Instek PEL-5006C-150-600, PEL-5008C-1200-320, PEL-5024C-600-1680, PEL-5008-150-800, PEL-5010C-150-1000 User Manual

...
High Power Electronic Load
PEL-5000C Series
USER MANUAL
ISO-9001 CERTIFIED MANUFACTURER
This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of Good Will company.
The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the rights to change specification, equipment, and maintenance procedures at any time without notice.
Good Will Instrument Co., Ltd. No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.
Table of Contents
Table of Contents
SAFETY INSTRUCTIONS .................................................. 4
GETTING STARTED .......................................................... 8
PEL-5000C Series Introduction .............................. 10
Accessories............................................................ 13
Operating Mode Description ................................. 14
Operating Area ...................................................... 20
Appearance ............................................................ 27
FUNCTION DESCRIPTION ............................................. 38
Function keys description ...................................... 39
Test keys description ............................................. 53
System keys description ........................................ 68
Test keys description ............................................. 77
CONNECTION ............................................................... 79
Rear Panel ............................................................. 80
Connecting the I-monitor to an oscilloscope ......... 84
Master/Slave Instructions ..................................... 85
INSTALLATION .............................................................. 88
Check line voltage .................................................. 89
Grounding requirements ....................................... 89
Power up ............................................................... 90
Connection to the load Input Terminal .................. 90
GPIB & RS232 interface option .............................. 91
RS232 interface option .......................................... 92
GPIB interface option ............................................ 92
USB interface option ............................................. 92
LAN interface option ............................................. 93
I/O connection ...................................................... 93
1
PEL-5000C User Manual
Load current slew rate setting ............................... 94
Load wire inductance ............................................ 96
REMOTE CONTROL ...................................................... 100
Interface Configuration ........................................ 101
Communication Interface programming command
list ....................................................................... 103
Command Syntax ................................................. 115
Command List ..................................................... 117
PRESET Commands ............................................. 119
Limit Commands ................................................. 132
STAGE commands ............................................... 135
System Commands .............................................. 141
Measure Commands ............................................ 143
APPLICATION ............................................................... 144
Local sense connections ...................................... 145
Remote sense connections .................................. 146
Constant Current mode application ..................... 148
Constant Voltage mode application ..................... 151
Constant Resistance mode application ................ 153
Constant Power mode application ....................... 155
CC + CV mode of operation application ............... 157
CP + CV mode of operation application ............... 159
Constant current source operating ....................... 161
Zero-Volt loading application ............................... 162
Parallel operation ................................................ 163
Power Supply OCP testing ................................... 164
Power Supply OPP testing ................................... 166
SHORT testing ..................................................... 168
Battery discharge test .......................................... 171
APPENDIX .................................................................... 175
PEL-5000C Default Settings ................................. 176
PEL-5000C Dimensions ........................................ 183
2
Table of Contents
PEL-5000C series Specifications .......................... 187
Certificate Of Compliance .................................... 208
GPIB programming Example ................................ 209
PEL-5000C series USB Instruction ....................... 213
PEL-5000C series Auto, Sequence function provide EDIT, ENTER, EXIT, TEST and STORE 5 keys
operation ............................................................. 215
PEL-5000C series LAN Instruction ....................... 219
3
PEL-5000C User Manual
WARNING
Warning: Identifies conditions or practices that could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that could result in damage to the instrument or to other properties.
DANGER High Voltage
Attention Refer to the Manual
Earth (ground) Terminal
Frame or Chassis Terminal
Do not dispose electronic equipment as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased.
SAFETY INSTRUCTIONS
This chapter contains important safety instructions that you must follow during operation and storage. Read the following before any operation to insure your safety and to keep the instrument in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the instrument.
4
SAFETY INSTRUCTIONS
General Guideline
CAUTION
Do not place any heavy object on the
instrument. Note: Only 2 units can be stacked vertically.
Avoid severe impact or rough handling that
leads to damaging the instrument.
Do not discharge static electricity to the
instrument.
Use only crimped wires, not bare wires, for the
terminals.
Do not block the cooling fan opening. Do not disassemble the instrument unless you
are qualified.
The equipment is not for measurements
performed for CAT II, III and IV.
(Measurement categories) EN 61010-1:2010 specifies the measurement categories and their requirements as follows.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
0 is for measurements performed on circuits not directly
connected to Mains.
Do NOT position the equipment so that it is
difficult to disconnect the appliance inlet or the power plug.
If the equipment is used in a manner not
specified by the manufacturer, the protection provided by the equipment may be impaired.
Safety Guidelines
5
PEL-5000C User Manual
Power Supply
WARNING
AC Input voltage range: 100-240VAC, Single
phase 90-250VAC
Frequency: 47-63Hz To avoid electrical shock connect the protective
grounding conductor of the AC power cord to an earth ground.
To avoid electric shock, the power cord
protective grounding conductor must be connected to ground. No operator serviceable components inside. Do not remove covers. Refer servicing to qualified personnel.
Cleaning
Disconnect the power cord before cleaning. Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Operation Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Temperature: 0°C to 40°C Humidity: 0 to 85% RH Altitude: <2000m Overvoltage category II
6
SAFETY INSTRUCTIONS
(Pollution Degree) EN 61010-1:2010 specifies the pollution degrees and their requirements as follows. The instrument falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to condensation which is expected. In such conditions, equipment is normally protected against exposure to direct sunlight, precipitation, and full wind pressure, but neither temperature nor humidity is controlled.
Storage environment
Location: Indoor Temperature: -20°C to 70°C Humidity: <90% RH
Disposal
Do not dispose this instrument as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased. Please make sure discarded electrical waste is properly recycled to reduce environmental impact.
7
PEL-5000C User Manual
PEL-5000C Series Introduction ............................. 10
Main Features ............................................................................... 10
Protection features ....................................................................... 11
Accessories ........................................................... 13
Operating Mode Description ................................ 14
CC Mode ....................................................................................... 14
CR mode ........................................................................................ 14
CV mode ........................................................................................ 14
CP mode ........................................................................................ 15
GETTING STARTED
The PEL-5000C series Electronic Load is designed to test, evaluation and burn-in of DC power supplies and batteries.
The PEL-5000C series high power electronic Load can be controlled locally at the front panel or remotely via computer over the GPIB/RS232/USB/LAN. Constant Current (CC) mode, Constant Resistance (CR) mode, and Constant Voltage (CV) mode. And Constant Power (CP) mode. The wide range dynamic load with independent rise and fall current slew rate and analog programming input with arbitrary wave-form input is available in Constant Current mode.
8
GETTING STARTED
Slew Rate ....................................................................................... 15
Dynamic Waveform Definition................................................. 17
Operating Area ...................................................... 20
Appearance ............................................................ 27
Front Panel .................................................................................... 27
LCD Display ................................................................................. 28
9
PEL-5000C User Manual
Features
CC, CR, CV, CP, Dynamic, and Short Operating
Mode.
Remote control via a choice of computer
interfaces.
High accuracy & resolution with 16 bit voltage
and current meter.
Built in pulse generators for dynamic loading. Independently adjustable current rise and fall
times.
Short circuit test with current measurement Dedicated over current and overpower
protection test functions
Programmable voltage sense capability. Full protection from overpower, over-
temperature, overvoltage, and reverse polarity.
Analogue programming input for tracking an
external signal
Current Monitor with BNC (non-isolated)
socket.
Digital Calibration Advance Fan speed control Ability to save load setup via the mainframe
memory (150 store/recall locations)
Auto sequence function allowing test routines
to be set from the mainframe
PEL-5000C Series Introduction
Main Features
10
GETTING STARTED
Overvoltage protection
The Electronic Load will turn OFF Load OFF if the overvoltage circuit is tripped. The message OVP will be displayed on the LCD. When the OVP fault has been removed the load can be set to sink power again. While the unit will attempt to protect itself given an OVP state it is strongly advised to guard against any potential OVP fault state by using external protection and the correctly rated electronic load.
The Overvoltage protection circuit is set at a predetermined voltage and cannot be adjusted. The OVP level is 105% of the PEL-5000C series nominal voltage rating.
Caution
Never apply an AC voltage to the input of the PEL­5000C series Load. Do not apply a DC voltage that is higher than PEL-5000C series Load rating. If this advice is ignored it is likely that damage will be caused to the electronic load module. This damage will not be covered by the warranty.
Over current protection (OCP)
The PEL-5000C series Electronic Load monitors the current level. The input to the load is automatically switched to LOAD OFF if the current is greater than 104% of the rated current input. If an over current condition occurs the display will show OCP.
Over power protection (OPP)
The PEL-5000C series Electronic Load monitors the power dissipation level. The input to the load is automatically switched to LOAD OFF if the power dissipation is greater than 105% of the rated power input. If an over power condition occurs the display will show OPP.
Protection features
The protection features of the PEL-5000C series Electronic load modules are as follows:
11
PEL-5000C User Manual
Over temperature protection
The load internal temperature at the heat sink is monitored. If the temperature reaches approximately 90°C the OTP message will be displayed and the unit will automatically switch to the LOAD OFF state. If an OTP error occurs please check the ambient temperature is between 0 to 40°C. Also ensure that the front and rear air vents of the mainframe are not obstructed. The air flow is taken from the front of the mainframe and exhausted from the rear. Therefore a suitable gap needs to be left at the rear of the mainframe. A minimum of 15cm is recommended. After a suitable cooling period the load can be switched.
Reverse Polarity
The PEL-5000C series load module will tolerate a reverse current up to the maximum current rating of the load module. The ‘-‘symbol will be shown on the voltage and current displays.
Caution
If a reverse polarity situation occurs the load will sink power even if the LOAD button is OFF. No current will be displayed on the PEL-5000C series load module.
Current up to the load’s maximum current rating will
be tolerated in reverse polarity. However there is no OVP OCP and OPP protection. It is strongly recommended that the load lines be fused if it is likely that the load could be subject to reverse polarity. These fuses should be fast acting and rated at the maximum current of the load module +5%.
12
GETTING STARTED
Standard Accessories
Description
PCs
PEL-5000C series operation manual
It can be downloaded from GW Instek website.
BANANA PLUGS
1
BNC – BNC CABLE
1
HD-DSUB 15PIN Parallel wire
1 Optional Accessories
Description
PCs
GPIB+RS232 interface
PEL-030
1
RS232 interface
PEL-023
1
GPIB interface
PEL-022
1
USB interface + USB driver (The driver can be downloaded from GW Instek website)
PEL-025
LAN interface + LAN driver (The driver can be downloaded from GW Instek website)
PEL-024
GPIB cable
GTL-250 GPIB Cable, 0.6m
1
GPIB cable
GTL-248 GPIB Cable, 2m
1
USB cable
GTL-246 USB Cable, 1.2m
1
PEL-5000C, AEL-5006, AEL-5008, AEL-5012 and AEL-5015 handle
PEL-028
1 PEL-5000C Hook Ring
PEL-026
Rack Mount Kit For PEL-5006C
PEL-027-1
Rack Mount Kit For PEL-5008C, PEL-5010C, PEL-5012C
PEL-027-2
Rack Mount Kit For PEL-5015C, PEL-5018C
PEL-027-3
Rack Mount Kit For PEL-5020C, PEL-5024C
PEL-027-4
Accessories
13
PEL-5000C User Manual
Background
With the operating mode of Constant Current, the PEL-5000C Series electronic load will sink a current in accordance with the programmed value regardless of the input voltage
CURRENT SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
CC
Background
At Constant Resistance mode, the PEL-5000C series electronic load will sink a current linearly proportional to the load input voltage in accordance with the programmed resistance setting
RESISTANCE
SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
I
Background
At Constant Voltage mode, the PEL-5000C series electronic load will attempt to sink enough current
Operating Mode Description
CC Mode
CR mode
CV mode
14
until the load input voltage reaches the programmed value
VOLTAGE
SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
I
CP mode
Background
At Constant Power mode, the PEL-5000C series electronic load will attempt to sink load power (load voltage * load current) in accordance with the programmed power.
POWER
SETTING
LOAD
CURRENT
INPUT VOLTAGE
V
I
Background
Slew rate is defined as the change in current or voltage over time. A programmable slew rate allows for a controlled transition from one load setting to another. It can be used to minimize induced voltage drops on inductive power wiring, or to control induced transients on a test device (such as would occur during power supply transient response testing).
In cases where the transition from one setting to
GETTING STARTED
Slew Rate
15
PEL-5000C User Manual
another is large, the actual transition time can be calculated by dividing the voltage or current transition by the slew rate. The actual transition time is defined as the time required for the input to change from 10% to 90% or from 90% to 10% of the programmed excursion.
In cases where the transition from one setting to another is small, the small signal bandwidth (of the load) limits the minimum transition time for all programmable slew rates. Because of this limitation, the actual transition time is longer than the expected time based on the slew rate.
Rise Time Transition Limitation
Therefore, both minimum transition time and slew rate must be considered when determining the actual transition time. Following detail description is excluding in specification sheet.
The minimum transition time for a given slew rate as about a 30% or greater load change, the slew rate increases from the minimum transition time to the Maximum transition time at a 100% load change. The actual transition time will be either the minimum transition time, or the total slew time (transition divided by slew rate), whichever is longer.
Example
PEL-5012C-600-840 600V/840A/12000W (CCH ­CCL >840Ax 30%)
16
GETTING STARTED
Use the following formula to calculate the minimum transition time for a given slew rate min transition time=252A/slew rate (in amps/second).
10.5uS (252A/24) x 0.8(10%~90%) =8.4uS
Use the following formula to calculate the maximum transition time for a given slew rate max transition time=840/slew rate (in amps/second).
35uS (840A/24) x 0.8(10~90%) = 28uS
EX. CCH=168A, CCL=0A Slew Rate =24A, the expected time is 5.6uS but the actual Transition
Time Will be limited to 4.8Us.
7uS (168/24 x 0.8(10%~90%) = 5.6uS
Note
When CC mode rang1 slew rate, CCL setting at least
0.1% larger than the specification.
Background
Along with static operation the PEL-5000C series electronic load are built with a dynamic mode for operation in Constant Current (CC), Constant Resistance (CR) or Constant Power (CP). This allows the test engineer to simulate real world pulsing loads or implement a load profile that varies with time.
A dynamic waveform can be programmed from the front panel of the PEL-5000C electronic load. The user would first set a High and low value of load current using the Level button. The Dynamic Setting then allows for the rise and fall time between these 2 current values to be adjusted. The time period that the waveform is high (Thigh) along with the time period that the waveform is low (Tlow) can also be set.
Dynamic Waveform Definition
17
PEL-5000C User Manual
Dynamic Wave form
I
V
LOAD
CURRENT
RISE
SLEW RATE
HIGH LOAD
LOAD
LOW LOAD
LEVEL
T
HIGHTLOW
FALL SLEW RATE
The dynamic waveform can also be set up via the optional computer interface. Dynamic waveform settings made from the front panel of the load module can also be saved in the memory of the PEL-5000C series Electronic Load. For the store/recall procedure and the computer command set please refer to the relevant operating manual for the PEL-5000C series Electronic Load.
Further dynamic waveform definitions are:
The period of dynamic waveform is Thigh +
Tlow
The dynamic frequency = 1 /( Thigh + Tlow ) The duty cycle = Thigh / ( Thigh + Tlow )
Example 1
PEL-5000C series, Dynamic up to 50 KHz frequency
Dynamic highest frequency 50 KHz = 0.02ms=20us
Setting THIGH=10 uS, TLOW=10uS, THIGH+TLOW=20uS
CCH-CCL/SR10uS
Setting CCH=30A, CCL=10A
(30-10)/2.5A/uS10 uS
8 uS10 uS ,Compliance with frequency 50KHz
Example 2
Setting THIGH=10 uS, TLOW=10uS, THIGH+TLOW=20uS
CCH-CCL/SR10uS
18
GETTING STARTED
Setting CCH=50A, CCL=0A
(50-0)/2.5A/uS=20uS, 20uS>10uS, It's not compliance the frequency 50 KHz
The analogue programming input also provides a convenient method of implementing a dynamic waveform.
19
PEL-5000C User Manual
PEL-5006C-150-600 power contour
150V
10V
600A
40A
6KW
Power Curve
Current
0.7V
Voltage
PEL-5008C-150-800 power contour
150V
10V
800A
53.3A
8KW
Power Curve
Current
Voltage
0.7V
PEL-5010C-150-1000 power contour
150V
10V
1000A
66.6A
10KW
Power Curve
Current
Voltage
0.7V
Operating Area
The PEL-5000C series electronic load can be operated for manual and GPIB operation.
The PEL-5000C series high power electronic Load can be controlled locally at the front panel or remotely via computer over the GPIB/RS232/USB/LAN. Constant current (CC) mode, constant resistance (CR) mode, and constant voltage (CV) mode and constant power (CP) mode. The wide range dynamic load with independent rise and fall current slew rate and analog programming input with arbitrary wave-form input is available in Constant Current mode.
20
GETTING STARTED
PEL-5012C-150-1200 power contour
150V
10V
1200A
80A
12KW
Power Curve
Current
Voltage
0.7V
PEL-5015C-150-1500 power contour
150V
10V
1500A
100A
15KW
Power Curve
Current
Voltage
0.7V
PEL-5018C-150-1800 power contour
150V
10V
1800A
120A
18KW
Power Curve
Current
Voltage
0.7V
PEL-5020C-150-2000 power contour
150V
10V
2000A
133.3A
20KW
Power Curve
Current
Voltage
0.7V
21
PEL-5000C User Manual
PEL-5024C-150-2000 power contour
150V
12V
2000A
160A
24KW
Power Curve
Current
Voltage
0.7V
PEL-5006C-600-420 power contour
600V
14.29V
420A
10A
6KW
Power Curve
Current
Voltage
10V
PEL-5008C-600-560 power contour
600V
14.29V
560A
13.33A
8KW
Power Curve
Current
Voltage
10V
PEL-5010C-600-700 power contour
600V
14.29V
700A
16.66A
10KW
Power Curve
Current
Voltage
10V
22
GETTING STARTED
PEL-5012C-600-840 power contour
600V
14.29V
840A
20A
12KW
Power Curve
Current
Voltage
10V
PEL-5015C-600-1050 power contour
600V
14.29V
1050A
25A
15KW
Power Curve
Current
Voltage
10V
PEL-5018C-600-1260 power contour
600V
14.29V
1260A
4.16A
18KW
Power Curve
Current
Voltage
10V
PEL-5020C-600-1400 power contour
600V
14.29V
1400A
33.33A
20KW
Power Curve
Current
Voltage
10V
23
PEL-5000C User Manual
PEL-5024C-600-1680 power contour
600V
14.29V
1680A
40A
24KW
Power Curve
Current
Voltage
10V
PEL-5006C-1200-240 power contour
1200V
25V
240A6A
6KW
Power Curve
Current
Voltage
15V
1000V
3A
PEL-5008C-1200-320 power contour
1200V
25V
320A8A
8KW
Power Curve
Current
Voltage
15V
1000V
4A
PEL-5010C-1200-400 power contour
1200V
25V
400A
10A
10KW
Power Curve
Current
Voltage
15V
1000V
5A
24
GETTING STARTED
PEL-5012C-1200-480 power contour
1200V
25V
480A12A
12KW
Power Curve
Current
Voltage
15V
1000V
6A
PEL-5015C-1200-600 power contour
1200V
25V
600A15A
15KW
Power Curve
Current
Voltage
15V
1000V
7.5A
PEL-5018C-1200-720 power contour
1200V
25V
720A
18A
18KW
Power Curve
Voltage
15V
1000V
9A
PEL-5020C-1200-800 power contour
Current
1200V
25V
800A20A
20KW
Power Curve
Voltage
15V
1000V
10A
25
PEL-5000C User Manual
PEL-5024C-1200-960 power contour
1200V
25V
960A24A
24KW
Power Curve
Current
Voltage
15V
1000V
12A
26
GETTING STARTED
3 4
5
6 721
1
Power switch
2
LCD Multi-function display
3
System keys
4
Function keys
5
Test function keys
6
Number keypad
7 Knob setting
Appearance
Front Panel
27
LCD Display
1
3
6 7
9
13
2
15
8
14
4
5
12
9
10 11
1
Model number and sink ranges
The model number along with maximum voltage, current and power values are detailed in this position at the top of the load front panel.
2
Left 5 digit LCD display
The 5 digit LCD display is a multi-function display. The function of the display changes depending whether the user is in NORMAL mode or in a SHORT, OPP or OCP modes:
Status display: When enter System Setting or AUTO SEQUENCE, the display setting item.
Normal mode
The left 5 digit display displays the voltage present at the load’s input terminals. The value displayed will include the automatic voltage compensation if the sense terminals are also connected to the device under test (DUT).
Note
If V-sense is set to “AUTO” and the sense leads are connected to the DUT the losses need to be approx. 700mV (PEL-5006C-150-600) before the display compensates for the voltage loss.
If V-sense is set to “ON” and the sense terminals are connected to the DUT the load will check and compensate for all voltage drops.
PEL-5000C User Manual
28
Loading...
+ 193 hidden pages