Instek PSW30-36, PSW80-13.5, PSW160-7.2, PSW250-4.5, PSW800-1.44 User's Manual

...
Multi-Range DC Power Supply
PSW Series
USER MANUAL
GW INSTEK PART NO. 82SW-80400MH1
ISO-9001 CERTIFIED MANUFACTURER
This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of Good Will company.
The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the rights to change specification, equipment, and maintenance procedures at any time without notice.
Good Will Instrument Co., Ltd. No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.
SAFETY INSTRUCTIONS
Table of Contents
SAFETY INSTRUCTIONS ................................................... 5
GETTING STARTED ........................................................... 9
PSW Series Overview ........................... 10
Appearance .......................................... 15
Theory of Operation ............................. 22
OPERATION .................................................................... 35
Set Up .................................................. 37
Basic Operation ................................... 57
Parallel / Series Operation ................... 72
Test Scripts .......................................... 87
CONFIGURATION ........................................................... 96
Configuration ....................................... 97
ANALOG CONTROL ....................................................... 116
Analog Remote Control Overview ....... 117
Remote Monitoring ............................ 133
COMMUNICATION INTERFACE ..................................... 138
Interface Configuration ...................... 139
MAINTENANCE ............................................................. 154
FAQ ............................................................................... 156
APPENDIX ..................................................................... 158
PSW Default Settings ......................... 158
Error Messages & Messages .............. 161
3
Table of Contents
LED Display Format ........................... 161
PSW Specifications ............................ 162
PSW Dimensions ............................... 177
Declaration of Conformity .................. 182
INDEX ............................................................................ 183
4
SAFETY INSTRUCTIONS
WARNING
Warning: Identifies conditions or practices that could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that could result in damage to the PSW or to other properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
SAFETY INSTRUCTIONS
This chapter contains important safety instructions that you must follow during operation and storage. Read the following before any operation to insure your safety and to keep the instrument in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the instrument.
5
PSW Series User Manual
Do not dispose electronic equipment as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased.
General Guideline
CAUTION
Do not place any heavy object on the PSW. Avoid severe impact or rough handling that
leads to damaging the PSW.
Do not discharge static electricity to the PSW. Use only mating connectors, not bare wires, for
the terminals.
Do not block the cooling fan opening. Do not disassemble the PSW unless you are
qualified.
(Measurement categories) EN 61010-1:2010 and EN 61010-2-030 specify the measurement categories and their requirements as follows. The PSW falls under category II.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
0 is for measurements performed on circuits not directly
connected to Mains.
Power Supply
WARNING
AC Input voltage range: 85VAC~265VAC Frequency: 47Hz~63Hz To avoid electrical shock connect the protective
grounding conductor of the AC power cord to an earth ground.
Safety Guidelines
6
SAFETY INSTRUCTIONS
Cleaning the PSW
Disconnect the power cord before cleaning. Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Operation Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Relative Humidity: 20%~ 85% Altitude: < 2000m Temperature: 0°C to 50°C
(Pollution Degree) EN 61010-1:2010 and EN 61010-2-030 specify the pollution degrees and their requirements as follows. The PSW falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to condensation which is expected. In such conditions, equipment is normally protected against exposure to direct sunlight, precipitation, and full wind pressure, but neither temperature nor humidity is controlled.
Storage environment
Location: Indoor Temperature: -25°C to 70°C Relative Humidity: <90%, no condensation
Disposal
Do not dispose this instrument as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased. Please make sure discarded electrical waste is properly recycled to reduce environmental impact.
7
PSW Series User Manual
Green/ Yellow:
Earth
Blue:
Neutral
Brown:
Live (Phase)
Power cord for the United Kingdom
When using the power supply in the United Kingdom, make sure the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED IMPORTANT: The wires in this lead are coloured in accordance with the following code:
As the colours of the wires in main leads may not correspond with the coloured marking identified in your plug/appliance, proceed as follows:
The wire which is coloured Green & Yellow must be connected to the Earth terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment or contact the supplier.
This cable/appliance should be protected by a suitably rated and approved HBC mains fuse: refer to the rating information on the equipment and/or user instructions for details. As a guide, a cable of 0.75mm2 should be protected by a 3A or 5A fuse. Larger conductors would normally require 13A types, depending on the connection method used.
Any exposed wiring from a cable, plug or connection that is engaged in a live socket is extremely hazardous. If a cable or plug is deemed hazardous, turn off the mains power and remove the cable, any fuses and fuse assemblies. All hazardous wiring must be immediately destroyed and replaced in accordance to the above standard.
8
GETTING STARTED
PSW Series Overview ....................................................... 10
Series lineup .............................................................................................................. 10
Main Features ........................................................................................................... 11
Accessories ................................................................................................................ 12
PSW 30/80/160 Accessories .................................................................... 12
PSW 250/800 Accessories ........................................................................ 13
Appearance ..................................................................... 15
PSW Front Panel ..................................................................................................... 15
Rear Panel ................................................................................................................. 18
GETTING STARTED
This chapter describes the power supply in a nutshell, including its main features and front / rear panel introduction. After going through the overview, please read the theory of operation to become familiar with the operating modes, protection modes and other safety considerations.
9
PSW Series User Manual
Note
Throughout the user manual, PSW 30, PSW 80, PSW 160, PSW 250 or PSW 800 will refer to any of the PSW models with a maximum voltage rating of 30V, 80V, 160V, 250V or 800V, respectively.
Model name
Type
Voltage Rating
Current Rating
Power
PSW 30-36
Type I
0~30V
0~36A
360W
PSW 80-13.5
Type I
0~80V
0~13.5A
360W
PSW 160-7.2
Type I
0~160V
0~7.2A
360W
PSW 250-4.5
Type I
0~250V
0~4.5A
360W
PSW 800-1.44
Type I
0~800V
0~1.44A
360W
PSW 30-72
Type II
0~30V
0~72A
720W
PSW 80-27
Type II
0~80V
0~27A
720W
PSW 160-14.4
Type II
0~160V
0~14.4A
720W
PSW 250-9
Type II
0~250V
0~9A
720W
PSW 800-2.88
Type II
0~800V
0~2.88A
720W
PSW 30-108
Type III
0~30V
0~108A
1080W
PSW 80-40.5
Type III
0~80V
0~40.5A
1080W
PSW 160-21.6
Type III
0~160V
0~21.6A
1080W
PSW 250-13.5
Type III
0~250V
0~13.5A
1080W
PSW 800-4.32
Type III
0~800V
0~4.32A
1080W
PSW Series Overview
Series lineup
The PSW series consists of 15 models, divided into 3 different model types covering 3 power capacities: Type I (360 Watt), Type II (720 Watt) and Type III (1080 Watt).
10
GETTING STARTED
360 Watt models
Type I
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30 -36
360W
Multi-Range DC Power Supply
Voltage
Current
720 Watt models
Type II
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30 -72
720W
Voltage
Current
Multi-Range DC Power Supply
1080 Watt models
Type III
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30 -108
1080W
Voltage
Current
Multi-Range DC Power Supply
Performance
High performance/power Power efficient switching type power supply Low impact on load devices Fast transient recovery time of 1ms Fast output response time
Features
OVP, OCP and OTP protection Adjustable voltage and current slew rates User adjustable bleeder control to quickly
dissipate the power after shutdown to safe levels.
Extensive remote monitoring and control
options
Support for serial* and parallel connections.
*(30, 80, 160 volt models only)
Power on configuration settings. Supports test scripts Web server monitoring and control
Apart from the differences in output, each unit differs in size. The 720 and 1080 watt models are larger than the 360 watt models to accommodate the increase in power.
Main Features
11
PSW Series User Manual
Interface
Ethernet port Analog connector for analog voltage and current
monitoring
USB host and device port
Standard Accessories
Part number
Description
CD-ROM
User manual, programming manual
4323-30600101
Power cord (Type I/II)
4320-91001101
Power cord (Type III)
1042-SWLV0301
Output terminal cover
GTL-123
Test leads: 1x red, 1x black
GTL-240
USB Cable
PSW-004
Basic Accessory Kit:
M4 terminal screws and washers x2, M8 terminal bolts, nuts and washers x2, Air filter x1, Analog control protection dummy x1, Analog control lock level x1
Optional Accessories
Part number
Description GET-001
Extended terminal
PSW-001
Accessory Kit:
Pin contact x10, Socket x1, Protection cover x1
Accessories
Please check the contents before using the PSW.
PSW 30/80/160 Accessories
12
GETTING STARTED
PSW-002
Simple IDC Tool
PSW-003
Contact Removal Tool
PSW-005
Series operation cable for 2 units.
PSW-006
Parallel operation cable for 2 units.
PSW-007
Parallel operation cable for 3 units.
GRA-410-J
Rack mount adapter (JIS)
GRA-410-E
Rack mount adapter (EIA)
GUG-001
GPIB to USB adapter
GTL-240
USB Cable
57RG-30B00201
Large filter (Type II/III)
Download
Name
Description
psw_cdc.inf
USB driver
Standard Accessories
Part number
Description
CD-ROM
User manual, programming manual
4323-30600101
Power cord (Type I/II)
4320-91001101
Power cord (Type III)
1042-SWHV0301
High voltage output terminal cover
GTL-240
USB Cable
39BT-50900401
High voltage output terminal
PSW 250/800 Accessories
13
PSW Series User Manual
PSW-008
Basic Accessory Kit:
(Air filter x1, Analog control protection dummy x1, Analog control lock level x1
Optional Accessories
Part number
Description GET-002
Extended terminal
PSW-001
Accessory Kit:
Pin contact x10, Socket x1, Protection cover x1
PSW-002
Simple IDC Tool
PSW-003
Contact Removal Tool
PSW-006
Parallel operation cable for 2 units.
PSW-007
Parallel operation cable for 3 units.
GRA-410-J
Rack mount adapter (JIS)
GRA-410-E
Rack mount adapter (EIA)
GTL-130
Test leads: 2x red, 2x black
GUG-001
GPIB to USB adapter
GTL-240
USB Cable
57RG-30B00201
Large filter (Type II/III)
Download
Name
Description
psw_cdc.inf
USB driver
14
GETTING STARTED
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30 -72
720W
Voltage
Current
Multi-Range DC Power Supply
Current knob
Output key
Power switch
Voltage knob
USB A port
Display
Cover panel
Function keys
1080W: PSW 30-108, 80-40.5, 160-21.6, 250-13.5, 800-4.32
360W: PSW 30-36, 80-13.5, 160-7.2, 250-4.5, 800-1.44
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30- 108
1080W
Voltage
Current
Multi-Range DC Power Supply
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30- 36
360W
Multi-Range DC Power Supply
Voltage
Current
Appearance
PSW Front Panel
720W: PSW 30-72, 80-27, 160-14.4, 250-9, 800-2.88
15
PSW Series User Manual
Function Keys
The Function keys along with the Output key will light up when a key is active.
Function
The Function key is used to configure the power supply.
OVP/OCP
Set the over current or over voltage protection levels.
Set
Sets the current and voltage limits.
Test
Used to run customized scripts for testing.
Lock/Local
Locks or unlocks the panel keys to prevent accidentally changing panel settings.
PWR DSPL
Toggles the display from viewing V/A V/W or A/W*. *Press the Voltage knob for V/W, press the Current knob for A/W.
Display Indicators
VSR
Voltage Slew Rate
C V
Constant Voltage Mode
RMT
Remote Control Mode
ALM
Alarm on
DLY
Delay Output
C C
Constant Current Mode
ISR
Current Slew Rate
16
GETTING STARTED
20 40 60
80 100 % W
Power bar Indicates the current power output
as a percentage.
Voltage Knob
Voltage
Sets the voltage.
Current Knob
Current
Sets the current.
Output
Output
Press to turn on the output. The Output key will light up when the output is active.
USB
USB A port for data transfer, loading test scripts etc.
Power Switch
Used to turn the power on/off.
17
PSW Series User Manual
Output terminal (+)
Fan
Output terminal (-)
USB B port
LAN
AC Input
Sense­terminal
Analog control connector
LAN
100 240V
1000VA MAX.
AC 47 63Hz
SER.NO. LABEL
Sense+ terminal
Chassis ground
1080W: PSW 30-108, 80-40.5, 160-21.6
360W: PSW 30-36, 80-13.5, 160-7.2
100 240VAC
1500VA MAX.
47 63Hz
LAN
LN
SER.NO. LABEL
AC Input
LAN
100 240V
47 63Hz 500VA MAX.
AC
Rear Panel
720W: PSW 30-72, 80-27, 160-14.4
18
GETTING STARTED
LAN
100 240V
1000VA MAX.
AC 47 63Hz
SER.NO. LABEL
V SN.C. S V
Output terminals +V
Fan
Chassis ground
USB B port
LAN
AC Input
Sense­terminal
Analog control connector
Sense+ terminal
Output terminals -V
1080W: PSW 250-13.5, 800-4.32
360W: PSW 250-4.5, 800-1.44
LAN
LN
SER.NO. LABEL
47 63Hz
1500VA MAX.
AC100 240V
V VSN.C. S
AC Input
LAN
100 240V
47 63Hz500VA MAX.
AC
V SN.C. S V
720W: PSW 250-9, 800-2.88
19
PSW Series User Manual
Analog Control Connector
Standard 26 pin MIL connector (OMRON XG4 IDC plug).
The analog control connector is used to monitor current and voltage output, machine status (OVP, OCP, OTP etc.), and for analog control of the current and voltage output.
Use an OMRON XG5 IDC socket as the mating socket.
Output Terminals (30, 80, 160 volt models)
Positive (+) and negative (-) output terminals.
Chassis ground
Sense (-S) and Sense (+S) terminals.
Output Terminals (250, 800 volt models)
The 250 and 800 volt models use a 9 pin connector and a plug for the output and sense terminal connections. The plug is a MC420-38109Z plug by DECA SwitchLab Inc. This plug is also available separately (GW part number 39BT-50900401).
V SN.C. S V
Positive (V+) and negative (V-) output terminals (3 of each).
V SN.C. S V
Chassis ground
V SN.C. S V
Sense (-S) and Sense (+S) terminals.
20
GETTING STARTED
USB B port
The USB B port is used for remote control.
Fans
Temperature controlled fans
Ethernet Port
LAN
The ethernet port is used for remote control and digital monitoring from a PC.
Line Voltage Input
(Type I/TypeII)
Type I: PSW 30-36/80-13.5/ 160-7.2/250-4.5, 800-1.44
Type II: PSW 30-72/80-27/ 160-14.4/250-9, 800-2.88
Voltage Input: 100~240 VAC Line frequency: 50Hz/60 Hz
(Automatically switchable)
Line Voltage Input
(Type III)
LN
Type III: PSW 30-108/80-40.5/160-21.6/ 250-13.5/800-4.32
Voltage Input: 100~240 VAC Line frequency: 50Hz/60 Hz
(Automatically switchable)
21
PSW Series User Manual
Background
The PSW power supplies are regulated DC power supplies with a high voltage and current output. These operate in CC or CV mode within a wide operating range limited only by the output power.
The operating area of each power supply is determined by the rated output power as well as the voltage and current rating. For example the operating area and rated power output for the PSW 30-36 is shown below.
Voltage
Current
30
360W rated power
10
12 36
PSW 30-36 Operating Area
When the power supply is configured so that the total output (current x voltage output) is less than the rated power output, the power supply functions as a typical constant current, constant voltage power supply.
If however, the power supply is configured such that the total output (current x voltage output) exceeds the rated power output, the
Theory of Operation
The theory of operation chapter describes the basic principles of operation, protection modes and important considerations that must be taken into account before use.
Operating Area Description
22
GETTING STARTED
effective output is actually limited to the power limit of the unit. In this case the output current and voltage then depend purely on the load value.
Below is a comparison of the operating areas of each power supply.
PSW 800V Series Operating Area
0
100
800
Current (A)
Voltage (V)
200
300
400
700
0
1
2
3
4
900
5
Type III
Type II
Type I
500
600
0.45 0.9 1.35
800
250
2.88 4.321.44
PSW 250V Series Operating Area
Current (A)
Voltage (V)
0
3
6
9
12
15
Type III
Type II
Type I
1.44 2.88 4.32
250
80
9 13.54.5
250
200
150
100
50
0
23
PSW Series User Manual
PSW 160V Series Operating Area
0
20
160
Current (A)
Voltage (V)
40
60
80
140
0
5
10
15
20
180
25
Type III
Type II
Type I
100
120
2.25 4.5 6.75
160
50
14.4 21.67.2
PSW 80V Series Operating Area
Current (A)
Voltage (V)
26.6
4.5 9.0 13.5
80
Type III
Type II
Type I
30
45
40205
10
15
25
0
35
0
20
40
60
80
90
27 40.5
24
GETTING STARTED
PSW 30V Series Operating Area
0
5
30
Current (A)
Voltage (V)
10
15
20
25
0 20
40
60
80
100
10
12 24 36
30
35
120
Type III
Type II
Type I
72 108
CC and CV mode Description
When the power supply is operating in constant current mode (CC) a constant current will be supplied to the load. When in constant current mode the voltage output can vary, whilst the current remains constant. When the load resistance increases to the point where the current limit (I
SET
) can no longer be sustained the power supply switches to CV mode. The point where the power supply switches modes is the crossover point.
When the power supply is operating in CV mode, a constant voltage will be supplied to the load, whilst the current will vary as the load varies. At the point that the load resistance is too low to maintain a constant voltage, the power supply will switch to CC mode and maintain the set current limit.
The conditions that determine whether the power supply operates in CC or CV mode depends on the set current (I
SET
), the set voltage
CC and CV Mode
25
PSW Series User Manual
(V
SET
), the load resistance (RL) and the critical resistance (RC). The critical resistance is determined by V
SET/ISET
. The power supply will operate in CV mode when the load resistance is greater than the critical resistance. This means that the voltage output will be equal to the V
SET
voltage but the current will be
less than I
SET
. If the load resistance is reduced to the point that the current output reaches the I
SET
level, the power supply switches to CC
mode.
Conversely the power supply will operate in CC mode when the load resistance is less than the critical resistance. In CC mode the current output is equal to I
SET
and the voltage output is
less than V
SET
.
RL=R
C
RL<R
C
VSET
ISET
CV
CC
V
I
RL>R
C
Crossover
point
26
Slew Rate
Theory
The PSW has selectable slew rates for CC and CV mode. This gives the PSW power supply the ability to limit the current/voltage draw of the power supply. Slew rate settings are divided into High Speed Priority and Slew Rate Priority. High Speed Priority mode disables slew rate settings for CC or CV mode. Slew Rate Priority mode allows for user adjustable slew rates for CC or CV mode. The rising and falling slew rate can be set independently.
Slew rate=
Disabled
Slew rate =
Enabled
Background
The PSW DC power supplies employ a bleed resistor in parallel with the output terminals.
PSW
Load
Bleed
resistor
Bleed resistors are designed to dissipate the power from the power supply filter capacitors
GETTING STARTED
Bleeder Control
27
PSW Series User Manual
when power is turned off and the load is disconnected. Without a bleed resistor, power may remain charged on the filter capacitors for some time and be potentially hazardous.
In addition, bleed resistors also allow for smoother voltage regulation of the power supply as the bleed resistor acts as a minimum voltage load.
The bleed resistance can be turned on or off using the configuration settings.
Note
By default the bleed resistance is on. For battery charging applications, be sure to turn the bleed resistance off as the bleed resistor can discharge the connected battery when the unit is off.
Background
On the PSW, the internal resistance of the power supply can be user-defined in software. (Internal Resistance Setting, page 105). When the internal resistance is set it can be seen as a resistance in series with the positive output terminal. This allows the power supply to simulate power sources that have internal resistances such as lead acid batteries.
Internal Resistance Range
Unit Model
Internal Resistance Range
PSW 30-36
0.000 ~ 0.833Ω
PSW 30-72
0.000 ~ 0.417Ω
PSW 30-108
0.000 ~ 0.278Ω
PSW 80-13.5
0.000 ~ 5.926Ω
PSW 80-27
0.000 ~ 2.963Ω
PSW 80-40.5
0.000 ~ 1.975Ω
PSW 160-7.2
0.000 ~ 22.222Ω
PSW 160-14.4
0.000 ~ 11.111Ω
PSW 160-21.6
0.000 ~ 7.407Ω
Internal Resistance
28
GETTING STARTED
PSW 250-4.5
0.00 ~ 55.55Ω
PSW 250-9
0.00 ~ 27.77Ω
PSW 250-13.5
0.00 ~ 18.51Ω
PSW 800-1.44
0.0 ~ 555.5Ω
PSW 800-2.88
0.0 ~ 277.8Ω
PSW 800-4.32
0.0 ~ 185.1Ω
OVP
Overvoltage protection (OVP) prevents a high voltage from damaging the load.
OCP
Overcurrent protection prevents high current from damaging the load.
OTP
Over temperature protection protects the instrument from overheating.
Power Switch Trip
When the Power Switch Trip configuration setting is enabled, the power supply will automatically shut down when a protection setting has been tripped (OCP, OVP, OTP).
Alarm output
Alarms are output via the analog control connector. The alarm output is an isolated open-collector photo coupler output.
Alarms
The PSW power supplies have a number of protection features. When one of the protection alarms are set, the ALM icon on the display will be lit. For details on how to set the protection modes, please see page 57.
29
PSW Series User Manual
Inrush current
When the power supply switch is first turned on, an inrush current is generated. Ensure there is enough power available for the power supply when first turned on, especially if a number of units are turned on at the same time.
Caution
Cycling the power on and off quickly can cause the inrush current limiting circuit to fail as well as reduce the working life of the input fuse and power switch.
Pulsed or Peaked loads
When the load has current peaks or is pulsed, it is possible for the maximum current to exceed the mean current value. The PSW power supply ammeter only indicates mean current values, which means for pulsed current loads, the actual current can exceed the indicated value. For pulsed loads, the current limit must be increased, or a power supply with a greater capacity must be chosen. As shown below, a pulsed load may exceed the current limit and the indicated current on the power supply ammeter.
Considerations
The following situations should be taken into consideration when using the power supply.
30
GETTING STARTED
Current limit
level
Measured
Ammeter
current
Reverse Current: Regenerative load
When the power supply is connected to a regenerative load such as a transformer or inverter, reverse current will feed back to the power supply. The PSW power supply cannot absorb reverse current. For loads that create reverse current, connect a resistor in parallel to the power supply to bypass the reverse current. This description only applies when the bleed resistance is off.
PSW Load
Resistor
Reverse current
Note
The current output will decrease by the amount of current absorbed by the resistor.
Ensure the resistor used can withstand the power capacity of the power supply/load.
31
PSW Series User Manual
Reverse Current: Accumulative energy.
When the power supply is connected to a load such as a battery, reverse current may flow back to the power supply. To prevent damage to the power supply, use a reverse-current­protection diode in series between the power supply and load.
PSW Load
Diode
CAUTION
Ensure the reverse withstand voltage of the diode is able to withstand 2 times the rated output voltage of the power supply and the forward current capacity can withstand 3 to 10 times the rated output current of the power supply.
Ensure the diode is able to withstand the heat generated in the following scenarios.
When the diode is used to limit reverse voltage, remote sensing cannot be used.
32
GETTING STARTED
Floating
As the output terminals are floating, the load and all load cables must have an insulation capacity that is greater than the isolation voltage of the power supply.
PSW
Load
Ext-V Ext-R
Analog
connector
( ) Insulation capacity isolation voltage
of power supply
WARNING
If the insulation capacity of the load and load cables is not greater than the isolation voltage of the power supply, electric shock may occur.
Grounding
The output terminals of the PSW power supplies are isolated with respect to the protective grounding terminal. The insulation capacity of the load, the load cables and other connected devices must be taken into consideration when connected to the protective ground or when floating.
33
PSW Series User Manual
Grounded output terminal
If the positive or negative terminal is connected to the protective ground terminal, the insulation capacity needed for the load and load cables is greatly reduced. The insulation capacity only needs to be greater than the maximum output voltage of the power supply with respect to ground.
PSW
Load
Ext-V Ext-R
Analog
connector
( ) Insulation capacity voltage of power
supply with respect to ground
CAUTION
If using external voltage control, do not ground the external voltage terminal as this will create a short circuit.
34
OPERATION
Set Up ............................................................................. 37
Line Voltage Connection – Type III Models ....................................................... 37
Filter Installation ...................................................................................................... 39
Power Up .................................................................................................................. 40
Wire Gauge Considerations .................................................................................... 41
Output Terminals PSW-30/80/160 ...................................................................... 42
Using the Output Terminal Cover PSW-30/80/160 .......................................... 44
Output Terminals PSW-250/800 .......................................................................... 46
Using the Output Terminal Cover PSW-250/800 .............................................. 50
Using the Rack Mount Kit...................................................................................... 51
How to Use the Instrument ................................................................................... 51
Reset to Factory Default Settings .......................................................................... 53
View System Version and Build Date ................................................................... 54
Basic Operation .............................................................. 57
Setting OVP/OCP Levels ...................................................................................... 57
Set to C.V. Mode ..................................................................................................... 59
Set to C.C. Mode ...................................................................................................... 63
Display Modes .......................................................................................................... 66
Panel Lock ................................................................................................................ 67
Remote Sense ........................................................................................................... 68
Parallel / Series Operation .............................................. 72
Master-Slave Parallel Overview .............................................................................. 73
Master-Slave Parallel Connection .......................................................................... 76
Master-Slave Parallel Operation ............................................................................. 79
Master-Slave Series Overview ................................................................................ 81
Master-Slave Series Connection ............................................................................. 83
Master-Slave Series Operation ............................................................................... 85
Test Scripts ..................................................................... 87
Test Script File Format ........................................................................................... 88
Test Script Settings .................................................................................................. 88
OPERATION
35
PSW Series User Manual
Setting the Test Script Settings .............................................................................. 89
Load Test Script from USB .................................................................................... 90
Run Test Script (Manual) ........................................................................................ 91
Run Test Script (Automatically at Startup) ........................................................... 92
Export Test Script to USB ..................................................................................... 93
Remove Test Script ................................................................................................. 94
Checking the Available Memory ............................................................................ 95
36
OPERATION
Background
The Type III (PSW 30-108/80-40.5/160-
21.6/250-13.5/800-4.32) models use a universal power input that can be used with 100 and 200 VAC systems. To connect or replace the power cord (GW Instek part number: 4320-91001101, use the procedure below:
Warning
The following procedure should only be attempted by competent persons.
Ensure the AC power cord is not connected to power.
Removal
1. Turn off the power switch.
1
2. Unscrew the power cord
protective sheath.
3. Remove the 2 screws
holding the power cord cover and remove.
3
2
Set Up
Line Voltage Connection – Type III Models
37
PSW Series User Manual
4. Slide the cover off the AC
terminals.
5. Remove the AC power
cord wires.
5
4
Installation
1. Connect the AC power
cord wires to the AC input terminals.
White/Blue Neutral
(N)
Green/Green-
yellowGND ( )
Black/Brown Line
(L)
LN
Line
Neutral
Ground
2. Set the cover back over the
AC terminals.
2
3. Re-install the power cord
cover.
4. Screw the power cord
sheath back onto the cover.
3
4
38
OPERATION
Background
The PSW has a small filter (GW Instek part number, 57RG-30B00101) that must first be inserted under the control panel before operation. The small filter must be inserted for all model types (Type I/II/III).
Steps
1. Insert the small filter
in the open area under the control panel.
Type II shown as an example
2. The unit is now ready to power up.
Filter Installation
39
Power Up
Steps
1. Type I or II: Connect the
power cord to the rear panel socket.
Type III: Connect the power cord to the universal power input.
Page 37
2. Press the POWER key. If used for the first time,
the default settings will appear on the display, otherwise The PSW recovers the state right before the power was last turned OFF.
For default configuration settings, see page 158.
V
A
CAUTION
The power supply takes around 8 seconds to fully turn on and shutdown.
Do not turn the power on and off quickly. Please wait for the display to fully turn off.
PSW Series User Manual
40
OPERATION
Background
Before connecting the output terminals to a load, the wire gauge of the cables should be considered.
It is essential that the current capacity of the load cables is adequate. The rating of the cables must equal or exceed the maximum current rated output of the instrument.
Recommended wire gauge
Wire Gauge
Nominal Cross Section
Maximum Current
20
0.5 9 18
0.75
11
18
1
13
16
1.5
18
14
2.5
24
12
4
34
10
6
45 8 10
64 6 16
88 4 25
120 2 32
145 1 50
190 0 70
240 0 95
290 0 120
340
The maximum temperature rise can only be 60 degrees above the ambient temperature. The ambient temperature must be less than 30 deg.
Wire Gauge Considerations
41
PSW Series User Manual
Background
Before connecting the output terminals to the load, first consider whether voltage sense will be used, the gauge of the cable wiring and the withstand voltage of the cables and load.
The output terminals can be connected to load cables using M4 sized screws or M8 sized bolts.
WARNING
Dangerous voltages. Ensure that the power to the instrument is disabled before handling the power supply output terminals. Failing to do so may lead to electric shock.
Steps
1. Turn the power switch off.
2. Remove the output terminal cover.
Page 44
3. If necessary, screw the chassis
ground terminal to either the positive or negative terminal. See the grounding chapter for details.
Page 33
Sense joining plates
Ground
4. Choose a suitable wire gauge for
the load cables.
Page 41
Output Terminals PSW-30/80/160
42
OPERATION
5. Choose a suitable crimp for the terminals.
6. If using voltage sense, remove the
sense terminal joining plates and connect sensing wires to the load(s).
Page 68
7. Connect the positive load cable to the positive
output terminal and the negative cable to the negative output terminal.
8. Reattach the output terminal
cover.
Page 44
Connection with local sense wiring
Using M4 screws
Negative potential
Positive
potential
Using M8 bolts
Negative potential
Positive
potential
Connection with voltage sense wiring
Using M4 screws
Sense +
Sense -
Using M8 bolts
Sense +
Sense -
43
PSW Series User Manual
Steps
1. Remove the screw holding the top cover to the
bottom cover.
2. Line-up the bottom cover with the notches in
the output terminals.
3. Place the top terminal cover over the bottom
cover.
Details
2
3
1
4. Use your thumb to slide the terminal covers
shut, as shown in the diagram below.
5. When the top and bottom covers are flush, re-
insert the screw that was removed in step 1.
4
5
Using the Output Terminal Cover PSW-30/80/160
44
OPERATION
Removal
Reverse the procedure to remove the terminal covers.
45
PSW Series User Manual
Background
The high voltage models (PSW 250 and PSW 800 models) use a 9 pin socket for the output voltage and sense connections. The corresponding plugs (GW part number 39BT­50900401 //DECA SwitchLab MC420-38109Z) should be used to connect the terminals to the appropriate cable.
Before connecting the output terminals to the load, first consider whether voltage sense will be used, the gauge of the cable wiring and the withstand voltage of the cables and load.
WARNING
Dangerous voltages. Ensure that the power to the instrument is disabled before handling the power supply output terminals. Failing to do so may lead to electric shock.
Please note the wire gauge used and the capacity of the plug/socket. It may be necessary to wire the load to a number of terminals to offset the capacity over a number of terminals.
Output Connector Overview
When using the output connector make sure the wires that are used follow the following guidelines:
Wire gauge:
AWG 26 to AWG 16
Strip length
6.5mm // 0.26 in.
Current rating
10A
Insulation resistance
AC 2000V min
Insulation withstand voltage
>2000MΩ DC500V
Operation Temperature
-40ºC to +105ºC
Output Terminals PSW-250/800
46
OPERATION
Output Connector Pinout
-V
-S N.C.
+S
+V
-V: -V terminals (x3)
-S: -Sense terminal NC: Not connected +S: +Sense terminal +V: +V terminals (x3)
Wiring the Connector Plug
c
Tighten
Loosen
a
b
a. Unscrew the
appropriate terminal anticlockwise to release the receptacle.
b. Insert a wire that has
had at least ~7mm stripped from the insulation.
c. Tighten the
receptacle by screwing clockwise.
Steps
1. Turn the power switch off.
2. Remove the output terminal cover.
Page 50
3. Choose a suitable wire gauge for
the load cables.
Page 41
4. Strip ~7mm from one end of each load cable.
5. Connect the positive load cable to one of the
+V pins and the negative cable to one of the -V pins.
47
PSW Series User Manual
WARNING
Please note the wire gauge used and the capacity of the plug/socket. It may be necessary to wire the load to a number of terminals to offset the capacity over a number of terminals.
6. If using local sense, connect the -S pin to a -V
pin, and connect the +S pin to a +V pin.
V SN.C. S V
7. If not using local sense, see the
remote sense section to wire the sense terminals for remote sensing.
Page 68
8. If necessary, connect the chassis
ground terminal to either the -V or +V pin. See the grounding chapter for details.
Page 33
V SN.C. S V
9. Reattach the output terminal
cover.
Page 50
48
OPERATION
Local Sense Wiring
To positive
potential
To negative
potential
-V +V
Remote Sense Wiring
To positive
potential
To negative
potential
-S
-V +V
+S
49
PSW Series User Manual
Steps
1. Screw the bottom
cover onto the rear panel using the two M4 screws.
1
2. Slide the top cover
over the bottom cover.
2
3. Finally, secure the
top cover with the screw in the center of the top cover.
3
Removal
Reverse the procedure to remove the terminal covers.
Using the Output Terminal Cover PSW-250/800
50
OPERATION
Background
The PSW series has an optional Rack Mount Kit (GW Instek part number: [JIS] GRA-410-J, [EIA] GRA-410-E[EIA]) that can be used to hold 6x PSW Type I models, 3x Type II models, 2x Type III models or a combination of all models (1x Type I, 1x Type II and 1x Type III).
Rack mount diagram
Type I Type II Type III
Background
The PSW power supplies use a novel method of configuring parameter values only using the Voltage or Current knobs. The knobs are used to quickly edit parameter values at 0.01, 0.1 or 1 unit steps at a time.
When the user manual says to set a value or parameter, use the steps below.
Example
Use the Voltage knob to set a voltage of 10.05 volts.
Using the Rack Mount Kit
How to Use the Instrument
51
PSW Series User Manual
1. Repeatedly press the Voltage knob
until the last digit is highlighted. This will allow the voltage to be edited in 0.01 volt steps.
2. Turn the Voltage knob till 0.05
volts is shown.
Voltage
Voltage
V
A
V
A
3. Repeatedly press the Voltage knob until the
first digit is highlighted. This will allow the voltage to be edited in 1 volt steps.
4. Turn the Voltage knob until 10.05 is shown.
V
A
V
A
Note
Notice the Set key becomes illuminated when setting the current or voltage.
If the Voltage or Current knobs are unresponsive, press the Set key first.
52
OPERATION
Background
The F-88 configuration setting allows the PSW to be reset back to the factory default settings. See page 158 for the default factory settings.
Steps
1. Press the Function key. The
Function key will light up.
Function
2. The display should show F-
01 on the top and the configuration setting for F-01 on the bottom.
3. Rotate the Voltage knob to change
the F setting to F-88 (Factory Set Value).
Voltage
4. Use the Current knob to set the
F-88 setting to 1 (Return to factory settings).
Current
5. Press the Voltage knob to confirm.
ConF will be displayed when successful.
Voltage
6. Press the Function key again to
exit. The function key light will turn off.
Function
Reset to Factory Default Settings
53
PSW Series User Manual
Background
The F-89 configuration setting allows you to view the PSW version number, build date, keyboard version, analog-control version, kernel build, test command version, test command build date, and the USB driver version.
Steps
1. Press the Function key. The
Function key will light up.
Function
2. The display should show F-
01 on the top and the configuration setting for F-01 on the bottom.
3. Rotate the Voltage knob to change
the F setting to F-89 (Show Version).
Voltage
4. Rotate the Current knob to view
the version and build date for the various items.
Current
View System Version and Build Date
54
OPERATION
F-89
0-XX: PSW Main Program Version 1-XX: PSW Main Program Version 2-XX: PSW Main Program Build On­Year. 3-XX: PSW Main Program Build On­Year. 4-XX: PSW Main Program Build On­Month. 5-XX: PSW Main Program Build On­Day. 6-XX: Keyboard CPLD version. 7-XX: Keyboard CPLD version. 8-XX: Analog CPLD version. 9-XX: Analog CPLD version. A-XX: Reserved. B-XX: Reserved. C-XX: Kernel Build On-Year. D-XX: Kernel Build On-Year. E -XX: Kernel Build On-Month. F-XX: Kernel Build On-Day. G-XX: Test Command Version. H-XX: Test Command Version. I-XX: Test Command Build On-Year. J-XX: Test Command Build On-Year. K-XX: Test Command Build On-Month. L-XX: Test Command Build On-Day. M-XX: USB Driver version (Major). N-XX: USB Driver version (Minor).
5. Press the Function key again to
exit. The function key light will turn off.
Function
Example
Main Program Version: Vt1.50, 2014/08-03
0-t1: PSW Main Program Version 1-50: PSW Main Program Version 2-20: PSW Main Program Build On-Year. 3-14: PSW Main Program Build On-Year. 4-01: PSW Main Program Build On-Month. 5-13: PSW Main Program Build On-Day.
55
PSW Series User Manual
Example
Keyboard CPLD Version: 0x030c
6-03: Keyboard CPLD Version. 7-0c: Keyboard CPLD Version.
Example
Analog CPLD Version: 0x0427
8-04: Analog CPLD Version. 9-27: Analog CPLD Version.
Example
Kernel Version: 2013/03/22
C-20: Kernel Build On-Year. D-13: Kernel Build On-Year. E-03: Kernel Build On-Month. F-22: Kernel Build On-Day.
Example
Test Command Version: V01:00, 2011/08/01
G-01: Test Command Version. H-00: Test Command Version. I-20: Test Command Build On-Year. J-11: Test Command Build On-Year. K-08: Test Command Build On-Month. L-01: Test Command Build On-Day.
Example
USB Driver Version: V02.01:
M-02: USB Driver Version (Major release). N-01: USB Driver Version (Minor release).
56
OPERATION
Background
For most models the OVP level has a selectable range of approximately* 10% to 110% of the rated output voltage. Likewise the OCP level for most models has a selectable range of approximately* 10%~ 110% of the rated output current. The OVP and OCP level is set to the maximum by default. The OCP level can also be turned off.
*Note that the actual setting range differs for each model.
When one of the protection measures are on, ALM is shown on the panel display. By default, the power switch will turn off when any of the protection levels are tripped.
Basic Operation
This section describes the basic operations required to operate the power supply.
Setting OVP/OCP → from page 57 C.V. mode → from page 59 C.C. mode → from page 63 Display modes → page 66 Panel lock → page 67 Remote sensing → from page 68
Before operating the power supply, please see the Getting Started chapter, page 9.
Setting OVP/OCP Levels
57
PSW Series User Manual
ALM
V
A
Before setting the OVP or OCP level:
Ensure the load is not connected. Ensure the output is set to off.
Setting Ranges
PSW (360W)
30-36
80-13.5
160-7.2
250-4.5
800-1.44
OVP Range (V)
3-33
8-88
16-176
20-275
20-880
OCP Range (A)
3.6-39.6
1.35-14.85
0.72-7.92
0.45-4.95
0.144-1.584
PSW (720W)
30-72
80-27
160-14.4
250-9
800-2.88
OVP Range (V)
3-33
8-88
16-176
20-275
20-880
OCP Range (A)
5-79.2
2.7-29.7
1.44-15.84
0.9-9.9
0.288-3.168
PSW (1080W)
30-108
80-40.5
160-21.6
250-13.5
800-4.32
OVP Range (V)
3-33
8-88
16-176
20-275
20-880
OCP Range (A)
5-118.8
4.05-44.55
2.16-23.76
1.35-14.85
0.432-4.752
Steps
1. Press the OVP/OCP key. The
OVP/OCP key lights up.
OVP/OCP
2. The OVP setting will be displayed on the top
and the OCP setting (or OFF) will be displayed on the bottom.
V
A
OVP Setting
OCP Setting
58
OPERATION
OVP Level
3. Use the Voltage knob to set the
OVP level.
Voltage
OCP Level
4. Use the Current knob to set the
OCP level, or to turn OCP off.
Current
5. Press OVP/OCP again to exit. The
OVP/OCP indicator will turn off.
OVP/OCP
Power switch trip
Set F-95 (Power switch trip) to 1 (to disable the power switch trip) or to 0 (to enable the power switch trip) and save.
Page 114
F-95
1 (Disable) or 0 (Enable)
Clear OVP/OCP protection
The OVP or OCP protection can be cleared after it has been tripped by holding the OVP/OCP button for 2 seconds. (Only applicable when the power switch trip setting is disabled [F-95 = 1])
OVP/OCP
(hold)
Set to C.V. Mode
When setting the power supply to constant voltage mode, a current limit must also be set to determine the crossover point. When the current exceeds the crossover point, the mode switches to C.C. mode. For details about C.V. operation, see page 22. C.C. and C.V. mode have two selectable slew rates: High Speed Priority and Slew Rate Priority. High Speed Priority will use the fastest slew rate for the instrument while Slew Rate Priority will use a user-configured slew rate.
59
PSW Series User Manual
Background
Before setting the power supply to C.V. mode, ensure:
The output is off. The load is connected.
Steps
1. Press the Function key. The
Function key will light up.
Function
2. The display should show F-
01 on the top and the configuration setting for F-01 on the bottom.
3. Rotate the Voltage knob to change
the F setting to F-03 (V-I Mode Slew Rate Select).
Voltage
4. Use the Current knob to set the F-
03 setting.
Set F-03 to 0 (CV High Speed Priority) or 2 (CV Slew Rate Priority).
Current
F-03
0 = CV High Speed Priority 2 = CV Slew Rate Priority
5. Press the Voltage knob to save the
configuration setting. ConF will be displayed when successful.
Voltage
60
OPERATION
6. If CV Slew Rate Priority was chosen as the
operating mode, repeat steps 3~5 to set F-04 (Rising Voltage Slew Rate) and the F-05 (Falling Voltage Slew Rate) and save.
F-04 / F-05
0.1V/s~60V/s (PSW 30-XX)
0.1V/s~160V/s (PSW 80-XX)
0.1V/s~320V/s (PSW 160-XX)
0.1V/s~500.0V/s (PSW 250-XX) 1V/s~1600V/s (PSW 800-XX)
7. Press the Function key again to exit
the configuration settings. The function key light will turn off.
Function
8. Use the Current knob to set the
current limit (crossover point).
Current
9. Use the Voltage knob to set the
voltage.
Voltage
Note
Notice the Set key becomes illuminated when setting the current or voltage. If the Voltage or Current knobs are unresponsive, press the Set key first.
10. Press the Output key. The Output
key becomes illuminated.
Output
61
PSW Series User Manual
C V
% W
V
A
CV and the Power Bar
will become illuminated
(top left & center)
20 40 60 80 100 % W
Note
Only the voltage level can be altered when the output is on. The current level can only be changed by pressing the Set key.
For more information on the Normal Function Settings (F-00 ~ F-61, F-88~F-89) see page 102.
62
OPERATION
Background
Before setting the power supply to C.C. mode, ensure:
The output is off. The load is connected.
Steps
1. Press the Function key. The
Function key will light up.
Function
2. The display should show F-
01 on the top and the configuration setting for F-01 on the bottom.
3. Rotate the Voltage knob to change
the F setting to F-03 (V-I Mode Slew Rate Select).
Voltage
4. Use the Current knob to set the F-
03 setting.
Set F-03 to 1 (CC High Speed Priority) or 3 (CC Slew Rate Priority) and save.
Current
Set to C.C. Mode
When setting the power supply to constant current mode, a voltage limit must also be set to determine the crossover point. When the voltage exceeds the crossover point, the mode switches to C.V. mode. For details about C.C. operation, see page 22. C.C. and C.V. mode have two selectable slew rates: High Speed Priority and Slew Rate Priority. High Speed Priority will use the fastest slew rate for the instrument while Slew Rate Priority will use a user-configured slew rate.
63
PSW Series User Manual
F-03
1 = CC High Speed Priority 3 = CC Slew Rate Priority
5. Press the Voltage knob to save the
configuration setting. ConF will be displayed when successful.
Voltage
6. If CC Slew Rate Priority was chosen as the
operating mode, set F-06 (Rising Current Slew Rate) and F-07 (Falling Current Slew Rate) and save.
F-06 / F-07
0.01A/s~72.00A/s (PSW 30-36)
0.1A/s~144.0A/s (PSW 30-72)
0.1A/s~216.0A/s (PSW 30-108)
0.01A/s~27.00A/s (PSW 80-13.5)
0.01A/s~54.00A/s (PSW 80-27)
0.01A/s~81.00A/s (PSW 80-40.5)
0.01A/s~14.40A/s (PSW 160-7.2)
0.01A/s~28.80A/s (PSW 160-14.4)
0.01A/s~43.20A/s (PSW 160-21.6)
0.001A/s~9.000A/s (PSW 250-4.5)
0.01A/s~18.00A/s (PSW 250-9)
0.01A/s~27.00A/s (PSW 250-13.5)
0.001A/s~2.880A/s (PSW 800-1.44)
0.001A/s~5.760A/s (PSW 800-2.88)
0.001A/s~8.640A/s (PSW 800-4.32)
7. Press the Function key again to exit
the configuration settings. The function key light will turn off.
Function
64
OPERATION
8. Use the Voltage knob to set the
voltage limit (crossover point).
Voltage
9. Use the Current knob to set the
current.
Current
Note
Notice the Set key becomes illuminated when setting the current or voltage. If the Voltage or Current knobs are unresponsive, press the Set key first.
10. Press the Output key. The Output
key becomes illuminated.
Output
% W
V
A
C C
% W
20 40 60 80 100
CC and the Power Bar
will become illuminated
(bottom left & center)
Note
Only the current level can be altered when the output is on. The voltage level can only be changed by pressing the Set key.
For more information on the Normal Function Settings (F-00 ~ F-61, F-88~F-89) see page 102.
65
PSW Series User Manual
Steps
1. Press the PWR/DSPL key. The
PWR DSPL key lights up.
PWR DSPL
2. The display changes to voltage and power
(V/W).
3. To switch between displaying A/W and V/W,
simply press the corresponding Voltage or Current knob.
For example: when in A/W mode, press the Voltage knob to display V/W. Conversely when in V/W mode, press the Current knob to display A/W.
Voltage
Current
When V/W is displayed, the Voltage knob
can still be used to change the voltage level.
When A/W is displayed, the Current knob
can still be used to change the current level.
Exit
Press the PWR/DSPL key again to return to normal display mode. The PWR DSPL light will turn off.
PWR DSPL
V W W
A
Display Modes
The PSW power supplies allow you to view the output in three different modes: voltage and current, voltage and power or current and power.
66
OPERATION
Activate the panel lock
Press the Lock/Local key to active the panel lock. The key will become illuminated.
Lock/Local
Disable the panel lock
Hold the Lock/Local key for ~3 seconds to disable the panel lock. The Lock/Local light turns off.
Lock/Local
Panel Lock
The panel lock feature prevents settings from being changed accidentally. When activated, the Lock/Local key will become illuminated and all keys and knobs except the Lock/Local key and Output key (if active) will be disabled.
If the instrument is remotely controlled via the USB/LAN interface, the panel lock is automatically enabled.
67
PSW Series User Manual
WARNING
Ensure the output is off before connecting any sense cables.
Use sense cables with a voltage rating exceeding the isolation voltage of the power supply.
Never connect sensing cables when the output is on. Electric shock or damage to the power supply could result.
Note
Be sure to remove the Sense joining plates so the units are not using local sensing.
Single Load
1. Connect the Sense+ terminal to the positive
potential of the load. Connect the Sense­terminal to the negative potential of the load.
Output
Sense
Sense
PSW
Output
Load Input Input
Page 42
Remote Sense
Remote sense is used to compensate for the voltage drop seen across load cables due to the resistance inherent in the load cables. The remote sense terminals are connected to the load terminals to determine the voltage drop across the load cables.
Remote sense can compensate up to 0.6 volts for 30V/80V/160V models and 1V for 250V/800V models (compensation voltage). Load cables should be chosen with a voltage drop less than the compensation voltage.
68
OPERATION
2. Operate the instrument as normal.
See the Basic Operation chapter for details.
Page 57
Parallel PSW Units
1. Connect the Sense+ terminals to the positive
potential of the load. Connect the Sense­terminals to the negative potential of the load.
Output
Sense
Sense
PSW #2
Output
Output
Sense
Sense
PSW #1
Output
Load Input Input
Page 42
2. Operate the instrument as normal.
See the Parallel Operation chapter for details.
Page 73
69
PSW Series User Manual
Serial PSW Units
1. a. Connect the 1
st
Sense+ terminal to the
positive potential of the load.
b. Connect the 1st Sense- terminal to the positive output terminal of the second PSW unit.
c. Connect the 2nd Sense+ terminal to the positive terminal of the second PSW unit.
d. Connect the 2nd Sense- terminal to negative terminal of the load.
PSW #2
a
b
c
d
Load Input Input
Output
Sense
Sense
PSW #1
Output
Output
Sense
Sense
Output
Page 42
2. Operate the instrument as normal.
See the Serial Operation chapter for details.
Page 81
70
OPERATION
Wire Shielding and Load line impedance
To help to minimize the oscillation due to the inductance and capacitance of the load cables, use an electrolytic capacitor in parallel with the load terminals.
To minimize the effect of load line impedance use twisted wire pairing.
PSW Load
s s
Twisted pair
Capacitor
71
PSW Series User Manual
CAUTION
250V and 800V models do not support series operation!
Parallel / Series Operation
This section describes the basic operations required to operate the power supply in series or parallel. Operating the PSW series in parallel increases the total power output of the power supply units. When used in series, the total output voltage of the power supplies can be increased.
The number of the power supplies that can be connected in series or parallel depends on the model and the mode:
Series Mode: 2 units maximum; 30V, 80V and 160V models only.
Parallel Mode: 3 units maximum
To use the power supplies in series or parallel, units must be used in a Master-Slave configuration. In the master-slave configuration a
“master” power supply controls any other connected “slave”
power supplies.
Master-Slave Parallel overview → from page 73 Parallel connection → from page 76 Parallel operation → from page 79 Master-Slave Series overview → page 81 Series connection → page 83 Series operation → from page 85
Before operating the power supply, please see the Getting Started chapter, page 9.
72
OPERATION
Background
When connecting the PSW power supplies in parallel, up to 3 units can be used in parallel and all units must be of the same model. The Analog Control Connector is used as the interface for parallel the connections.
When the units are used in parallel, a number of precautions and limitations apply. Please read this overview before operating the power supplies in parallel.
Parallel Connection Overview
Master
Load
Ext-V Ext-R
Slave
VMON
IMON
Slave
Analog Control Connectors
Limitations
Display
Only the master unit will display the voltage
and current.
Master-Slave Parallel Overview
73
PSW Series User Manual
OVP/ OCP
The master unit can shut down slave units
when OVP/OCP is tripped on the master unit (if the slave connector is wired for shut down on alarm).
OVP/OCP can be independently tripped on
each slave unit, however the shutdown of the power or output of the unit is disabled. Only the alarm will be enabled.
Remote monitoring
Voltage monitoring (VMON) and current
monitoring (IMON) are only supported on the master unit.
The IMON current represents the total
current of the all the parallelized units.
Remote Sense
Please see the remote sense chapter for
details, page 68.
External Voltage and Resistance Control
Voltage/Resistance controlled remote
control can only be used with the master unit.
The full scale current (in parallel) is
equivalent to the maximum external voltage or resistance.
Internal Resistance
For 2 units in parallel, the internal resistance
is actually half of the setting value.
For 3 units in parallel, the internal resistance
is actually a third of the setting value.
74
OPERATION
Bleeder Control
The Master unit is used to control the
bleeder settings. The bleeder resistors in all the slave units are always turned off when in parallel mode.
Output Voltage/ Output Current
Model
Single unit
2 units
3 units
PSW 30-36
30V
30V
30V
36A
72A
108A
PSW 80-13.5
80V
80V
80V
13.5A
27A
40.5A
PSW 160-7.2
160V
160V
160V
7.2A
14.4A
21.6A
PSW 250-4.5
250V
250V
250V
4.5A
9A
13.5A
PSW 800-1.44
800V
800V
800V
1.44A
2.88A
4.32A
PSW 30-72
30V
30V
30V
72A
144A
216A
PSW 80-27
80V
80V
80V 27A
54A
81A
PSW 160-14.4
160V
160V
160V
14.4A
28.8A
43.2A
PSW 250-9
250V
250V
250V
9A
18A
27A PSW 800-2.88
800V
800V
800V
2.88A
5.76A
8.64A
PSW 30-108
30V
30V
30V 108A
216A
324A
PSW 80-40.5
80V
80V
80V 40.5A
81A
121.5A
PSW 160-21.6
160V
160V
160V
21.6A
43.2A
64.8A
PSW 250-13.5
250V
250V
250V
13.5A
27A
40.5A
PSW 800-4.32
800V
800V
800V
4.32A
8.64A
12.96A
75
PSW Series User Manual
Master-Slave Connector
The Analog Control Connector is used for both serial and parallel connections. The way the connector is configured determines the behavior of the master and slave units. For the complete connector pin assignment, see page
117.
Analog Connector Connection
To operate the power supplies in parallel, connect the analog connectors on the master and slave units as shown in the diagrams below.
Alternatively pre-configured cables (optional) can be used. The PSW-006 is used for two units in parallel. The PSW-007 is used for 3 units in parallel.
Master with 2 slave units:
121314
15172021
24 20 12
17 15 3 1715
312
24 20
11 1
2
1
OUTPUT ON STATUS21
Master unit
ALM STATUS20
STATUS COM17
FEEDBACK15
CURRENT_SUM_113
SHUTDOWN12
OUT ON/OFF CONT24
Slave Unit 1
12 SHUTDOWN
20 ALM STATUS
15 FEEDBACK
3 CURRENT SUM OUT
Slave Unit 2
OUT ON/OFF CONT24
12 SHUTDOWN
17 STATUS COM 17 STATUS COM
2 D COM
15 FEEDBACK
CURRENT_SUM_2 CURRENT SUM OUT314
20 ALM STATUS
11 1 1I MON CURRENT SHARE CURRENT SHARE
Master-Slave Parallel Connection
76
OPERATION
Master with 1 slave unit:
2
12
1315172021
24 20 12
17 15 3
23
OUTPUT ON STATUS21
Master unit
ALM STATUS20
STATUS COM17
FEEDBACK15
CURRENT_SUM_113
SHUTDOWN12
OUT ON/OFF CONT24
Slave Unit 1
12 SHUTDOWN
20 ALM STATUS
15 FEEDBACK
3 CURRENT SUM OUT
17 STATUS COM
2 D COM
11 1I MON CURRENT SHARE
11 1
Parallel Output Connection
-
+
Load
Master
unit
Slave
unit 2
Slave unit 1
Steps
1. Ensure the power is off on all power supplies.
2. Choose a master and a slave unit(s).
3. Connect the analog connectors for the master
and slave unit as shown above.
4. Remove the Output Terminal
covers and the protection dummy plug from the analog control connector.
Page 44
77
PSW Series User Manual
5. Connect the master and slave unit in parallel as
shown above.
6. Reattach the terminal covers.
Page 44
Note
Ensure the load cables have sufficient current capacity.
Page 41
Re-attach the Protection dummy plug when not in use.
78
OPERATION
Master-Slave Configuration
Before using the power supplies in parallel, the master and slave units need to be configured.
Steps
1. Configure the OVP and OCP
settings for the master unit.
Page 57
2. For each unit, hold the Function
key while turning the power on to enter the power on configuration settings.
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30 -36
360W
Voltage
Current
Multi-Range DC Power Supply
3. Configure F-93 (Master/Slave)
setting for each master/slave unit.
Page 114 Unit
F-93
Master (with 1 slave in parallel)
1
Master (with 2 slaves in parallel)
2
Slave unit (parallel slave)
3
4. Cycle the power on the units (reset the power).
Note
Configuration settings can be checked for both the master and slave units by pressing the Function key and checking F-93.
Only the Master OVP and OCP level is used for over voltage and current protection. Slave OVP and OCP level is disregarded.
OTP works independently for each unit.
Master-Slave Parallel Operation
79
PSW Series User Manual
Master-Slave Operation
Only operate the power supplies in parallel if the units are configured correctly.
1. Turn on the master and slave units. The slave
unit(s) will show a blank display.
Master unit
Slave units
2. Operation of all units is controlled
via the master unit. Operation of the master unit is the same as for a single unit. See the Basic Operation chapter.
Page 57.
3. Press the Output key to begin.
Output
Caution
Only operate the power supplies in parallel if using units of the same model number.
Only a maximum of 3 units can be used in parallel.
Note
The panel controls are disabled on slave units, including the output key. On slave units only the Function key can be used to view the current settings.
80
OPERATION
Background
When connecting PSW power supplies in series, up to 2 units* can be used in series and all units must be of the same model. The Analog Control Connector is used as the interface for serial connections.
When the units are used in series, a number of precautions and limitations apply. Please read this overview before operating the power supplies in series.
CAUTION
*250V and 800V models do not support series operation!
Series Connection Overview
Slave
Load
Master
Ext-V
Ext-R
VMON
IMON
Analog Control
Connectors
Limitations
Display
Only the master unit will display the
current.
Master and slave units display the voltage.
The total voltage is the sum of the units.
Master-Slave Series Overview
81
PSW Series User Manual
OVP/OCP
The master unit can shut down the slave
unit when OVP/OCP is tripped on the master unit (if the slave connector is wired for shut down on alarm).
OVP and OCP level is determined by the
master OVP and OCP level. The OVP and OCP level on the slave unit is ignored.
Remote monitoring
Voltage monitoring (VMON) and current
monitoring (IMON) are only supported on the master unit.
The VMON voltage represents the total
voltage of the all the serialized units.
Remote Sense
Please see the remote sense chapter for
details, page 68.
External Voltage and Resistance Control
Voltage/Resistance controlled remote
control can only be used with the master unit.
The full scale voltage (in series) is equivalent
to the maximum external voltage or resistance.
Slew Rate
The actual slew rate is double that of the
setting slew rate. I.e., A slew rate setting of
60.00V/s is actually 120V/s when in series.
Internal Resistance
The internal resistance is actually twice that
of the setting value.
82
OPERATION
Bleeder Control
The Master unit is used to control the
bleeder settings. The bleeder resistor is always turned on for the slave unit in series mode.
Output Voltage/ Output Current
Model
Single unit
2 units
PSW 30-36
30V
60V
36A
36A PSW 80-13.5
80V
160V
13.5
13.5A
PSW 160-7.2
160V
320V
7.2A
7.2A
PSW 30-72
30V
60V
72A
72A
PSW 80-27
80V
160V
27A
27A
PSW 160-14.4
160V
320V
14.4A
14.4A
PSW 30-108
30V
60V 108A
108A
PSW 80-40.5
80V
160V
40.5A
40.5A
PSW 160-21.6
160V
320V
21.6A
21.6A
Master-Slave Connector
The Analog Control Connector is used for both serial and parallel connections. The way the connector is configured determines the behavior of the master and slave units. For the connector pin assignment, see page 117.
Master-Slave Series Connection
83
PSW Series User Manual
Analog Connector Connection
To operate the power supplies in series, connect the analog connectors on the master and slave unit as shown in the diagram below.
Alternatively, the optional PSW-005 cable is pre-configured for serial use.
2
12
172021
Master unit
A COM16
OUTPUT ON STATUS21
ALM STATUS20
STATUS COM17
SHUTDOWN12
Slave Unit 1
25 SER SLV IN
20 ALM STATUS
12 SHUTDOWN
2 D COM
24 OUT OFF/ON CONT
2 D COM
24 20 12
17
25
2
16
17 STATUS COM
Series Output Connection
Master unit
Load
+
­Slave unit
Steps
1. Ensure the power is off on both power supplies.
2. Choose a master and slave unit.
3. Connect the analog connectors for the master
and slave unit as shown above.
4. Remove the output terminal cover
and the protection dummy plug from the analog control connector.
Page 44
84
OPERATION
5. Connect the master and slave unit in series as
shown above.
6. Reattach the terminal cover.
Page 44
Note
Ensure load cables have sufficient current capacity.
Page 41
Re-attach the protection dummy plug when not in use.
Master-Slave Configuration
Before using the power supplies in series, the master and slave units need to be configured.
1. Configure the OVP and OCP
settings for the master unit.
Page 57
2. For each unit, hold the Function
key while turning the power on to enter the power on configuration settings.
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP Set
Output
PWR DSPLLock/LocalTest
PSW 30 -36
360W
Voltage
Current
Multi-Range DC Power Supply
3. Configure F-93 (Master/Slave)
setting for each master/slave unit.
Page 114 Unit
F-93
Master (local or series operation)
0
Slave unit (series)
4
4. Cycle the power on the units (reset the power).
Master-Slave Series Operation
85
PSW Series User Manual
Note
Configuration settings can be checked for both the master and slave units by pressing the Function key.
Master-Slave Operation
Only operate the power supplies in series if the units are configured correctly.
1. Turn on the master and slave unit. The slave
unit will only show the combined voltage of both units while the master unit will show both the combined voltage and the current of both units.
Master unit
Slave unit
V
A
V
2. Operation of all units is controlled
via the master unit. Operation of the master unit is the same as for a single unit. Please see the basic operation chapter for details.
Page 57
3. Press the Output key to begin.
Output
CAUTION
Only operate the power supplies in series if using units of the same model number. 250V and 800V models do not support series operation!
Only a maximum of 2 units can be used in series.
Note
The panel controls are disabled on slave units, including the output key.
86
OPERATION
Test Scripts
This section describes how to use the Test function to run, load and save test scripts for automated testing. The Test function is useful if you want to perform a number of tests automatically. The PSW test function can store ten test scripts in memory.
Each test script is programmed in a scripting language. For more information on how to create test scripts, please contact GW Instek.
Test Script File Format→ from page 88 Test Script Settings → from page 88 Setting the Test Script Settings → from page 89 Load Test Script → from page 90 Run Test Script (Manually) → from page 91 Run Test Script (Automatically at startup) → from page 92 Export Test Script → from page 93 Remove Test Script → from page 94 Check the Available Memory Capacity → from page 95
87
PSW Series User Manual
Background
The test files are saved in *.tst file format.
Each file is saved as tXXX.tst, where XXX is the save file number 001~010.
Test Run
Runs the chosen test script from the internal memory. A script must first be loaded into the internal memory before it can be run. See the test function Test Save, below.
The script will run as soon as the test function is started.
T-01
1~10
Test Load
Loads a test script from the USB drive to the designated save slot in memory. A script must first be loaded into internal memory before it can be run.
T-02
1~10 (USBPSW)
Test Export
Exports a script from the designated memory save slot to the USB drive.
T-03
1~10 (PSWUSB)
Test Remove
Deletes the chosen test file from the PSW internal memory.
T-04
1~10
Test Memory
Displays the amount of internal memory that is available on the unit in kilobytes (1024 bytes).
T-05
Max: 1848 KB
Test Script File Format
Test Script Settings
88
OPERATION
Steps
The test script settings (T-01~T-04) are set with the Test key.
1. Press the Test key. The Test key
will light up.
Test
2. The display will show T-01 on the top and the
memory no. for T-01 on the bottom.
Test Setting
Memory
number
3. Rotate the Voltage knob to change
the T setting (Test setting).
Voltage
Test Run Test Load Test Export Test Remove Test Memory
T-01 T-02 T-03 T-04 T-05
4. Rotate the Current knob to choose
a memory number.
Current
Range
1~10
5. Press the Voltage knob to complete
the setting.
Voltage
Setting the Test Script Settings
89
PSW Series User Manual
Exit
Press the Test key again to exit the Test settings. The Test key light will turn off.
Test
Overview
Before a test script can be run, it must first be loaded into a one of the 10 memory save slots. Before loading a test script into memory:
Ensure the script file is placed in the root
directory.
Ensure the file name number corresponds to
the memory number that you wish to save to.
For example: A test file named t001.tst can only be saved to memory number 01, t002.tst can only be saved to memory number 02, and so on.
Steps
1. Insert a USB flash drive into the
front panel USB-A slot. Ensure the flash drive contains a test script in the root directory.
2. Turn on the power. MS (Mass Storage) will be
displayed on the screen after a few seconds if the USB drive is recognized.
Load Test Script from USB
90
OPERATION
Note
If the USB drive is not recognized, check to see that the function settings for F-20 = 1 (page 106). If not, reinsert the USB flash drive.
3. Configure T-02 (Test Load) to 1~10
(save memory slot)
Page 89
T-02 range
1~10 (t001 ~t010)
4. The script will now be available in the memory
slot the script was saved to.
Note
Error messages: If you load a file that is not
present on the USB drive “Err 002” will be
displayed on the display.
Overview
A test script can be run from one of ten memory slots.
Steps
1. Before a test script can be run, it
must first be loaded into one of the 10 memory save slots.
Page 90
2. Configure T-01 (Run Test) to 1~10
(save memory slot#)
Page 89
T-01 range
1~10
3. The test script will automatically start to run.
Run Test Script (Manual)
91
PSW Series User Manual
Note
Error messages: If you try to run a test script from an empty memory location “Err 003” will be displayed on the display.
Note
When a script starts to run, there is no way to abort the script. Pressing the Output key has no effect. If you wish to stop a test early, turn the power off.
Overview
The power supply can be configured to automatically run a test script at startup.
Steps
1. Before a test script can be run, it
must first be loaded into one of the 10 memory save slots.
Page 90
2. Turn the unit off.
3. Enter the power-on configuration
settings and set F-92 (Power-ON Output) to run the desired test script.
Page 114
Range
T001~T010*
4. The selected test script will automatically start
to run the next time the unit is powered on.
Run Test Script (Automatically at Startup)
92
OPERATION
Note
*Setting F-92 to 0 or 1 will disable loading a test script at startup. 0 will turn the output off at startup. 1 will turn the output on at startup. See the power on configuration settings for details, page 110.
Note
When a script starts to run, there is no way to abort the script. Pressing the Output key has no effect. If you wish to stop a test early, turn the power off.
Overview
The Export Test function saves a test file to the root directory of a USB flash drive.
Files will be saved as tXXX.tst where XXX is
the memory number 001~010 from which the test script was exported from.
Files of the same name on the USB flash
drive will be written over.
Steps
1. Insert a USB flash drive into the
front panel USB-A slot.
2. Turn on the power. MS (Mass Storage) will be
displayed on the screen after a few seconds if the USB drive is recognized.
Export Test Script to USB
93
PSW Series User Manual
Note
If the USB drive is not recognized, check to see that the function settings for F-20 = 1 (page 106). If not, reinsert the USB flash drive.
3. Configure T-03 (Test Export) to
0~10 (save memory slot)
Page 89
T-03 range
1~10
4. The script will now be copied to the USB flash
drive.
Note
Error messages: If you try to export a test script from an empty memory location “Err 003” will be displayed on the display.
Overview
The Remove Test function will delete a test script from the internal memory.
Steps
1. Select T-04 (Test Remove) and
choose which test script to remove from the internal memory.
Page 89
T-04 range
1~10
2. The test script will be removed from the
internal memory.
Remove Test Script
94
OPERATION
Note
Error messages: If you try to remove a test script from an empty memory location “Err 003” will be displayed on the display.
Overview
The T-05 function displays the amount of internal memory that is left on the unit to load test scripts. The displayed units are in kilobytes (1024 bytes).
Steps
Select T-05 (Test Memory). The available memory in kilobytes is displayed.
Page 89
T-05 range
1~1848 KB
Checking the Available Memory
95
PSW Series User Manual
Configuration .................................................................. 97
Configuration Table ................................................................................................ 97
Normal Function Settings .................................................................................... 102
USB/GPIB Settings .............................................................................................. 106
LAN Settings .......................................................................................................... 107
System Settings ....................................................................................................... 108
Power On Configuration Settings ....................................................................... 110
Calibration .............................................................................................................. 111
CONFIGURATION
96
CONFIGURATION
Normal Function Settings
Setting
Setting Range
Output ON delay time
F-01
0.00s~99.99s
Output OFF delay time
F-02
0.00s~99.99s
V-I mode slew rate select
F-03
0 = CV high speed priority 1 = CC high speed priority 2 = CV slew rate priority 3 = CC slew rate priority
Rising voltage slew rate
F-04
0.01V/s~60.00V/s (PSW 30-XX)
0.1V/s~160.0V/s (PSW 80-XX)
0.1V/s~320.0V/s (PSW 160-XX)
0.1V/s~500.0V/s (PSW 250-XX) 1V/s~1600V/s (PSW 800-XX)
Falling voltage slew rate
F-05
0.01V/s~60.00V/s (PSW 30-XX)
0.1V/s~160.0V/s (PSW 80-XX)
0.1V/s~320.0V/s (PSW 160-XX)
0.1V/s~500.0V/s (PSW 250-XX) 1V/s~1600V/s (PSW 800-XX)
Configuration
Configuration of the PSW power supplies is divided into five different configuration settings: Normal Function, USB/GPIB, LAN, Power ON Configuration, Calibration Settings and System Settings. Power ON Configuration differs from the other settings in that the settings used with Power ON Configuration settings can only be set during power up. The other configuration settings can be changed when the unit is already on. This prevents some important configuration parameters from being changed inadvertently. Power On Configuration settings are numbered F-90 to F-95 and the other configuration settings are numbered F-00 to F-61 and F-88 to F-89.
Configuration Table
Please use the configuration settings listed below when applying the configuration settings.
97
PSW Series User Manual
Rising current slew rate
F-06
0.01A/s~72.00A/s (PSW 30-36)
0.1A/s~144.0A/s (PSW 30-72)
0.1A/s~216.0A/s (PSW 30-108)
0.01A/s~27.00A/s (PSW 80-13.5)
0.01A/s~54.00A/s (PSW 80-27)
0.01A/s~81.00A/s (PSW 80-40.5)
0.01A/s~14.40A/s (PSW 160-7.2)
0.01A/s~28.80A/s (PSW 160-14.4)
0.01A/s~43.20A/s (PSW 160-21.6)
0.001A/s ~ 9.000A/s (PSW 250-4.5)
0.01A/s ~ 18.00A/s (PSW 250-9)
0.01A/s ~ 27.00A/s (PSW 250-13.5)
0.001A/s ~ 2.880A/s (PSW 800-1.44)
0.001A/s ~ 5.760A/s (PSW 800-2.88)
0.001A/s ~ 8.640A/s (PSW 800-4.32)
Falling current slew rate
F-07
0.01A/s~72.00A/s (PSW 30-36)
0.1A/s~144.0A/s (PSW 30-72)
0.1A/s~216.0A/s (PSW 30-108)
0.01A/s~27.00A/s (PSW 80-13.5)
0.01A/s~54.00A/s (PSW 80-27)
0.01A/s~81.00A/s (PSW 80-40.5)
0.01A/s~14.40A/s (PSW 160-7.2)
0.01A/s~28.80A/s (PSW 160-14.4)
0.01A/s~43.20A/s (PSW 160-21.6)
0.001A/s ~ 9.000A/s (PSW 250-4.5)
0.01A/s ~ 18.00A/s (PSW 250-9)
0.01A/s ~ 27.00A/s (PSW 250-13.5)
0.001A/s ~ 2.880A/s (PSW 800-1.44)
0.001A/s ~ 5.760A/s (PSW 800-2.88)
0.001A/s ~ 8.640A/s (PSW 800-4.32)
98
CONFIGURATION
Internal resistance setting
F-08
0.000~0.833 (PSW 30-36)
0.000~0.417 (PSW 30-72)
0.000~0.278 (PSW 30-108)
0.000~5.926 (PSW 80-13.5)
0.000~2.963 (PSW 80-27)
0.000~1.975 (PSW 80-40.5)
0.000~22.222 (PSW 160-7.2)
0.000~11.111 (PSW 160-14.4)
0.000~7.407 (PSW 160-21.6)
0.00Ω ~ 55.55Ω (PSW 250-4.5)
0.00Ω ~ 27.77Ω (PSW 250-9)
0.00Ω ~ 18.51Ω (PSW 250-13.5)
0.0Ω ~ 555.5Ω (PSW 800-1.44)
0.0Ω ~ 277.8Ω (PSW 800-2.88)
0.0Ω ~ 185.1Ω (PSW 800-4.32)
Bleeder circuit control
F-09
0 = OFF, 1 = ON
Buzzer ON/OFF control
F-10
0 = OFF, 1 = ON
Measurement Average Setting
F-17
0 = Low, 1 = Middle, 2 = High
Lock Mode
F-19
0 = Panel lock: allow output off 1 = Panel lock: allow output on/off
USB/GPIB settings
Front panel USB State
F-20
0 = Absent, 1 = Mass Storage
Rear panel USB State
F-21
0 = Absent, 2 = USB-CDC, 3 = GPIB­USB adapter
Rear panel USB mode
F-22
0 = Disable, 1 = GPIB-USB adapter, 2 = Auto detect speed, 3 = Full speed only
GPIB address
F-23
0~30
LAN settings
MAC Address-1
F-30
0x00~0xFF
MAC Address-2
F-31
0x00~0xFF
MAC Address-3
F-32
0x00~0xFF
MAC Address-4
F-33
0x00~0xFF
MAC Address-5
F-34
0x00~0xFF
MAC Address-6
F-35
0x00~0xFF
LAN
F-36
0 = Disable, 1 = Enable
DHCP
F-37
0 = Disable, 1 = Enable
IP Address-1
F-39
0~255
IP Address-2
F-40
0~255
99
PSW Series User Manual
IP Address-3
F-41
0~255
IP Address-4
F-42
0~255
Subnet Mask-1
F-43
0~255
Subnet Mask-2
F-44
0~255
Subnet Mask-3
F-45
0~255
Subnet Mask-4
F-46
0~255
Gateway-1
F-47
0~255
Gateway-2
F-48
0~255
Gateway-3
F-49
0~255
Gateway-4
F-50
0~255
DNS address -1
F-51
0~255
DNS address -2
F-52
0~255
DNS address-3
F-53
0~255
DNS address-4
F-54
0~255
Sockets active
F-57
0 = Disable, 1 = Enable
Web Server active
F-59
0 = Disable, 1 = Enable
Web password active
F-60
0 = Disable, 1 = Enable
Web setting password
F-61
0000~9999
System Settings
Factory Set Value
F-88
0 = Disable 1 = Return to factory settings
Show Version
F-89
0, 1 = PSW version 2, 3 = PSW build year 4, 5 = PSW build month/day 6, 7 = Keyboard CPLD version 8, 9 = Analog-Control CPLD version A, B = Reserved C, D = Kernel build year E, F = Kernel build month/day G, H = Test command version I, J = Test command build year K, L = Test command build month/day
M, N = USB Driver version.
Power On Configuration Settings*
100
Loading...