
High Power Electronic Load
ISO-9001 CERTIFIED MANUFACTURER

This manual contains proprietary information, which is protected by
copyright. All rights are reserved. No part of this manual may be
photocopied, reproduced or translated to another language without
prior written consent of Good Will company.
The information in this manual was correct at the time of printing.
However, Good Will continues to improve products and reserves the
rights to change specification, equipment, and maintenance
procedures at any time without notice.
Good Will Instrument Co., Ltd.
No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.

Table of Contents
Table of Contents
SAFETY INSTRUCTIONS .................................................. 4
GETTING STARTED .......................................................... 8
PEL-5000C Series Introduction .............................. 10
Accessories............................................................ 13
Operating Mode Description ................................. 14
Operating Area ...................................................... 20
Appearance ............................................................ 27
FUNCTION DESCRIPTION ............................................. 38
Function keys description ...................................... 39
Test keys description ............................................. 53
System keys description ........................................ 68
Test keys description ............................................. 77
CONNECTION ............................................................... 79
Rear Panel ............................................................. 80
Connecting the I-monitor to an oscilloscope ......... 84
Master/Slave Instructions ..................................... 85
INSTALLATION .............................................................. 88
Check line voltage .................................................. 89
Grounding requirements ....................................... 89
Power up ............................................................... 90
Connection to the load Input Terminal .................. 90
GPIB & RS232 interface option .............................. 91
RS232 interface option .......................................... 92
GPIB interface option ............................................ 92
USB interface option ............................................. 92
LAN interface option ............................................. 93
I/O connection ...................................................... 93
1

PEL-5000C User Manual
Load current slew rate setting ............................... 94
Load wire inductance ............................................ 96
REMOTE CONTROL ...................................................... 100
Interface Configuration ........................................ 101
Communication Interface programming command
list ....................................................................... 103
Command Syntax ................................................. 115
Command List ..................................................... 117
PRESET Commands ............................................. 119
Limit Commands ................................................. 132
STAGE commands ............................................... 135
System Commands .............................................. 141
Measure Commands ............................................ 143
APPLICATION ............................................................... 144
Local sense connections ...................................... 145
Remote sense connections .................................. 146
Constant Current mode application ..................... 148
Constant Voltage mode application ..................... 151
Constant Resistance mode application ................ 153
Constant Power mode application ....................... 155
CC + CV mode of operation application ............... 157
CP + CV mode of operation application ............... 159
Constant current source operating ....................... 161
Zero-Volt loading application ............................... 162
Parallel operation ................................................ 163
Power Supply OCP testing ................................... 164
Power Supply OPP testing ................................... 166
SHORT testing ..................................................... 168
Battery discharge test .......................................... 171
APPENDIX .................................................................... 175
PEL-5000C Default Settings ................................. 176
PEL-5000C Dimensions ........................................ 183
2

Table of Contents
PEL-5000C series Specifications .......................... 187
Certificate Of Compliance .................................... 208
GPIB programming Example ................................ 209
PEL-5000C series USB Instruction ....................... 213
PEL-5000C series Auto, Sequence function provide
EDIT, ENTER, EXIT, TEST and STORE 5 keys
operation ............................................................. 215
PEL-5000C series LAN Instruction ....................... 219
3

PEL-5000C User Manual
Warning: Identifies conditions or practices that
could result in injury or loss of life.
Caution: Identifies conditions or practices that
could result in damage to the instrument or to
other properties.
Attention Refer to the Manual
Frame or Chassis Terminal
Do not dispose electronic equipment as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased.
SAFETY INSTRUCTIONS
This chapter contains important safety instructions that you must
follow during operation and storage. Read the following before any
operation to insure your safety and to keep the instrument in the
best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the
instrument.
4

SAFETY INSTRUCTIONS
General
Guideline
CAUTION
Do not place any heavy object on the
instrument. Note: Only 2 units can be stacked
vertically.
Avoid severe impact or rough handling that
leads to damaging the instrument.
Do not discharge static electricity to the
instrument.
Use only crimped wires, not bare wires, for the
terminals.
Do not block the cooling fan opening.
Do not disassemble the instrument unless you
are qualified.
The equipment is not for measurements
performed for CAT II, III and IV.
(Measurement categories) EN 61010-1:2010 specifies the
measurement categories and their requirements as follows.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
0 is for measurements performed on circuits not directly
connected to Mains.
Do NOT position the equipment so that it is
difficult to disconnect the appliance inlet or the
power plug.
If the equipment is used in a manner not
specified by the manufacturer, the protection
provided by the equipment may be impaired.
Safety Guidelines
5

PEL-5000C User Manual
AC Input voltage range: 100-240VAC, Single
phase
90-250VAC
Frequency: 47-63Hz
To avoid electrical shock connect the protective
grounding conductor of the AC power cord to
an earth ground.
To avoid electric shock, the power cord
protective grounding conductor must be
connected to ground. No operator serviceable
components inside. Do not remove covers.
Refer servicing to qualified personnel.
Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Temperature: 0°C to 40°C
Humidity: 0 to 85% RH
Altitude: <2000m
Overvoltage category II
6

SAFETY INSTRUCTIONS
(Pollution Degree) EN 61010-1:2010 specifies the pollution degrees
and their requirements as follows. The instrument falls under
degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric
strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused
by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to
condensation which is expected. In such conditions, equipment
is normally protected against exposure to direct sunlight,
precipitation, and full wind pressure, but neither temperature
nor humidity is controlled.
Location: Indoor
Temperature: -20°C to 70°C
Humidity: <90% RH
Do not dispose this instrument as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased. Please make sure
discarded electrical waste is properly recycled to
reduce environmental impact.
7

PEL-5000C User Manual
PEL-5000C Series Introduction ............................. 10
Main Features ............................................................................... 10
Protection features ....................................................................... 11
Accessories ........................................................... 13
Operating Mode Description ................................ 14
CC Mode ....................................................................................... 14
CR mode ........................................................................................ 14
CV mode ........................................................................................ 14
CP mode ........................................................................................ 15
GETTING STARTED
The PEL-5000C series Electronic Load is designed to test,
evaluation and burn-in of DC power supplies and batteries.
The PEL-5000C series high power electronic Load can be controlled
locally at the front panel or remotely via computer over the
GPIB/RS232/USB/LAN. Constant Current (CC) mode, Constant
Resistance (CR) mode, and Constant Voltage (CV) mode. And
Constant Power (CP) mode. The wide range dynamic load with
independent rise and fall current slew rate and analog
programming input with arbitrary wave-form input is available in
Constant Current mode.
8

GETTING STARTED
Slew Rate ....................................................................................... 15
Dynamic Waveform Definition................................................. 17
Operating Area ...................................................... 20
Appearance ............................................................ 27
Front Panel .................................................................................... 27
LCD Display ................................................................................. 28
9

PEL-5000C User Manual
CC, CR, CV, CP, Dynamic, and Short Operating
Mode.
Remote control via a choice of computer
interfaces.
High accuracy & resolution with 16 bit voltage
and current meter.
Built in pulse generators for dynamic loading.
Independently adjustable current rise and fall
times.
Short circuit test with current measurement
Dedicated over current and overpower
protection test functions
Programmable voltage sense capability.
Full protection from overpower, over-
temperature, overvoltage, and reverse polarity.
Analogue programming input for tracking an
external signal
Current Monitor with BNC (non-isolated)
socket.
Digital Calibration
Advance Fan speed control
Ability to save load setup via the mainframe
memory (150 store/recall locations)
Auto sequence function allowing test routines
to be set from the mainframe
PEL-5000C Series Introduction
Main Features
10

GETTING STARTED
The Electronic Load will turn OFF Load OFF if the
overvoltage circuit is tripped. The message OVP
will be displayed on the LCD. When the OVP fault
has been removed the load can be set to sink
power again. While the unit will attempt to
protect itself given an OVP state it is strongly
advised to guard against any potential OVP fault
state by using external protection and the correctly
rated electronic load.
The Overvoltage protection circuit is set at a
predetermined voltage and cannot be adjusted.
The OVP level is 105% of the PEL-5000C series
nominal voltage rating.
Never apply an AC voltage to the input of the PEL5000C series Load. Do not apply a DC voltage that is
higher than PEL-5000C series Load rating. If this
advice is ignored it is likely that damage will be caused
to the electronic load module. This damage will not be
covered by the warranty.
Over current
protection (OCP)
The PEL-5000C series Electronic Load monitors the
current level. The input to the load is automatically
switched to LOAD OFF if the current is greater
than 104% of the rated current input. If an over
current condition occurs the display will show
OCP.
Over power
protection (OPP)
The PEL-5000C series Electronic Load monitors the
power dissipation level. The input to the load is
automatically switched to LOAD OFF if the power
dissipation is greater than 105% of the rated power
input. If an over power condition occurs the
display will show OPP.
Protection features
The protection features of the PEL-5000C series Electronic load
modules are as follows:
11

PEL-5000C User Manual
Over temperature
protection
The load internal temperature at the heat sink is
monitored. If the temperature reaches
approximately 90°C the OTP message will be
displayed and the unit will automatically switch to
the LOAD OFF state. If an OTP error occurs please
check the ambient temperature is between 0 to
40°C. Also ensure that the front and rear air vents
of the mainframe are not obstructed. The air flow
is taken from the front of the mainframe and
exhausted from the rear. Therefore a suitable gap
needs to be left at the rear of the mainframe. A
minimum of 15cm is recommended. After a
suitable cooling period the load can be switched.
The PEL-5000C series load module will tolerate a
reverse current up to the maximum current rating
of the load module. The ‘-‘symbol will be shown
on the voltage and current displays.
If a reverse polarity situation occurs the load will sink
power even if the LOAD button is OFF. No current will
be displayed on the PEL-5000C series load module.
Current up to the load’s maximum current rating will
be tolerated in reverse polarity. However there is no
OVP OCP and OPP protection. It is strongly
recommended that the load lines be fused if it is likely
that the load could be subject to reverse polarity.
These fuses should be fast acting and rated at the
maximum current of the load module +5%.
12

GETTING STARTED
PEL-5000C series operation manual
It can be downloaded
from GW Instek website.
HD-DSUB 15PIN Parallel wire
USB interface + USB driver (The
driver can be downloaded from GW
Instek website)
LAN interface + LAN driver (The
driver can be downloaded from GW
Instek website)
PEL-5000C, AEL-5006, AEL-5008,
AEL-5012 and AEL-5015 handle
Rack Mount Kit For PEL-5006C
Rack Mount Kit For PEL-5008C,
PEL-5010C, PEL-5012C
Rack Mount Kit For PEL-5015C,
PEL-5018C
Rack Mount Kit For PEL-5020C,
PEL-5024C
Accessories
13

PEL-5000C User Manual
With the operating mode of Constant Current, the
PEL-5000C Series electronic load will sink a
current in accordance with the programmed value
regardless of the input voltage
CURRENT SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
CC
At Constant Resistance mode, the PEL-5000C
series electronic load will sink a current linearly
proportional to the load input voltage in
accordance with the programmed resistance
setting
RESISTANCE
SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
I
At Constant Voltage mode, the PEL-5000C series
electronic load will attempt to sink enough current
Operating Mode Description
CC Mode
CR mode
CV mode
14

until the load input voltage reaches the
programmed value
VOLTAGE
SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
I
CP mode
At Constant Power mode, the PEL-5000C series
electronic load will attempt to sink load power
(load voltage * load current) in accordance with
the programmed power.
POWER
SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
I
Slew rate is defined as the change in current or
voltage over time. A programmable slew rate
allows for a controlled transition from one load
setting to another. It can be used to minimize
induced voltage drops on inductive power wiring,
or to control induced transients on a test device
(such as would occur during power supply
transient response testing).
In cases where the transition from one setting to
GETTING STARTED
Slew Rate
15

PEL-5000C User Manual
another is large, the actual transition time can be
calculated by dividing the voltage or current
transition by the slew rate. The actual transition
time is defined as the time required for the input to
change from 10% to 90% or from 90% to 10% of the
programmed excursion.
In cases where the transition from one setting to
another is small, the small signal bandwidth (of the
load) limits the minimum transition time for all
programmable slew rates. Because of this
limitation, the actual transition time is longer than
the expected time based on the slew rate.
Rise Time
Transition
Limitation
Therefore, both minimum transition time and slew
rate must be considered when determining the
actual transition time. Following detail description
is excluding in specification sheet.
The minimum transition time for a given slew rate
as about a 30% or greater load change, the slew
rate increases from the minimum transition time to
the Maximum transition time at a 100% load
change. The actual transition time will be either the
minimum transition time, or the total slew time
(transition divided by slew rate), whichever is
longer.
PEL-5012C-600-840 600V/840A/12000W (CCH CCL >840Ax 30%)
16

GETTING STARTED
Use the following formula to calculate the
minimum transition time for a given slew rate min
transition time=252A/slew rate (in amps/second).
10.5uS (252A/24) x 0.8(10%~90%) =8.4uS
Use the following formula to calculate the
maximum transition time for a given slew rate max
transition time=840/slew rate (in amps/second).
35uS (840A/24) x 0.8(10~90%) = 28uS
EX. CCH=168A, CCL=0A Slew Rate =24A, the
expected time is 5.6uS but the actual Transition
Time Will be limited to 4.8Us.
7uS (168/24 x 0.8(10%~90%) = 5.6uS
When CC mode rang1 slew rate, CCL setting at least
0.1% larger than the specification.
Along with static operation the PEL-5000C series
electronic load are built with a dynamic mode for
operation in Constant Current (CC), Constant
Resistance (CR) or Constant Power (CP). This
allows the test engineer to simulate real world
pulsing loads or implement a load profile that
varies with time.
A dynamic waveform can be programmed from
the front panel of the PEL-5000C electronic load.
The user would first set a High and low value of
load current using the Level button. The Dynamic
Setting then allows for the rise and fall time
between these 2 current values to be adjusted. The
time period that the waveform is high (Thigh)
along with the time period that the waveform is
low (Tlow) can also be set.
Dynamic Waveform Definition
17

PEL-5000C User Manual
The dynamic waveform can also be set up via the
optional computer interface. Dynamic waveform
settings made from the front panel of the load
module can also be saved in the memory of the
PEL-5000C series Electronic Load. For the
store/recall procedure and the computer
command set please refer to the relevant operating
manual for the PEL-5000C series Electronic Load.
Further dynamic waveform definitions are:
The period of dynamic waveform is Thigh +
Tlow
The dynamic frequency = 1 /( Thigh + Tlow )
The duty cycle = Thigh / ( Thigh + Tlow )
PEL-5000C series, Dynamic up to 50 KHz
frequency
Dynamic highest frequency 50 KHz = 0.02ms=20us
Setting THIGH=10 uS, TLOW=10uS,
THIGH+TLOW=20uS
CCH-CCL/SR≦10uS
Setting CCH=30A, CCL=10A
(30-10)/2.5A/uS≦10 uS
8 uS≦10 uS ,Compliance with frequency 50KHz
Setting THIGH=10 uS, TLOW=10uS,
THIGH+TLOW=20uS
CCH-CCL/SR≦10uS
18

GETTING STARTED
Setting CCH=50A, CCL=0A
(50-0)/2.5A/uS=20uS, 20uS>10uS, It's not
compliance the frequency 50 KHz
The analogue programming input also provides a
convenient method of implementing a dynamic
waveform.
19

PEL-5000C User Manual
PEL-5006C-150-600
power contour
150V
10V
600A
40A
6KW
Power Curve
Current
0.7V
Voltage
PEL-5008C-150-800
power contour
150V
10V
800A
53.3A
8KW
Power Curve
Current
Voltage
0.7V
PEL-5010C-150-1000
power contour
150V
10V
1000A
66.6A
10KW
Power Curve
Current
Voltage
0.7V
Operating Area
The PEL-5000C series electronic load can be operated for manual
and GPIB operation.
The PEL-5000C series high power electronic Load can be controlled
locally at the front panel or remotely via computer over the
GPIB/RS232/USB/LAN. Constant current (CC) mode, constant
resistance (CR) mode, and constant voltage (CV) mode and
constant power (CP) mode. The wide range dynamic load with
independent rise and fall current slew rate and analog
programming input with arbitrary wave-form input is available in
Constant Current mode.
20

GETTING STARTED
PEL-5012C-150-1200
power contour
150V
10V
1200A
80A
12KW
Power Curve
Current
Voltage
0.7V
PEL-5015C-150-1500
power contour
150V
10V
1500A
100A
15KW
Power Curve
Current
Voltage
0.7V
PEL-5018C-150-1800
power contour
150V
10V
1800A
120A
18KW
Power Curve
Current
Voltage
0.7V
PEL-5020C-150-2000
power contour
150V
10V
2000A
133.3A
20KW
Power Curve
Current
Voltage
0.7V
21

PEL-5000C User Manual
PEL-5024C-150-2000
power contour
150V
12V
2000A
160A
24KW
Power Curve
Current
Voltage
0.7V
PEL-5006C-600-420
power contour
600V
14.29V
420A
10A
6KW
Power Curve
Current
Voltage
10V
PEL-5008C-600-560
power contour
600V
14.29V
560A
13.33A
8KW
Power Curve
Current
Voltage
10V
PEL-5010C-600-700
power contour
600V
14.29V
700A
16.66A
10KW
Power Curve
Current
Voltage
10V
22

GETTING STARTED
PEL-5012C-600-840
power contour
600V
14.29V
840A
20A
12KW
Power Curve
Current
Voltage
10V
PEL-5015C-600-1050
power contour
600V
14.29V
1050A
25A
15KW
Power Curve
Current
Voltage
10V
PEL-5018C-600-1260
power contour
600V
14.29V
1260A
4.16A
18KW
Power Curve
Current
Voltage
10V
PEL-5020C-600-1400
power contour
600V
14.29V
1400A
33.33A
20KW
Power Curve
Current
Voltage
10V
23

PEL-5000C User Manual
PEL-5024C-600-1680
power contour
600V
14.29V
1680A
40A
24KW
Power Curve
Current
Voltage
10V
PEL-5006C-1200-240
power contour
1200V
25V
240A6A
6KW
Power Curve
Current
Voltage
15V
1000V
3A
PEL-5008C-1200-320
power contour
1200V
25V
320A8A
8KW
Power Curve
Current
Voltage
15V
1000V
4A
PEL-5010C-1200-400
power contour
1200V
25V
400A
10A
10KW
Power Curve
Current
Voltage
15V
1000V
5A
24

GETTING STARTED
PEL-5012C-1200-480
power contour
1200V
25V
480A12A
12KW
Power Curve
Current
Voltage
15V
1000V
6A
PEL-5015C-1200-600
power contour
1200V
25V
600A15A
15KW
Power Curve
Current
Voltage
15V
1000V
7.5A
PEL-5018C-1200-720
power contour
1200V
25V
720A
18A
18KW
Power Curve
Voltage
15V
1000V
9A
PEL-5020C-1200-800
power contour
Current
1200V
25V
800A20A
20KW
Power Curve
Voltage
15V
1000V
10A
25

PEL-5000C User Manual
PEL-5024C-1200-960
power contour
1200V
25V
960A24A
24KW
Power Curve
Current
Voltage
15V
1000V
12A
26

GETTING STARTED
LCD Multi-function display
Appearance
Front Panel
27

LCD Display
1
3
6 7
9
13
2
15
8
14
4
5
12
9
10
11
Model number
and sink ranges
The model number along with maximum
voltage, current and power values are detailed
in this position at the top of the load front
panel.
The 5 digit LCD display is a multi-function
display. The function of the display changes
depending whether the user is in NORMAL
mode or in a SHORT, OPP or OCP modes:
Status display:
When enter System Setting or AUTO
SEQUENCE, the display setting item.
The left 5 digit display displays the voltage
present at the load’s input terminals. The
value displayed will include the automatic
voltage compensation if the sense terminals
are also connected to the device under test
(DUT).
If V-sense is set to “AUTO” and the sense leads
are connected to the DUT the losses need to be
approx. 700mV (PEL-5006C-150-600) before the
display compensates for the voltage loss.
If V-sense is set to “ON” and the sense terminals
are connected to the DUT the load will check and
compensate for all voltage drops.
PEL-5000C User Manual
28