This manual contains proprietary information, which is protected by
copyright. All rights are reserved. No part of this manual may be
photocopied, reproduced or translated to another language without
prior written consent of Good Will company.
The information in this manual was correct at the time of printing.
However, Good Will continues to improve products and reserves the
rights to change specification, equipment, and maintenance
procedures at any time without notice.
Good Will Instrument Co., Ltd.
No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.
Declaration of Conformity ...................................... 298
INDEX .......................................................................... 300
2
SAFETY INSTRUCTIONS
WARNING
Warning: Identifies conditions or practices that
could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that
could result in damage to the instrument or to
other properties.
DANGER High Voltage
Attention Refer to the Manual
Earth (ground) Terminal
Frame or Chassis Terminal
Do not dispose electronic equipment as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased.
SAFETY INSTRUCTIONS
This chapter contains important safety
instructions that you must follow during
operation and storage. Read the following before
any operation to insure your safety and to keep
the instrument in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the
instrument.
3
PEL-3000(H) User Manual
General
Guideline
CAUTION
Do not place any heavy object on the
instrument. Note: Only 2 units can be stacked
vertically.
Avoid severe impact or rough handling that
leads to damaging the instrument.
Do not discharge static electricity to the
instrument.
Use only crimped wires, not bare wires, for the
terminals.
Do not block the cooling fan opening.
Do not disassemble the instrument unless you
are qualified.
The equipment is not for measurements
performed for CAT II, III and IV.
(Measurement categories) EN 61010-1:2010 specifies the
measurement categories and their requirements as follows.
Measurement category IV is for measurement
performed at the source of low-voltage
installation.
Measurement category III is for measurement
performed in the building installation.
Measurement category II is for measurement
performed on the circuits directly connected to
the low voltage installation.
0 is for measurements performed on circuits not
directly connected to Mains.
Do NOT position the equipment so that it is
difficult to disconnect the appliance inlet or the
power plug.
If the equipment is used in a manner not
specified by the manufacturer, the protection
provided by the equipment may be impaired.
Safety Guidelines
4
SAFETY INSTRUCTIONS
Power Supply
WARNING
AC Input voltage range: 100-120VAC/200-
240VAC
(90-132VAC/180-250VAC)
Frequency: 47-63Hz
Power:
PEL-3021(H): 90VA Max
PEL-3041(H): 110VA Max
PEL-3111(H): 190VA Max
PEL-3211(H): 230VA Max
To avoid electrical shock connect the protective
grounding conductor of the AC power cord to
an earth ground.
To avoid electric shock, the power cord
protective grounding conductor must be
connected to ground. No operator serviceable
components inside. Do not remove covers.
Refer servicing to qualified personnel.
Cleaning
Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Operation
Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Temperature: 0°C to 40°C
Humidity: 0 to 85% RH
Altitude: <2000m
Overvoltage category II
5
PEL-3000(H) User Manual
(Pollution Degree) EN 61010-1:2010 specifies the pollution degrees
and their requirements as follows. The instrument falls under
degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric
strength or surface resistivity”.
Pollution degree 1: No pollution or only dry,
non-conductive pollution occurs. The pollution
has no influence.
Pollution degree 2: Normally only non-
conductive pollution occurs. Occasionally,
however, a temporary conductivity caused by
condensation must be expected.
Pollution degree 3: Conductive pollution
occurs, or dry, non-conductive pollution occurs
which becomes conductive due to condensation
which is expected. In such conditions,
equipment is normally protected against
exposure to direct sunlight, precipitation, and
full wind pressure, but neither temperature nor
humidity is controlled.
Storage
environment
Location: Indoor
Temperature: -20°C to 70°C
Humidity: <90% RH
Disposal
Do not dispose this instrument as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased. Please make sure
discarded electrical waste is properly recycled to
reduce environmental impact.
6
GETTING STARTED
PEL-3000(H) Series Introduction ............................... 9
Model Line Up ................................................................................... 9
Main Features ................................................................................... 10
This chapter provides a brief overview of the
PEL-3000(H), the package contents, instructions
for first time use and an introduction to the front
panel, rear panel and GUI.
Help Menu......................................................................................... 50
8
GETTING STARTED
Model
Voltage (DC)
Current
Power
PEL-3021(H)
0V-150V(0V-800V)
35A(8.75A)
175W
PEL-3041(H)
0V-150V(0V-800V)
70A(17.5A)
350W
PEL-3111(H)
0V-150V(0V-800V)
210A(52.5A)
1050W
Booster Model
Voltage (DC)
Current
Power
PEL-3211(H)
0V-150V(0V-800V)
420A(105A)
2100W
PEL-3000(H) Series Introduction
The PEL-3000(H) Series is a family of high performance DC
electronic loads positioned to test a wide range of different power
sources. The DC electronic loads are fully programmable to
simulate anything from basic static loads to complex dynamic loads.
With the ability to operate independently or in parallel, the PEL3000(H) Series is extremely robust and capable of molding to any
test environment.
Please note that throughout this manual the term “PEL-3000(H)”
refers to any one of the models in the series lineup, unless
specifically stated otherwise.
Model Line Up
There are a total of 3 DC electronic load models and 1 booster pack
model.
9
Main Features
Performance
High slew rates of up to 16A/μS(PEL-3111(H))
for a fast response speed
High capacity when used in parallel:
5250W, 1050A(262.5A) (PEL-3111(H) x 5)/
9450W, 1890A(472.5A) (PEL-3111(H) + PEL3211(H) x 4)
High resolution – 16 bit
Features
7 operating modes: CC, CV, CR, CP, CC+CV,
CR+CV, CP+CV
Independent and parallel operation
Fully programmable with normal and fast
sequences
Soft start
Dynamic mode
OCP, OVP and other protection features
Remote sense
Integrated meter
Rack-mountable
Load booster
Interface
USB, RS232, LAN(option) and GPIB(option)
External voltage or resistance control
Front panel trigger out BNC
Front panel voltage/current monitoring BNC
Analog external control
Rear panel voltage/current monitoring
PEL-3000(H) User Manual
10
GETTING STARTED
Standard
Accessories
Part number
Description
Quick Start Guide
User / Programming manual CD
Region dependent
Power cord
PEL-011
Load input terminal Cover
M3
screw
PEL-012
Terminal fittings: 2 sets of
bolts/nuts/springs/washers (type:
M8), Terminal Cover x1 (only for
PEL-3000H series), Monitor Out
Cover x 1(only for PEL-3021H, PEL3041H, PEL-3111H)
J1/J2 Protection plug x2 (It is
installed on the device)
61SF-062104N1
Front terminal washers
Spring washer (M6) x2
GTL-255
300mm Frame Link Cable (for
linking units that are stacked).Note
that this accessories is optional for
the PEL-3021(H)/ 3041(H).
Optional
Accessories
Part number
Description
3813-030D0501
CR123A 3V lithium battery for clock.
GRA-413-E
Rack mount bracket for booster PEL3211(H) (EIA)
GRA-413-J
Rack mount bracket for booster PEL3211(H) (JIS)
GRA-414-E
Rack mount frame for PEL-3021(H),
PEL-3041(H), PEL-3111(H)/EIA
GRA-414-J
Rack mount frame for PEL-3021(H),
PEL-3041(H), PEL-3111(H)/JIS
GTL-248
GPIB cable, 2.0m
GTL-246
USB cable, Type A - Type B
PEL-010
Dust Filter
PEL-004
GPIB card
PEL-005
Connect Cu Plate
PEL-006
Connect Cu Plate
PEL-007
Connect Cu Plate
PEL-008
Connect Cu Plate
PEL-009
Connect Cu Plate
PEL-018
LAN card
12
GETTING STARTED
Opening the box
Contents
(single unit)
Main unit
Quick Start manual
User / Programming
manual CD
Terminal fittings
Power cord x1
(region dependent)
Calibration certificate
Package Contents
Check the contents before using the instrument.
13
PEL-3000(H) User Manual
I MON OUT TRIG OUT
1.5 - 150V
175W
0 - 35A
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
Utility
Local
File
0
1
4
7
2
5
8
3
6
9
EnterClear
Shift
Preset
Load
On/
Off
Main
Help
FUNC
Short
Air inletLCD DisplayPower key
FUNC/File
Help/Utility
Short
Load On/Off
USB Port, Preset
and Shift keys
Number pad, Clear/
Lock and Enter keys
Main/Local
Scroll wheel
Function keys
Input
terminals
I MON OUT,
TRIG OUT
V
MON OUT
TRIG OUT
5 -800V
350W
0 -8.75A
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
Utility
Local
File
0
1
4
7
2
5
8
3
6
9
EnterClear
Shift
Preset
Load
On/
Off
Main
Help
FUNC
Short
Air inletLCD DisplayPower key
FUNC/File
Help/Utility
Short
Load On/Off
USB Port, Preset
and Shift keys
Number pad, Clear/
Lock and Enter keys
Main/Local
Scroll wheel
Function keys
Input
terminals
VMON OUT, I MON
OUT, TRIG OUT
I
MON OUT
A/ B
Appearance
Front Panel
PEL-3021/ PEL-3041
PEL-3021H/ PEL-3041H
14
PEL-3111
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
Utility
Local
File
0
1
4
7
2
5
8
3
6
9
EnterClear
Shift
Preset
Load
On/
Off
Main
Help
FUNC
Short
TRIG
OUT
I MON
OUT
1.5 - 150V
1050W
0 - 70A
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
Utility
Local
File
0
1
4
7
2
5
8
3
6
9
EnterClear
Shift
Preset
Load
On/
Off
Main
Help
FUNC
Short
TRIG OUT
I
MON OUT
5 - 800V
1050W
0 – 52.5A
V
MON OUT
A/B
LINK STBY
Air Inlet
The air inlet has a removable dust filter
LCD display
3.5 inch LCD display
Function keys
The function keys directly correspond to the soft
menu keys at the bottom of the display.
PEL-3111H
GETTING STARTED
PEL-3211(H) Booster Pack
15
PEL-3000(H) User Manual
ON/STBY
Turns the unit on or puts the unit
into standby mode. Use the power
switch on the rear panel to turn
the unit off.
Main/Local
Main
Main: Sets the operating mode:
CC, CV, CR, CP mode.
Local
Main
Shift
Local (Shift + Main): Puts
the instrument back into
local mode from remote
mode.
FUNC/File
FUNC
FUNC: Sets the program function,
sequence function or other special
functions.
File
FUNC
Shift
File (Shift + FUNC):
Accesses the file system.
Help/Utility
Help
Help: Access the help menu.
Utility
Help
Shift
Utility (Shift + Help):
Access the utility menu.
Short
Short
Pressing the Short key will
simulate shorting the input
terminals.
The Short key will be lit when
active.
Load on/off
Load
On/
Off
Turns the load on or off.
The Load On/Off key will be lit
when active.
Scroll wheel
Use the scroll wheel to navigate
the menu system or to edit
parameters. See page 45 for usage
details.
16
GETTING STARTED
Enter
Enter
Press the Enter key to select
highlighted menu items.
Number pad
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
0
1
4
7
2
5
8
3
6
9
Clear
Number pad: Used to enter numerical values.
P0-P9 (Preset + Number keys): Loads one of 10
preset settings.
Clear/Lock
Lock
Clear
Clear: Clears the current
parameter values.
Lock (Shift + Clear): Locks the
front panel keys and selector knob.
Shift
Shift
Shift: Used in conjunction with
other keys to select secondary
functions.
Preset
Preset
Used in conjunction with the
number pad to save or load preset
settings P0 to P9.
USB Port
USB A port. Used for save and
recall functions.
Front panel input
terminals
5-800V
350W
0 - 35A
Negative terminal.
Positive terminal.
17
PEL-3000(H) User Manual
IMON Out
I MON OUT
Current monitor BNC terminal:
Output connector used to monitor
the current by outputting a
voltage. An output voltage of 1V
(10V for PEL-3000H) corresponds
to the full scale current for the H
and L ranges. 0.1V (1V for PEL3000H) corresponds to the full
scale current in the M range.
VMON Out
V MON OUT
Voltage monitor BNC terminal:
Output connector used to monitor
the voltage by outputting a
voltage. An output voltage of 8V
corresponds to the full scale
voltage.
TRIG OUT
TRIG OUT
Trigger out BNC terminal:
Outputs a pulse signal during
sequence or dynamic operation.
The trigger signal has a 5V output
with a pulse width of a least 2us
and an impedance of 500Ω.
LINK/STBY
Indicator
(PEL-3211(H))
LINKSTBY
The LINK and STBY indicators
indicate when the booster pack is
properly connected and when the
power has been turned on,
respectively.
18
GETTING STARTED
47 -63 Hz
90 VA MAX.
AC
100- 120 VAC
200- 240 VAC
FRAME CONT
J 1
J 2
SER. NO. LB
RS232C
GPIB
WARNING
TO AVOID ELECTRIC SHOCK THE POWER CORD
DO NOT REMOVE COVERS.
NO OPERATOR SERVICEABLE COMPONENTS INSIDE.
PROTECTIVE GROUNDING CONDUCTOR MUST BE
REFER SERVICING TO QUALIFIED PERSONNEL.
CONNECTED TO GROUND.
Remote sense
inputs
Frame control ports,
J1, J2
RS232C port
USB port
USB device
port
Exhaust fanGPIB(Optinal)Power socket
and switch
Rear panel
inputs
47 - 63 Hz
90 VA MAX.
AC
100 - 120 VAC
200 - 240 VAC
FRAME CONT
J 1
J 2
RS232C
GPIB
Remote sense
inputs
Frame control ports,
J1, J2
RS232C port
USB port
USB device
port
Exhaust fan
GPIB(Optional)
Power socket
and switch
Rear panel
inputs
VR1
VR2 VR3 VR4
V/I MON OUT
1
Monitor Out
ports J3
Variable
Resistor
Rear Panel
PEL-3021/ PEL-3041
PEL-3021H/ PEL-3041H
19
PEL-3111
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
Utility
Local
File
0
1
4
7
2
5
8
3
6
9
EnterClear
Shift
Preset
Load
On/
Off
Main
Help
FUNC
Short
TRIG
OUT
I MON
OUT
1.5 - 150V
1050W
0 - 70A
PEL-3111H
PEL-3000(H) User Manual
PEL-3211 Booster Pack
20
GETTING STARTED
RS232C port
GPIB port
USB B port
The USB B, RS232C and GPIB port are used for
remote control.
USB B port
RS232C 9 pin
DSUB port.
GPIB 24 pin
female.
Frame control
ports, J1, J2
FRAME CONT
J 1
J 2
J1: The J1 connector is assigned to external control.
J2: The J2 connector is used for parallel operation
control.
PEL-3211H Booster Pack
21
PEL-3000(H) User Manual
Monitor Out
ports J3
J3: The J3 connector is assigned to current and
voltage monitor out.
Variable Resistor
The variable resistors are used to adjust the full
scale and offset setting for the input value of the
external control sources such as voltage or
resistance.
Exhaust fan
The exhaust fan is used to expel the heat from the
unit. Please ensure there is at least 20cm distance
between any object and the fan.
Rear Panel Input
terminals
Rear Panel Input Terminals. Electrically connected
to the front panel input terminals. Accepts M8
bolts or M4/M3 sized screws. See page 35 for
connection details.
Remote Sensing
Terminals
Sensing terminals for remote sense. See page 36.
Accepts M3 sized screws.
Power Socket
Power Socket:
100-120V, 200-240V
47-63Hz.
22
GETTING STARTED
Power Switch
Turns the unit on/off.
USB A
USB A Slave port. USB 1.1/2.0
LAN port
LAN
Ethernet port for controlling the
PEL-3000(H) remotely.
23
Display
Date
setting
area
Operation
status
Measurement
area
Mainframe status panel
Soft menus
ModeCCI Range
H 8.75A
V Range
H800V
Function
Static
Configure
0.00
V
0.0000
A
0.00
W
SlewRate140.00
CC B Value0.0000
CC A Value0.0000
LOADRS232
A Value
Fine
01/Oct/2017
mA/us
A
A
panel
Setting area
The setting area is used to display and edit the
settings for the current mode/function.
Measurement
area
Displays the voltage, current and power values.
Date
Displays the date.
Mainframe status
panel
The mainframe status panel displays the status of
the load, remote control and short function.
When an icon is green it indicates that the
function is off. When the icon is orange, the
function is on.
Operation Status
Panel
This status panel is used to display the status of
the current mode.
Soft-keys
The soft-key menus are used to select different
functions or parameters.
PEL-3000(H) User Manual
24
GETTING STARTED
Description
The PEL-3000(H) has a number of rack mount
options for installation. The GRA-413 rack mounts
are suitable for the PEL-3211(H) booster pack. The
GRA-414 rack mounts are capable of holding 1x
PEL-3111(H) or
2x PEL-3021(H)/3041(H) units.
For installation details, please see the GRA-413
and GRA-414 Rack Mount Assembly Manual.
Please see your distributor for which rack mount
is suitable for your application.
GRA-413-E
(EIA standard)
128
532
.
5
482
.
6
First Time Use Instructions
Use the procedures below when first using the PEL-3000(H) to
install the rack mount kit, power up the instrument, set the internal
clock, restore the factory default settings and check the firmware
version. Lastly, the Conventions section will introduce you to the
basic operating conventions used throughout the user manual.
Rack Mount Kits
25
PEL-3000(H) User Manual
GRA-413-J
(JIS standard)
149
532
.
5
482
.
6
GRA-414-E
(EIA standard)
132
382
.
5
477
.
6
26
GETTING STARTED
GRA-414-J
(JIS standard)
149
382
.
5
477
.
6
27
PEL-3000(H) User Manual
Steps
1. Insert the AC power cord into the power
socket.
Turn the external power
switch on.
(O → —)
If the unit doesn’t turn on, press the On/Standby
key.
The ON/STBY key will go from standby (red)
to on (green).
The unit will show the splash screen and then load
the settings from when the unit was last powered
down.
Note
If the PEL-3000(H) fails to start up properly or does
not turn on, please see you local distributor.
Description
When first using the PEL-3000(H), recall the
factory default settings to ensure the unit is in a
known state. See page 241 for a list of the default
settings.
The date and time settings are used to time-stamp
files when saving files.
The date is shown on top of the display.
Operation
1.Press
Shift
+
Utility
Help
> Time Set[F4] to set
the date and time.
Settings:
Month, Day, Year, Hour, Minute
System
Info
LoadInterface Time Set
LOADRS232
03/Oct/2018
Other
0
Hour9
Year2018
Minute
Day
Month
3
10
Date/Time
Date
Setting the Date and Time
Load Wiring
29
PEL-3000(H) User Manual
Wire Gauge
considerations
Before connecting the unit to a power source, the
wire gauge must be taken into account. Load
wires must be large enough to resist overheating
when a short-circuit condition occurs as well as to
maintain a good regulation. The size, polarity and
length of a wire are all factors in determining if a
wire will withstand short circuiting.
Wires that are selected must be large enough to
withstand a short circuit and limit voltage drops
to no more than 2V per wire. Use the table below
to help make a suitable selection.
AWG
Gauge
Conduct or
Diameter
mm
Ohms per
km
Max amps
for chassis
wiring
0000
11.684
0.16072
380 000
10.4038
0.2027
328 00
9.26592
0.25551
283 0
8.25246
0.32242
245 1
7.34822
0.40639
211 2
6.54304
0.51266
181 3
5.82676
0.64616
158 4
5.18922
0.81508
135 5
4.62026
1.02762
118 6
4.1148
1.29593
101 7
3.66522
1.6341
89 8
3.2639
2.0605
73 9
2.90576
2.59809
64 10
2.58826
3.27639
55 11
2.30378
4.1328
47
12
2.05232
5.20864
41 13
1.8288
6.56984
35 14
1.62814
8.282
32
15
1.45034
10.44352
28 16
1.29032
13.17248
22
17
1.15062
17.60992
19 18
1.02362
20.9428
16 19
0.91186
26.40728
14 20
0.8126
33.292
11
30
GETTING STARTED
21
0.7239
41.984
9
Load Line
Inductance
Considerations
When using the PEL-3000(H) load generator,
voltage drop and voltage generated due to load
line inductance and current change must be taken
into account. Extreme changes in voltage may
exceed the minimum or maximum voltage limits.
Exceeding the maximum voltage limit may
damage the PEL-3000(H).
To determine the voltage generated, the following
equation can be used.
E = L x (∆ I / ∆ T)
E= voltage generated
L=load line inductance
∆ I= change of current (A)
∆ T= time (us)
Load line inductance (L) can be approximated as
1uH per 1 meter of wire. (∆ I / ∆ T) is the slew rate
in A/us.
Current
Voltage
time
time
∆I
∆T
E
Min. V
The diagram above shows how changes in current
can affect voltage.
Limiting Load line
inductance
Load line inductance can be reduced in two ways.
1. Ensure load wires are as short as possible and
twist the positive and negative load wires
together.
2. Current change can be limited by limiting the
31
PEL-3000(H) User Manual
slew rate or response speed when switching in
CR and CC mode.
“Twisted pair” will be shown on any connection
diagram where the load wires should be twisted
together.
DUT
-
+
Electronic
Load
+
-
Twisted
pair
DUT
-
+
Electronic
Load
+
-
32
GETTING STARTED
Description
The PEL-3000(H) has input terminals on both the
front and rear panels.
Follow the procedures below for all load
connections. Please adhere to the following
precautions to ensure your safety and to protect
the unit from damage.
Connection
1. When connecting the PEL-3000(H) to the DUT,
make sure that the polarity of the connection
between the DUT and the unit matches.
2. Ensure that the maximum input voltage is not
exceeded. The maximum input voltage is
150(800) volts.
DUT
-
+
Electronic
Load
+
-
Caution
If the polarity to the input terminals is reversed, the
reverse voltage protection function is tripped. The
reverse voltage protection function is tripped when
reverse voltages greater than -0.3V are detected.
Do not touch any of the input terminals when the
voltage is applied to an input terminal.
Connecting the input terminals to the wrong polarity
can damage the DUT or the PEL-3000(H).
The front panel and rear panel input terminals are
physically connected. Any voltage that is input to one
set of terminals will also appear on the other set of
terminals.
Load Wire Connections
33
PEL-3000(H) User Manual
Description
The front panel input terminals feature polaritydistinct caps and accept M6 sized crimped
terminals.
Caution
The front panel input terminals on the PEL-3000(H)
are physically connected to the rear panel terminals.
Steps
1. Turn the power off from the rear panel or put
the unit into standby mode.
2. Turn the power off from the DUT.
3. Connect the load wires to the input terminals:
Connect the positive (+) input terminal on the
load generator to the high potential output of
the DUT.
Connect the negative (-) input terminal to the
low potential output of the DUT.
+ potential
- potential
Negative
terminal
Positive
terminal
Using the Front Panel Input Terminals
34
GETTING STARTED
Description
The rear panel input terminals accept up to M8sized crimped terminals. The rear terminals come
with a load input terminal cover for safety.
Caution
The front panel input terminals on the PEL-3000(H)
are physically connected to the rear panel terminals.
Steps
1. Turn the power off from the rear panel or put
the unit into standby mode.
2. Turn the power off from the DUT.
3. Connect the load wires to the input terminals:
Connect the positive (+) input terminal on the
load generator to the high potential output of
the DUT.
Connect the negative (-) input terminal to the
low potential output of the DUT.
+ potential
- potential
Using the Rear Panel Input Terminals
35
PEL-3000(H) User Manual
Description
The rear panel terminal cover should be used to
prevent electric shock. The rear panel terminal
covers should always be used when connecting a
load to the rear panel terminals. As the front panel
and rear panel terminals are physically connected,
the terminal cover should also be used as a safety
measure when a DUT is connected to the front
terminals
Caution
Ensure the power is off before making any
connections to the PEL-3000(H).
Note
In the following diagrams, the cable wiring is not
shown for clarity.
1. Remove the screw holding the top cover to the
bottom cover.
1
2. Line-up the bottom cover with the notches in
the output terminals.
3. Place the top terminal cover over the bottom
cover.
Using the Terminal Cover (PEL-011)
36
GETTING STARTED
2
Detail
3
4. Use your thumb to slide the terminal covers
shut, as shown in the diagram below.
4
5. When the top and bottom covers are flush,
reinsert the screw that was removed in step 1.
37
PEL-3000(H) User Manual
5
Description
The flexible rear panel terminal cover should be
used when the load wiring becomes too thick to be
used with the PEL-011 terminal cover. This is
especially true when using the load generators in
parallel. Like the PEL-013 terminal cover, the PEL011 is used to prevent electric shock. The rear
panel terminal covers should always be used
when connecting a load to the rear panel
terminals.
Caution
Ensure the power is off before making any
connections to the booster pack.
6. Wrap the insulation sheets around the
terminals and load cables, as shown below.
Make sure the terminals and any exposed
wires are covered by the sheets.
Insulation sheet
1
7. Secure the insulation sheets using the supplied
velcro fasteners. 2 fasteners should be used for
each sheet.
Using the Terminal Cover (PEL-013)
38
GETTING STARTED
Fasteners
2
39
PEL-3000(H) User Manual
Description
After connection is finished, please lock terminal
cover to avoid electric shock when using the
frame control terminal for PEL-3000H series.
If connection is needed, please unlock terminal
cover, If connection isn’t needed, please lock
terminal cover to avoid electric shock for PEL3000 series.
Caution
Ensure the power is off before making any
connections to the booster pack.
Install the terminal cover as shown in the picture
below (for PEL-3000H series).
Using the Terminal Cover
40
GETTING STARTED
Install the terminal cover as shown in the picture
below (for PEL-3000 series).
Description
After connection is finished, please lock monitor
out cover to avoid electric shock when using the
monitor out ports.
Caution
Ensure the power is off before making any
connections to the booster pack.
Install the monitor out cover as shown in the
picture below.
Using the Monitor Out Cover (Only for PEL-3021H, PEL3041H, PEL-3111H)
41
Remote Sense
Description
Remote sense can be used to help compensate for
long cable length. The longer the cable, the higher
the potential resistance and inductance, therefore
a short cable is best. Twisting the cable can help
reduce induced inductance and using the Vsense
terminals compensates the voltage drop seen
across the load leads, especially leads with higher
resistance. This is useful when used in CV, CR or
CP mode.
Steps
1. Turn the power off from the rear panel or put
the unit into standby mode.
2. Turn the power off from the DUT.
3. Connect the sense wires to the sense terminals:
Connect the positive sense (+S) terminal to the
high potential output of the DUT.
Connect the negative sense (-S) terminal to the
low potential output of the DUT.
DUT
-
+
Programable
Electronic
Load
+
-
+S
-S
Twisted
pair
PEL-3000(H) User Manual
42
GETTING STARTED
Description
The PEL-3000(H) allows the firmware to be
updated by end-users. Before using the PEL3000(H), please check the GW Instek website or
ask your local distributor for the latest firmware.
System version
Before updating the firmware, please check the
firmware version.
Operation
1.Press
Shift
+
Utility
Help
.
2. Select System/Info[F1].
3. The System information is listed on the
display.
Model: PEL-3000(H) model number.
Serial Number: XXXXXXXX
Firmware Ver.: Firmware version number.
Website address.
4. To view other system information, press
System[F1] and select Memo.
System
Info
LoadInterface Time Set
LOADRS232
03/Sep/2018
Model : PEL-3XXX(H)
Firmware Ver. : X.XX
Serial Number : XXXXXXXX
Other
http://www.goodwill.com.tw
Firmware Update
43
PEL-3000(H) User Manual
Update Firmware
1. Insert a USB drive into the USB port. Ensure
the USB drive has the firmware file located in
the root directory.
2. Press
Shift
+
File
FUNC
.
3. Select USB with the Media[F1] soft-key.
4. Press the File Utility[F5] soft-key.
5. Select the *.UPG upgrade file and press
Select[F1] twice. Once to select the file and
once to confirm.
6. Wait for the update to complete and reset the
power when prompted.
Note
Do not turn the load generator off or remove the USB
memory when the firmware is being read or
upgraded.
44
GETTING STARTED
Soft Menu keys
The F1 to F5 function keys at the bottom of the
display correspond directly to the soft-menu keys
on top.
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
Utility
Local
File
0
1
4
7
2
5
8
3
6
9
EnterClear
Shift
Preset
Load
On/
Off
Main
Help
FUNC
Short
F1 ~ F5
Function keys
Soft menus
ModeCCI Range
H 8.75A
V Range
H800 V
Function
Static
Configure
0.00
V
0.0000A
0.00W
SlewRate 140.00
CC B Value 0.0000
CC A Value 0.0000
LOADRS232
A Value
Fine
01/Oct/2017
mA/us
A
A
Select Sub Menu
Configure
Pressing this type of soft-menu key will enter a
submenu.
Conventions
The following conventions are used throughout the user manual.
Read the conventions below for a basic grasp of how to operate the
PEL-3000(H) menu system using the front panel keys.
45
PEL-3000(H) User Manual
Toggle Parameter
or State
Mode
CC
Function/Item
Parameter or State
This type of soft-menu icon has the function/item
on the top of the label and the selected setting or
mode on the bottom of the label.
Repeatedly press the associated function key (F1F5) to cycle through each setting. For example,
repeatedly pressing the Mode soft-menu key will
cycle through the CC, CR, CV and CP modes.
Mode
CR
Mode
CC
Mode
CV
Mode
CP
For some parameters, a popup window will also
appear. Selection of the setting is the same.
Repeatedly pressing the relevant function key (F1F5) will cycle through each setting. The selection
on the popup window will also be reflected on the
label.
ModeCCI Range
H 8.75A
V Range
H800V
Function
Static
Configure
0.00
V
0.0000A
0.00W
SlewRate140.00
CCBValue0.0000
CCAValue0.0000
LOADRS232
AValue
Fine
01/Oct/2017
mA/us
A
A
LOW
Middle
High
87.5mA
0.875A
8.750A
label
Popup window
Prameter selection
Parameter Input
The scroll wheel, Enter key and number pad can
be used to edit parameter values.
46
GETTING STARTED
Number pad
Scroll wheel
Enter key
P0
P1
P4
P7
CAL.
P2
P5
P8
Lock
P3
P6
P9
0
1
4
7
2
5
8
3
6
9
ClearEnter
1. Use the scroll wheel to move the cursor to the
desired parameter.
A scroll bar is shown when there are additional
parameters off-screen.
ModeCPI Range
H 8.75A
V Range
H800V
Function
Dynamic
Configure
0.00
V
0.0000A
0.00W
Timer10.025
Level 20.00
Level
1
0.00
LOADRS232
Fine
01/Oct/2018
ms
W
W
Scroll bar
Cursor
2. Press the Enter key to select the parameter. The
parameter will become highlighted in white
3. Then use the number pad* or scroll wheel** to
edit the parameter value.
ModeCCI Range
H 8.75A
V Range
H800V
Function
Static
Configure
0.00
V
0.0000A
0.00W
SlewRate140.00
CC B Value
CC A Value 0.000
LOADRS232
A Value
Fine
01/Oct/2018
mA/us
A
A
1.000
Parameter
4. Press the Enter key again to finish editing the
parameter value.
47
PEL-3000(H) User Manual
Clearing a Value*
*When editing a parameter with the number pad,
pressing the
Clear
key will restore the
parameter to the previous value.
Using the Scroll
Wheel to Edit a
Parameter**
**To edit a parameter using the scroll wheel,
simply turn the scroll wheel. Clockwise increases
the value, counterclockwise decrease the value.
Pressing the scroll wheel when a parameter is
highlighted allows you to change the step
resolution. There are two different step resolution
methods: Step Mode and Cursor Mode. Step
Mode: This is the default step resolution method
and will only be available to use when it is
applicable (Indicated by Fine or Coarse in the
Operation Status panel).
When a parameter is highlighted (step 3 above)
pressing the scroll wheel will toggle the step
resolution between fine and coarse. For details on
how to set the step resolution, see page 81.
ModeCCI Range
H 8.75A
V Range
H800V
Function
Static
Configure
0.00
V
0.0000A
0.00W
SlewRate140.00
CC B Value
CC A Value 0. 000
LOADRS232
A Value
Fine
01/Oct/2018
mA/us
A
A
1.000
Highlighted
parameter
Coarse/Fine
adjustment
+
Cursor Mode: This method must first be enabled
before it can be used. Pressing the scroll wheel
when a parameter is highlighted allows you to set
the step resolution by a digit value. An orange line
will appear under the currently selected digit
value. Repeatedly pressing the scroll wheel moves
to the next digit. See page 80 for details.
48
GETTING STARTED
ModeCCI Range
H 8.75A
VRange
H800V
Function
Static
Configure
0.00
V
0.0000A
0.00W
SlewRate140.00
CC B Value
CC A Value 0.0000
LOADRS232
A Value
Cursor
01/Oct/2018
mA/us
A
A
1.0000
+
Cursor
Mode
Indicator
0.00
w
LOADRS232
A
A
Highlighted
parameter
Cursor
position
Entering
Alphanumeric
Characters
When renaming files, creating memos or notes,
you will be required to enter alphanumeric
characters when the character entry screen
appears.
Only alphanumeric characters as well as space
[ ], underscore [_] and minus [-] characters
allowed.
1. Use the scroll wheel to move the cursor to the
desired character.
A B C D E F G H I J K L M
N O P Q R S T U V W X Y Z
1 2 3 4 5 6 7 8 9 0 _ 1
Rename:
Filename
Cursor
2.Press the
Enter
key or Enter Character[F1]
to select a character.
OR
Enter
Character
3. To delete a character, press Back Space[F2].
4. To save the file name or memo, press Save[F3].
49
PEL-3000(H) User Manual
Help Selection
1. Press any function key or soft-menu key.
2. Press
Help
to see the help contents on that
particular function key or menu.
3. Use the scroll to navigate the help contents.
4. Press the Exit[F5] key to exit the help menu.
Help
on Help
LOADRS232
03/Oct/2018
Exit
HELP
Press F5 to exit the Help mode.
Rotate the VARIABLE knob to scroll all
the contents.
-End-
Help Menu
When any function key has been pressed or when a menu has been
opened, the HELP key can be used to display a detailed description.
Edit Tracking of MPPT function ................................................ 173
Auto Load of MPPT function ..................................................... 174
Data file of test result .................................................................... 179
53
PEL-3000(H) User Manual
Description
In Constant Current Mode the load units will sink
the amount of current programmed. Regardless of
the voltage, the current will stay the same. For
more details on CC mode, please see the Appendix
on page 259.
Warning
If you change the mode or the range when the load is
already on, the load will be turned off automatically.
Operation
1. Make sure the load is off.
2. Press
Main
.
3. Select CC mode with the Mode[F1] soft-key.
4. Select the current range with the I Range[F2]
soft-key.
Range:
High, Middle, Low
5. Select the voltage range with the V Range[F3]
soft-key.
Range:
High, Low
Basic Operation
The PEL-3000(H) supports 7 main operating modes:
CC, CC+CV;
CR, CR+CV;
CV;
CP, CP+CV
CC Mode
54
OPERATION
6. Set the current level parameters using the scroll
wheel and number pad.
For Static mode, set CC A Value and/or CC B
Value.
For Dynamic mode, set Level1 and Level2.
The maximum and minimum current levels
depend on the selected ranges.
7. To add CV mode to CC mode (CC+CV), see
page 61.
8. Set the remaining basic configuration settings
such as the slew rate, and switching function
settings. See page 66 for details.
Display
ModeCCI Range
H 8.75A
VRange
L 80V
Function
Static
Configure
0.000
V
0.0000
A
0.00
W
SlewRate140.00
CC B Value0.0000
CC A Value0.0000
LOADRS232
A Value
Fine
01/Oct/2018
mA/uS
A
A
Mode
Current range
Voltage range
Active setting
Current setting A
Current setting B
Note
Basic CC mode configuration is complete. See page 66
for more configuration options.
The current range and voltage range applies to all the
operating modes.
55
CR Mode
Description
In Constant Resistance Mode, the unit will
maintain a constant resistive load by varying the
current. CR mode uses ohms, Ω (resistance) or
siemens, S (conductance) for the setting units. For
more details on CR mode, see the appendix on
page 260.
Warning
If you change the mode or the range when the load is
already on, the load will be turned off automatically.
Operation
1. Make sure the load is off.
2. Press
Main
.
3. Select CR mode with the Mode[F1] soft-key.
4. Select the current range with the I Range[F2]
soft-key.
Range:
High, Middle, Low
5. Select the voltage range with the V Range[F3]
soft-key.
Range:
High, Low
6. Set the resistance or conductance level
parameters using the scroll wheel and number
pad.
For Static mode, set CR A Value and/or CR B
Value.
For Dynamic mode, set Level1 and Level2.
The maximum and minimum conductance/
resistance levels depend on the selected current
range.
7. To add CV mode to CR mode (CR+CV), see
page 61.
8. Set the remaining basic configuration settings
PEL-3000(H) User Manual
56
such as the slew rate, and switching function
settings. See page 66 for details.
Display
ModeCRI Range
H 8.75A
V Range
L 80V
Function
Static
Configure
0.000
V
0.0000
A
0.00
W
SlewRate14.000
CR B Value 0.54422
CR A Value 0.54422
LOADRS232
A Value
Fine
01/Oct/2017
mA/uS
Ω
Ω
Mode
Current range
Voltage
range
Active
setting
Conductance/
Resistance
settings
Note
Basic CR mode configuration is complete. See page 66
for more configuration options.
The current range and voltage range applies to all the
operating modes.
CR Units
Description
The CR setting units can be set to ohm (Ω) or
millisiemens (mS).
Operation
1. Make sure the load is off.
2. Press
Main
> Configure[F5] > Other[F2] and
set the CR Unit setting.
Range:
Ω, mS
OPERATION
57
CV Mode
Description
In Constant Voltage Mode, the unit will maintain a
constant voltage. In CV mode you set the constant
voltage level. For more details on CV mode, see the
appendix on page 263.
Warning
If you change the mode or the range when the load is
already on, the load will be turned off automatically.
Operation
1. Make sure the load is off.
2. Press
Main
.
3. Select CV mode with the Mode[F1] soft-key.
4. Select the current range with the I Range[F2]
soft-key.
Range:
High, Middle, Low
5. Select the voltage range with the V Range[F3]
soft-key.
Range:
High, Low
6. Set the voltage level parameters using the scroll
wheel and number pad.
Set CV A Value and/or CV B Value.
The maximum and minimum voltage levels
depend on the selected voltage range.
7. Set the remaining basic configuration settings
such as the response settings. See page 66 for
details.
PEL-3000(H) User Manual
58
Display
ModeCVI Range
H 8.75A
V Range
L 80V
Response
Slow
Configure
0.000
V
0.0000
A
0.00
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2018
V
V
Mode
Current range
Voltage
range
Active
setting
Currentsetting
Voltage
settings
Note
Basic CV mode configuration is complete. See page 66
for more configuration options.
The current range and voltage range applies to all the
operating modes.
CP Mode
Description
In Constant Power Mode, the unit will maintain a
constant power by varying the current. For more
details on CP mode, see the appendix on page 262.
Warning
If you change the mode or the range when the load is
already on, the load will be turned off automatically.
Operation
1. Make sure the load is off.
2. Press
Main
.
3. Select CP mode with the Mode[F1] soft-key.
4. Select the current range with the I Range[F2]
soft-key.
Range:
High, Middle, Low
5. Select the voltage range with the V Range[F3]
soft-key.
Range:
High, Low
OPERATION
59
PEL-3000(H) User Manual
6. Set the power level parameters using the scroll
wheel and number pad.
For Static mode, set CP A Value and/or CP B
Value.
For Dynamic mode, set Level1 and Level2.
The maximum and minimum power levels
depend on the selected current range.
For static mode, the parameter that is set last
becomes the “active” setting. This will be
shown in the Operation Status Panel.
7. To add CV mode to CP mode (CP+CV), see
page 61.
8. Set the remaining basic configuration settings
such as the slew rate, and timer settings. See
page 66 for details.
Display
ModeCPI Range
H 8.75A
V Range
H 800V
Function
Static
Configure
0.00
V
0.0000
A
0.00
W
CP B Value0.00
CP A Value0.00
LOADRS232
A Value
Fine
01/Oct/2017
W
W
Current range
Active
setting
Currentsetting
Power
settings
+CVOFF
Mode
Voltage
range
Note
Basic CP mode configuration is complete. See page 66
for more configuration options.
The current range and voltage range applies to all the
operating modes.
60
+CV Mode
Description
+CV mode can be added to CC, CR and CP mode.
The +CV settings apply to all applicable modes.
Operation
1. Make sure the load is off.
2. Press
Main
and select to Mode, I Range and
V Range.
3. Set the +CV voltage level. (You may need to
scroll down to the +CV setting)
Range:
OFF - rated voltage+5%
Display
Mode
CP + CV
I Range
H 8.75A
V Range
L 80V
Function
Dynamic
Configure
0.000
V
0.0000
A
0.00
W
+CV5.500
Timer20.025
Timer10.025
LOADRS232
01/Oct/2018
V
ms
ms
+CV setting
Note
The +CV settings apply to all the applicable operating
modes.
For example: The +CV settings made in CR mode will
be carried over to the +CV settings in CC and CP
mode.
Note
+CV settings cannot be controlled with external
control. (The external control is not possible only in
+CV settings)
See page 185 for +CV settings with external control
OPERATION
61
PEL-3000(H) User Manual
Description
1. The load can be turned on and off by pressing
the
Load
On/
Off
key.
The
Load
On/
Off
key will turn orange when the load
is “on”.
The LOAD icon in the Main Frame status panel
will turn orange when the load is on.
Note
The load can be set to automatically turn on at
start up. See page 78.
The load can be turned on via remote control.
See the programming manual.
The load can be turned on via external control.
See page 194.
By default the load will automatically turn off if
the range or operating mode (CC, CV, CR, CP)
is changed. To disable this behavior, Set Load Off (Mode) and Load Off (Range) to the OFF
setting. See page 79 for details.
Display
LOADRS232
03/Oct/2018
LOAD on
Description
The Short key can be used to simulate a short
circuit of the load input terminals. A short circuit is
simulated by:
Setting the current to the maximum value in CC
mode.
Setting the resistance to the minimum value in
CR mode.
Turning on the Load
Shorting the Load
62
OPERATION
Setting the voltage to the minimum value in CV
mode.
Setting the power to the maximum value in CP
mode.
When the load is shorted, the external
controller also sends a short signal. See page
200 for usage details.
Operation
1. The short function can be turned on and off by
pressing the
Short
key.
The
Short
key will turn red when the short
function is active.
The Short icon will appear when the short
function is active.
Display
LOADRS232SHORT
03/Oct/2018
SHORT on
Note
If the load is already off, pressing the Short key will
turn the load on (shorted) at the same time. Pressing
the Short key again will also turn the load off again as
well.
If the load is already on and the Short key is pressed,
then when the Short key is pressed again the load will
remain on (the electronic load will return to its
previous load condition).
Note
The Short key will be disabled if the Short Function
setting is turned off. See page 64 for details.
Description
When activated, the safety short function only
allows the short key to be used when the load is
already on.
Safety Short
63
PEL-3000(H) User Manual
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
set the Short Safety.
When set to OFF, the load can be shorted at
anytime.
When set to ON, the load can only be shorted
when the load is already on.
Short (Safety):
OFF, ON
Note
The Short Safety setting will be grayed out if Short
Function is set to OFF. See page 64 for details.
Description
The Short key can be configured to Toggle or Hold.
By Default the Short key is set to Toggle.
Toggle: Pressing the Short key will toggle the
shorting function on or off.
Hold: Holding the short key will short the load.
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
set the Short Key setting.
Range:
Toggle, Hold
Note
The Short Key setting will be grayed out if Short
Function is set to OFF. See page 64 for details.
Short Key Configuration
64
OPERATION
Description
The short key can be disabled to prevent the
operator accidentally shorting the load.
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
set the Short Function.
When set to OFF, the Short key is disabled and
all short configuration options in the
Main>Configure>Other menu are also
disabled.
When set to ON, the Short key is enabled.
Short Function:
OFF, ON
Description
The keys and scroll wheel on the front panel can be
locked to prevent settings from being changed.
Operation
1. The keys can be locked and unlocked by
pressing
Shift
+
Lock
Clear
.
LOCK will appear in the Mainframe status
panel when the keys are locked.
The
Load
On/
Off
key will not be locked if the load
is on.
Display
LOCK will appear in the Mainframe status panel when
the keys are locked.
LOADRS232
03/Oct/2018
LOCK
LOCK icon
Short Function Enable/Disable
Locking the Front Panel Controls
65
PEL-3000(H) User Manual
Description
The PEL-3000(H) has two switching function, static
and dynamic. The switching function allows the
PEL-3000(H) to switch between two preset levels.
Static mode can only switch between the two levels
manually, while Dynamic mode switches between
each level automatically based on a timer.
Static mode: A Value, B Value
Dynamic mode: Level1, Level2
When the unit is set to static mode, only one value
(A Value or B Value) can be active at a time. The
active value is shown in the Operation Status
Panel.
Configure
W
LOADRS232
A Value
Fine
Active
setting
When the unit is set to dynamic mode, the unit will
switch between Level1 and Level2 based on the
Timer1 and Timer2 parameters, shown below.
Basic Configuration
The basic configuration settings are the common configuration
settings that are used for each operating mode. After selecting a
basic operating mode (CC, CR, CV or CP mode), the slew rate,
switching function, response rate and other common parameters
should be configured.
Select the Switching Function
66
OPERATION
Level
Time
Level 2
Level 1
Timer1 Timer2Timer1
Dynamic Mode
Note
Dynamic mode is not available for CV mode.
Operation
1. Make sure the load is off.
2. Press
Main
.
3. Select Dynamic or Static mode with the
Function[F4] soft-key.
A different switching function can be set for
CC, CR and CP mode.
4. For dynamic mode, set the Timer1 and Timer2
parameters using the scroll wheel and number
pad.
Timer1 sets the Level1 on-time.
Timer2 sets the Level2 on-time.
Take the slew rate settings into consideration
when setting the timers.
The frequency of the dynamic switching is
output via the TRIG OUT BNC.
5. In the static mode, select either value A or value
B as the “active” value for execution followed
by pressing the
Shift
+
Preset
.
The “active” value will be shown in the
Operation Status Panel.
The load can be “on” when switching between
A Value and B Value.
67
PEL-3000(H) User Manual
Display:
Static Mode
ModeCPI Range
H 8.75A
V Range
H 800V
Function
Static
Configure
0.00
V
0.0000
A
0.00
W
CP B Value0.00
CP A Value0.00
LOADRS232
A Value
Fine
01/Oct/2018
W
W
Active setting
A Value
B Value
+CVOFF V
Static mode
Display:
Dynamic Mode
ModeCPI Range
H 8.75A
V Range
L 80V
Function
Dynamic
Configure
0.000
V
0.0000
A
0.00
W
Timer10.025
Level20.00
Level10.00
LOADRS232
Fine
01/Oct/2018
mS
W
W
Dynamic mode
Level1
Level2
Timer1
Description
When Dynamic mode is selected, the Level1 and
Level2 values can be set to either discrete values or
as a percentage of a set value.
The setting applies to all applicable operation
modes.
By default the units are set to Value.
When Percent is chosen, 100% = 100% of the Set
power, current or resistance value.
Select the Display Units for Dynamic Mode Levels
68
OPERATION
Operation
1. Make sure the load is off.
2. Press
Main
> Configure[F5] > Other[F2] and
set the Dyna. Level setting.
Range:
Value, Percent
Display:
Percent Setting
ModeCPI Range
H 8.75A
V Range
L 80V
Function
Dynamic
Configure
0.000
V
0.0000
A
0.00
W
Timer10.025
Level50.0
Set1.00
LOADRS232
Fine
01/Oct/2018
ms
%
W
Set level
% from the Set value
Example
Level
Time
Set
Level
Timer1 Timer2Timer1
Dynamic Mode:
Dyna. Level = Percent
Description
The switching time for dynamic mode can be
configured to switch between two preset on-times
(Timer1, Timer2) or by setting a switching
frequency and duty cycle.
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
set the Dyna. Time setting.
Range:
T1/T2, Freq. Duty
Select the Switching Time Configuration for Dynamic Mode
69
Slew Rate
Description
The current slew rate can be set for CC and CR
mode. The slew rate setting is used to limit the
change in current when switching.
For static mode, only a single slew rate can be set.
Operation
1. Make sure the load is off.
2. Press
Main
.
3. Set the slew rate(s) using the scroll wheel and
number pad.
For static mode, only a single slew rate can be
set.
For dynamic mode, set both the rising and
falling slew rates.
Take the timer settings into consideration when
setting the slew rates.
Display
ModeCCI Range
H 8.75A
V Range
H 800V
Function
Dynamic
Configure
0.00
V
0.0000
A
0.00
W
Timer10.025
SlewRate140.00
SlewRate140.00
LOADRS232
01/Oct/2018
ms
mA/us
mA/us
SlewratesettingsSlewrate settings
PEL-3000(H) User Manual
70
OPERATION
Description
The response speed setting is the response speed
for the negative feedback control of the load
current when used in CV, +CV mode. Response
speed settings are only applicable to CV, +CV
mode.
A response speed that is too fast could cause
the unit to be unstable.
Reducing the response speed can improve
stability.
Operation
1. Make sure the load is off.
2. Press
Main
. Make sure the unit is in CV
mode by using the Mode[F1] soft-key.
3. Select the response speed with the Response[F4]
soft-key.
Range:
Slow, Fast (Fast, 6, 5, 4, 3, 2, 1, slow)
CV mode: The response speed settings
Fast, 6, 5, 4 are all the same
for CV mode.
+CV mode: The response speed settings
5 and 4 are the same for CV
mode. The response speed
settings Slow and 1 is the
same.
CV, +CV Mode Response Speed
71
PEL-3000(H) User Manual
Display
ModeCVI Range
H 8.75A
V Range
L 80V
Response
Slow
Configure
0.000
V
0.0000
A
0.00
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2018
V
V
Response
setting
Description
By default, the “normal current response” speed is
set to 1/1. The response speed can be reduced to
1/2, 1/5, 1/10.
Reducing the current response speed can affect
other settings such as the slew rate and soft
start settings.
Operation
1. Make sure the load is off.
2. Press
Main
> Configure[F5] > Other[F2] and
set the Response parameter.
Range:
1
1
,
2
1
,
5
1
,
10
1
CC, CR and CP Mode Response Speed
72
OPERATION
Description
The soft start setting is used to limit the amount of
input current at start-up or from when the Von
Voltage threshold is tripped.
The soft start setting only applies to CC, CR
and CP mode (CP mode only for PEL-3000
series).
Input I
Time
Soft Start = ON
Input I
Time
Soft Start= OFF
Rise voltage
Rise current
Rise current
Rise voltage
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
set the Soft Start time.
Range:
OFF, 1-200ms for PEL-3000
OFF, 3-200ms for PEL-3000H
Advanced Configuration Settings
Use the advanced configuration settings to configure settings other
than those described in the basic configuration chapter.
Soft Start
73
PEL-3000(H) User Manual
Description
The Von Voltage is the threshold voltage at which
the load module will start to sink current.
Time
Von voltage
Von
V
Time
I
PEL-3000
V out
Load on
Operation
2. Press
Main
> Configure[F5] > Other[F2] and
set the Von Voltage level.
Range:
Von Voltage: 0.00-rating voltage
Von Voltage Settings
Von Voltage
74
OPERATION
Description
When Von Latch is set to ON, the load will
continue to sink current after being “latched”, even
if the voltage drops below the Von Voltage
threshold level.
When Von Latch is set to OFF, the load will turn
off when the voltage drops below the Von Voltage
threshold level.
By default Von Latch is set to OFF.
Time
Von Latch = OFF
Von
V
Time
I
PEL-3000
V out
Load on
Load offLoad on
Time
Von Latch = ON
Von
V
Time
I
PEL-3000
V out
Load on
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
set the Von Latch setting.
Range:
Von Latch: OFF, ON
Von Latch
75
PEL-3000(H) User Manual
Description
Von Delay is the amount of time the unit will wait
before turning the load on after the Von Voltage
threshold has been latched. This will prevent
overshoot current from affecting the Von Voltage
threshold.
CR mode can have the delay time set separately from
the other modes (called
Von Delay –CR
when in CR
mode).
Description
When Count Time is set to on, it will count the
elapsed time from when the load was turned on to
when it was turned off.
This function is applicable to manual and
automatic shutdown (such as from protection
functions such as UVP etc.)
The elapsed time will be shown in the display
Measurement area.
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
turn the Count Time on or off.
Range:
ON, OFF
Von Delay
Timer Functions
Count Time
76
Display
0.000
V
0.0000
A
0.00
W
LOADRS232
01/Oct/2017
0:00:05
Elapsed time
Cut Off Time
Description
The Cut Off Time function will turn the load off
after a set-amount of time. After the load has been
turned off, a popup screen will display the voltage
level when the load was turned off.
Operation
1. Press
Main
> Configure[F5] > Other[F2] and
set the Cut Off Time.
Range:
OFF, 1 second - 999 hours:59
minutes:59 seconds
Display
ModeCPI Range
H 8.75A
V Range
L 80V
Function
Dynamic
Configure
0.000
V
0.0000
A
0.00
W
Timer10.025
Level20.00
Level10.00
LOADRS232
Fine
01/Oct/2018
mS
W
W
0:00:05
Cut off time
Time Up
Voltage : 5.1223V
Enter
Voltage at cut off time
OPERATION
77
PEL-3000(H) User Manual
Description
The PEL-3000(H) can be configured to
automatically load the last program, normal
sequence, fast sequence or load setting at startup.
By default, this setting is disabled.
Operation
1.Press
Shift
+
Utility
Help
> Load[F2].
2. Turn Auto Load On or Off.
When set to OFF, the Auto Load setting is
disabled.
3. Select the Auto Load On configuration.
This will select whether the PEL-3000(H) will
automatically load the last program, normal
sequence, fast sequence or load settings.
Auto Load On:
Load, Prog, NSeq, FSeq
Auto Load Configuration
78
OPERATION
Description
By default the load will automatically turn off
when the either the operating mode (CC, CV, CR,
CP) or the range (I range, V range) is changed.
To allow the load to stay on when the operating
mode is changed, set the Load Off (Mode) setting to
OFF.
To allow the load to stay on when the current or
voltage range is changed, set the Load Off (Range)
setting to OFF.
By default, these settings are set to ON.
Operation
1.Press
Shift
+
Utility
Help
> Load[F2].
2. Select Load Off (Mode) setting.
When set to OFF, the load will stay on when the
operating mode is changed.
Load Off (Mode):
OFF, ON
3. Select Load Off (Range) setting.
When set to OFF, the load will stay on when the
range is changed.
Load Off (Range):
OFF, ON
Load Off (Mode) and Load Off (Range)
79
PEL-3000(H) User Manual
Description
Cursor mode allows you to edit the selected
parameter one digit at a time. When editing a
parameter, pressing the scroll wheel determines
which digit is selected. Turning the scroll wheel
will then edit the parameter by the step resolution
of the digit.
See the Conventions section on page 45 for
operation details.
Operation
1. Press
Main
> Configure[F5] > Next Menu[F4]
> Knob[F2] and set the Status setting is set to
Cursor.
Display
ParallelKnobExternal
Previous
Menu
3.00
CCL Step0.300
CCM Step0.00300
LOADRS232
01/Oct/2018
mS
mA
A
CRH Step
CCH Step
Status
0.0300
CursorA
CC
8.75A
80V
Static
Configure
Step Resolution Configuration
There are two different ways to set the resolution when using the
scroll wheel to edit parameters. Step Mode and Cursor Mode. Step
Mode is the default method. Only one mode can be active at a time;
When one mode is active, the other mode is deactivated.
Cursor Mode Configuration
80
OPERATION
Description
When set to Step Mode, the voltage, current,
resistance and power settings can have the step
resolution configured. The step resolution refers to
the step resolution of the coarse adjustment for
these settings. The fine adjustment cannot be
configured.
See the Conventions section on page 45 for details
on how to switch between coarse and fine
adjustment modes.
Settings
The step resolution of each setting is configured
separately for each current range.
Settings
Description
CCH Step
CC mode, IRange = High
CCM Step
CC mode, IRange = Middle
CCL Step
CC mode, IRange = Low
CRH Step
CR mode, IRange = High
CRM Step
CR mode, IRange = Middle
CRL Step
CR mode, IRange = Low
CVH Step
CV mode, VRange = High
CVL Step
CV mode, VRange = Low
CPH Step
CP mode, IRange = High
CPM Step
CP mode, IRange = Middle
CPL Step
CP mode, IRange = Low
Step Mode Configuration
81
PEL-3000(H) User Manual
Operation
1. Press
Main
> Configure[F5] > Next Menu[F4]
> Knob[F2] and make sure the Status setting is
set to Step.
2. Set the desired step resolution settings. (The
step resolution settings are only available when
Status=Step (coarse/fine))
For example if the step resolution for CCM Step
is 0.5A, then the resolution can be incremented
in 0.5A steps.
Display
ParallelKnobExternal
Previous
Menu
3.00
CCL Step0.300
CCM Step0.00600
LOADRS232
01/Oct/2018
mS
mA
A
CRH Step
CCH Step
Status
0.0300
Step (coarse/fine)
A
CC
8.75A
80V
Static
Configure
82
OPERATION
Description
For OCP, the PEL-3000(H) can be configured to
either limit the current or turn off the load.
The OCP levels can be set to 10% higher than the
rating current.
Operation
1. Press
Main
> Configure[F5] > Protection[F1]
and set the OCP Level and OCP Setting.
Range:
OCP Level: Rating current + 10%
OCP Setting: LIMIT, Load Off
Alarm
When OCP Setting is configured to Load Off, a
message will be displayed on the screen when
OCP is tripped. The Enter key must be pressed
to clear the alarm message.
When configured to LIMIT, OCP will be
displayed on the screen when the OCP is
tripped and the current will be limited to the
OCP Level setting.
Protection Settings
The Protection settings are used to prevent damage to the unit or
the DUT by excessive current, voltage or power.
An alarm is generated and a message is displayed on the screen
when a protection setting is tripped. When an alarm is activated,
the load is turned off (or limited), and the ALARM STATUS pin of
the J1 connector on the rear panel (pin 16) turns on (open collector
output by a photocoupler). The protection settings can be used
regardless of whether the remote sense connections are used or not.
OCP
83
Display
8.653
V
50.006
mA
0.4327
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2017
V
V
OCP Alarm
Please Press Enter
To Clear Alarm
OCP
OCP indicator
Alarm message
when OCP is
set to Load Off
ModeCVI Range
L87.5mA
V Range
L 80V
Response
Fast
Configure
OPP
Description
For OPP, the PEL-3000(H) can be configured to
either limit the power or turn off the load.
The OPP levels can be set to 10% higher than the
rating power.
Operation
1. Press
Main
> Configure[F5] > Protection[F1]
and set the OPP Level and OPP Setting.
Range:
OPP Level: Rating power + 10%
OPP Setting: LIMIT, Load Off
Alarm
When OPP Setting is configured to Load Off, a
message will be displayed on the screen when
OPP is tripped. The Enter key must be pressed
to clear the alarm message.
When configured to LIMIT, OPP will be
displayed on the screen when the OPP is
tripped and the power will be limited to the
OPP Level setting.
PEL-3000(H) User Manual
84
Display
8.653
V
50.006
mA
0.4327
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2017
V
V
OPP Alarm
Please Press Enter
To Clear Alarm
OPP
OPP indicator
Alarm message
when OPP is
set to Load Off
ModeCVI Range
L87.5mA
V Range
L 80V
Response
Fast
Configure
UVP
Description
If the UVP is tripped, the PEL-3000(H) will turn off
the load.
The UVP levels can be set from 0V to 10% higher
than the rating voltage.
Operation
1. Press
Main
> Configure[F5] > Protection[F1]
and set the UVP Level.
Range:
UVP Level: OFF, 0-Rating voltage + 10%
Alarm
The UVP indicator and a message will only
appear on the screen when the input voltage is
below the UVP level. The Enter key must be
pressed to clear the alarm message.
To clear the UVP indicator, remove the cause of
the under voltage - i.e., increase the input
voltage.
OPERATION
85
Display
8.653
V
50.006
mA
0.4327
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2017
V
V
UVP Alarm
Please Press Enter
To Clear Alarm
UVP
UVP indicator
Alarm message
when UVP is
set to Load Off
ModeCVI Range
L87.5mA
V Range
L 80V
Response
Fast
Configure
UVP Ring Time
Description
The UVP Ring Time settings allows the UVP alarm
to keep sounding for a user-set amount of time
after the UVP has been tripped.
The alarm will continue ringing for the set amount
of time even if the voltage rises back above the
UVP level~ unless the alarm is cleared manually.
Operation
1. Press
Main
> Configure[F5] > Protection[F1]
and set the UVP Ring Time.
Range:
UVP Ring Time: OFF, 0-600s
PEL-3000(H) User Manual
86
OPERATION
Alarm
When the voltage dips below the UVP level, the
UVP indicator and message will appear on the
screen. The UVP buzzer will sound if UVP Ring
Time is set. Under this scenario the following
outcomes are possible:
1. Pressing the Enter key will clear the message
and the buzzer. The UVP indicator will remain
on the display until the voltage level rises back
above the UVP level.
2. If the UVP Ring Time is allowed to elapse, the
buzzer will stop. However the UVP indicator
and message will remain on screen until the
voltage increases and the message is cleared.
3. If the voltage rises back above the UVP level,
the UVP indicator will be cleared from the
display but the buzzer will continue to sound
until the UVP Ring Time has elapsed and the
message will remain until it has been cleared.
Display
2.596
V
500.06
mA
1.2982
w
CV B Value15.000
CV A Value15.000
LOADRS232
A Value
Fine
03/Sep/2012
V
V
UVP Alarm
Please Press Enter
To Clear Alarm
UVP
UVP indicator
Alarm message
when UVP is
tripped
ModeCVI Range
L 0.7A
V Range
L 15V
Response
Fast
Configure
87
OVP
Description
If the OVP is tripped, the PEL-3000(H) will turn off
the load.
The OVP levels can be set from 0V to 10% higher
than the rating voltage.
Operation
1. Press
Main
> Configure[F5] > Protection[F1]
and set the OVP Level.
Range:
OVP Level: OFF, 0-Rating voltage + 10%
Note
To turn OVP off, set the OVP voltage greater than the
current rating voltage + 10%.
Alarm
The OVP indicator and a message will only
appear on the screen when the input voltage is
below the UVP level. The Enter key must be
pressed to clear the alarm message.
To clear the OVP indicator, remove the cause of
the over voltage - i.e., reduce the input voltage.
Display
8.653
V
50.006
mA
0.4327
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2017
V
V
OVP Alarm
Please Press Enter
To Clear Alarm
OVP
OVP indicator
Alarm message
when OVP is
set to Load Off
ModeCVI Range
L87.5mA
V Range
L 80V
Response
Fast
Configure
PEL-3000(H) User Manual
88
UnReg
Description
The UnReg error message will appear on the
display when the electronic load is operating in an
unregulated state.
Alarm
The UnReg indicator will appear on the display
when the set load is inadequate for the source.
To clear the UnReg indicator, increase the load
or reduce the load requirements.
Display
8.653
V
50.006
mA
0.4327
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2018
V
V
UnReg
UnReg indicator
ModeCVI Range
L87.5mA
V Range
L 80V
Response
Fast
Configure
OPERATION
89
Para
Description
The Para error message will appear on the display
when the PEL-3000(H) is used in parallel and if an
error is produced.
Alarm
The Para error message indicates one of the
following possible conditions: UnReg, ROCP,
OTP.
To clear the Para indicator, remove the cause of
the alarm.
Display
8.653
V
50.006
mA
0.4327
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2018
V
V
Para
Para indicator
ModeCVI Range
L87.5mA
V Range
L 80V
Response
Fast
Configure
PEL-3000(H) User Manual
90
RVP
Description
If the RVP is tripped, the PEL-3000H Series will
turn off the load.
Alarm
The RVP error message indicates when the
terminal voltage is negative.
The Enter key must be pressed to clear the
alarm message.
Display
8.653
V
50.006
mA
0.4327
W
CV B Value80.000
CV A Value80.000
LOADRS232
A Value
Fine
01/Oct/2017
V
V
RVP Alarm
Please Press Enter
To Clear Alarm
RVP
RVP indicator
Alarm message
when RVP is
set to Load Off
ModeCVI Range
L87.5mA
V Range
L 80V
Response
Fast
Configure
OPERATION
91
PEL-3000(H) User Manual
Description
Turns the speaker sound on or off for the user
interface, such as key press tones and scrolling
tones.
Operation
1.Press
Shift
+
Utility
Help
> Other[F5].
2. Set the Speaker settings on or off.
When set to OFF, the speaker setting will not
disable the tones for Go-NoGo or protection
alarms.
System Settings
The following section covers a number or miscellaneous system
settings such as:
Speaker settings
Display settings
Alarm tone settings
Input control settings
Language settings
Input/output trigger settings
All system settings are accessible in the Utility menu.
Sound Settings
Speaker Settings
92
OPERATION
Description
The alarm tone for the unit can be turned on or off
in the utility menu. The alarm tone can be set
separately for the protection settings (OCP, OPP,
UVP, OVP), Go-NoGo testing or for when the unit
is operating in an unregulated state (see page 89).
The Knob Type setting determines if values are
updated immediately as they are edited or if they
are only updated after the Enter key is pressed.
The Updated setting is applicable for when the load
is already on and the user wishes to change the set
values (current, voltage, etc.) in realtime.
The Old setting will only update the values after
the Enter key is pressed.
Operation
1.Press
Shift
+
Utility
Help
> Other[F5].
2. Set the Knob type and Slave knob settings.
Range:
Knob type: Updated, Old
Description
The PEL-3000(H) supports only English.
Operation
1.Press
Shift
+
Utility
Help
> Other[F5].
2. Set the Language setting.
Supported languages:
English
Description
The Trig In Delay setting determines how long to
delay any action after a trigger is received.
Control Settings
Language Settings
Input/Output Trigger Settings
Trigger In Delay
94
OPERATION
Operation
1.Press
Shift
+
Utility
Help
> Other[F5].
2. Set the Trig In Delay setting.
Range:
0.01~100ms, Default: 0.01ms
Description
The Trigger Out Width setting sets the trigger
output signal’s pulse width.
Operation
1.Press
Shift
+
Utility
Help
> Other[F5].
2. Set the Trig Out Width setting.
Range:
2.5~5000.0µs, Default: 10µs
Description
The Measure Average setting is used to set the
speed of the measurement display. The setting has
three modes. They are slow, normal and fast
The default mode for Measure Average setting is
slow.
Operation
1.Press
Shift
+
Utility
Help
> Other[F5].
2. Set the Measure Average setting.
Slow
Normal
Fast
Default
Average 64 times; Display spend
time:1280ms
Average 16 times; Display spend
time:320ms
Average 4 times; Display spend
time:320ms
Slow mode
Trigger Out Width
Measure Average
95
RVP Load Off
Description
When the input terminal detects reverse voltage, a
warning message will be displayed and the RVP
Load Off setting can be set to turn on or off the
load as well. The setting has two modes. They are
ON and OFF.
The default mode for RVP Load Off setting is ON.
Operation
1.Press
Shift
+
Utility
Help
> Other[F5].
2. Set the Load Off setting.
ON
When the input terminal detects the
reverse voltage, a warning message will
be displayed on the screen and the load
will be turned off.
OFF
When the input terminal detects the
reverse voltage, a warning message will
be displayed on the screen but the load
will not be turned off.
PEL-3000(H) User Manual
96
OPERATION
Description
The Go-NoGo setting limits can be set as either
discrete high & low values or as a percentage offset
from a center value.
Operation
3. Press
Main
> Configure[F5] > Go-NoGo[F3].
4. Select Entry Mode and choose how to set the
pass/fail limits.
Value will allow you to set the limits as discrete
values.
Percent will allow you to set the limits as a
percentage offset from a center value.
5. If Entry Mode was set to Value, Set the High &
Low limit values.
High:
Low:
0-rating current/voltage
0-rating current/voltage
6. If Entry Mode was set to Percent, Set the Center
voltage/current and High, Low % values.
Center:
High:
Low:
0-rating current/voltage
0-100% of center voltage/current
0-100% of center voltage/current
Go-NoGo
The Go-NoGo configuration is used to create pass/fail limits on the
voltage or current input. If the voltage/current exceeds the
pass/fail limits, an alarm will be output.
The Go-NoGo configuration can be used with the Program function
to create complex pass/fail tests.
Setting the Go-NoGo Limits
97
PEL-3000(H) User Manual
7. Set the Delay Time.
The delay time setting will delay activating the
Go-NoGo testing by a specified amount of time.
The delay setting can compensate for startup
oscillation and other instabilities during
startup.
Delay Time
0.0-1.0 seconds (0.1s resolution )
Note
When the Main settings are saved or recalled, the GoNoGo settings are also saved/recalled. See the
Save/Recall chapter for details, page 100.
Description
Go-NoGo test results are displayed in the
measurement panel.
GO indicates pass (good).
NG indicates fail (no good).
Operation
1. Press
Main
> Configure[F5] > Go-NoGo[F3].
2. Set SPEC Test to ON.
When SPEC Test is ON, SPEC will appear in the
Operation Status Panel. This means the unit is
ready for Go-NoGo testing.
3. Turn the load on.
The test starts from the time the load was
turned on + the Delay Time.
Display:
GO
0.000
V
0.0000
A
0.00
W
Level10.00
LOADRS232
01/Oct/2018
W
SPEC test = ON
SPEC
GO
Test result
Running a Go-NoGo Test
98
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.