Instek PSU6-200, PSU8-180, PSU12.5-120, PSU15-100, PSU20-76 Programming Manual

...
Programmable DC Power Supply
PSU Series
PROGRAMMING MANUAL
ISO-9001 CERTIFIED MANUFACTURER
This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of Good Will company.
The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the rights to change specification, equipment, and maintenance procedures at any time without notice.
Good Will Instrument Co., Ltd. No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.
Table of Contents
Table of Contents
SAFETY INSTRUCTIONS .................................................. 4
GETTING STARTED .......................................................... 8
PSU Series Overview.................................................. 9
Appearance .............................................................. 14
Configuration Settings ............................................. 22
REMOTE CONTROL ....................................................... 33
Interface Configuration ............................................ 35
Command Syntax ..................................................... 68
Command List ......................................................... 71
Status Register Overview ....................................... 139
Error List ............................................................... 152
APPENDIX .................................................................... 161
PSU Factory Default Settings ................................. 162
PSU Preset Default Settings .................................. 165
Error Messages & Messages .................................. 166
LED ASCII Table Character Set ............................... 167
INDEX .......................................................................... 168
3
PSU Series Programming Manual
WARNING
Warning: Identifies conditions or practices that could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that could result in damage to the PSU or to other properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
SAFETY INSTRUCTIONS
This chapter contains important safety instructions that you must follow during operation and storage. Read the following before any operation to insure your safety and to keep the instrument in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the instrument.
4
SAFETY INSTRUCTIONS
Do not dispose electronic equipment as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased.
General Guideline
CAUTION
Do not place any heavy object on the PSU. Avoid severe impact or rough handling that
leads to damaging the PSU.
Do not discharge static electricity to the PSU. Use only mating connectors, not bare wires, for
the terminals.
Do not block the cooling fan opening. Do not disassemble the PSU unless you are
qualified.
(Measurement categories) EN61010-1:2010 and EN61010-2-030 specifies the measurement categories and their requirements as follows. The PSU falls under category II.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
0 is for measurements performed on circuits not directly
connected to Mains.
Power Supply
WARNING
AC Input voltage range: 85Vac~265Vac Frequency: 47Hz to 63Hz To avoid electrical shock connect the protective
grounding conductor of the AC power cord to an earth ground.
Safety Guidelines
5
PSU Series Programming Manual
Cleaning the PSU
Disconnect the power cord before cleaning. Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Operation Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Relative Humidity: 20%~ 85% (no condensation) Altitude: < 2000m Temperature: 0°C to 50°C
(Pollution Degree) EN61010-1:2010 and EN61010-2-030 specifies the pollution degrees and their requirements as follows. The PSU falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to condensation which is expected. In such conditions, equipment is normally protected against exposure to direct sunlight, precipitation, and full wind pressure, but neither temperature nor humidity is controlled.
Storage environment
Location: Indoor Temperature: -25°C to 70°C Relative Humidity: 90%(no condensation)
Disposal
Do not dispose this instrument as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased. Please make sure discarded electrical waste is properly recycled to reduce environmental impact.
6
SAFETY INSTRUCTIONS
Green/ Yellow:
Earth
Blue:
Neutral
Brown:
Live (Phase)
Power cord for the United Kingdom
When using the power supply in the United Kingdom, make sure the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED IMPORTANT: The wires in this lead are coloured in accordance with the following code:
As the colours of the wires in main leads may not correspond with the coloured marking identified in your plug/appliance, proceed as follows:
The wire which is coloured Green & Yellow must be connected to the Earth terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment or contact the supplier.
This cable/appliance should be protected by a suitably rated and approved HBC mains fuse: refer to the rating information on the equipment and/or user instructions for details. As a guide, a cable of 0.75mm2 should be protected by a 3A or 5A fuse. Larger conductors would normally require 13A types, depending on the connection method used.
Any exposed wiring from a cable, plug or connection that is engaged in a live socket is extremely hazardous. If a cable or plug is deemed hazardous, turn off the mains power and remove the cable, any fuses and fuse assemblies. All hazardous wiring must be immediately destroyed and replaced in accordance to the above standard.
7
PSU Series Programming Manual
PSU Series Overview .................................................. 9
Series lineup ............................................................................................ 9
Main Features .......................................................................................10
Accessories ...........................................................................................11
Appearance .............................................................. 14
PSU Series Front Panel ......................................................................14
PSU Series Display and Operation Panel ........................................17
Rear Panel .............................................................................................19
Configuration Settings ............................................. 22
Setting Normal Function Settings ....................................................22
Setting Power On Configuration Settings .......................................24
Configuration Table ............................................................................26
GETTING STARTED
This chapter describes the power supply in a nutshell, including its main features and front / rear panel introduction. After going through the overview, please read the theory of operation to become familiar with the operating modes, protection modes and other safety considerations.
8
GETTING STARTED
Model name
Voltage Rating1
Current Rating2
Power
PSU 6-200
6V
200A
1200W
PSU 8-180
8V
180A
1440W
PSU 12.5-120
12.5V
120A
1500W
PSU 15-100
15V
100V
1500W
PSU 20-76
20V
76A
1520W
PSU 30-50
30V
50A
1500W
PSU 40-38
40V
38A
1520W
PSU 50-30
50V
30A
1500W
PSU 60-25
60V
25A
1500W
PSU 80-19
80V
19A
1520W
PSU 100-15
100V
15A
1500W
PSU 150-10
150V
10A
1500W
PSU 300-5
300V
5A
1500W
PSU 400-3.8
400V
3.8A
1520W
PSU 600-2.6
600V
2.6A
1560W
1
Minimum voltage guaranteed to 0.2% of rating voltage.
2
Minimum current guaranteed to 0.4% of rating current.
PSU Series Overview
Series lineup
The PSU series consists of 15 models, covering a number of different current, voltage and power capacities:
9
Main Features
Performance
High power density: 1500W in 1U Universal input voltage 85~265Vac, continuous
operation.
Output voltage up to 600V, current up to 200A.
Features
Active power factor correction. Parallel master/slave operation with active
current sharing.
Remote sensing to compensate for voltage drop
in load leads.
19 rack mounted ATE applications. A built-in Web server. OVP, OCP and OHP protection. Preset memory function. Adjustable voltage and current slew rates. Bleeder circuit ON/OFF setting. CV, CC priority start function. (Prevents
overshoot with output ON)
Supports test scripts.
Interface
Built-in RS-232/485, LAN and USB interface. Analog output programming and monitoring. Optional interfaces: GPIB, Isolated Voltage (0-
5V/0-10V) and Isolated Current (4-20mA) programming and monitoring interface. (Factory options)
PSU Series Programming Manual
10
GETTING STARTED
Standard Accessories
Part number
Description
Qty. Output terminal cover
1
Analog connector plug kit
1
Output terminal M8 bolt set (6V~60V model)
1 Input terminal cover
1
Power Cord (230VAC/10A,
1.8M, provide for some region only)
1 82GW1SAFE0M*1
Safety Guide
1
62SB-8K0HD1*1
1U Handle, ROHS
2 62SB-8K0HP1*1
1U BRACKET (LEFT), RoHS
1
62SB-8K0HP2*1
1U BRACKET (RIGHT), RoHS
1
CD-ROM
User manual, Programming manual
1 set 82SU-PSU00K*1
Packing list
82GW-00000C*1
* CTC GW/INSTEK JAPAN USE ,RoHS
1
Factory Installed Options
Part number
Description PSU-GPIB
GPIB interface
PSU-ISO-V
Voltage programming isolated analog interface
PSU-ISO-I
Current programming isolated analog interface
PSU-001
Front Panel Filter Kit (Operation Temperature is guaranteed to 40˚C)
Accessories
Before using the PSU power supply unit, check the package contents to make sure all the standard accessories are included.
11
PSU Series Programming Manual
Optional Accessories
Part number
Description
PSU-01C
Cable for 2 units of PSU-Series in parallel mode connection
PSU-01B
Bus Bar for 2 units of PSU-Series in parallel mode connection
PSU-01A
Joins a vertical stack of 2 PSU units together. 2U-sized handles x2, joining plates x2.
PSU-02C
Cable for 3 units of PSU-Series in parallel mode connection
PSU-02B
Bus Bar for 3 units of PSU-Series in parallel mode connection
PSU-02A
Joins a vertical stack of 3 PSU units together. 3U-sized handles x2, joining plates x2.
PSU-03C
Cable for 4 units of PSU-Series in parallel mode connection
PSU-03B
Bus Bar for 4 units of PSU-Series in parallel mode connection
PSU-03A
Joins a vertical stack of 4 PSU units together. 4U-sized handles x2, joining plates x2.
PSU-232
RS232 cable with DB9 connector kit.
It Includes RS232 cable with DB9 connector, RS485 used master cable (gray plug), slave cable (black plug), intermediate connector and end terminal connector.
PSU-485
RS485 cable with DB9 connector kit.
It Includes RS485 cable with DB9 connector, RS485 used master cable (gray plug), slave cable (black plug), intermediate connector and end terminal connector.
12
GETTING STARTED
GRM-001
Rack-mount slides (General Devices P/N: C-300-S-116-RH-LH)
GTL-246
USB Cable 2.0-A-B Type, Approx. 1.2M
GPW-001
Power Cord SJT 12AWG/3C, 3m MAX Length, 105 ºC, RNB5-5*3P UL/CSA type
GPW-002
Power Cord H05W-F 1.5mm2/3C, 3m MAX Length, 105 ºC, RNB5-5*3P VDE type
GPW-003
Power Cord VCTF 3.5mm2/3C, 3m MAX Length, 105 ºC, RNB5-5*3P PSE type
Download
Name
Description
psu_cdc.inf
PSU USB driver
Other
Name
Description
Certificate of traceable calibration
13
PSU Series Programming Manual
Lock/Local PROT Function Test Set Output
Unlock ALM_CLR M 1 M 2 M 3
Shift
: Long Push
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGE CURRENT
PSU 40-38
DC Power Supply
0 -40V / 0 - 38A
Voltage Current
2 3 4 5
Display Area
1
116 7 8 9 10 12 13
1.
Power Switch
Used to turn the power on/off.
2.
USB A Port
USB A port for data transfer, loading test scripts etc.
3.
Air Inlet
Air inlet for cooling the inside of the PSU series.
4.
Voltage Knob
Voltage
Used to set the voltage value or select a parameter number in the Function settings.
Display Area
The display area shows setting values, output values and parameter settings. The function LEDs below show the current status and mode of the power supply. See page 17 for details.
5.
Current Knob
Current
Used to set the current value or change the value of a Function parameter.
Appearance
PSU Series Front Panel
14
GETTING STARTED
6.
Lock/Local Button
Lock/Local
Unlock
Used to lock all front panel buttons other than the Output Button or it switches to local mode.
Unlock Button
(Long push) Used to unlock the front panel buttons.
7.
PROT Button
PROT
ALM_CLR
Used to set and display OVP, OCP and UVL.
ALM_CLR Button
(Long push) Used to release protection functions that have been activated.
8.
Function Button
Function
M1
Used to configure the various functions.
M1 Button
(+Shift) Used to recall the M1 setup. (+Shift and hold) Used to save the current setup to M1.
9.
Test Button
TEST
M2
Used to run customized scripts for testing.
M2 Button
(+Shift) Used to recall the M2 setup. (+Shift and hold) Used to save the current setup to M2.
10.
Set Button
SET
M3
Used to set and confirm the output voltage and output current.
M3 Button
(+Shift) Used to recall the M3 setup. (+Shift and hold) Used to save the current setup to M3.
15
PSU Series Programming Manual
11.
Shift Button
Shift
Used to enable the functions that are written in blue characters below certain buttons.
12.
Output Button
Output
Used to turn the output on or off.
13.
Output ON LED
Lights in green when the output is on.
16
GETTING STARTED
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGE CURRENT
Display Area
14 1516 17
18 19 20 21 22 23 24
25
26 27 28
14.
Voltage Meter
Displays the voltage or the parameter number of a Function parameter.
15.
Current Meter
Displays the current or the value of a Function parameter.
16.
CV LED
Lights in green during constant voltage mode.
17.
CC LED
Lights in green during constant current mode.
18.
VSR LED
Lights up when CV Slew Rate Priority is enabled.
19.
LAN LED
Lights up when the LAN interface is connected.
20.
RMT LED
Lights in green during remote control.
21.
ERR LED
Lights in red when an SCPI error has occurred.
22.
DLY LED
The Output On/Off Delay indicator LED.
23.
ALM LED
Lights in red when a protection function has been activated.
PSU Series Display and Operation Panel
17
PSU Series Programming Manual
24.
ISR LED
Lights up when CC Slew Rate Priority is enabled.
25.
M1 LED
Lights in green when the memory value are being recalled or saved.
26.
M2 LED
Lights in green when the memory value are being recalled or saved.
27.
M3 LED
Lights in green when the memory value are being recalled or saved.
28.
RUN LED
Lights up when a Test Script has been activated.
Note
Only the ERR and ALM LED’s are red. All the others
are green.
18
Rear Panel
S LS SLSNC
REMOTE SENSE
ANALOG PROGRAMMING
RS485 / 232
OUT IN
LAN
DC OUTPUT
AC INPUT
L N
100 240V
2000VA MAX.
AC 47 63Hz
234 15678
9 10
6-60V models: PSU 6-200, 8-180, 12.5-120,
80-600V models: PSU 80-19, 100-15, 150-10,
S LS SLSNC
REMOTE SENSE
ANALOG PROGRAMMING
OUT IN
RS485 / 232
LAN
L N
AC INPUT
100 240V
2000VA MAX.
AC 47 63Hz
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
0 – 5V / 0 – 10V
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
4 – 20mA
15-100, 20-76, 30-50, 40-38, 50-30, 60-25
300-5, 400-3.8, 600-2.6
1.
AC Input
L N
AC INPUT
Wire clamp connector.
2.
DC Output
Output terminals for 6V to 60V models.
Output terminals for 80V to 600V
models.
3.
USB
USB port for controlling the PSU remotely.
GETTING STARTED
19
PSU Series Programming Manual
4.
LAN
LAN
RS 485 / 232
Ethernet port for controlling the PSU remotely.
5.
Remote-IN
LAN
RS 485 / 232
Two different types of cables can be used for RS232 or RS485-based remote control.
PSU-232: RS232 cable with DB9 connector kit.
PSU-485: RS485 cable with DB9 connector kit.
6.
Remote-OUT
LAN
RS 485 / 232
RJ-45 connector that is used to daisy chain power supplies with the Remote-IN port to form a communication bus.
PSU-485S: Serial link cable with RJ-45 shielded connector.
7.
Analog Control
ANALOG PROGRAMMING
External analog control connector.
8.
Remote Sense
S LS SLSNC
Compensation of load wire drop.
9.
Option Slot
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
0 – 5V / 0 – 10V
Blank sub-plate for standard units. Isolated Analog connector for units equipped with Isolated Current and Voltage Programming and Monitoring option. GPIB connector for units equipped with IEEE programming option.
20
GETTING STARTED
10.
Ground Screw
Connectors for grounding the output (two positions, shown in red).
L N
AC INPUT
100 240V
2000VA MAX.
AC 47 63Hz
21
PSU Series Programming Manual
The normal function settings, F-01~F-61, F-70~F­78, F-88~F-89 and F100~F122 can be easily configured with the Function key.
Ensure the load is not connected. Ensure the output is off. Function settings F-90~97 can only be viewed.
Note
Function setting F-89 (Show Version) can only be viewed, not edited.
Configuration settings F-90~ F-97 cannot be edited in the Normal Function Settings. Use the Power On Configuration Settings. See page 24 for details.
Steps
1. Press the Function key. The
function key will light up.
Function
2. The display will show F-01 on the left and the
configuration setting for F-01 on the right.
VOLTAGE CURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C V C C
V A
3. Rotate the voltage knob to change the
F setting.
Voltage
Range
F-00~F-61, F-70~F-78, F­88~F-97, F100~F122
Configuration Settings
Setting Normal Function Settings
22
GETTING STARTED
4. Use the current knob to set the
parameter for the chosen F setting.
Current
Press the Voltage knob to save the configuration setting. ConF will be displayed when it is configuring.
Voltage
VOLTAGE CURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C V C C
V A
Exit
Press the Function key again to exit the configuration settings. The function key light will turn off.
Function
23
PSU Series Programming Manual
Background
The Power On configuration settings can only be changed during power up to prevent the configuration settings being inadvertently changed.
Ensure the load is not connected. Ensure the power supply is off.
Steps
1. Hold the Function key whilst turning the
power on.
Lock/Local PROT Function Test Set
Output
Unlock ALM_CLR M 1 M 2 M 3
Shift
: Long Push
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGE CURRENT
PSU 40-38
DC Power Supply
0 - 40V / 0 - 38A
Voltage Current
2. The display will show F-90 on the left and the
configuration setting for F-90 on the right.
VOLTAGE CURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C V C C
V A
3. Rotate the voltage knob to change the
F setting.
Voltage
Range
F-90 ~ F-97
4. Use the current knob to set the
parameter for the chosen F setting.
Current
Setting Power On Configuration Settings
24
GETTING STARTED
Press the Voltage knob to save the configuration setting. ConF will be displayed when it is configuring.
Voltage
VOLTAGE CURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C V C C
V A
Exit
Cycle the power to save and exit the configuration settings.
25
PSU Series Programming Manual
Normal Function Settings
Setting
Setting Range
Output ON delay time
F-01
0.00s~99.99s
Output OFF delay time
F-02
0.00s~99.99s
V-I mode slew rate select
F-03
0 = CV high speed priority (CVHS) 1 = CC high speed priority (CCHS) 2 = CV slew rate priority (CVLS) 3 = CC slew rate priority (CVLS)
Rising voltage slew rate
F-04
0.001~0.060V/msec (PSU 6-200)
0.001~0.080V/msec (PSU 8-180)
0.001~0.125V/msec (PSU 12.5-120)
0.001~0.150V/msec (PSU 15-100)
0.001~0.200V/msec (PSU 20-76)
0.001~0.300V/msec (PSU 30-50)
0.001~0.400V/msec (PSU 40-38)
0.001~0.500V/msec (PSU 50-30)
0.001~0.600V/msec (PSU 60-25)
0.001~0.800V/msec (PSU 80-19)
0.001~1.000V/msec (PSU 100-15)
0.001~1.500V/msec (PSU 150-10)
0.001~1.500V/msec (PSU 300-5)
0.001~2.000V/msec (PSU 400-3.8)
0.001~2.400V/msec (PSU 600-2.6)
Falling voltage slew rate
F-05
0.001~0.060V/msec (PSU 6-200)
0.001~0.080V/msec (PSU 8-180)
0.001~0.125V/msec (PSU 12.5-120)
0.001~0.150V/msec (PSU 15-100)
0.001~0.200V/msec (PSU 20-76)
0.001~0.300V/msec (PSU 30-50)
0.001~0.400V/msec (PSU 40-38)
0.001~0.500V/msec (PSU 50-30)
0.001~0.600V/msec (PSU 60-25)
0.001~0.800V/msec (PSU 80-19)
0.001~1.000V/msec (PSU 100-15)
0.001~1.500V/msec (PSU 150-10)
Configuration Table
Please use the configuration settings listed below when applying the configuration settings.
26
GETTING STARTED
0.001~1.500V/msec (PSU 300-5)
0.001~2.000V/msec (PSU 400-3.8)
0.001~2.400V/msec (PSU 600-2.6)
Rising current slew rate
F-06
0.001~2.000A/msec (PSU 6-200)
0.001~1.800A/msec (PSU 8-180)
0.001~1.200A/msec (PSU 12.5-120)
0.001~1.000A/msec (PSU 15-100)
0.001~0.760A/msec (PSU 20-76)
0.001~0.500A/msec (PSU 30-50)
0.001~0.380A/msec (PSU 40-38)
0.001~0.300A/msec (PSU 50-30)
0.001~0.250A/msec (PSU 60-25)
0.001~0.190A/msec (PSU 80-19)
0.001~0.150A/msec (PSU 100-15)
0.001~0.100A/msec (PSU 150-10)
0.001~0.025A/msec (PSU 300-5)
0.001~0.008A/msec (PSU 400-3.8)
0.001~0.006A/msec (PSU 600-2.6)
Falling current slew rate
F-07
0.001~2.000A/msec (PSU 6-200)
0.001~1.800A/msec (PSU 8-180)
0.001~1.200A/msec (PSU 12.5-120)
0.001~1.000A/msec (PSU 15-100)
0.001~0.760A/msec (PSU 20-76)
0.001~0.500A/msec (PSU 30-50)
0.001~0.380A/msec (PSU 40-38)
0.001~0.300A/msec (PSU 50-30)
0.001~0.250A/msec (PSU 60-25)
0.001~0.190A/msec (PSU 80-19)
0.001~0.150A/msec (PSU 100-15)
0.001~0.100A/msec (PSU 150-10)
0.001~0.025A/msec (PSU 300-5)
0.001~0.008A/msec (PSU 400-3.8)
0.001~0.006A/msec (PSU 600-2.6)
Internal resistance setting
F-08
0~0.030Ω (PSU 6-200)
0~0.044Ω (PSU 8-180) 0~0.104Ω (PSU 12.5-120) 0~0.150Ω (PSU 15-100) 0~0.263Ω (PSU 20-76) 0~0.600Ω (PSU 30-50) 0~1.053Ω (PSU 40-38)
27
PSU Series Programming Manual
0~1.667Ω (PSU 50-30) 0~2.400Ω (PSU 60-25) 0~4.210Ω (PSU 80-19) 0~6.667Ω (PSU 100-15) 0~15.00Ω (PSU 150-10) 0~60.00Ω (PSU 300-5) 0~105.3Ω (PSU 400-3.8) 0~230.8Ω (PSU 600-2.6)
Bleeder circuit control
F-09
0 = OFF, 1 = ON, 2 = AUTO
Buzzer ON/OFF control
F-10
0 = OFF, 1 = ON
OCP Delay Time
F-12
0.1 ~ 2.0 sec
Current Setting Limit (I-Limit)
F-13
0 = OFF, 1 = ON
Voltage Setting Limit (V-Limit)
F-14
0 = OFF, 1 = ON
Display memory parameter when recalling (M1, M2, M3)
F-15
0 = OFF, 1 = ON
Auto Calibration Parallel Control
F-16
0 = Disable, 1 = Enable, 2 = Execute Parallel Calibration and set to Enable. Note: Must be a short between each unit before starting.
Measurement Average Setting
F-17
0 = Low, 1 = Middle, 2 = High
Alarm Recovery and Output Status
F-18
0 = Safe Mode, 1 = Force Mode
Lock Mode
F-19
0:Lock Panel, Allow Output OFF 1:Lock Panel, Allow Output ON/OFF
USB/GPIB settings
Show front panel USB status
F-20
0 = None, 1 = Mass Storage
Show rear panel USB status
F-21
0 = None, 1 = Linking to PC
Setup rear USB Speed
F-22
0 = Disable USB, 1 = Full Speed, 2 = Auto Detect Speed
GPIB Address
F-23
0 ~ 30
GPIB Enable/Disable
F-24
0 = Disable GPIB, 1 = Enable GPIB
Show GPIB available status
F-25
0 = No GPIB, 1 = GPIB is available SCPI Emulation
F-26
0 = GW Instek, 1 = TDK GEN, 2 =
28
GETTING STARTED
Agilent 5700, 3 = Kikusui PWX, 4 = AMREL SPS*
LAN settings
Show MAC Address-1
F-30
0x00~0xFF
Show MAC Address-2
F-31
0x00~0xFF
Show MAC Address-3
F-32
0x00~0xFF
Show MAC Address-4
F-33
0x00~0xFF
Show MAC Address-5
F-34
0x00~0xFF
Show MAC Address-6
F-35
0x00~0xFF
LAN Enable
F-36
0 = OFF, 1 = ON
DHCP
F-37
0 = OFF, 1 = ON
IP Address-1
F-39
0~255
IP Address-2
F-40
0~255
IP Address-3
F-41
0~255
IP Address-4
F-42
0~255
Subnet Mask-1
F-43
0~255
Subnet Mask-2
F-44
0~255
Subnet Mask-3
F-45
0~255
Subnet Mask-4
F-46
0~255
Gateway-1
F-47
0~255
Gateway-2
F-48
0~255
Gateway-3
F-49
0~255
Gateway-4
F-50
0~255
DNS address -1
F-51
0~255
DNS address -2
F-52
0~255
DNS address-3
F-53
0~255
DNS address-4
F-54
0~255
Socket Server Enable/Disable
F-57
0 = Disable, 1 = Enable Show Socket Server Port
F-58
No setting
Web Server Enable/Disable
F-59
0 = Disable, 1 = Enable
Web Password Enable/Disable
F-60
0 = Disable, 1 = Enable Web Enter Password
F-61
0000~9999
UART Settings
UART Mode
F-70
0 = Disable UART, 1 = RS232, 2 = RS485 4W, 3 = RS485 2W
29
PSU Series Programming Manual
UART Baud Rate
F-71
0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600, 4 = 19200, 5 = 38400, 6 = 57600, 7 = 115200
UART Data Bits
F-72
0 = 7 bits, 1 = 8 bits
UART Parity
F-73
0 = None, 1 = Odd, 2 = Even
UART Stop Bit
F-74
0 = 1 Bit, 1 = 2 Bits
UART TCP
F-75
0 = SCPI, 1 = TDK (emulation mode)
UART Address (For multi-unit remote control)
F-76
00 ~ 30
UART Multi-Drop control
F-77
0 = Disable, 1 = Master, 2 = Slave, 3 = Display information
UART Multi-Drop status
F-78
Displayed parameter: AA-S AA: 00~30 (Address), S: 0~1 (Off-line/On-line status).
System Settings
Factory Set Value
F-88
0 = None 1 = Return to factory default settings
Show Version
F-89
0, 1 = Version 2, 3, 4, 5 = Build date (YYYYMMDD) 6, 7 = Keyboard CPLD 8, 9 = Analog Board CPLD A, B = Analog Board FPGA C, D, E, F = Kernel Build
(YYYYMMDD) G, H = Test Command Version I, J, K, L = Test Command Build
(YYYYMMDD) M, N = Reserved O, P = Option Module
Power On Configuration Settings*
CV Control
F-90
0 = Control by Local 1 = Control by External Voltage 2 = Control by External Resistor -
Rising
3 = Control by External Resistor -
Falling
4 = Control by Isolated Board
30
Loading...
+ 138 hidden pages