This manual contains proprietary information, which is protected by
copyright. All rights are reserved. No part of this manual may be
photocopied, reproduced or translated to another language without
prior written consent of Good Will company.
The information in this manual was correct at the time of printing.
However, Good Will continues to improve products and reserves the
rights to change specification, equipment, and maintenance
procedures at any time without notice.
Good Will Instrument Co., Ltd.
No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.
Certificate Of Compliance ...................................... 209
INDEX .......................................................................... 210
4
SAFETY INSTRUCTIONS
WARNING
Warning: Identifies conditions or practices that
could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that
could result in damage to the PSU or to other
properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
SAFETY INSTRUCTIONS
This chapter contains important safety
instructions that you must follow during
operation and storage. Read the following before
any operation to insure your safety and to keep
the instrument in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the
instrument.
5
PSU Series User Manual
Do not dispose electronic equipment as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased.
General
Guideline
CAUTION
Do not place any heavy object on the PSU.
Avoid severe impact or rough handling that
leads to damaging the PSU.
Do not discharge static electricity to the PSU.
Use only mating connectors, not bare wires, for
the terminals.
Do not block the cooling fan opening.
Do not disassemble the PSU unless you are
qualified.
(Measurement categories) EN61010-1:2010 and EN61010-2-030
specifies the measurement categories and their requirements as
follows. The PSU falls under category II.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
0 is for measurements performed on circuits not directly
connected to Mains.
Power Supply
WARNING
AC Input voltage range: 85Vac~265Vac
Frequency: 47Hz to 63Hz
To avoid electrical shock connect the protective
grounding conductor of the AC power cord to
an earth ground.
Safety Guidelines
6
SAFETY INSTRUCTIONS
Cleaning the PSU
Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Operation
Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Relative Humidity: 20%~ 85% (no condensation)
Altitude: < 2000m
Temperature: 0°C to 50°C
(Pollution Degree) EN61010-1:2010 and EN61010-2-030 specifies
the pollution degrees and their requirements as follows. The PSU
falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric
strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused
by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to
condensation which is expected. In such conditions, equipment
is normally protected against exposure to direct sunlight,
precipitation, and full wind pressure, but neither temperature
nor humidity is controlled.
Do not dispose this instrument as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased. Please make sure
discarded electrical waste is properly recycled to
reduce environmental impact.
7
PSU Series User Manual
Green/ Yellow:
Earth
Blue:
Neutral
Brown:
Live (Phase)
Power cord for the United Kingdom
When using the power supply in the United Kingdom, make sure
the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED
IMPORTANT: The wires in this lead are coloured in accordance with the
following code:
As the colours of the wires in main leads may not correspond with
the coloured marking identified in your plug/appliance, proceed
as follows:
The wire which is coloured Green & Yellow must be connected to
the Earth terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal
which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the
terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment
or contact the supplier.
This cable/appliance should be protected by a suitably rated and
approved HBC mains fuse: refer to the rating information on the
equipment and/or user instructions for details. As a guide, a cable
of 0.75mm2 should be protected by a 3A or 5A fuse. Larger
conductors would normally require 13A types, depending on the
connection method used.
Any exposed wiring from a cable, plug or connection that is
engaged in a live socket is extremely hazardous. If a cable or plug is
deemed hazardous, turn off the mains power and remove the cable,
any fuses and fuse assemblies. All hazardous wiring must be
immediately destroyed and replaced in accordance to the above
standard.
8
GETTING STARTED
PSU Series Overview................................................ 10
Series lineup ...................................................................................... 10
Main Features ................................................................................... 11
This chapter describes the power supply in a
nutshell, including its main features and front /
rear panel introduction. After going through the
overview, please read the theory of operation to
become familiar with the operating modes,
protection modes and other safety considerations.
9
PSU Series User Manual
Model name
Voltage Rating1
Current Rating2
Power
PSU 6-200
6V
200A
1200W
PSU 8-180
8V
180A
1440W
PSU 12.5-120
12.5V
120A
1500W
PSU 15-100
15V
100V
1500W
PSU 20-76
20V
76A
1520W
PSU 30-50
30V
50A
1500W
PSU 40-38
40V
38A
1520W
PSU 50-30
50V
30A
1500W
PSU 60-25
60V
25A
1500W
PSU 80-19
80V
19A
1520W
PSU 100-15
100V
15A
1500W
PSU 150-10
150V
10A
1500W
PSU 300-5
300V
5A
1500W
PSU 400-3.8
400V
3.8A
1520W
PSU 600-2.6
600V
2.6A
1560W
1
Minimum voltage guaranteed to 0.2% of rating voltage.
2
Minimum current guaranteed to 0.4% of rating current.
PSU Series Overview
Series lineup
The PSU series consists of 15 models, covering a number of
different current, voltage and power capacities:
10
Main Features
Performance
High power density: 1500W in 1U
Universal input voltage 85~265Vac, continuous
operation.
Output voltage up to 600V, current up to 200A.
Features
Active power factor correction.
Parallel master/slave operation with active
current sharing.
Remote sensing to compensate for voltage drop
in load leads.
19” rack mounted ATE applications.
A built-in Web server.
OVP, OCP and OHP protection.
Preset memory function.
Adjustable voltage and current slew rates.
Bleeder circuit ON/OFF setting.
CV, CC priority start function. (Prevents
overshoot with output ON)
Supports test scripts.
Interface
Built-in RS-232/485, LAN and USB interface.
Analog output programming and monitoring.
Optional interfaces: GPIB, Isolated Voltage (0-
5V/0-10V) and Isolated Current (4-20mA)
programming and monitoring interface.
(Factory options)
GETTING STARTED
11
PSU Series User Manual
Standard
Accessories
Part number
Description
Qty.
Output terminal cover
1
Analog connector plug kit
1
Output terminal M8 bolt set
(6V~60V model)
1
Input terminal cover
1
Power Cord (230VAC/10A,
1.8M, provide for some region
only)
1
82GW1SAFE0M*1
Safety Guide
1
62SB-8K0HD1*1
1U Handle, ROHS
2 62SB-8K0HP1*1
1U BRACKET (LEFT), RoHS
1
62SB-8K0HP2*1
1U BRACKET (RIGHT), RoHS
1
CD-ROM
User manual, Programming
manual
1 set
82SU-PSU00K*1
Packing list
82GW-00000C*1
* CTC GW/INSTEK JAPAN
USE ,RoHS
1
Factory Installed
Options
Part number
Description
PSU-GPIB
GPIB interface
PSU-ISO-V
Voltage programming isolated analog
interface
PSU-ISO-I
Current programming isolated analog
interface
PSU-001
Front Panel Filter Kit (Operation
Temperature is guaranteed to 40˚C)
Accessories
Before using the PSU power supply unit, check the package
contents to make sure all the standard accessories are included.
12
GETTING STARTED
Optional
Accessories
Part number
Description
PSU-01C
Cable for 2 units of PSU-Series in
parallel mode connection
PSU-01B
Bus Bar for 2 units of PSU-Series in
parallel mode connection
PSU-01A
Joins a vertical stack of 2 PSU units
together. 2U-sized handles x2, joining
plates x2.
PSU-02C
Cable for 3 units of PSU-Series in
parallel mode connection
PSU-02B
Bus Bar for 3 units of PSU-Series in
parallel mode connection
PSU-02A
Joins a vertical stack of 3 PSU units
together. 3U-sized handles x2, joining
plates x2.
PSU-03C
Cable for 4 units of PSU-Series in
parallel mode connection
PSU-03B
Bus Bar for 4 units of PSU-Series in
parallel mode connection
PSU-03A
Joins a vertical stack of 4 PSU units
together. 4U-sized handles x2, joining
plates x2.
PSU-232
RS232 cable with DB9 connector kit.
It Includes RS232 cable with DB9
connector, RS485 used master cable
(gray plug), slave cable (black plug),
intermediate connector and end
terminal connector.
PSU-485
RS485 cable with DB9 connector kit.
It Includes RS485 cable with DB9
connector, RS485 used master cable
(gray plug), slave cable (black plug),
intermediate connector and end
terminal connector.
Power Cord SJT 12AWG/3C, 3m MAX
Length, 105 ºC, RNB5-5*3P UL/CSA
type
GPW-002
Power Cord H05W-F 1.5mm2/3C, 3m
MAX Length, 105 ºC, RNB5-5*3P VDE
type
GPW-003
Power Cord VCTF 3.5mm2/3C, 3m
MAX Length, 105 ºC, RNB5-5*3P PSE
type
Download
Name
Description
psu_cdc.inf
PSU USB driver
Other
Name
Description
Certificate of traceable calibration
14
GETTING STARTED
Lock/Local PROT Function Test SetOutput
Unlock ALM_CLR M 1 M 2 M 3
Shift
: Long Push
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGECURRENT
PSU 40-38
DC Power Supply
0 -40V / 0 - 38A
VoltageCurrent
2345
Display Area
1
116 7 8 9 1012 13
1.
Power Switch
Used to turn the power on/off.
2.
USB A Port
USB A port for data transfer,
loading test scripts etc.
3.
Air Inlet
Air inlet for cooling the inside of
the PSU series.
4.
Voltage Knob
Voltage
Used to set the voltage value or
select a parameter number in the
Function settings.
Display Area
The display area shows setting values, output
values and parameter settings. The function LEDs
below show the current status and mode of the
power supply. See page 18 for details.
5.
Current Knob
Current
Used to set the current value or
change the value of a Function
parameter.
Appearance
PSU Series Front Panel
15
PSU Series User Manual
6.
Lock/Local
Button
Lock/Local
Unlock
Used to lock all front panel
buttons other than the Output
Button or it switches to local
mode.
Unlock
Button
(Long push) Used to unlock the
front panel buttons.
7.
PROT Button
PROT
ALM_CLR
Used to set and display OVP, OCP
and UVL.
ALM_CLR
Button
(Long push) Used to release
protection functions that have
been activated.
8.
Function
Button
Function
M1
Used to configure the various
functions.
M1 Button
(+Shift) Used to recall the M1
setup.
(+Shift and hold) Used to save the
current setup to M1.
9.
Test Button
TEST
M2
Used to run customized scripts for
testing.
M2 Button
(+Shift) Used to recall the M2
setup.
(+Shift and hold) Used to save the
current setup to M2.
10.
Set Button
SET
M3
Used to set and confirm the output
voltage and output current.
M3 Button
(+Shift) Used to recall the M3
setup.
(+Shift and hold) Used to save the
current setup to M3.
16
GETTING STARTED
11.
Shift Button
Shift
Used to enable the functions that
are written in blue characters
below certain buttons.
12.
Output
Button
Output
Used to turn the output on or off.
13.
Output ON
LED
Lights in green when the output is
on.
17
PSU Series User Manual
VSRLANRMTERRDLYALMISRM 1M 2M 3RUN
C C
A
C V
V
VOLTAGECURRENT
Display Area
14151617
18192021222324
25
262728
14.
Voltage
Meter
Displays the voltage or the parameter number of a
Function parameter.
15.
Current
Meter
Displays the current or the value of a Function
parameter.
16.
CV LED
Lights in green during constant voltage mode.
17.
CC LED
Lights in green during constant current mode.
18.
VSR LED
Lights up when CV Slew Rate Priority is enabled.
19.
LAN LED
Lights up when the LAN interface is connected.
20.
RMT LED
Lights in green during remote control.
21.
ERR LED
Lights in red when an SCPI error has occurred.
22.
DLY LED
The Output On/Off Delay indicator LED.
23.
ALM LED
Lights in red when a protection function has been
activated.
PSU Series Display and Operation Panel
18
GETTING STARTED
24.
ISR LED
Lights up when CC Slew Rate Priority is enabled.
25.
M1 LED
Lights in green when the memory value are being
recalled or saved.
26.
M2 LED
Lights in green when the memory value are being
recalled or saved.
27.
M3 LED
Lights in green when the memory value are being
recalled or saved.
28.
RUN LED
Lights up when a Test Script has been activated.
Note
Only the ERR and ALM LED’s are red. All the others
are green.
19
Rear Panel
S LS SLSNC
REMOTE SENSE
ANALOG PROGRAMMING
RS485 / 232
OUT IN
LAN
DC OUTPUT
AC INPUT
L N
100 240V
2000VA MAX.
AC
47 63Hz
23415678
910
6-60V models:
PSU 6-200, 8-180, 12.5-120,
80-600V models:
PSU 80-19, 100-15, 150-10,
S LS SLSNC
REMOTE SENSE
ANALOG PROGRAMMING
OUT IN
RS485 / 232
LAN
L N
AC INPUT
100 240V
2000VA MAX.
AC
47 63Hz
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
0 – 5V / 0 – 10V
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
4 – 20mA
15-100, 20-76, 30-50,
40-38, 50-30, 60-25
300-5, 400-3.8, 600-2.6
1.
AC Input
LN
AC INPUT
Wire clamp connector.
2.
DC Output
Output terminals for 6V to 60V
models.
Output terminals for 80V to 600V
models.
3.
USB
USB port for controlling the PSU
remotely.
PSU Series User Manual
20
GETTING STARTED
4.
LAN
LAN
RS 485 / 232
Ethernet port for controlling the
PSU remotely.
5.
Remote-IN
LAN
RS 485 / 232
Two different types of cables can
be used for RS232 or RS485-based
remote control.
PSU-232: RS232 cable with DB9
connector kit.
PSU-485: RS485 cable with DB9
connector kit.
6.
Remote-OUT
LAN
RS 485 / 232
RJ-45 connector that is used to
daisy chain power supplies with
the Remote-IN port to form a
communication bus.
PSU-485S: Serial link cable with
RJ-45 shielded connector.
7.
Analog
Control
ANALOG PROGRAMMING
External analog control connector.
8.
Remote
Sense
S LSSLSNC
Compensation of load wire drop.
9.
Option Slot
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
0 – 5V / 0 – 10V
Blank sub-plate for standard
units.
Isolated Analog connector for
units equipped with Isolated
Current and Voltage
Programming and Monitoring
option.
GPIB connector for units
equipped with IEEE
programming option.
21
PSU Series User Manual
10.
Ground
Screw
Connectors for grounding the output (two
positions, shown in red).
L N
AC INPUT
100 240V
2000VA MAX.
AC
47 63Hz
22
GETTING STARTED
Background
The PSU power supplies are regulated DC power
supplies with a high voltage and current output.
These operate in CC or CV mode within a wide
operating range limited only by the voltage or
current output.
The operating area of each power supply is
determined by the rated output power as well as
the voltage and current rating.
Below is a comparison of the operating areas of
each power supply.
PSU Series Operating Area (6-80V models)
Current (A)
Voltage (V)
20
3876120
12018016080601000140
0
10
20
30
200
200
40
50
60
25
6
20 40
PSU 6-200
PSU 8-180
PSU 12.5-120
PSU 15-100
PSU 20-76
PSU 30-50
PSU 40-38
PSU 50-30
PSU 60-25
PSU 80-19
80
180
15
12.5
8
30
40
50
80
10050196030
70
Theory of Operation
The theory of operation chapter describes the basic principles of
operation, protection modes and important considerations that
must be taken into account before use.
Operating Area Description
23
PSU Series User Manual
PSU Series Operating Area (100-600V models)
Current (A)
Voltage (V)
300
3.8510
400
12168610
0
14
0
100
200
300
15
600
400
500
600
2.6
100
150
PSU 100-15
PSU 150-10
PSU 300-5
PSU 400-3.8
PSU 600-2.6
42
CC and CV mode
Description
When the power supply is operating in constant
current mode (CC) a constant current will be
supplied to the load. When in constant current
mode the voltage output can vary, whilst the
current remains constant. When the load
resistance increases to the point where the set
current limit (I
SET
) can no longer be sustained the
power supply switches to CV mode. The point
where the power supply switches modes is the
crossover point.
When the power supply is operating in CV mode,
a constant voltage will be supplied to the load,
whilst the current will vary as the load varies. At
the point that the load resistance is too low to
maintain a constant voltage, the power supply will
switch to CC mode and maintain the set current
limit.
The conditions that determine whether the power
supply operates in CC or CV mode depends on
the set current (I
SET
), the set voltage (V
SET
), the load
CC and CV Mode
24
GETTING STARTED
resistance (RL) and the critical resistance (RC). The
critical resistance is determined by V
SET/ISET
. The
power supply will operate in CV mode when the
load resistance is greater than the critical
resistance. This means that the voltage output will
be equal to the V
SET
voltage but the current will be
less than I
SET
. If the load resistance is reduced to
the point that the current output reaches the I
SET
level, the power supply switches to CC mode.
Conversely the power supply will operate in CC
mode when the load resistance is less than the
critical resistance. In CC mode the current output
is equal to I
SET
and the voltage output is less than
V
SET
.
RL=R
C
RL<R
C
VSET
ISET
CV
CC
V
I
RL>R
C
Crossover
point
Note
For loads that generate a transient surge voltage, VSET
must be set so that the surge voltage does not reach
the voltage limit.
For loads in which transient peak current flows, ISET
must be set so that the peak value does not reach the
current limit.
25
Slew Rate
Theory
The PSU has selectable slew rates for CC and CV
mode. This gives the PSU power supply the ability
to limit the current/voltage draw of the power
supply. Slew rate settings are divided into High
Speed Priority and Slew Rate Priority. High speed
priority mode will use the fastest slew rate for the
instrument. Slew Rate Priority mode allows for
user adjustable slew rates for CC or CV mode. The
rising and falling slew rate can be set
independently.
High Speed
Priority
mode
Slew rate =
Enabled
Background
The PSU DC power supplies employ a bleed
resistor in parallel with the output terminals.
PSU
Load
Bleed
resistor
Bleed resistors are designed to dissipate the power
from the power supply filter capacitors when
power is turned off and the load is disconnected.
Without a bleed resistor, power may remain
charged on the filter capacitors for some time and
PSU Series User Manual
Bleeder Control
26
GETTING STARTED
be potentially hazardous.
In addition, bleed resistors also allow for smoother
voltage regulation of the power supply as the
bleed resistor acts as a minimum voltage load.
The bleed resistance can be turned on or off using
the configuration settings.
Note
By default the bleed resistance is on. For battery
charging applications, be sure to turn the bleed
resistance off as the bleed resistor can discharge the
connected battery when the unit is off.
Background
On the PSU, the internal resistance of the power
supply can be user-defined in software. (Internal
Resistance Setting, see the Normal Function
Settings on page 101.) When the internal resistance
is set it can be seen as a resistance in series with
the positive output terminal. This allows the
power supply to simulate power sources that have
internal resistances such as lead acid batteries.
By default the internal resistance is 0Ω.
Internal
Resistance Range
Unit Model
Internal Resistance Range
PSU 6-200
0.000 ~ 0.030Ω
PSU 8-180
0.000 ~ 0.044Ω
PSU 12.5-120
0.000 ~ 0.104Ω
PSU 15-100
0.000 ~ 0.150Ω
PSU 20-76
0.000 ~ 0.263Ω
PSU 30-50
0.000 ~ 0.600Ω
PSU 40-38
0.000 ~ 1.053Ω
PSU 50-30
0.000 ~ 1.667Ω
PSU 60-25
0.000 ~ 2.400Ω
PSU 80-19
0.000 ~ 4.210Ω
Internal Resistance
27
PSU Series User Manual
PSU 100-15
0.000 ~ 6.667Ω
PSU 150-10
0.00 ~ 15.00Ω
PSU 300-5
0.00 ~ 60.00Ω
PSU 400-3.8
0.0 ~ 105.3Ω
PSU 600-2.6
0.0 ~ 230.8Ω
OVP
Over voltage protection (OVP) prevents a high
voltage from damaging the load. This alarm can
be set by the user.
OCP
Over current protection prevents high current
from damaging the load. This alarm can be set by
the user.
UVL
Under voltage limit. This function sets a minimum
voltage setting level for the output. It can be set by
the user.
OHP
Over temperature protection for slave and master
board. OHP is a hardware protection function.
Only when the unit has cooled can the over
temperature protection alarms be cleared.
OH1
Master board over temperature protection.
OH2
Slave board over temperature protection.
Alarms
The PSU power supplies have a number of protection features.
When one of the protection alarms is tripped, the ALM icon on the
display will be lit and the type of alarm that has been tripped will
be shown on the display. When an alarm has been tripped the
output will be automatically turned off. For details on how to clear
an alarm or to set the protection modes, please see page 49.
28
GETTING STARTED
ALM SENS
Sense alarm. This alarm will detect if the sense
wires have been connected to the wrong polarity.
HW OVP
Hardware over voltage protection. This is a
hardware OVP that is fixed at approximately
120% of the rated voltage output.
AC
AC Fail. This alarm function is activated when a
low AC input is detected.
FAN FAIL
Fan failure. This alarm function is activated when
the fan RPMs drop to an abnormally low level.
Shutdown
Force Shutdown is not activated as a result of the
PSU series detecting an error. It is a function that
is used to turn the output off through the
application of a signal from the rear-panel analog
control connector when an abnormal condition
occurs.
Alarm output
Alarms are output via the analog control
connector. The alarm output is an isolated opencollector photo coupler output.
Inrush current
When the power supply switch is first turned on,
an inrush current is generated. Ensure there is
enough power available for the power supply
when first turned on, especially if a number of
units are turned on at the same time.
Pulsed or Peaked
loads
When the load has current peaks or is pulsed, it is
possible for the maximum current to exceed the
mean current value. The PSU power supply
Considerations
The following situations should be taken into consideration when
using the power supply.
29
PSU Series User Manual
ammeter only indicates mean current values,
which means for pulsed current loads, the actual
current can exceed the indicated value. For pulsed
loads, the current limit must be increased, or a
power supply with a greater capacity must be
chosen. As shown below, a pulsed load may
exceed the current limit and the indicated current
on the power supply ammeter.
Current limit
level
Measured
Ammeter
current
Reverse Current:
Regenerative load
When the power supply is connected to a
regenerative load such as a transformer or
inverter, reverse current will feed back to the
power supply. The PSU power supply cannot
absorb reverse current. For loads that create
reverse current, connect a resistor in parallel to the
power supply to bypass the reverse current. This
description only applies when the bleed resistance
is off.
PSULoad
Resistor
Reverse current
Note
The current output will decrease by the amount of
current absorbed by the resistor.
Ensure the resistor used can withstand the power
capacity of the power supply/load.
30
GETTING STARTED
Reverse Current:
Accumulative
energy.
When the power supply is connected to a load
such as a battery, reverse current may flow back to
the power supply. To prevent damage to the
power supply, use a reverse-current-protection
diode in series between the power supply and
load.
PSULoad
Diode
CAUTION
Ensure the reverse withstand voltage of the diode is
able to withstand 2 times the rated output voltage of
the power supply and the forward current capacity can
withstand 3 to 10 times the rated output current of
the power supply.
Ensure the diode is able to withstand the heat
generated in the following scenarios.
When the diode is used to limit reverse voltage,
remote sensing cannot be used.
Floating
As the output terminals are floating, the load and
all load cables must have an insulation capacity
that is greater than the isolation voltage of the
power supply.
Grounding
The output terminals of the PSU power supplies are isolated with
respect to the protective grounding terminal. The insulation
capacity of the load, the load cables and other connected devices
must be taken into consideration when connected to the protective
ground or when floating.
31
PSU Series User Manual
PSU
Load
Ext-V
Ext-R
Analog
connector
( ) Insulation capacity ≥ isolation voltage
of power supply
WARNING
If the insulation capacity of the load and load cables
are not greater than the isolation voltage of the power
supply, electric shock may occur.
Grounded output
terminal
If the positive or negative terminal is connected to
the protective ground terminal, the insulation
capacity needed for the load and load cables is
greatly reduced. The insulation capacity only
needs to be greater than the maximum output
voltage of the power supply with respect to
ground.
PSU
Load
Ext-V
Ext-R
Analog
connector
( ) Insulation capacity ≥ voltage of power
supply with respect to ground
CAUTION
If using external voltage control, do not ground the
external voltage terminal as this will create a short
circuit.
Master-Slave Series Overview ........................................................ 79
Series Connection ............................................................................ 81
Series Operation ............................................................................... 82
Test Scripts .............................................................. 85
Test Script File Format ................................................................... 86
Test Script Settings .......................................................................... 86
Setting the Test Script Settings ...................................................... 87
OPERATION
34
OPERATION
Load Test Script from USB ........................................................... 88
Run Test Script ................................................................................. 89
Export Test Script to USB ............................................................. 90
Remove Test Script ......................................................................... 91
35
PSU Series User Manual
Background
The PSU power supplies use a universal power
input that can be used with 100 and 240 Vac
systems. To connect or replace the power cord
(user supplied, specification below), use the
procedure below:
Warning
The following procedure should only be attempted by
competent persons.
Ensure the AC power cord is not connected to power.
Always allow the power supply to fully discharge
before disconnecting the AC power cord.
Recommended
Power Cord
Specifications
Note
25A 250V, 3x12 AWG, outer diameter: 9-11mm, rated
60 ºC min., 3m maximum length and approved by the
national safety standards for the country of use.
There are two type power cord protective sheaths in
the standard accessories. One is black color and it is
used for outer diameter: 8~13.5mm power cord.
The other is gray color and it is used for outer
diameter: 5.5~11.2mm power cord.
The PSU has a number of power cord options
available. Please see the optional accessories on page
12 for details.
Removal
1. Turn off the power switch and unplug the
power from the socket.
Set Up
Line Voltage Connection
36
OPERATION
2. Unscrew the power cord protective sheath.
3. Remove the 2 screws holding the power cord
cover and remove.
4. Remove the AC power cord wires with a flat
head screwdriver.
3
2
2-M3x6L
Pan Head Screw
GND: Green or
Green and Yellow
N: White or Blue
L: Black or Brown
4
Installation
1. Connect the AC power
cord wires to the AC input
terminals.
Black/Brown Line (L)
White/Blue Neutral (N)
Green /Green & Yellow
Ground ()
Wire gauge: Awg12 to
Awg10.
Wire diameter: 2.05mm-
2.588mm.
AC INPUT
2000VA MAX.
47 63Hz
100 240VAC
NL
Ground
Line
Neutral
2. Make sure the sheath is
tightened to the lock nut.
3. Re-install the power cord
cover.
Screw on
locknut
37
Power Up
Steps
1. Connect the power cord to the
universal power input.
Page 36
2. Press the POWER switch on.
3. The power supply will show the Power On
settings (Pon) at start up. If no Power On
settings are configured, the PSU will recover
the state right before the power was last turned
OFF. If used for the first time, the default
settings will appear on the display.
For default configuration settings, see page 194.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Note
You may also configure how the PSU will behave on
startup by altering the Power On Configuration
settings, see page 109.
Power Down
To turn the PSU power supply off, press the power
switch again (0 position). It may take a few
seconds for the power supply to fully turn off.
CAUTION
The power supply takes around 8 seconds to fully turn
on or shutdown.
Do not turn the power on and off quickly. Please wait
for the display to fully turn off.
PSU Series User Manual
38
OPERATION
Background
Before connecting the output terminals to a load,
the wire gauge of the cables should be considered.
It is essential that the current capacity of the load
cables is adequate. The rating of the cables must
equal or exceed the maximum current rated
output of the instrument.
Recommended
wire gauge
Wire Gauge
Nominal Cross
Section
Maximum Current
20
0.5
9 18
0.75
11
18113
16
1.5
18
14
2.5
24
12434
10645
8
10
64
6
16
88
4
25
120 2
32
145
1
50
190
00
70
240
000
95
290
0000
120
340
The maximum operation current depends on the
maximum allowable temperature of the insulation
on the cable.
Under this condition, above table figures the
maximum current that insulation’s temperature
rise should be under 60 degree and ambient
temperature must be less than 30 degrees.
To minimize noise pickup or radiation, the load
wires and remote sense wires should be twistedpairs of the shortest possible length. Shielding of
Wire Gauge Considerations
39
PSU Series User Manual
the sense leads may be necessary in high noise
environments. Where shielding is used, connect
the shield to the chassis via the rear panel ground
screw. Even if noise is not a concern, the load and
remote sense wires should be twisted-pairs to
reduce coupling, which might impact the stability
of the power supply. The sense leads should be
separated from the power leads.
Background
Before connecting the output terminals to the load,
first consider whether voltage sense will be used,
the gauge of the cable wiring and the withstand
voltage of the cables and load.
The output terminals are of two types:
- Two solid bars equipped with M8 sized bolt
and nuts for low voltage models (PSU 6-200,
8-180, 12.5-120, 15-100, 20-76, 30-50, 40-38,
50-30, 60-25)
- Clamp block terminals for medium and high
voltage models (PSU 80-19, 100-15, 150-10,
300-5, 400-3.8, 600-2.6).
WARNING
Dangerous voltages. Ensure that the power to the
instrument is disabled before handling the power
supply output terminals. Failing to do so may lead to
electric shock.
Steps
1. Turn the power switch off.
2. Remove the output terminal cover.
Page 42
Output Terminals
40
OPERATION
3. If necessary, connect the chassis
ground terminal to either the
positive or negative terminal. See
the grounding chapter for details.
Page 31
4. Choose a suitable wire gauge and
crimping terminal for the load
cables.
Page 39
5. Connect the positive load cable to the positive
output terminal and the negative cable to the
negative output terminal.
Use the included M8-sized bolt set to connect the
load cables to the output terminals. Make sure that
the connections are tight and that washers and spring
washers are used to ensure a good connection.
Reverse the procedure to remove the terminal
covers.
Using the Output Terminal Cover
42
OPERATION
Background
The PSU series are designed to be directly
mounted into 19 inch 1U rack mounts.
The PSU can be installed using the sliding mounts
(GW Part number: GRM-001). See the GRM-001
manual for installation instructions.
Rack mount
diagram: Sliding
mounts
The following diagram shows the approximate
dimensions of the GRM-001 sliding mounts. These
sliding mounts should only be used within racks with
a depth of 500mm.
405
380
Unit = mm
Background
The PSU power supplies use a novel method of
configuring parameter values only using the
voltage or current knobs. The knobs are used to
quickly edit parameter values at 0.01, 0.1 or 1 unit
steps at a time.
When the user manual says to set a value or
parameter, use the steps below.
Using the Rack Mount Kit
How to Use the Instrument
43
PSU Series User Manual
Example
Use the Voltage knob to set a voltage of 10.05
volts.
1. Repeatedly press the Voltage knob
until the least significant digit is
highlighted. This will allow the
voltage to be edited in 0.01 volt
steps.
2. Turn the Voltage knob till 0.05 volts
is shown on the voltage display.
Voltage
Voltage
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
3. Repeatedly press the Voltage knob until the
most significant digit is highlighted. This will
allow the voltage to be edited in 1 volt steps.
4. Turn the Voltage knob until 10.05 is shown.
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
Note
Notice the Set key becomes illuminated when setting
the current or voltage.
If the voltage or current knobs are unresponsive,
press the Set key first.
44
OPERATION
Background
The F-88 configuration setting allows the PSU to
be reset back to the factory default settings. See
page 194 for the default factory settings.
Steps
1. Press the Function key. The Function
key will light up.
Function
2. The display should show F-01 on the top and
the configuration setting for F-01 on the
bottom.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
3. Rotate the Voltage knob to change
the F setting to F-88 (Factory Set
Value).
Voltage
4. Use the Current knob to set the
F-88 setting to 1 (Return to factory
default settings).
Current
5. Press the Voltage knob to confirm.
ConF will be displayed when it is
configuring.
Voltage
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
6. Press the Function key again to exit.
The Function key light will turn off.
Function
Reset to Factory Default Settings
45
PSU Series User Manual
Background
The F-89 configuration setting allows you to view
the PSU version number, build date, keyboard
version, analog-control version, kernel build, test
command version and test command build date.
Steps
1. Press the Function key. The
Function key will light up.
Function
2. The display should show F-01 on the top and
the configuration setting for F-01 on the
bottom.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
3. Rotate the Voltage knob to change
the F setting to F-89 (Show Version).
Voltage
4. Rotate the Current knob to view the
version and build date for the
various items.
Current
F-89
0-XX: Version (1/2)
1-XX: Version (2/2)
2-XX: Build On-Year. (1/2)
3-XX: Build On-Year. (2/2)
4-XX: Build On-Month.
5-XX: Build On-Day.
6-XX: Keyboard CPLD. (1/2)
7-XX: Keyboard CPLD. (2/2)
8-XX: Analog Board CPLD. (1/2)
9-XX: Analog Board CPLD. (2/2)
A-XX: Analog Board FPGA (1/2)
B-XX: Analog Board FPGA. (1/2)
View System Version and Build Date
46
OPERATION
C-XX: Kernel Build On-Year. (1/2)
D-XX: Kernel Build On-Year. (2/2)
E -XX: Kernel Build On-Month.
F-XX: Kernel Build On-Day.
G-XX: Test Command Version. (1/2)
H-XX: Test Command Version. (2/2)
I-XX: Test Command Build On-Year. (1/2)
J-XX: Test Command Build On-Year. (2/2)
K-XX: Test Command Build On-Month.
L-XX: Test Command Build On-Day.
M-XX: Reserved. (1/2)
N-XX: Reserved. (2/2)
O-XX: Option version. (1/2)
P-XX: Option version. (2/2)
5. Press the Function key again to
exit. The Function key light will
turn off.
Function
Example
Main Program Version: V01.00, 2013/06-01
0-01: Version
1-00: Version
2-20: Build On-Year.
3-13: Build On-Year.
4-06: Build On-Month.
5-01: Build On-Day.
G-01: Test Command Version.
H-00: Test Command Version.
I-20: Test Command Build On-Year.
J-13: Test Command Build On-Year.
K-06: Test Command Build On-Month.
L-01: Test Command Build On-Day.
The OVP level and OCP level has a selectable
range that is based on the output voltage and
output current, respectively. The OVP and OCP
level is set to the highest level by default. The
actual selectable OVP and OCP range depends on
the PSU model.
When one of the protection measures are on, ALM
indicator is lit red on the front panel and the type
of alarm is also shown on the display. The
ALM_CLR button can be used to clear any
protection functions that have been tripped. By
default, the output will turn off when the OVP or
OCP protection levels are tripped.
The UVL will prevent you from setting a voltage
that is less than the UVL setting. The UVL setting
range is from 0% ~ 105% of the rated output
voltage.
Basic Operation
This section describes the basic operations required to operate the
power supply.
Setting OVP/OCP/UVL → from page 49
C.V. priority mode → from page 52
C.C. priority mode → from page 56
Panel lock → page 59
Save/Recall setups → from page 59/60
Voltage Sense → from page 61
Before operating the power supply, please see the Getting Started
chapter, page 9.
Setting OVP/OCP/UVL Levels
49
PSU Series User Manual
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Example: OVP alarm
Before setting the protection settings:
Ensure the load is not connected.
Ensure the output is turned off.
Note
You can use the Function settings (F-13 and F-14) to
apply limits to the voltage and current settings,
respectively. You can set limitations so that the values
do not exceed the set OVP and the set OCP level, and
so that the values are not lower than the set UVL trip
point.
By using this feature, you can avoid turning the output
off by mistakenly setting the voltage or current to a
value that exceeds the set OVP or OCP level or to a
value that is lower than the set UVL trip point.
If you have selected to limit the voltage setting (F-14),
you will no longer be able to set the output voltage to
a value that is above about 95% of the OVP trip point
or to a value that is lower than the UVL trip point.
If you have selected to limit the current setting (F-13),
you will no longer be able to set the output current to
a value that is above about 95% of the OCP trip point.
Steps
1. Press the PROT key. The PROT key
lights up.
PROT
50
OPERATION
2. The OVP protection function will be displayed
on the voltage display and the setting will be
displayed on the current display.
Protection
function
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
V
Protection
setting
A
Choose a
Protection
Function
3. Use the Voltage knob to select a
protection function.
Voltage
Range
OVP, OCP, UVL
Setting the
Protection Level
4. Use the Current knob to set the
protection level for the selected
function.
Current
Setting Range
PSU Model
OCP
OVP
UVL
6-200
5~220
0.6~6.6
0~6.3
8-180
5~198
0.8~8.8
0~8.4
12.5-120
5~132
1.25~13.75
0~13.12
15-100
5~110
1.5~16.5
0~15.75
20-76
5~83.6
2~22
0~21
30-50
5~55
3~33
0~31.5
40-38
3.8~41.8
4~44
0~42
50-30
3~33
5~55
0~52.5
60-25
2.5~27.5
5~66
0~63
80-19
1.9~20.9
5~88
0~84
100-15
1.5~16.5
5~110
0~105
150-10
1~11
5~165
0~157.5
300-5
0.5~5.5
5~330
0~315
400-3.8
0.38~4.18
5~440
0~420
600-2.6
0.26~2.86
5~660
0~630
51
PSU Series User Manual
5. Press PROT again to exit. The
PROT key light will turn off.
PROT
Clear
OVP/OCP/UVL
protection
The OVP, OCP or UVL protection can
be cleared after it has been tripped by
holding the ALM_CLR button for 3
seconds.
PROT
ALM_CLR
Background
Before setting the power supply to C.V. mode,
ensure:
The output is off.
The load is connected.
Steps
1. Press the Function key. The
Function key will light up.
Function
2. The display will show the function (F-01) on the
voltage display and the setting for the function
in the current display.
VOLTAGECURRENT
LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Function
number
Function
setting
Set to C.V. Priority Mode
When setting the power supply to constant voltage mode, a current
limit must also be set to determine the crossover point. When the
current exceeds the crossover point, the mode switches to C.C.
mode. For details about C.V. operation, see page 24. C.C. and C.V.
mode have two selectable slew rates: High Speed Priority and Slew
Rate Priority. High Speed Priority will use the fastest slew rate for
the instrument while Slew Rate Priority will use a user-configured
slew rate.
52
OPERATION
3. Rotate the Voltage knob to change
the F setting to F-03 (V-I Mode Slew
Rate Select).
Voltage
4. Use the Current knob to set the F-03
setting.
Set F-03 to 0 (CV High Speed
Priority) or 2 (CV Slew Rate Priority).
configuration setting. ConF will be
displayed when it is configuring.
Voltage
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
VSR indicator for CV Slew
Rate Priority (F-03=2)
6. If CV Slew Rate Priority was chosen as the
operating mode, set F-04 (Voltage Slew Rate
Up) and the F-05 (Voltage Slew Rate Down)
and save.
53
PSU Series User Manual
F-04 / F-05
0.001V~0.060V/msec (PSU 6-200)
0.001V~0.080V/msec (PSU 8-180)
0.001V~0.125V/msec (PSU 12.5-120)
0.001V~0.150V/msec (PSU 15-100)
0.001V~0.200V/msec (PSU 20-76)
0.001V~0.300V/msec (PSU 30-50)
0.001V~0.400V/msec (PSU 40-38)
0.001V~0.500V/msec (PSU 50-30)
0.001V~0.600V/msec (PSU 60-25)
0.001V~0.800V/msec (PSU 80-19)
0.001V~1.000V/msec (PSU 100-15)
0.001V~1.500V/msec (PSU 150-10)
0.001V~1.500V/msec (PSU 300-5)
0.001V~2.000V/msec (PSU 400-3.8)
0.001V~2.400V/msec (PSU 600-2.6)
7. Press the Function key again to exit
the configuration settings. The
function key light will turn off.
Function
8. Use the Current knob to set the
current limit (crossover point).
Current
9. Use the Voltage knob to set the
voltage.
Voltage
Note
Notice the Set key becomes illuminated when setting
the current or voltage. If the Voltage or Current knobs
are unresponsive, press the Set key first.
10. Press the Output key. The
Output ON LED becomes
lit.
Output
54
OPERATION
CV will become
illuminated (center)
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
Note
Only the voltage level can be altered when the output
is on. The current level can only be changed by
pressing the Set key.
For more information on the Normal Function
Settings, see page 101.
55
PSU Series User Manual
Background
Before setting the power supply to
C.C. mode, ensure:
The output is off.
The load is connected.
Steps
1. Press the Function key. The
Function key will light up.
Function
2. The display will show the function (F-01) on the
voltage display and the setting for the function
in the current display.
VOLTAGECURRENT
LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Function
number
Function
setting
3. Rotate the Voltage knob to change
the F setting to F-03 (V-I Mode Slew
Rate Select).
Voltage
4. Use the Current knob to set the F-03
setting.
Set F-03 to 1 (CC High Speed
Priority) or 3 (CC Slew Rate Priority)
and save.
Current
Set to C.C. Priority Mode
When setting the power supply to constant current mode, a voltage
limit must also be set to determine the crossover point. When the
voltage exceeds the crossover point, the mode switches to C.V.
mode. For details about C.C. operation, see page 24. C.C. and C.V.
mode have two selectable slew rates: High Speed Priority and Slew
Rate Priority. High Speed Priority will use the fastest slew rate for
the instrument while Slew Rate Priority will use a user-configured
slew rate.
56
OPERATION
F-03
1 = CC High Speed Priority
3 = CC Slew Rate Priority
5. Press the Voltage knob to save the
configuration setting. ConF will be
displayed when it is configuring.
Voltage
VOLTAGECURRENT
LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
ISR indicator for CC Slew
Rate Priority (F-03=3)
6. If CC Slew Rate Priority was chosen as the
operating mode, set F-06 (Current Slew Rate
Up) and F-07 (Current Slew Rate Down) and
save.
F-06 / F-07
0.001A~2.000A / msec (PSU 6-200)
0.001A~1.800A / msec (PSU 8-180)
0.001A~1.200A / msec (PSU 12.5-120)
0.001A~1.000A / msec (PSU 15-100)
0.001A~0.760A / msec (PSU 20-76)
0.001A~0.500A / msec (PSU 30-50)
0.001A~0.380A / msec (PSU 40-38)
0.001A~0.300A / msec (PSU 50-30)
0.001A~0.250A / msec (PSU 60-25)
0.001A~0.190A / msec (PSU 80-19)
0.001A~0.150A / msec (PSU 100-15)
0.001A~0.100A / msec (PSU 150-10)
0.001A~0.025A / msec (PSU 300-5)
0.001A~0.008A / msec (PSU 400-3.8)
0.001A~0.006A / msec (PSU 600-2.6)
7. Press the Function key again to exit
the configuration settings. The
Function key light will turn off.
Function
57
PSU Series User Manual
8. Use the Voltage knob to set the
voltage limit (crossover point).
Voltage
9. Use the Current knob to set the
current.
Current
Note
Notice the Set key becomes illuminated when setting
the current or voltage. If the Voltage or Current knobs
are unresponsive, press the Set key first.
10. Press the Output key. The
Output key becomes
illuminated.
Output
CC will become
illuminated (right)
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
Note
Only the current level can be altered when the output
is on. The voltage level can only be changed by
pressing the Set key.
For more information on the Normal Function
Settings, see page 101.
58
OPERATION
Activate the panel
lock
Press the Lock/Local key to active the
panel lock. The key will become
illuminated.
Lock/Local
Disable the panel
lock
Hold the Lock/Local key for ~3
seconds to disable the panel lock. The
key’s light will turn off.
Lock/Local
Unlock
Save Setup
11. Press the SHIFT key. The shift key
will light blue.
Shift
12. Hold the desired memory key for
>3 seconds (M1, M2, M3).
Function
M1
(hold)
Panel Lock
The panel lock feature prevents settings from being changed
accidentally. When activated, the Lock/Local key will become
illuminated and all keys and knobs except the Lock/Local key and
Output key (if active) will be disabled.
If the instrument is remotely controlled via the USB/LAN interface,
the panel lock is automatically enabled.
Save Setup
The PSU has 3 dedicated keys (M1, M2, M3) to save the set current,
set voltage, OVP, OCP and ULV settings.
59
PSU Series User Manual
13. When the setup is saved the unit will beep, the
setup will be saved and the memory number
will be shown on the display.
Saved setup
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
Save Setup
1. Press the SHIFT key. The shift key
will light blue.
Shift
2. Hold the desired memory key to
recall the desired setup (M1, M2,
M3).
Function
M1
3. When the setup is recalled the setup will be
loaded and the memory number will be shown
on the display.
Recalled setup
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
Note
The F-15 function setting will determine whether the
saved contents of the recalled memory setting are
displayed or not.
Recall Setup
The PSU has 3 dedicated keys (M1, M2, M3) to recall setups.
60
OPERATION
WARNING
Ensure the output is off before handling the remote
sense connector.
Use sense cables with a voltage rating exceeding the
isolation voltage of the power supply.
Never connect sensing cables when the output is on.
Electric shock or damage to the power supply could
result.
Remote Sense
Connector
Overview
When using the remote sense connector make sure
the wires that are used follow the following guidelines:
Wire gauge:
AWG 28 to AWG 16
Wire diameter:
0.320mm-1.29mm
Strip length:
5mm // 0.2 in.
+S
+LS
NC
-LS
-S
+S: Remote(+) sense
+LS: Local (+) sense
NC: Not connected
-LS: Local (-) sense
-S: Remote (-) sense
Voltage Sense
The PSU power supplies can be operated using local or remote
voltage sense. By default the PSU ships configured for local sense.
Remote Sense Connector
The Remote Sense connector includes a detachable plug to facilitate
making the sense connections. The remote sense connector also has
a safety cover.
61
PSU Series User Manual
WARNING
Ensure the output is off before handling the remote
sense connector.
Use sense cables with a voltage rating exceeding the
isolation voltage of the power supply.
Never connect sensing cables when the output is on.
Electric shock or damage to the power supply could
result.
Always operate the PSU with the remote sense cover.
Connector
1. Place the cover
over the remote
sense connector.
2. Secure the cover
with the provided
screw.
M3x8L
Pan Head Screw
Remote Sense Cover
62
Local Sense
Local Sense
Connection
PSULoad
Output
Output
Input
Input
S+
LS+
LS-
S-
Remote
Sense
Page 61
When using local sense, the sensing terminals are connected to the
local sense terminals (via the local sense connections) and thus do
not compensate for any possible voltage drop that is seen on the
load cables. Local sense is only recommended when the voltage
drop is of no consequence or for load-current applications. By
default, the sense plug is already configured to local sensing.
Remote Sense
Remote sense is used to compensate for the voltage drop seen
across load cables due to the resistance inherent in the load cables.
The remote sense terminals are connected to the load terminals of
the DUT to determine the voltage drop across the load cables.
Remote sense can compensate up to 1 volt (PSU 6-200/8-180/
12.5-120/15-100/20-76), 1.5 volts (PSU 30-50), 2 volts (PSU 40-38
/50-30), 3 volts (PSU 60-25), 4 volts (PSU 80-19) or 5 volts (PSU 10015/150-10/300-5/400-3.8/600-2.6) (compensation voltage, single
line). Load cables should be chosen with a voltage drop less than
the compensation voltage.
Although you can use remote sense to compensate up to 5V for a
single line, it is recommended that the voltage drop is minimized to
a maximum of 1V to prevent excessive output power consumption
from the power supply and poor dynamic response to load changes.
OPERATION
63
PSU Series User Manual
WARNING
Ensure the output is off before connecting any sense
cables.
Use sense cables with a voltage rating exceeding the
isolation voltage of the power supply.
Never connect sensing cables when the output is on.
Electric shock or damage to the power supply could
result.
Note
Be sure to remove the sense jumpers from the remote
sense connector so the unit is not using local sensing.
Single Load
1. Connect the S+ terminal to the positive
potential of the load. Connect the S- terminal to
the negative potential of the load.
Output
S+
S-
PSU
Output
Load
Input
Input
Page 61
2. Operate the instrument as normal.
See the Basic Operation chapter for
details.
Page 49
Parallel PSU
Units
1. Connect the S+ terminals to the positive
potential of the load. Connect the S- terminals
to the negative potential of the load.
64
OPERATION
Output
S+
S-
PSU #2
Output
Output
S+
S-
PSU #1
Output
Load
Input
Input
Page 61
2. Operate the instrument as normal.
See the Parallel Operation chapter
for details.
Page 68
Serial PSU Units
1. a. Connect the 1
st
S+ terminal to the positive
potential of the load.
b. Connect the 1st S- terminal to the positive
output terminal of the second PSU unit.
c. Connect the 2nd S+ terminal to the positive
terminal of the second PSU unit.
d. Connect the 2nd S- terminal to negative
terminal of the load.
65
PSU Series User Manual
PSU #2
a
b
c
d
Load
Input
Input
Output
S+
S-
PSU #1
Output
Output
S+
S-
Output
Page 61
2. Operate the instrument as normal.
See the Serial Operation chapter
for details.
Page 77
Wire Shielding
and Load line
impedance
To help to minimize the oscillation due to the
inductance and capacitance of the load cables, use
an electrolytic capacitor in parallel with the load
terminals.
To minimize the effect of load line impedance use
twisted wire pairing.
PSULoad
s
s
Twisted pair
Capacitor
Shield the sense wires and connect
the shield to the chassis ground.
Twisted pair
66
OPERATION
Parallel / Series Operation
This section describes the basic operations required to operate the
power supply in series or parallel. Operating the PSU series in
parallel increases the total current output of the power supply units.
When used in series, the total output voltage of the power supplies
can be increased.
When the units are used in parallel or in series, a number of
precautions and limitations apply. Please read the following
sections before operating the power supplies in parallel or series.
Master-slave parallel overview → from page 68
Parallel connection → from page 71
Parallel operation → from page 75
Master-slave parallel calibration → from page 77
Master-slave Series overview → page 79
Series connection → page 81
Series operation → from page 82
67
PSU Series User Manual
Background
When connecting the PSU power supplies in
parallel, up to 4 units can be used in parallel and
all units must be of the same model with similar
output settings.
To use the power supplies in parallel, units must
be used in a “master-slave” configuration. In the
master-slave configuration a “master” power
supply controls any other connected “slave”
power supplies. In order for the master unit to
control the slave units, the master unit must use
the analog control connector to control the slave
units.
When using the Analog Control Connector, the
connector must be wired correctly between the
master and each of the slave units. For the
complete connector pin assignment, see page 118,
or alternatively, the PSU-01C, PSU-02C and the
PSU-03C cables can be used to connect a master to
unit to 1, 2 or 3 slave units, respectively.
Master-Slave Parallel Overview
68
OPERATION
Master
Load
Ext-V
Ext-R
Slave
VMON
IMON
Slave
Slave
Analog Control Connector
Limitations
Display
Only the master unit will display the voltage
and current.
OVP/ OCP/UVL
Slave units follow the settings of the master
when OVP/OCP/UVL is tripped on the master
unit.
Remote monitoring
Voltage monitoring (VMON) and current
monitoring (IMON) are only supported on the
master unit.
The IMON current represents the total current
of the all the parallelized units.
Remote Sense
Please see the remote sense chapter for details,
page 63.
69
PSU Series User Manual
Parallel Calibration
The parallel calibration function can be used to
offset cables losses.
External Voltage and Resistance Control
Voltage/Resistance controlled remote control
can only be used with the master unit.
The full scale current (in parallel) is equivalent
to the maximum external voltage or resistance.
Internal Resistance
For 2 units in parallel, the internal resistance is
actually half of the setting value.
For 3 units in parallel, the internal resistance is
actually a third of the setting value.
For 4 units in parallel, the internal resistance is
actually a fourth of the setting value.
See function setting F-08 for internal resistance
settings, page 103.
Bleeder Control
The Master unit is used to control the bleeder
settings. The bleeder resistors in all the slave
units are always turned off when in parallel
mode.
Output Voltage/
Output Current
Model
1 unit
2 units
3 units
4 units
PSU 6-200
6V
6V
6V
6V
200A
400A
600A
800A
PSU 8-180
8V
8V
8V
8V
180A
360A
540A
720A
PSU 12.5-120
12.5V
12.5V
12.5V
12.5V
120A
240A
360A
480A
PSU 15-100
15V
15V
15V
15V
100A
200A
300A
400A
PSU 20-76
20V
20V
20V
20V
76A
152A
228A
304A
70
OPERATION
PSU 30-50
30V
30V
30V
30V
50A
100A
150A
200A
PSU 40-38
40V
40V
40V
40V
38A
76A
114A
152A
PSU 50-30
50V
50V
50V
50V
30A
60A
90A
120A
PSU 60-25
60V
60V
60V
60V
25A
50A
75A
100A
PSU 80-19
80V
80V
80V
80V
19A
38A
57A
76A
PSU 100-15
100V
100V
100V
100V
15A
30A
45A
60A
PSU 150-10
150V
150V
150V
150V
10A
20A
30A
40A
PSU 300-5
300V
300V
300V
300V
5A
10A
15A
20A
PSU 400-3.8
400V
400V
400V
400V
3.8A
7.6A
11.4A
15.2A
PSU 600-2.6
600V
600V
600V
600V
2.6A
5.2A
7.8A
10.4A
Analog Control
Connection
To operate the power supplies in parallel with the
analog connectors, connect the analog connectors
on the master and slave units as shown in the
diagrams below. Alternatively, preconfigured
cables can be used:
PSU-01C: 1 master with 1 slave
PSU-02C: 1 master with 2 slaves
PSU-03C: 1 master with 3 slaves
Master-Slave Parallel Connection
71
PSU Series User Manual
12
11
1
16
13
14
PRL OUT+9
8
20
19
13
14
PRL IN+
A COM
Status COM1
OUT ON Status
Current SUM
Alarm Status
PRL IN-
A COM
OUT ON/OFF CONT
Current Sum
Alarm_Status
MASTERSLAVE #1
SLAVE #2
7
20
Shut_Down
A COM
7
16
Shut_Down
OUT ON Status
1Status COM1
9
8
20
19
13
14
PRL IN+
PRL IN-
A COM
OUT ON/OFF CONT
Current Sum
Alarm_Status
7
16
Shut_Down
OUT ON Status
1Status COM1
SLAVE #3
9
8
20
19
13
14
PRL IN+
PRL IN-
A COM
OUT ON/OFF CONT
Current Sum
Alarm_Status
7Shut_Down
1Status COM1
72
OPERATION
Note
After the power supplies are connected in
parallel, if you want to use the analog connector
to control the power supplies, you must
disassemble the cable of the master and then
wire it yourself for control.
Pin signal diagram is as shown below.
22
23
21
23
19
20
EXT-V/R CV CONT
A COM
EXT-V/R CC CONT
A COM
OUT ON/OFF CONT
A COM
MASTER
The model of connecting in parallel has no place
voltage problem and can be used in common
ground.
The model of connecting in series has high
voltage due to the location. If analog control is
to be used, it cannot be used in common ground
and requires isolation control.
Pin signal diagram is as shown below.
22
23
21
23
19
20
Isolated Analog
0-10V
Isolated Analog
0-10V
NO relay driven
By 24V DO
MASTER
Parallel Output
Connection
If grounding the positive or negative terminals to the
reference ground, be sure to ground the appropriate
terminal on each unit (either positive or negative).
73
PSU Series User Manual
Example with
negative terminal
connected to
ground
Slave #1
Master
Load
Input
Input
Output
Ground
Output
Output
Ground
Output
Slave #2
Output
Ground
Output
Steps
1. Ensure the power is off on all power supplies.
2. Choose a master and a slave unit(s).
3. Connect the analog connectors for the master
and slave units as shown above.
4. Remove the Output Terminal
covers.
Page 42
5. Connect the master and slave unit in parallel as
shown above.
6. Reattach the terminal covers.
Page 42
Note
Ensure the load cables have sufficient
current capacity.
Page 39
The load wires and remote sense wires should use
twisted-paired wiring of the shortest possible length.
74
OPERATION
Master-Slave
Configuration
Before using the power supplies in parallel, the
master and slave units need to be configured.
Steps
1. Configure the OVP, OCP and ULV
settings for the master unit.
Page 49
2. For each unit, hold the Function key while
turning the power on to enter the power on
configuration settings.
Lock/Local PROT Function Test Set
Output
Unlock ALM_CLR M1 M 2 M 3
Shift
: Long Push
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGECURRENT
PSU 40-38
DC Power Supply
0 - 40V / 0 - 38A
VoltageCurrent
3. Configure F-93 (Master/Slave)
setting for each master/slave unit.
Page 114
Unit
F-93
Independent (default setting)
0
Master unit with 1 slave in parallel
1
Master unit with 2 slaves in parallel
2
Master unit with 3 slaves in parallel
3
Slave (parallel)
4
4. Cycle the power on the units (reset the power).
Note
Configuration settings can be checked on both the
master and slave units by pressing the Function key
and checking F-93.
Only the Master OVP, OCP and UVL settings are used
for protection. Slave protection levels are disregarded.
OHP works independently for each unit.
Master-Slave Parallel Operation
75
PSU Series User Manual
Master-Slave
Operation
Only operate the power supplies in parallel if the
units are configured correctly.
Steps
1. Turn on the master and slave units. The slave
unit(s) will show a blank display.
Master unit
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Slave units
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
2. Operation of all units is controlled
via the master unit. Operation of
the master unit is the same as for a
single unit. See the Basic Operation
chapter.
Page 49.
3. Press the Output key to
begin. The output LED will
become lit.
Output
Caution
Only operate the power supplies in parallel if using
units of the same model number.
Note
The panel controls are disabled on slave units,
including the output key. On slave units, only the
Function key can be used to view the current settings.
76
OPERATION
Master-Slave
Configuration
The F-16 function setting can be used to calibrate
the output of PSU units connected in parallel.
If you feel the accuracy is not good enough when
you measure the accuracy in parallel mode, the
parallel calibration can be used to get better
measurement accuracy.
Steps
1. Short all the terminals together. This is best
accomplished by connecting the master and all
the slave units in parallel and then shorting the
output terminals.
Slave #1, 2, 3
Master
Output
Ground
Output
Output
Ground
Output
Short
2. Connect the slave units to the
master unit using the analog
control connectors as described
previously.
Page 71
3. Configure F-93 (Master/Slave)
setting for each master/slave unit,
as described previously.
Page 75
4. Cycle the power on the units (reset the power).
Master-Slave Parallel Calibration
77
PSU Series User Manual
5. On the master unit, set F-16 (Auto
Calibration Parallel Control) to 2 to
turn on the parallel calibration.
Calibration will begin immediately.
Page 104
6. Whilst calibration is being performed, WAIT
will be displayed on the master screen.
Calibration will take a few moments.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
7. When the calibration has finished, OK will be
displayed on the master screen.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
8. Remove the shorts from the terminals, and
proceed with parallel operation.
Note
When performing parallel calibration, make sure the
terminals are connected with cables or bus bars that
are able to withstand the combined current capacity of
all the units in parallel.
78
OPERATION
Background
When connecting PSU power supplies in series, up
to 2 units can be used in series and all units must
be of the same model. When operated in series, the
power supplies can be used to increase the voltage
output or setup the power supplies to output both
positive and negative polarities. Unlike with the
parallel operation, the series operation does not
require any special configuration as each power
supply is operated and controlled individually.
When the units are used in series, a number of
precautions and limitations apply. Please read this
overview before operating the power supplies in
series.
Master
Load
Ext-V
Ext-R
Slave
VMON
IMON
Ext-V
Ext-R
VMON
IMON
Limitations
Display
Master and slave units display both the current
and the voltage. The total voltage is the sum of
the units.
OVP/OCP/UVL
OVP, OCP and UVL level for each unit must be
set separately.
The OVP and OCP protections are tripped
independently on the master and slave.
Master-Slave Series Overview
79
PSU Series User Manual
Remote monitoring
Voltage monitoring (VMON) and current
monitoring (IMON) should be performed on
both units.
The VMON voltage represents the voltage of
that particular unit.
Remote Sense
Please see the voltage sense chapter for details,
page 61.
External Voltage and Resistance Control
Voltage/Resistance controlled remote control
should be used on both units separately.
The full scale voltage (in series) is equivalent to
the maximum external voltage or resistance.
Slew Rate
The slave rate should be set for both units.
Internal Resistance
The internal resistance should be set for both
units.
Bleeder Control
The bleeder resistor setting should be set
equally on both units.
CAUTION
When using analog control connector to program
or measure with PSU power supplies connected in
series, make sure that each unit is separated and
floating from each other.
WARNING
When PSU power supplies are connected in series
and the load or one of the output terminals is
grounded, no point on the output shall be more
than ±600VDC above or below chassis ground.
80
OPERATION
Series Connection
to increase
Voltage Output
Unit #2
Unit #1
Load
Input
Input
Output
Ground
Output
Output
Ground
Output
Series Connection
to Output
Positive and
Negative Polarity
Unit #2
Unit #1
Load
Input
Input
Output
Ground
Output
Output
Ground
Output
COM
Series Connection
If using the PSU in series, please be aware that each unit acts
independently and thus there are no special communication buses
for serial connections.
81
PSU Series User Manual
Note
The output reference ground (COMMON) can be
grounded at the power supply side instead of the load,
depending on the requirements. Local sensing should
be used in this configuration.
Caution
When connecting the units in series, diodes should be
connected across each output to prevent reverse
voltage.
Steps
1. Ensure the power is off on both power supplies.
2. Connect the master and slave unit in series as
shown above to either increase the voltage
output or to create a positive and negative
output. Remember that how the units are
grounded depends on the configuration of the
series connection.
3. Use diodes across the output terminals to
prevent reverse voltage at startup or if one of
the units unexpectedly shuts down. Ensure the
diodes are rated to withstand the voltage and
current output of the power supply.
4. Reattach the terminal cover.
Page 42
Note
Ensure load cables have sufficient
current capacity.
Page 39
Series
Configuration
Before using the power supplies in series, the
master and slave units need to be configured.
1. Configure the OVP, OCP and UVL
settings for each unit.
Page 49
Series Operation
82
OPERATION
2. For each unit, hold the Function key while
turning the power on to enter the power on
configuration settings.
Lock/Local PROT Function Test Set
Output
Unlock ALM_CLR M1 M 2 M 3
Shift
: Long Push
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGECURRENT
PSU 40-38
DC Power Supply
0 - 40V / 0 - 38A
VoltageCurrent
3. Make sure each unit is set to
Independent (F-93 = 0). When
using the power supplies in series,
each unit is operated individually,
and thus no unit is considered the
master or slave.
Page 114
Unit
F-93
Independent
0
4. Cycle the power on the units (reset the power).
Note
Configuration settings can be checked for both the
master and slave units by pressing the Function key.
Series Operation
Only operate the power supplies in series if the
units are configured correctly.
1. Turn on both units. When connected in series
unit will only show the voltage and current of
their own unit.
Unit #1
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Unit #2
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
83
PSU Series User Manual
2. Operation of both units is the same
as for a single unit. Each unit will
only draw as much power as is
programmed. Please see the basic
operation chapter for details.
Page 49
3. Press the Output key on
each unit to begin. The
output LED will become lit.
Output
CAUTION
Only operate the power supplies in series if using
units of the same model number.
Only a maximum of 2 units can be used in series.
CAUTION
Ensure that the insulation capacity of the wiring is
sufficient when connected in series. See page 31 for
insulation capacity and grounding details.
84
OPERATION
Test Scripts
This section describes how to use the Test function to run, load and
save test scripts for automated testing. The Test function is useful if
you want to perform a number of tests automatically. The PSU test
function can store ten test scripts in memory.
Each test script is programmed in a scripting language. For more
information on how to create test scripts, please contact GW Instek.
Test script file format→ from page 86
Test script settings → from page 86
Setting the test script settings → from page 87
Load test script → from page 88
Run test script → from page 89
Export test script → from page 90
Remove test script → from page 91
85
PSU Series User Manual
Background
The test files are saved in *.tst file format.
Each file is saved as tXXX.tst, where XXX is the
save file number 001~010.
Test Run
Runs the chosen test script from the internal
memory. A script must first be loaded into the
internal memory before it can be run. See the test
function Test Save, below.
The script will run as soon as the test function is
started.
T-01
1~10
Test Copy
Copies a test script from the USB drive to the
designated save slot in memory. A script must first
be copied into internal memory before it can be
run.
T-02
1~10 (USBPSU)
Test Export
Exports a script from the designated memory save
slot to the USB drive.
T-03
1~10 (PSUUSB)
Test Remove
Deletes the chosen test file from the PSU internal
memory.
T-04
1~10
Available Test
Memory
Shows the amount of space left in memory for
tests.
T-05
Displays the available memory in bytes.
Test Script File Format
Test Script Settings
86
OPERATION
Steps
The test script settings (T-01~T-10) are set with the
Test key.
1. Press the Test key. The Test key
will light up.
TEST
2. The display will show T-01 on the left and the
memory no. for T-01 on the right.
The middle of the display will indicate if the
desired file is available in memory or not. Y
indicates Yes, N indicates No.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Test numberTest setting
Available Y/N
3. Rotate the Voltage knob to change
the T setting (Test setting).
Voltage
Test Run
Test Copy
Test Export
Test Remove
T-01
T-02
T-03
T-04
Setting the Test Script Settings
87
PSU Series User Manual
4. Rotate the Current knob to choose a
memory number. (Excluding T-05)
Current
Range
1~10
5. Press the Voltage knob to complete
the setting.
Voltage
Exit
Press the Test key again to exit the Test
settings. The Test key light will turn
off.
TEST
Overview
Before a test script can be run, it must first be
loaded into a one of the 10 memory save slots.
Before loading a test script into memory:
Ensure the script file is placed in the root
directory.
Ensure the file name number corresponds to the
memory number that you wish to save to. For
example t001.tst can only be loaded into
memory number #01, t002.tst into memory
number #02, and so on.
Use the T-05 setting to see how much memory is
available in internal memory.
Steps
1. Insert a USB flash drive into the
front panel USB-A slot. Ensure the
flash drive contains a test script in
the root directory.
Load Test Script from USB
88
OPERATION
2. Turn on the power. MS ON (Mass Storage) will
be displayed on the screen after a few seconds
if the USB drive is recognized. Conversely, MS
OFF will be displayed if removed.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Note
If the USB drive is not recognized, check to see that
the function settings for F-20 = 1 (page 104). If not,
reinsert the USB flash drive.
3. Configure T-02 (Test Copy) to 1~10
(save memory slot)
Page 87
T-02 range
1~10
4. OK will be displayed when completed.
5. The script will now be available in the memory
slot the script was saved to.
Note
Error messages: If you load a file that is not present on
the USB drive “Err 002” will be displayed on the
display.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Overview
A test script can be run from one of ten memory
slots.
Steps
1. Before a test script can be run, it
must first be loaded into one of the
10 memory save slots.
Page 88
Run Test Script
89
PSU Series User Manual
2. Configure T-01 (Run Test) to 1~10
(save memory slot no. to run)
Page 87
T-01 range
1~10
3. The test script will automatically start to run.
Note
Error messages: If you try to run a test script from an
empty memory location “Err 003” will be displayed on
the display.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Stop a Test
To stop (abort) a running test at any
time, press the Test key. TEST STOP
will be displayed and the unit will
return to normal operation after a few
moments.
TEST
Overview
The Export Test function saves a test file to the root
directory of a USB flash drive.
Files will be saved as tXXX.tst where XXX is the
memory number 001~010 from which the test
script was exported from.
Files of the same name on the USB flash drive
will be written over.
Steps
1. Insert a USB flash drive into the
front panel USB-A slot.
Export Test Script to USB
90
OPERATION
2. Turn on the power. MS (Mass Storage) will be
displayed on the screen after a few seconds if
the USB drive is recognized.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Note
If the USB drive is not recognized, check to see that
the function settings for F-20 = 1 (page 103). If not,
reinsert the USB flash drive.
3. Configure T-03 (Test Export) to
1~10 (save memory slot)
Page 87
T-03 range
1~10
4. The script will now be copied to the USB flash
drive.
OK will be displayed when completed.
Note
Error messages: If you try to export a test script from
an empty memory location “Err 002” will be displayed
on the display.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Overview
The Remove Test function will delete a test script
from the internal memory.
Steps
1. Select T-04 (Test Remove) and
choose which test script to remove
from the internal memory.
Page 87
T-04 range
1~10
Remove Test Script
91
PSU Series User Manual
2. The test script will be removed from the
internal memory.
OK will be displayed when completed.
Note
Error messages: If you try to remove a test script from
an empty memory location “Err 003” will be displayed
System Settings ............................................................................... 108
Power On Configuration Settings ............................................... 109
Trigger Input and Output Configuration Settings ................... 111
Special Function ............................................................................. 112
Setting Normal Function Settings ............................................... 112
Setting Power On Configuration Settings ................................. 114
CONFIGURATION
93
PSU Series User Manual
Normal Function
Settings
Setting
Setting Range
Output ON delay time
F-01
0.00s~99.99s
Output OFF delay time
F-02
0.00s~99.99s
V-I mode slew rate select
F-03
0 = CV high speed priority (CVHS)
1 = CC high speed priority (CCHS)
2 = CV slew rate priority (CVLS)
3 = CC slew rate priority (CVLS)
Rising voltage slew rate
F-04
0.001~0.060V/msec (PSU 6-200)
0.001~0.080V/msec (PSU 8-180)
0.001~0.125V/msec (PSU 12.5-120)
0.001~0.150V/msec (PSU 15-100)
0.001~0.200V/msec (PSU 20-76)
0.001~0.300V/msec (PSU 30-50)
0.001~0.400V/msec (PSU 40-38)
0.001~0.500V/msec (PSU 50-30)
Configuration Overview
Configuration of the PSU power supplies is divided into five
different configuration settings: Normal Function, USB/GPIB, LAN,
UART, System Configuration Settings, Power ON Configuration,
Trigger Input/Output Configuration Settings and Special Function
Settings. Power ON Configuration differs from the other settings in
that the settings used with Power ON Configuration settings can
only be set during power up. The other configuration settings can
be changed when the unit is already on. This prevents some
important configuration parameters from being changed
inadvertently. Power On Configuration settings are numbered F-90
to F-98 and the other configuration settings are numbered F-00 to F61, F-70 to F-78, F-88 to F-89 and F100 to F122. The Special Function
Settings are used for calibration, firmware updated and other
special functions; these functions are not supported for end-user
use.
Configuration Table
Please use the configuration settings listed below when applying
the configuration settings.