 B1.8
The Model 200X is an auxiliary transformer for use in the secondary of main current transformers to change the ratio for metering
applications.
Since the Model 200X is used in the secondary of another current transformer it has no voltage rating. It is given a 2,500 volt 60 Hz high
potential test. It is designed to be used on circuits not to exceed 600 volts to ground or between winding.