This manual contains proprietary information, which is protected by
copyright. All rights are reserved. No part of this manual may be
photocopied, reproduced or translated to another language without
prior written consent of Good Will company.
The information in this manual was correct at the time of printing.
However, Good Will continues to improve products and reserves the
rights to change specification, equipment, and maintenance
procedures at any time without notice.
Good Will Instrument Co., Ltd.
No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.
LED ASCII Table Character Set ............................... 167
INDEX .......................................................................... 168
3
PSU Series Programming Manual
WARNING
Warning: Identifies conditions or practices that
could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that
could result in damage to the PSU or to other
properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
SAFETY INSTRUCTIONS
This chapter contains important safety
instructions that you must follow during
operation and storage. Read the following before
any operation to insure your safety and to keep
the instrument in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the
instrument.
4
SAFETY INSTRUCTIONS
Do not dispose electronic equipment as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased.
General
Guideline
CAUTION
Do not place any heavy object on the PSU.
Avoid severe impact or rough handling that
leads to damaging the PSU.
Do not discharge static electricity to the PSU.
Use only mating connectors, not bare wires, for
the terminals.
Do not block the cooling fan opening.
Do not disassemble the PSU unless you are
qualified.
(Measurement categories) EN61010-1:2010 and EN61010-2-030
specifies the measurement categories and their requirements as
follows. The PSU falls under category II.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
0 is for measurements performed on circuits not directly
connected to Mains.
Power Supply
WARNING
AC Input voltage range: 85Vac~265Vac
Frequency: 47Hz to 63Hz
To avoid electrical shock connect the protective
grounding conductor of the AC power cord to
an earth ground.
Safety Guidelines
5
PSU Series Programming Manual
Cleaning the PSU
Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Operation
Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Relative Humidity: 20%~ 85% (no condensation)
Altitude: < 2000m
Temperature: 0°C to 50°C
(Pollution Degree) EN61010-1:2010 and EN61010-2-030 specifies
the pollution degrees and their requirements as follows. The PSU
falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric
strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused
by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to
condensation which is expected. In such conditions, equipment
is normally protected against exposure to direct sunlight,
precipitation, and full wind pressure, but neither temperature
nor humidity is controlled.
Do not dispose this instrument as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased. Please make sure
discarded electrical waste is properly recycled to
reduce environmental impact.
6
SAFETY INSTRUCTIONS
Green/ Yellow:
Earth
Blue:
Neutral
Brown:
Live (Phase)
Power cord for the United Kingdom
When using the power supply in the United Kingdom, make sure
the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED
IMPORTANT: The wires in this lead are coloured in accordance with the
following code:
As the colours of the wires in main leads may not correspond with
the coloured marking identified in your plug/appliance, proceed
as follows:
The wire which is coloured Green & Yellow must be connected to
the Earth terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal
which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the
terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment
or contact the supplier.
This cable/appliance should be protected by a suitably rated and
approved HBC mains fuse: refer to the rating information on the
equipment and/or user instructions for details. As a guide, a cable
of 0.75mm2 should be protected by a 3A or 5A fuse. Larger
conductors would normally require 13A types, depending on the
connection method used.
Any exposed wiring from a cable, plug or connection that is
engaged in a live socket is extremely hazardous. If a cable or plug is
deemed hazardous, turn off the mains power and remove the cable,
any fuses and fuse assemblies. All hazardous wiring must be
immediately destroyed and replaced in accordance to the above
standard.
7
PSU Series Programming Manual
PSU Series Overview .................................................. 9
Series lineup ............................................................................................ 9
Main Features .......................................................................................10
This chapter describes the power supply in a
nutshell, including its main features and front /
rear panel introduction. After going through the
overview, please read the theory of operation to
become familiar with the operating modes,
protection modes and other safety considerations.
8
GETTING STARTED
Model name
Voltage Rating1
Current Rating2
Power
PSU 6-200
6V
200A
1200W
PSU 8-180
8V
180A
1440W
PSU 12.5-120
12.5V
120A
1500W
PSU 15-100
15V
100V
1500W
PSU 20-76
20V
76A
1520W
PSU 30-50
30V
50A
1500W
PSU 40-38
40V
38A
1520W
PSU 50-30
50V
30A
1500W
PSU 60-25
60V
25A
1500W
PSU 80-19
80V
19A
1520W
PSU 100-15
100V
15A
1500W
PSU 150-10
150V
10A
1500W
PSU 300-5
300V
5A
1500W
PSU 400-3.8
400V
3.8A
1520W
PSU 600-2.6
600V
2.6A
1560W
1
Minimum voltage guaranteed to 0.2% of rating voltage.
2
Minimum current guaranteed to 0.4% of rating current.
PSU Series Overview
Series lineup
The PSU series consists of 15 models, covering a number of
different current, voltage and power capacities:
9
Main Features
Performance
High power density: 1500W in 1U
Universal input voltage 85~265Vac, continuous
operation.
Output voltage up to 600V, current up to 200A.
Features
Active power factor correction.
Parallel master/slave operation with active
current sharing.
Remote sensing to compensate for voltage drop
in load leads.
19” rack mounted ATE applications.
A built-in Web server.
OVP, OCP and OHP protection.
Preset memory function.
Adjustable voltage and current slew rates.
Bleeder circuit ON/OFF setting.
CV, CC priority start function. (Prevents
overshoot with output ON)
Supports test scripts.
Interface
Built-in RS-232/485, LAN and USB interface.
Analog output programming and monitoring.
Optional interfaces: GPIB, Isolated Voltage (0-
5V/0-10V) and Isolated Current (4-20mA)
programming and monitoring interface.
(Factory options)
PSU Series Programming Manual
10
GETTING STARTED
Standard
Accessories
Part number
Description
Qty.
Output terminal cover
1
Analog connector plug kit
1
Output terminal M8 bolt set
(6V~60V model)
1
Input terminal cover
1
Power Cord (230VAC/10A,
1.8M, provide for some region
only)
1
82GW1SAFE0M*1
Safety Guide
1
62SB-8K0HD1*1
1U Handle, ROHS
2 62SB-8K0HP1*1
1U BRACKET (LEFT), RoHS
1
62SB-8K0HP2*1
1U BRACKET (RIGHT), RoHS
1
CD-ROM
User manual, Programming
manual
1 set
82SU-PSU00K*1
Packing list
82GW-00000C*1
* CTC GW/INSTEK JAPAN
USE ,RoHS
1
Factory Installed
Options
Part number
Description
PSU-GPIB
GPIB interface
PSU-ISO-V
Voltage programming isolated analog
interface
PSU-ISO-I
Current programming isolated analog
interface
PSU-001
Front Panel Filter Kit (Operation
Temperature is guaranteed to 40˚C)
Accessories
Before using the PSU power supply unit, check the package
contents to make sure all the standard accessories are included.
11
PSU Series Programming Manual
Optional
Accessories
Part number
Description
PSU-01C
Cable for 2 units of PSU-Series in
parallel mode connection
PSU-01B
Bus Bar for 2 units of PSU-Series in
parallel mode connection
PSU-01A
Joins a vertical stack of 2 PSU units
together. 2U-sized handles x2, joining
plates x2.
PSU-02C
Cable for 3 units of PSU-Series in
parallel mode connection
PSU-02B
Bus Bar for 3 units of PSU-Series in
parallel mode connection
PSU-02A
Joins a vertical stack of 3 PSU units
together. 3U-sized handles x2, joining
plates x2.
PSU-03C
Cable for 4 units of PSU-Series in
parallel mode connection
PSU-03B
Bus Bar for 4 units of PSU-Series in
parallel mode connection
PSU-03A
Joins a vertical stack of 4 PSU units
together. 4U-sized handles x2, joining
plates x2.
PSU-232
RS232 cable with DB9 connector kit.
It Includes RS232 cable with DB9
connector, RS485 used master cable
(gray plug), slave cable (black plug),
intermediate connector and end
terminal connector.
PSU-485
RS485 cable with DB9 connector kit.
It Includes RS485 cable with DB9
connector, RS485 used master cable
(gray plug), slave cable (black plug),
intermediate connector and end
terminal connector.
Power Cord SJT 12AWG/3C, 3m MAX
Length, 105 ºC, RNB5-5*3P UL/CSA
type
GPW-002
Power Cord H05W-F 1.5mm2/3C, 3m
MAX Length, 105 ºC, RNB5-5*3P VDE
type
GPW-003
Power Cord VCTF 3.5mm2/3C, 3m
MAX Length, 105 ºC, RNB5-5*3P PSE
type
Download
Name
Description
psu_cdc.inf
PSU USB driver
Other
Name
Description
Certificate of traceable calibration
13
PSU Series Programming Manual
Lock/Local PROT Function Test SetOutput
Unlock ALM_CLR M 1 M 2 M 3
Shift
: Long Push
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGECURRENT
PSU 40-38
DC Power Supply
0 -40V / 0 - 38A
VoltageCurrent
2345
Display Area
1
116 7 8 9 1012 13
1.
Power Switch
Used to turn the power on/off.
2.
USB A Port
USB A port for data transfer,
loading test scripts etc.
3.
Air Inlet
Air inlet for cooling the inside of
the PSU series.
4.
Voltage Knob
Voltage
Used to set the voltage value or
select a parameter number in the
Function settings.
Display Area
The display area shows setting values, output
values and parameter settings. The function LEDs
below show the current status and mode of the
power supply. See page 17 for details.
5.
Current Knob
Current
Used to set the current value or
change the value of a Function
parameter.
Appearance
PSU Series Front Panel
14
GETTING STARTED
6.
Lock/Local
Button
Lock/Local
Unlock
Used to lock all front panel
buttons other than the Output
Button or it switches to local
mode.
Unlock
Button
(Long push) Used to unlock the
front panel buttons.
7.
PROT Button
PROT
ALM_CLR
Used to set and display OVP, OCP
and UVL.
ALM_CLR
Button
(Long push) Used to release
protection functions that have
been activated.
8.
Function
Button
Function
M1
Used to configure the various
functions.
M1 Button
(+Shift) Used to recall the M1
setup.
(+Shift and hold) Used to save the
current setup to M1.
9.
Test Button
TEST
M2
Used to run customized scripts for
testing.
M2 Button
(+Shift) Used to recall the M2
setup.
(+Shift and hold) Used to save the
current setup to M2.
10.
Set Button
SET
M3
Used to set and confirm the output
voltage and output current.
M3 Button
(+Shift) Used to recall the M3
setup.
(+Shift and hold) Used to save the
current setup to M3.
15
PSU Series Programming Manual
11.
Shift Button
Shift
Used to enable the functions that
are written in blue characters
below certain buttons.
12.
Output
Button
Output
Used to turn the output on or off.
13.
Output ON
LED
Lights in green when the output is
on.
16
GETTING STARTED
VSRLANRMTERRDLYALMISRM 1M 2M 3RUN
C C
A
C V
V
VOLTAGECURRENT
Display Area
14151617
18192021222324
25
262728
14.
Voltage
Meter
Displays the voltage or the parameter number of a
Function parameter.
15.
Current
Meter
Displays the current or the value of a Function
parameter.
16.
CV LED
Lights in green during constant voltage mode.
17.
CC LED
Lights in green during constant current mode.
18.
VSR LED
Lights up when CV Slew Rate Priority is enabled.
19.
LAN LED
Lights up when the LAN interface is connected.
20.
RMT LED
Lights in green during remote control.
21.
ERR LED
Lights in red when an SCPI error has occurred.
22.
DLY LED
The Output On/Off Delay indicator LED.
23.
ALM LED
Lights in red when a protection function has been
activated.
PSU Series Display and Operation Panel
17
PSU Series Programming Manual
24.
ISR LED
Lights up when CC Slew Rate Priority is enabled.
25.
M1 LED
Lights in green when the memory value are being
recalled or saved.
26.
M2 LED
Lights in green when the memory value are being
recalled or saved.
27.
M3 LED
Lights in green when the memory value are being
recalled or saved.
28.
RUN LED
Lights up when a Test Script has been activated.
Note
Only the ERR and ALM LED’s are red. All the others
are green.
18
Rear Panel
S LS SLSNC
REMOTE SENSE
ANALOG PROGRAMMING
RS485 / 232
OUT IN
LAN
DC OUTPUT
AC INPUT
L N
100 240V
2000VA MAX.
AC
47 63Hz
23415678
910
6-60V models:
PSU 6-200, 8-180, 12.5-120,
80-600V models:
PSU 80-19, 100-15, 150-10,
S LS SLSNC
REMOTE SENSE
ANALOG PROGRAMMING
OUT IN
RS485 / 232
LAN
L N
AC INPUT
100 240V
2000VA MAX.
AC
47 63Hz
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
0 – 5V / 0 – 10V
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
4 – 20mA
15-100, 20-76, 30-50,
40-38, 50-30, 60-25
300-5, 400-3.8, 600-2.6
1.
AC Input
LN
AC INPUT
Wire clamp connector.
2.
DC Output
Output terminals for 6V to 60V
models.
Output terminals for 80V to 600V
models.
3.
USB
USB port for controlling the PSU
remotely.
GETTING STARTED
19
PSU Series Programming Manual
4.
LAN
LAN
RS 485 / 232
Ethernet port for controlling the
PSU remotely.
5.
Remote-IN
LAN
RS 485 / 232
Two different types of cables can
be used for RS232 or RS485-based
remote control.
PSU-232: RS232 cable with DB9
connector kit.
PSU-485: RS485 cable with DB9
connector kit.
6.
Remote-OUT
LAN
RS 485 / 232
RJ-45 connector that is used to
daisy chain power supplies with
the Remote-IN port to form a
communication bus.
PSU-485S: Serial link cable with
RJ-45 shielded connector.
7.
Analog
Control
ANALOG PROGRAMMING
External analog control connector.
8.
Remote
Sense
S LSSLSNC
Compensation of load wire drop.
9.
Option Slot
1 2 3 4 5 6 7 8
ISOLATED PROGRAMMING
0 – 5V / 0 – 10V
Blank sub-plate for standard units.
Isolated Analog connector for
units equipped with Isolated
Current and Voltage
Programming and Monitoring
option.
GPIB connector for units equipped
with IEEE programming option.
20
GETTING STARTED
10.
Ground
Screw
Connectors for grounding the output (two
positions, shown in red).
L N
AC INPUT
100 240V
2000VA MAX.
AC
47 63Hz
21
PSU Series Programming Manual
The normal function settings, F-01~F-61, F-70~F78, F-88~F-89 and F100~F122 can be easily
configured with the Function key.
Ensure the load is not connected.
Ensure the output is off.
Function settings F-90~97 can only be viewed.
Note
Function setting F-89 (Show Version) can only be
viewed, not edited.
Configuration settings F-90~ F-97 cannot be edited in
the Normal Function Settings. Use the Power On
Configuration Settings. See page 24 for details.
Steps
1. Press the Function key. The
function key will light up.
Function
2. The display will show F-01 on the left and the
configuration setting for F-01 on the right.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
3. Rotate the voltage knob to change the
F setting.
Voltage
Range
F-00~F-61, F-70~F-78, F88~F-97, F100~F122
Configuration Settings
Setting Normal Function Settings
22
GETTING STARTED
4. Use the current knob to set the
parameter for the chosen F setting.
Current
Press the Voltage knob to save the
configuration setting. ConF will be
displayed when it is configuring.
Voltage
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Exit
Press the Function key again to exit
the configuration settings. The
function key light will turn off.
Function
23
PSU Series Programming Manual
Background
The Power On configuration settings can only be
changed during power up to prevent the
configuration settings being inadvertently
changed.
Ensure the load is not connected.
Ensure the power supply is off.
Steps
1. Hold the Function key whilst turning the
power on.
Lock/Local PROT Function Test Set
Output
Unlock ALM_CLR M1 M 2 M 3
Shift
: Long Push
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C C
A
C V
V
VOLTAGECURRENT
PSU 40-38
DC Power Supply
0 - 40V / 0 - 38A
VoltageCurrent
2. The display will show F-90 on the left and the
configuration setting for F-90 on the right.
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
3. Rotate the voltage knob to change the
F setting.
Voltage
Range
F-90 ~ F-97
4. Use the current knob to set the
parameter for the chosen F setting.
Current
Setting Power On Configuration Settings
24
GETTING STARTED
Press the Voltage knob to save the
configuration setting. ConF will be
displayed when it is configuring.
Voltage
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
VA
Exit
Cycle the power to save and exit the configuration
settings.
25
PSU Series Programming Manual
Normal Function Settings
Setting
Setting Range
Output ON delay time
F-01
0.00s~99.99s
Output OFF delay time
F-02
0.00s~99.99s
V-I mode slew rate select
F-03
0 = CV high speed priority (CVHS)
1 = CC high speed priority (CCHS)
2 = CV slew rate priority (CVLS)
3 = CC slew rate priority (CVLS)
Rising voltage slew rate
F-04
0.001~0.060V/msec (PSU 6-200)
0.001~0.080V/msec (PSU 8-180)
0.001~0.125V/msec (PSU 12.5-120)
0.001~0.150V/msec (PSU 15-100)
0.001~0.200V/msec (PSU 20-76)
0.001~0.300V/msec (PSU 30-50)
0.001~0.400V/msec (PSU 40-38)
0.001~0.500V/msec (PSU 50-30)
0.001~0.600V/msec (PSU 60-25)
0.001~0.800V/msec (PSU 80-19)
0.001~1.000V/msec (PSU 100-15)
0.001~1.500V/msec (PSU 150-10)
0.001~1.500V/msec (PSU 300-5)
0.001~2.000V/msec (PSU 400-3.8)
0.001~2.400V/msec (PSU 600-2.6)
Falling voltage slew rate
F-05
0.001~0.060V/msec (PSU 6-200)
0.001~0.080V/msec (PSU 8-180)
0.001~0.125V/msec (PSU 12.5-120)
0.001~0.150V/msec (PSU 15-100)
0.001~0.200V/msec (PSU 20-76)
0.001~0.300V/msec (PSU 30-50)
0.001~0.400V/msec (PSU 40-38)
0.001~0.500V/msec (PSU 50-30)
0.001~0.600V/msec (PSU 60-25)
0.001~0.800V/msec (PSU 80-19)
0.001~1.000V/msec (PSU 100-15)
0.001~1.500V/msec (PSU 150-10)
Configuration Table
Please use the configuration settings listed below when applying
the configuration settings.
setting to 2 (Auto Detect Speed) or
1 (USB Full Speed).
Page 22
Note
If you are not using the rear panel USB
device port, set F-22 to 0 (Disable USB).
Page 22
3. The RMT indicator will turn on when a remote
connection has been established.
RMT indicator
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
Interface Configuration
USB Remote Interface
Configuration
35
Function Check
Functionality
check
Invoke a terminal application such as Realterm.
To check the COM port No., see the Device
Manager in the PC. For WinXP; Control panel → System → Hardware tab.
Run this query command via the terminal
application after the instrument has been
configured for USB remote control (page 35).
*idn?
This should return the Manufacturer, Model
number, Serial number, and Firmware version in
the following format.
GW-INSTEK,PSU40-38,TW123456,T0.01.12345678
Manufacturer: GW-INSTEK
Model number : PSU40-38
Serial number : TW123456
Firmware version : T0.01.12345678
PSU Series Programming Manual
36
REMOTE CONTROL
Configure GPIB
1. Ensure the PSU is off before proceeding.
2. Connect a GPIB cable from a GPIB controller to
the GPIB port on the PSU.
3. Turn the PSU on.
4. Press the Function key to enter the
Normal configuration settings.
Page 22
5. Set the following GPIB settings.
F-24 = 1
Enable the GPIB port
F-23 = 0~30
Set the GPIB address (0~30)
6. Check to see that the GPIB option
is detected by the PSU. The F-25
setting indicates the GPIB port
status.
F-25 = 1
Indicates that the GPIB port is
available.
F-25 = 0
Indicates that the GPIB port is not
detected.
GPIB Remote Interface
Configuration
To use GPIB, the optional GPIB option (GW Instek part number:
PSU-GPIB) must be installed. This is a factory installed option and
cannot be installed by the end-user. Only one GPIB address can be
used at a time.
37
PSU Series Programming Manual
7. The RMT indicator will turn on when a remote
connection has been established.
RMT indicator
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
GPIB constraints
Maximum 15 devices altogether, 20m cable
length, 2m between each device
Unique address assigned to each device
At least 2/3 of the devices turned On
No loop or parallel connection
Background
To test the GPIB functionality, National
Instruments Measurement and Automation
Explorer can be used. This program is available on
the NI website, www.ni.com., via a search for the
VISA Run-time Engine page, or “downloads” at
the following URL, http://www.ni.com/visa/
Set the baud rate: 0=1200, 1=2400,
2=4800, 3=9600, 4=19200,
5=38400, 6=57600, 7=115200
44
REMOTE CONTROL
F-72 = 0 or 1
Data bits: 0=7 or 1=8
F-73 = 0 ~3
Parity: 0 = none, 1 = odd, 2 = even
F-74 = 0 or 1
Stop bits: 0 = 1, 1 = 2
F-75 = 0
TCP: 0 = SCPI
F-76 = 00~30
UART address for multi-unit
remote connection.
F-77 = 0
Disable Multi-Drop mode.
4. The RMT indicator will turn on when a remote
connection has been established.
RMT indicator
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
45
PSU Series Programming Manual
Functionality
check
Invoke a terminal application such as Realterm.
To check the COM port No, see the Device
Manager in the PC. For WinXP; Control panel → System → Hardware tab.
Run this query command via the terminal
application after the instrument has been
configured for either RS232 or RS485 remote
control.
SCPI commands
Command or response
Status
*IDN?
Typing
GW-INSTEK,PSU40-38,TW123456,
T0.01.12345678
Return
Return the manufacturer, model, serial
number, and firmware version in the
above format.
Manufacturer: GW-INSTEK
Model: PSU40-38
Serial number: TW123456
Firmware version: T0.01.12345678
Note
UART Function Check
46
REMOTE CONTROL
Operation
1. Check the F-89 (System version and build date)
settings first on all units. The two parameters
O and P (Option Module) must be the same on
all units before any multiple unit connection
can be established.
Example: F-89 O:00, P:01.
2. Connect the first unit’s IN port to a PC via
RS232 or RS485 serial cable.
Use the serial cables supplied in the PSU-
Multiple Unit Connection
The PSU power supplies can have up to 31 units daisy chained
together using the 8 pin connectors (IN OUT ports) on the rear
panel. The first unit (master) in the chain is remotely connected to a
PC using RS232 or RS485 (Legacy Multi-Drop mode), or USB, GPIB
or LAN (Multi-Drop mode). Each subsequent unit (slave) is daisy
chained to the next using a RS485 local bus. The OUT port of the
first unit must be connected to intermediate connector and the OUT
port of the last unit must be connected to end terminal connector.
There are two modes for controlling multiple units. In the first
mode (Legacy Multi-Drop mode), the PC is only allowed to use
RS232 or RS485 to connect to the first device, and all UART
parameters must be executed in this mode Configuration. The
remote command supports the SCPI commands or TDK GENESYS
legacy commands.
In the second mode (Multi-Drop mode), the PC is allowed to
connect to the first unit using USB-CDC/GPIB/LAN. In this mode,
you only need to specify the Multi-Drop parameter. Remote
commands only support SCPI commands.
For these two modes, each unit is assigned a unique address, which
can then be controlled independently of the host PC.
Legacy Multi-Drop mode
47
PSU Series Programming Manual
232 or PSU-485 connection kit.
3. Plug in intermediate connector to the OUT port
on the first unit then using the slave serial link
cable (black plug) to connect intermediate
connector to the IN port of the second unit.
4. Connect all the remaining units in the same
fashion until all the units have been daisychained together.
RS 485 / 232
OUTIN
Unit #1
RS 485 / 232
OUTIN
Unit #2
RS 485 / 232
OUTIN
Unit #N
End terminal
connector
To PC
RS232/RS485
serial cable
Slave serial
cable(black plug)
Slave serial
cable(black plug)
Intermediate
connector
5. Terminate the OUT port of the last unit with the
end terminal connector included in the PSU232 or PSU-485 connection kit.
6. Press the Function key to enter the
Normal configuration settings for
the master unit.
Page 4
Set the following settings:
F-70 = 1~3
Configure the master unit as you
normally would for RS232 or RS485
remote control, see page 42.
F-71 = 0~7
Set the baud rate (set all units the
same). See page 42.
F-72 = 1
Set to 8 data bits.
F-73 = 0
Parity to none.
F-74 = 0
1 Stop bit.
48
REMOTE CONTROL
F-75 = 0 or 1
F-75 = 0
Set the UART TCP to SCPI.
F-75 = 1
Set the UART TCP to TDK (emulation
mode).
F-76 = 00~30
Set the address of the master unit. It
must be a unique address identifier.
F-77 = 0
Disable Multi-Drop mode.
7. Press the Function key to enter the
Normal configuration settings for
the slave(s).
Page 4
Set the following settings:
F-70 = 2~3
Set the slave unit to RS485.
Connect to
PC using
F-70
(Master)
F-70
(All slave)
RS232
1
2
RS485 4W
2
2
RS485 2W
3
3
F-71 = 0~7
Set the baud rate (make all units,
including the master, the same baud).
See page 42.
F-72 = 1
Set to 8 data bits.
F-73 = 0
Parity to none.
F-74 = 0
1 Stop bit.
F-75 = 0~1
F-75 = 0
Set the UART TCP to SCPI.
F-75 = 1
Set the UART TCP to TDK (emulation
mode).
Set the uart tcp (make all units,
including the master, the same uart
tcp).
49
PSU Series Programming Manual
F-76 = 00~30
Set the address of each slave to a
unique address identifier
F-77 = 0
Disable Multi-Drop mode.
8. Multiple units can now be operated at the same
time. See the programming manual or see the
function check below for usage details.
Slave serial link
cable with RJ-45
shielded
connectors from
PSU-232 or PSU485 connection
kit
RS-485 slave serial link pin assignment
8 Pin Connector
(IN)(RJ-45)
8 Pin Connector
(OUT)(RJ-45)
Pin No.
Name
Pin No.
Name
Housing
Shield
Housing
Shield
1
SG 1
SG 6 TXD -
6 TXD -
3
TXD +
3 TXD +
5
RXD -
5 RXD -
4
RXD +
4 RXD +
1 8
(RJ-45)
1 8
(RJ-45)
50
REMOTE CONTROL
Diagram of
Intermediate
connector
Intermediate
connector from
PSU-232 or PSU485 connection
kit.
Intermediate connector
8 Pin (Male)
8 Pin (Female)
Pin No.
Name
Pin No.
Name
Remarks
Housing
Shield
Case
Shield
1 SG 1
SG 6
TXD -
6 TXD -
Internal paralleled
by 120 ohm
3
TXD +
3 TXD +
5
RXD -
5 RXD -
Internal paralleled
by 120 ohm
4
RXD+
4 RXD +
Diagram of End
terminal
connector
End terminal
connector from
PSU-232 or PSU485 connection
kit.
End terminal connector
8 Pin Connector
Pin No.
Remarks
3
Internal shorted
7 4 Internal shorted
Operation
1. Check the F-89 (System version and build date)
settings first on all units. The two parameters O
and P (Option Module) must be the same on all
units before any multiple unit connection can be
established.
Example: F-89 O:00, P:01.
2. All units must be powered down before starting
the Multi-Drop mode configuration.
Multi-Drop mode
51
PSU Series Programming Manual
3. Connect the first unit’s LAN, USB or GPIB port
to a PC.
4. Plug in intermediate connector to the OUT port
on the first unit then using the master serial link
cable (gray plug) to connect intermediate
connector to the IN port of the second unit.
5. Connect all the remaining units between the
OUT port and the IN port with the slave serial
link cable (black plug) supplied in the PSU-232
or PSU-485 connection kit until all the desired
units have been daisy-chained together.
RS 485 / 232
OUT
Unit #1
RS 485 / 232
OUTIN
Unit #2
RS 485 / 232
OUTIN
Unit #N
End terminal
connector
To PC
Master serial link
cable (gray plug)
Slave serial link
cable (black plug)
USB
LAN
GPIB
Intermediate
connector
6. Terminate the OUT port of the last unit with the
end terminal connector included in the PSU-232
or PSU-485 connection kit.
7. Power up all slave units.
8. Set the addresses of all slave units using the
F-76 parameter.
F-76 = 00~30
Set the address of the unit. It must
be a unique address identifier.
9. Set the Multi-Drop setting parameter (F-77) to
Slave for all slave units.
F-77 = 2
Set the Multi-Drop setting to slave.
10. Power up the master unit.
52
REMOTE CONTROL
11. Set the address of the master unit using the
F-76 parameter.
F-76 = 00~30
Set the address of the unit. It must
be a unique address identifier.
12. You can check the slaves’ addresses by using
the F-77 parameter on the master unit.
F-77 = 3
Display on each slave units the
configured address. This can show if
identical addresses have been
assigned individually to each slave
units.
13. Set the Multi-Drop setting parameter (F-77) to
Master.
F-77 = 1
Set the Multi-Drop setting to
master.
14. You can display the status of each slave unit by
commands. See the programming manual or see
the function check below for usage details.
53
PSU Series Programming Manual
Slave serial link
cable with RJ-45
shielded
connectors from
PSU-232 or PSU485 connection
kit
RS-485 slave serial link pin assignment
8 Pin Connector
(IN)(RJ-45)
8 Pin Connector
(OUT)(RJ-45)
Pin No.
Name
Pin No.
Name
Housing
Shield
Housing
Shield
1
SG 1
SG 6 TXD -
6 TXD -
3
TXD +
3 TXD +
5
RXD -
5 RXD -
4
RXD +
4 RXD +
1 8
(RJ-45)
1 8
(RJ-45)
Master serial link
cable with RJ-45
shielded
connectors from
PSU-232 or PSU485 connection
kit
RS-485 master serial link pin assignment
8 Pin Connector
(IN)(RJ-45)
8 Pin Connector
(OUT)(RJ-45)
Pin No.
Name
Pin No.
Name
Housing
Shield
Housing
Shield
1
SG 1
SG 6 TXD -
5 RXD -
3
TXD +
4 RXD +
5
RXD -
6 TXD -
4
RXD +
3 TXD +
1 8
(RJ-45)
1 8
(RJ-45)
54
REMOTE CONTROL
Diagram of
Intermediate
connector
Intermediate
connector from
PSU-232 or PSU485 connection
kit.
Intermediate connector
8 Pin (Male)
8 Pin (Female)
Pin No.
Name
Pin No.
Name
Remarks
Housing
Shield
Case
Shield
1 SG 1
SG 6
TXD -
6 TXD -
Internal paralleled
by 120 ohm
3
TXD +
3 TXD +
5
RXD -
5 RXD -
Internal paralleled
by 120 ohm
4
RXD +
4 RXD +
Diagram of End
terminal
connector
End terminal
connector from
PSU-232 or PSU485 connection
kit.
End terminal connector
8 Pin Connector
Pin No.
Remarks
3
Internal shorted
7
4
Internal shorted
8
Functionality
check
Invoke a terminal application such as Realterm.
To check the COM port No, see the Device
Manager in the PC. For WinXP; Control panel →
System → Hardware tab.
Below shows examples using the Legacy MultiDrop mode and the Multi-Drop mode.
Multiple units Function Check
55
PSU Series Programming Manual
Legacy MultiDrop mode
When using SCPI commands or TDK GENESYS
legacy commands, each unit can be individually
controlled using the unique address identifiers.
For this function check, we will assume that the
master unit is assigned to address 8, while a slave
is assigned address 11.
Run this query command via the terminal
application after the instruments have been
configured for multi-unit control with Legacy
Multi-Drop mode. See page 47.
SCPI commands
Command or response
Status
INST:SEL 8
Typing
*IDN?
Typing
GW-INSTEK,PSU40-38,,T0.01.12345678
Return
Selects the unit with address 8 and
returns its identity string.
Note
INST:SEL 11
Typing
*IDN?
Typing
GW-INSTEK,PSU6-200,,T0.01.12345678
Return
Selects the unit with address 11 and
returns its identity string.
Note
TDK GENESYS
legacy commands
(Because the terminal character used by the TDK
GENESYS legacy command is CR instead of LF,
the terminal characters are specifically listed
below)
Command or response
Status
ADR 8\r
Typing
OK\r
Return
IDN? \r
Typing
GW-INSTEK,PSU40-38,,T0.01.12345678\r
Return
56
REMOTE CONTROL
Selects the unit with address 8 and
returns its identity string.
Note
ADR 11\r
Typing
OK\r
Return
IDN? \r
Typing
GW-INSTEK,PSU6-200,,T0.01.12345678\r
Return
Selects the unit with address 11 and
returns its identity string.
Note
Note
TDK commands do not use LF (line feed) codes to
terminate commands. See the TDK GENESYS user
manual for further information.
Multi-Drop mode
When using the Multi-Drop mode, the entire SCPI
command list developed for the PSU can be used.
Each unit can be individually controlled after a
slave unit has been selected. For this function
check, we will assume that the master unit is
assigned to address 0, while a slave is assigned
address 5.
Run this query command via the terminal
application after the instruments have been
configured for multi-unit control with Multi-Drop
mode. See page 51.
SCPI commands
Command or response
Status
INST:SEL 0
Typing
*IDN?
Typing
GW-INSTEK,PSU150-10,,T0.01.12345678
Return
Selects the unit with address 0 and
returns its identity string.
Note
INST:SEL 5
Typing
*IDN?
Typing
57
PSU Series Programming Manual
GW-INSTEK, PSU150-10,,T0.01.12345678
Return
Selects the unit with address 5 and
returns its identity string.
Note
INST:SEL 6
Typing
Selects the unit with address 6 (not
configured in our example). An error is
displayed on the master front panel.
Note
INST:SEL 0
Typing
SYST:ERR?
Typing
-221, “Settings conflict”
Return
Query the system errors. “Settings
conflict” is returned.
Note
INST:STAT?
Typing
33,0
Return
Returns the active units and master unit
in the bus.
33=0b100001
The units at address 0 and address 5 are
on-line.
0
Master device's address is 0.
Note
58
REMOTE CONTROL
Ethernet
configuration
Parameters
For details on how to configure the Ethernet
settings, please see the configuration chapter on
page 4.
MAC Address (display
only)
LAN Enable/Disable
DHCP Enable/Disable
IP Address
Subnet Mask
Gateway
DNS Address
Sockets Server
Enable/Disable
Web Server
Enable/Disable
Web Password
Enable/Disable
Web Enter Password
Configuration
This configuration example will configure the PSU
as a web server and use DHCP to automatically
assign an IP address to the PSU.
1. Connect an Ethernet cable from the
network to the rear panel Ethernet
port.
LAN
Configure Ethernet Connection
The Ethernet interface can be configured for a number of different
applications. Ethernet can be configured for basic remote control or
monitoring using a web server or it can be configured as a socket
server.
The PSU series supports both DHCP connections so the instrument
can be automatically connected to an existing network or
alternatively, network settings can be manually configured.
Web Server Configuration
59
PSU Series Programming Manual
2. Press the Function key to enter the
Normal configuration settings.
Page 22
Set the following LAN settings:
F-36 = 1
Turn LAN on
F-37 = 1
Enable DHCP
F-59 = 1
Turn the web server on
F-60 = 0 or 1
Set to 0 to disable web password,
set to 1 to enable web password
F-61 = 0000
~9999
Set the web password
3. The LAN indicator will turn on when a
network cable is plugged in.
LAN indicator
AV
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M 1 M 2 M 3 RUN
C VC C
Note
It may be necessary to cycle the power or refresh the
web browser to connect to a network.
Functionality
check
Enter the IP address of the power supply in a web
browser after the instrument has been configured
as a web server (page 59).
The web server allows you to monitor the function
settings of the PSU.
You can check the IP address by checking F-39 to F-42.
F-39 = AAA
IP Address part 1 of 4
F-40 = BBB
IP Address part 2 of 4
F-41 = CCC
IP Address part 3 of 4
F-42 = DDD
IP Address part 4 of 4
Web Server Remote Control Function Check
60
REMOTE CONTROL
http:// AAA.BBB.CCC.DDD
The web browser interface appears.
The web browser interface allows you to access
the following:
Network configuration settings
Analog control pinouts & usage
PSU dimensions
Operating area diagram
61
PSU Series Programming Manual
Configuration
This configuration example will configure the PSU
socket server.
The following configuration settings will manually
assign the PSU an IP address and enable the socket
server. The socket server port number is fixed at
2268.
1. Connect an Ethernet cable from the
network to the rear panel Ethernet
port.
LAN
2. Press the Function key to enter the
Normal configuration settings.
Page 22
Set the following LAN settings:
F-36 = 1
Enable LAN
F-37 = 0
Disable DHCP
F-39 = 172
IP Address part 1 of 4
F-40 = 16
IP Address part 2 of 4
F-41 = 5
IP Address part 3 of 4
F-42 = 133
IP Address part 4 of 4
F-43 = 255
Subnet Mask part 1 of 4
F-44 = 255
Subnet Mask part 2 of 4
F-45 = 128
Subnet Mask part 3 of 4
F-46 = 0
Subnet Mask part 4 of 4
F-47 = 172
Gateway part 1 of 4
F-48 = 16
Gateway part 2 of 4
F-49 = 21
Gateway part 3 of 4
F-50 = 101
Gateway part 4 of 4
F-57 = 1
Enable Sockets
Sockets Server Configuration
62
REMOTE CONTROL
Background
To test the socket server functionality, National
Instruments Measurement and Automation
Explorer can be used. This program is available on
the NI website, www.ni.com., via a search for the
VISA Run-time Engine page, or “downloads” at
the following URL, http://www.ni.com/visa/
5. Enter the IP address and the port number of the
PSU. The port number is fixed at 2268.
6. Click the Validate button.
7. A popup will appear if a connection is
successfully established.
8. Click Next.
64
REMOTE CONTROL
6
5
7
8
9. Next configure the Alias (name) of the PSU
connection. In this example the Alias is:
PSU_DC1
10. Click finish.
9
10
11. The IP address of the PSU will now appear
under Network Devices in the configuration
panel. Select this icon now.
12. Click Open VISA Test Panel.
65
PSU Series Programming Manual
11
12
13. Click the Configuration icon,
14. Click on I/O Settings.
15. Make sure the Enable Termination Character
check box is checked, and the terminal
character is \n (Value: xA).
16. Click Apply Changes.
14
13
15
16
17. Click the Input/Output icon.
18. Enter *IDN? in the Select or Enter Command
dialog box if it is not already.
19. Click the Query button.
66
REMOTE CONTROL
20. The *IDN? query will return the Manufacturer,
model name, serial number and firmware
version in the dialog box.
GW-INSTEK,PSU40-38,TW123456,T0.02.20131205
18
17
19
20
67
PSU Series Programming Manual
Compatible
Standard
IEEE488.2
Partial compatibility
SCPI, 1999
Partial compatibility
Command
Structure
SCPI commands follow a tree-like structure,
organized into nodes. Each level of the command
tree is a node. Each keyword in a SCPI command
represents each node in the command tree. Each
keyword (node) of a SCPI command is separated
by a colon (:).
For example, the diagram below shows an SCPI
sub-structure and a command example.
DC
MEASure
SCALar
POWer
VOLTage
CURRent
DC
DC
MEASure:SCALar:CURRent:DC?
Command types
There are a number of different instrument
commands and queries. A command sends
instructions or data to the unit and a query
receives data or status information from the unit.
Command types
Simple
A single command with/without
a parameter
Example
*IDN?
Command Syntax
68
REMOTE CONTROL
Query
A query is a simple or compound
command followed by a question
mark (?). A parameter (data) is
returned.
Example
meas:curr:dc?
Compound
Two or more commands on the
same command line. Compound
commands are separated with
either a semi-colon (;) or a semicolon and a colon (;:).
A semi-colon is used to join two
related commands, with the
caveat that the last command
must begin at the last node of the
first command.
A semi-colon and colon are used
to combine two commands from
different nodes.
Example
meas:volt:dc?;:meas:curr:dc?
Command Forms
Commands and queries have two different forms,
long and short. The command syntax is written
with the short form of the command in capitals
and the remainder (long form) in lower case.
The commands can be written in capitals or lowercase, just so long as the short or long forms are
complete. An incomplete command will not be
recognized.
Commands that contain square brackets indicate
that the contents are optional. The function of the
command is the same with or without the square
bracketed items, as shown below.
Both “DISPlay:MENU[:NAME]?” and
“DISPlay:MENU?” are both valid forms.
Command
Format
1.5,5.2
12 3 4 5
APPLY
1. Command header
2. Space
3. Parameter 1
4. Comma (no space
before/after comma)
5. Parameter 2
Parameters
Type
Description
Example
<Boolean>
Boolean logic
0, 1
<NR1>
integers
0, 1, 2, 3
<NR2>
decimal
numbers
0.1, 3.14, 8.5
<NR3>
floating point
4.5e-1, 8.25e+1
<NRf>
any of NR1, 2, 3
1, 1.5, 4.5e-1
<block data>
Definitive length arbitrary block
data. A single decimal digit
followed by data. The decimal
digit specifies how many 8-bit
data bytes follow.
The DISPlay MENU command selects a screen
menu or queries the current screen menu.
Syntax
Query Sytax
:DISPlay:MENU[:NAME] <NR1>
:DISPlay:MENU[:NAME]?
Parameter/
Return parameter
<NR1>
Description
0
Measure voltage & current
1~2
Not Used
3
Set Menu
4
OVP / OCP Menu
5~99
Not Used.
100~199
F-00~99 Menu.
200~229
F100~F129 Menu.
Example
DISP:MENU:NAME 0
Sets the display to the Voltage/Current display
screen.
:DISPlay[:WINDow]:TEXT:CLEar
Set
Description
Clears the text on the main screen from
the :DISPlay[:WINDow]:TEXT[:DATA] command.
Syntax
:DISPlay[:WINDow]:TEXT:CLEar
Display Commands
76
REMOTE CONTROL
:DISPlay[:WINDow]:TEXT[:DATA]
Set
Query
Description
Sets or queries the data text that will be written to
the display. Writing to the display will overwrite
data that is currently on the screen. Overwriting a
display area with a shorter string may or may not
overwrite the screen. The string must be enclosed
in quotes: “STRING”. Only ASCII characters 20H
to 7EH can be used in the <string>.
Syntax
Query Syntax
:DISPlay[:WINDow]:TEXT[:DATA] <string>
:DISPlay[:WINDow]:TEXT[:DATA]?
Parameter/
Return parameter
<string>
ASCII character 20H to 7EH can be used
to in the string parameter. The string
must be enclosed in quotes: “STRING”
Example
DISP:WIND:TEXT:DATA “STRING”
Writes STRING to the display.
Query Example
DISP:WIND:TEXT:DATA?
“STRING”
Returns the text data string on the screen.
:DISPlay:BLINk
Set
Query
Description
Turns blink on or off for the display. Blink is set to
OFF by default.
This command continuously initiates software
triggers for the transient or output triggers.
Syntax
Query Syntax
:INITiate:CONTinuous[:TRANsient]
{<bool>|OFF|ON}
:INITiate:CONTinuous[:TRANsient]?
Parameter
OFF | 0
OFF
ON | 1
ON
Return parameter
0
OFF
1
ON
Example
INIT:TRAN 1
Turns on the continuous trigger.
:INITiate[:IMMediate]:NAME
Set
Description
The INITiate command starts the TRANsient or
OUTPut trigger.
Syntax
:INITiate[:IMMediate]:NAME {TRANsient|OUTPut}
Parameter
TRANSient
Starts the TRANsient trigger.
OUTPut
Starts the OUTPut trigger.
Example
INITiate:NAME TRANient
Starts the TRANSient trigger.
Initiate Commands
78
REMOTE CONTROL
:INITiate[:IMMediate][:TRANsient]
Set
Description
This command controls the enabling of output
triggers. When a trigger is enabled, a trigger
causes the specified action to occur. If the trigger
system is not enabled, all triggers are ignored.
Sets the Delay Time in seconds for turning the
output on. The delay is set to 0.00 by default.
Syntax
Query Syntax
:OUTPut:DELay:ON {<NR2>|MINimum|MAXimum}
:OUTPut:DELay:ON?
Parameter
<NR2>
0.00~99.99 seconds, where 0=no delay.
Return parameter
“0.00”
Returns the delay on time in seconds
until the output is turned on.
:OUTPut:DELay:OFF
Set
Query
Description
Sets the Delay Time in seconds for turning the
output off. The delay is set to 0.00 by default.
Syntax
Return Syntax
:OUTPut:DELay:OFF {<NR2> |MINimum|MAXimum}
:OUTPut:DELay:OFF?
Parameter
<NR2>
0.00~99.99 seconds, where 0=no delay.
Return parameter
“0.00”
Returns the delay off time in seconds
until the output is turned off.
Output Commands
85
PSU Series Programming Manual
:OUTPut:MODE
Set
Query
Description
Sets the PSU output mode. This is the equivalent
to the F-03 (V-I Mode Slew Rate Select) settings.
Syntax
Return Syntax
:OUTPut:MODE {<NR1>|CVHS|CCHS|CVLS|CCLS}
:OUTPut:MODE?
Parameter
CVHS | 0
CV high speed priority
CCHS | 1
CC high speed priority
CVLS | 2
CV slew rate priority
CCLS | 3
CC slew rate priority
Return parameter
<NR1>
Returns the output mode.
:OUTPut[:STATe][:IMMediate]
Set
Query
Description
Turns the output on or off.
Syntax
Query Syntax
:OUTPut[:STATe][:IMMediate] { <bool> | OFF | ON }
:OUTPut[:STATe][:IMMediate]?
Parameter
OFF | 0
Turns the output off.
ON | 1
Turns the output on.
Return parameter
<bool>
Returns output status of the instrument.
:OUTPut[:STATe]:TRIGgered
Set
Query
Description
Turns the output on or off when a software trigger
is generated.
Syntax
Query Syntax
:OUTPut[:STATe]:TRIGgered { <bool>|OFF|ON }
:OUTPut[:STATe]:TRIGgered?
Parameter
OFF | 0
Turns the output off when a software
trigger is generated (*TRG).
86
REMOTE CONTROL
ON | 1
Turns the output on when a software
trigger is generated (*TRG).
Return parameter
<bool>
Returns output trigger status of the
instrument.
:OUTPut:PROTection:CLEar
Set
Description
Clears over-voltage, over-current and overtemperature (OVP, OCP, OTP) protection circuits.
It also clears the shutdown and sense protection
circuit. The AC failure protection cannot be
cleared.
Syntax
:OUTPut:PROTection:CLEar
:OUTPut:PROTection:TRIPped
Query
Description
Queries the unit to see if a protection circuit has
been tripped.
Queries the bit sum of the Questionable
Instrument Summary Status Event register. This
query will also clear the contents of the register
(Multi-Drop mode).
Queries the status (bit sum) of the Questionable
Instrument Summary Status Condition register.
This query will not clear the register (Multi-Drop
mode).
This command resets the ENABle register, the
PTRansistion filter and NTRansistion filter on the
Operation Status and Questionable Status
Registers. The registers/filters will be reset to a
default value.
Default Register/Filter Values
Setting
QUEStionable Status Enable
0x0000
QUEStionable Status Positive Transition
0x7FFF
QUEStionable Status Negative Transition
0x0000
QUEStionable Instrument Summary1
Status Enable
0x7FFF
QUEStionable Instrument Summary2
Status Enable
0x7FFF
QUEStionable Instrument Summary3
Status Enable
0x7FFF
93
PSU Series Programming Manual
Operation Status Enable
0x0000
Operation Status Positive Transition
0x7FFF
Operation Status Negative Transition
0x0000
Summary: The Questionable Status Enable
registers and the Operation Status Enable registers
are both reset to 0.
The Questionable Status and Operation Status
Positive Transition filters are all set high (0x7FFF)
and the Negative Transition filters are all set low
(0x0000). I.e., only positive transitions will be
recognized for the Questionable Status and
Operation Status registers.
Per step is between 0.001A/msec and
rated current divided by 100 msec.
99
PSU Series Programming Manual
MIN
Minimum falling current slew rate is
0.001A/msec.
MAX
Maximum falling current slew rate is
rated current divided by 100msec.
Return Parameter
<NR2>
Returns the step current
Example
SOUR:CURR:SLEW:FALL MAX
Sets the falling current slew rate to the maximum.
[:SOURce]:MODE?
Set
Query
Description
Returns the status of the output mode (CC, CV,
Off) of the power supply.
The interface will return “CV’ if the supply is in
Constant Voltage Mode, “CC” if the supply is in
Constant Current Mode or “OFF” if the supply
output is off.
Query Syntax
[:SOURce]:MODE?
Return parameter
<string>
Returns the output state as a string, “CC”,
“CV”, “OFF”