Instrument Transformer, Div of GE 188 Data Sheet

GE
Energy Connections
Model 188
Current Transformer Auxiliary Transformer
Application
For use in the secondary of current transformers to change ratio for metering applications.
Frequency
50-400 Hz.
600 Volt, 10 kV BIL full wave.
Continuous Thermal Current Rating Factor
1.5 at 30 °C. amb., 1.0 at 55 °C. amb.
Terminals are No. 10-32 brass binding headscrews.
Approximate weight 10 lbs.
** The circuits of up to six secondaries may be totalized. Equal or unequal line current transformers can be summed with this transformer. Advise the ratios of the line current transformers to be totalized for unequal ratios. Output terminals are X1-X2.
Model 188 Auxiliary Transformer
ANSI Metering Class: 0.3 B0.2 * Exception: These ratios have no accuracy ratings.
The Model 188 is a low ratio auxiliary current transformer, suitable for primary currents up to 15 amperes. The table on the previous page lists the most common current ratings. The transformer core and coil are encapsulated in a polyurethane resin, which also secures the steel mounting base.
Since the Model 188 is used in the secondary of another transformer it has no voltage rating. It is given a 2500 volt 60 Hz high potential test. It is designed to be used on circuits not to exceed 600 volts to ground or between windings.
Grid-AIS-L4-ITI_Model_188-1268-2017_05-EN. © Copyright 2017. General Electric Company and Instrument Transformers LLC reserve the right to change specifications of described products at any time without notice and without obligation to notify any person of such changes.
Loading...