Instek Instek SPD-3606 Manual

DC Power Supply
SPD-3606
99 Washington Street Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com
USER MANUAL
GW INSTEK PART NO. 82PD-36060M0
ISO-9001 CERTIFIED MANUFACTURER
This manual contains
proprietary information, which is protected by copyrights. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of Good Will company.
The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the rights to change specification, equipment, and maintenance procedures at any time without notice.
Good Will Instrument Co., Ltd. No. 7-1, Jhongsing Rd., Tucheng City, Taipei County 236, Taiwan.
TABLE OF CONTENTS
SPD-3606 User Manual
FAQ ................................................................................ 56
Table of Contents
SAFETY INSTRUCTION ..................................................... 5
OVER
VIEW........................................................................ 9
SPD-3606 Main Features...................... 10
Principle of Operation.......................... 11
Front Panel Overview........................... 14
Rear Panel Overview ............................17
CV/CC Crossover Characteristics ......... 18
P............................................................................. 19
SETU
Installation Location ............................ 20
Power Up ............................................. 21
Over Voltage Protection Setup ............. 22
Load Cable Connection ........................ 24
Output On/Off..................................... 25
OPERA
TION.................................................................... 26
CH1/CH2 Independent Mode .............. 26
CH3 Independent Mode....................... 28
CH1/CH2 Tracking Series Mode........... 30
CH1/CH2 Tracking Parallel Mode ........ 36
APPENDI
IND
X ...................................................................... 57
Fuse Replacement................................ 57
Volume Guard (Optional).....................58
Specification ........................................ 59
Declaration of Conformity.................... 61
EX............................................................................. 62
REMOTE OUTPUT CONTR
PERFOR
MANCE VERIFICATION ...................................... 40
Output Voltage Verification.................. 42
Tracking Series Voltage Verification...... 45
Output Current verification.................. 47
OVP verification................................... 50
Recording Tables.................................. 54
OL.......................................... 39
3
4
SAFETY INSTRUCTION
y
SPD-3606 User Manual
Safety Guidelines
SAFETY INSTRUCTION
This chapter contains important safety instructions that you must follow when operating SPD-3606 and when keeping it in storage. Read the following before any operation to insure your safety and to keep the best condition for SPD-3606.
Safety Symbols
These safety symbols may appear in this manual or on SPD-3606.
WARNING
CAUTION
Warning: Identifies conditions or practices that could result in injury or loss of life.
Caution: Identifies conditions or practices that could result in damage to SPD-3606 or to other properties.
DANG
Attenti
ER High Voltage
on Refer to the Manual
General Guideline
CAUTION
Do not place any heavy object on SPD-3606.
Avoid severe impacts or rough handling that
leads to damaging SPD-360
Do not discharge static electricity to SPD-3606.
Do not block or obstruct the cooling fan vent
6.
opening.
Leave a space around SPD-3606, at least 3cm to
the left an
Do not perform measurement at circuits directl
d right.
connected to Mains (Note below).
Do not disassemble SPD-3606 unless you are
alified as service person
qu
(Measurement categories) EN 61010-1:2001 specifies the measurement categories and their requirements as follows. SPD­3606 falls under category I.
Measurement category IV is for measurement performed at the source of low-voltage installation.
Measurement category III is for measurement performed in the building installation.
Measurement category II is for measurement performed on the circuits directly connected to the low voltage installation.
Measurement category I is for measurements performed on circuits not directly connected to Mains.
nel.
Protecti
ve Conductor Terminal
Earth (gro
und) Terminal
Power Su
Fuse
5
6
pply
WARNING
WARNING
AC Input voltage: 115V/230V ±15%, 50/60Hz
Connect the protective grounding conductor of
the AC powe electrical shoc
Fuse type: T10A/250V
Make sure the correct type of fuse is installed
r cord to an earth ground, to avoid
k.
before power up.
SAFETY INSTRUCTION
To ensure fire protection, replace the fuse only
with the specified type and rati
Disconnect the power cord before fuse
ng.
replacement.
Make sure the cause of fuse blowout is fixed
before fuse replacement.
SPD-3606 User Manual
Power cord for the United Kingdom
When using SPD-3606 in the United Kingdom, make sure the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
Cleaning SPD­3
606
Operation Environment
Storage environment
Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of mild
detergent a
Do not use chemical or cleaner containing harsh
materi
nd water. Do not spray any liquid
al such as benzene, toluene, xylene,
.
and
acetone.
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note
Relative Humidity: < 80%
Altitude: < 2000m
Temperature: 0°C to 40°C
(Pollution Degree) EN 61010-1:2001 specifies the pollution degrees and their requirements as follows. SPD-3606 falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive pollution occurs. The pollution has no in
Pollution
Pollution degree 3: Conductive pollution occurs, or dry, non-
Location: Indoor
Relative Humidity: < 70%
Temperature: 10°C to 70°C
degree 2: Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
conductive pollution occurs which becomes conductive due to condensation which is expected. In such conditions, equipment is normally protected against exposure to direct sunlight, precipitation, and full wind pressure, but neither temperature nor humidity is controlled.
fluence.
below)
WARNING: THIS APPLIANCE MUST BE EARTHED
IMPORTANT: The wires in this lead are coloured in accordance with the following code:
Green/ Yellow: Earth
Blue: Neutral
Brown: Live (Phase)
As the colours of the wires in main leads may not correspond with the colours marking identified in your plug/appliance, proceed as follows:
The wire which is coloured Green & Yellow must be connected to the Earth terminal marked with the letter E or by the earth symbol
or
coloured Green or Green & Yellow.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment or contact the supplier.
This cable/appliance should be protected by a suitably rated and approved HBC mains fuse: refer to the rating information on the equipment and/or user instructions for details. As a guide, cable of
0.75mm
2
should be protected by a 3A or 5A fuse. Larger conductors would normally require 13A types, depending on the connection method used.
Any moulded mains connector that requires removal /replacement must be destroyed by removal of any fuse & fuse carrier and disposed of immediately, as a plug with bared wires is hazardous if a engaged in live socket. Any re-wiring must be carried out in accordance with the information detailed on this label.
7
8
OVERVIEW
SPD-3606 User Manual
SPD-3606 Main Features
OVERVIEW
This chapter describes SPD-3606 in a nutshell, including its main features and front / rear panel introduction. After going through the overview, follow the Setup chapter (page19) to properly power up and set operation environment.
For initial inspection, refer to the Performance verification chapter (page40).
60V/3A
30V/6A
Dual−Range DC Power Supply
OUTPUT CH2 CH1
O.V.P.
ON / OFF
SET C.V.
TRIP C.C.
CH1 / CH3CH2
CH2 CH1 CH3GND
0 60V , 3A 0 30V , 6A
TRACKING
INDEP. SERIES
PARALLEL
0 60V , 3A 0 30V , 6A
SLAVE MASTER
C.V.
C.C. PAR.
SPD-3606
VOLTAGEVOLTAGE CURRENTCURRENT
0.1 5V , 3A
CH1
CH3
CH3
OVER LOAD
VOLTAGE
Performance
Operation
Low noise (≤ 50dB, Cooling fan controlled by
sink temperature)
Heat
High efficiency power conversion, minimum
with full
70%
load
Fast Output On/Off response (100ms)
Low temperature coefficient
0ppm/°C+3mV, 150ppm/°C+3mA)
(10
Compact size, light weight (6kg)
Constant voltage operation
Constant current operation
Tracking Series operation
Tracking Parallel operation
Output On/Off control
3 outputs with full Voltage control
Output range selection for CH1 and CH2,
V/3A or 30V/6A
60
LED display
Main Feature SPD-3606 Main Features .................................10
Theory Principle of Operation ..................................... 11
Panel overview Front Panel Overview ......................................14
Protection
Interface
Over voltage protection (OVP)
Overload protection
Reverse polarity protection
Remote control output On/Off terminal
Rear Panel Overview........................................ 17
CV/CC CV/CC Crossover Characteristics.....................18
9
10
OVERVIEW
y
SPD-3606 User Manual
Principle of Operation
Block diagram
Power Supply
EMI Filter
Rectifier/
Doubler
PCB A
Power supply converts the AC mains into DC Power source for internal units. Channel 1/2/3 control and produce the actual DC output. Displa shows output and OVP level, receiving feedback from each channel. Internal components are placed on four printed circuit boards, A ~ D.
Detailed description of each module starts on the next page.
PCB B PCB C
CH2
Power
Stage
AUX
Power
CH1
AUX
Power
Power
Stage
CH3
Power
Stage
Output
Controller
Tracking
Controller
Controller
Output
Controller
Output
PCB D
Display
EMI Filter
Other than deleting conduction EMI
(electro­magnetic interference), the EMI unit contains protective circuits such as Inrush current limit resistor and Surge absorber. Internal units are protected under power-up sequence, normal
Rectifier / Doubler
operation, and AC mains fluctuation.
The Rect
ifier unit converts AC mains into DC Power source. For 115V±15% AC, double-wave rectification is used; for 230V±15% AC, full-wave rectification. An internal selector automatically switches the rectification circuit accordingly. The final DC Voltage reaches 240V ~ 370V.
CH1/2 Power Stage
The Power
stage for Channel1 and 2 produce the outputs using the combination of Half-bridge converter and Linear regulator. The Half-bridge converter adopts PWM (pulse-width modulation) with high frequency switching. The Linear regulator adjusts the output Voltage down to 0V.
CH1/2 AUX Power
The AUX
Power for Channel 1 and 2 produces the power source for auxiliary devices, such as analog/digital controller, relay, LED display, and cooling fan. Altogether four pairs of power source are generated for different purpose: ±12V, +5V, and +12V.
CH3 Power Stage
The Power
stage for Channel 3 produces both the channel output and the power source for auxiliary devices. It uses the combination of Flyback converter and Linear regulator, carrying lower efficiency compared to Channel 1 and 2. The flyback converter also produces ±12V for ICs and 4~8V settable Voltage.
11
12
OVERVIEW
O.V.P
OUTPUT
SPD-3606 User Manual
CH1/2/3 Controller
Feedback control unit
OVP setting unit
Fan control unit
Tr ac k in g Controller
The C
ontroller for Channel 1, 2, and 3 takes care of the interface between SPD-3606 and users. Several sub-units comprise the Controller, including:
Feedback control unit
OVP setting unit
Fan control unit
ailed description of each unit follows.
Det
The Feedback control unit receives the control signal for Voltage/Current output level and the level feedback signal from the actual output. The difference between the two signals are amplified and used as the control signal for the Power stage to achieve stable output level.
The SVR (small variable resistor) sets the protection point so that the OVP setting unit shuts down the output when the output Voltage level exceeds the configured level.
Using NTC (negative temperature coefficient) resistor, the Fan control unit changes the control Voltage for the cooling fan according to the temperature change, achieving low-noise and linear speed control.
The Tracking
controller controls Channel 2 output level when in tracking series or parallel mode. In tracking series mode, Channel2 output Voltage is controlled by Channel1 output Voltage level. In tracking parallel mode, Channel2 output Current is controlled by Channel1 output Current level.
Front Panel Overview
Tracking Mode
Switches
CH2 CH1 CH3GND
0 60V , 3A 0 30V , 6A
Ground
TRACKING
SLAVE MASTER
C.V.
C.C. PAR.
CH2
Te rm i na l
CH2 Output
Terminal
.
SET
TRIP
Switch
60V/3A
30V/6A
Dual−Range DC Power Supply
Output Key
OVP
OUTPUT CH2 CH1
ON / OFF
Indicator
Power Switch
CH2 Output
Knob
Power switch
OVP indicator
Output Key
CH2 MeterOutput Range
O.V.P.
SET C.V.
TRIP C.C.
Indicator
CH1/3 Meter
CH1/CH3 Meter Switch
CH1
CH1 / CH3CH2
CH3
SPD-3606
CH3 Overload
CH3
INDEP. SERIES
PARALLEL
VOLTAGEVOLTAGE CURRENTCURRENT
OVER LOAD
VOLTAGE
Indicator
CH3 Voltage Knob
0 60V , 3A 0 30V , 6A
CH1
0.1 5V , 3A
CH3 Output Terminal
Indicator
CH1 Output
Te rm i nal
Turns On
CH1 Output
Knob
or Off the main power.
For power up sequence, see page20.
Turns green durin
g the OVP setup. Turns red (tripped) when the output Voltage exceeds the setting. For OVP details, see page22.
Turns the o
utput On (green) or Off
(gray), all three channels at once.
LED Display
The LED d
isplay shows the Channel 1/2/3 output
ON / OFF
Voltage/Current level. The A/D converter changes the analog signal coming from each channel into digital format to be displayed.
13
Output range switch
14
60V/3A
30V/6A
ects the output range, 60V/3A or
Sel 30V/6A.
OVERVIEW
TRA
CKIN
g
OVE
L
OAD
SPD-3606 User Manual
CH2 meter
T
racking mode
switches
CH1/3 meter + switch
Displays Channel2 current (A) and voltage (V).
CH2
G
Acti
vates and selects the tracking
mode. For trackin
INDEP.
SERIES
PARALLEL
Independent
I
K
C
A
R
T
P
E
D
N
I
S
E
I
R
E
S
L
L
A
R
A
P
page30 (Series) and page36 (Parallel).
acking Serie s
Tr
G
N
.
L
E
TR
A
N
I
E
S
ARA
P
Displays Channel1 or Ch
G
N
I
K
C
.
P
E
D
S
E
RI
L
E
L
L
annel3 current (A) and
mode details, see
racking Parallel
T
G
N
I
K
C
A
R
T
.
EP
D
N
I
ES
I
R
E
S
L
E
L
L
A
R
PA
voltage (V). The switch on the right selects the channel, 1 (up) or 3 (down).
Channel1 CV/CC indicator
Channel2 CV/CC/PAR indicator
C.V.
C.C.
C.V.
C.C. PAR.
Turns green when operating in Constant Voltage (CV) mode, red in Constant Current (CC) mode. For CV/CC characteristics, see page18.
Independent mode: Turns green in Constant Voltage (CV) mode, red in Constant Current (CC) mode.
Tracking parallel mode (page36): When operating in the Tracking Parallel mode, the Channel2 indicator always stays red (PAR). Channel1 indicator shows the CV/CC status.
CH1
Channe
l3
overload indicator
R
CH1 / CH 3
Turns red wh
en Channel3 output
exceeds the current rating, 3A.
CH3
Channel3 switches from Constant Voltage (CV) mode to Constant Current (CC) mode.
Channel1/2/3 output terminal
CH3
0.1 5V , 3A
Accepts the load cables. For cable connection details, see page24.
15
16
OVERVIEW
g
C
g
SPD-3606 User Manual
Rear Panel Overview
Remote Control Terminal
OFF
ON
SER. NO. LB
Remote control terminal
OVP setting point
Power cord / fuse socket
OVP Settin Point
O.V.P. SETNORMAL
CH3CH2CH1
O.V .P. SETNORMAL
CH3CH2CH1
Cooling Fan
Power Cord / Fuse Socket
WARNING
DISCONNECT POWER CORD
BEFORE REPLACING FUSE
REPLACE FUSE
AS SPECIFIED
FUSE RATING
115V
T10A 250V
230V
550 WATTS 900 VA MAX 50/60 H z
Accepts remote output On/Of
AC
f control connection. For details, see page39.
Activates Over Voltage Protection (OVP) and sets the protection threshold for channel1/2/3. For OVP setup details, see page22.
The power co
rd socket accepts the AC mains: 115V/230V, 50/60Hz. For power up details, see page20.
CV/CC Crossover Characteristics
Background
Diagram
SPD-3606 automatically switches voltage mode (CV) and constant current mode (CC), according to load condition.
When the current level is smaller than the output setting, SPD-3606 operates in Constant Voltage mode. The indicator on the front panel turns green (C.V.) The Voltage level is kept at the setting and the Current level fluctuates according to the load condition until it reaches the output current setting.
When the curre
nt level reaches the
output setting, SPD-3606 starts
operating in Constant Current mode. The indicator on the front panel turns red (C.C.) The Current level is kept at the setting but the Voltage level becomes lower than the settin to suppress the output power level from overload. When the current level becomes lower than the setting, SPD­3606 goes back to the Constant Voltage mode.
Vout
Vmax
Constant
Voltage
between constant
C.V.
.C.
C.V.
C.C.
, in order
The fuse holder contains the AC
Constant
Current
main fuse. For fuse replacement details, see page57.
17
18
Imax
Iout
SETUP
O
SPD-3606 User Manual
Installation Location
SETUP
This chapter describes how to properly power up and configure SPD-3606 before the operation. For checking the functionality, refer to the Performance verification chapter, page40.
O.V.P. SETNORMAL
CH3CH2CH1
D
2 G
H
C
A
3
,
V
0
6
A
6
,
0
V
0
3
0
N
UTPUT
ON / OFF
Ventillation space
ooling fan
C opening
Leave at least 3cm around SPD-3606, to the left and right.
The cooling fan is located on the rear panel. Allocate extra space on the back of SPD-3606 so that the cooling fan opening would not become blocked.
Cooling
Fan
Installation Installation Location........................................20
Power Power Up ........................................................21
OVP Over Voltage Protection Set.............................22
Load Wire Load Cable Connection....................................24
Output Output On/Off ................................................25
19
20
SETUP
O
SPD-3606 User Manual
Power Up
Power On
Press the Power switch to turn On the power. The CH1/CH2 indicators and meters turn On.
CH1
VOLTAGECURRENT
MASTER
C.V.
C.C.
CH1
VOLTAGECURRENT
MASTER
C.V.
C.C.
CH2
CH2
SLAV E
CH2
SLAV E
C.V.
C.C. PAR.
C.V.
C.C. PAR.
VOLTAGECURRENT
VOLTAGECURRENT
CH1 / CH3
Over Voltage Protection Setup
Background
OVP setup
Over Voltage Protection (OVP) protects SPD and DUT from excessive output Voltage. The user sets the maximum output voltage limit before operation. When the output voltage exceeds this limit, the indicator shows the over voltage status and the output is shut off immediately.
1. Slide the rear panel swit to the “
O.V.P. SET”
position.
2. The OV f
ront panel
ndicating OVP
i
3. The Vo inst show zero
P indica
tor on the
turns green,
setup.
ltage meters show the OVP setting leve
ead of the output level. The Current mete
(0.00)
.
ch
O.V.P. SETNORMAL
CH3CH2CH1
.V.P.
SET
TRIP
l
rs
CH2
Power Off
Press the Po
wer switch again to turn Off the power. After two seconds, the meters and indicators turn Off.
CH1 / CH3
21
22
CH1 / CH3 CH1 / CH3
4. Adjust the g the rear panel
usin terminal. The setti the f
ront panel
change
Channel2
Setting range
s acco
level
OVP
DECREASE
ng on
meter
rdingly.
Channel1
1.0V ~ 67.0V
1.0V ~ 67.0V
Channe
l3
0.1V ~ 6.0V
CH1
INCREASE
SETUP
O
g
O
SPD-3606 User Manual
When OVP is
activated....
*
When setting the OVP for channel3, select CH3 meter using the CH1/CH3 meter switch.
5. When finished, slide the
rear panel switch to the “Normal” position. The OVP indicator on the front panel turns Off.
The OVP activates when one of channel1/2/3 output voltage exceeds the OVP settin
. The indicator turns red (tripped), and the output is shut Off immediately.
O.V.P.
O.V.P.
SET
TRIP
OUTPUT
ON / OFF
SET
TRIP
CH1
CH3
Load Cable Connection
D
N
Standard accessory (GTL-104)
O. V.P. SETNORMAL
CH3CH2CH1
1. Turn the terminal
counterclockwise and loose the screw.
2. Insert the cable
terminal.
H
C
1
0
6
0
0
3
0
2
.V.P.
SET
TRIP
.V.P.
SET
TRIP
OUTPUT
ON / OFF
3. Turn the terminal
clockwise and tighten the screw.
Banana plug
Insert the plug into the socket.
Wire type
When using load cables other than the attached, make sure they have enough current capacity for
2
H
C
3
A
3
,
V
0
6
A
6
,
0
V
0
3
0
2
H
C
A
3
,
V
0
6
A
6
0
,
V
0
3
0
minimizing cable loss and load line impedance. Voltage drop across a wire should not excess 0.5V. The following list is the wire current rating at 450A/cm
2
.
G
2
A
3
,
V
A
6
,
V
D
N
G
D
N
G
Wire size (AWG) Maximum current (A)
20 2.5
18 4
16 6
14 10
12 16
23
24
Output On/Off
P
U
P
U
TRA
CKIN
RALLE
L
O.V
OUT
PUT
Panel operation
atic Output
Autom Off
Pressing the Output key once Turns On the output, all channels 1/2/3 at once.
Pressi output.
Any of the following actions during output On automatically turns it Off. They might involve sudden and harmful change in the output level.
Change the
Cha
nge the tracking SW between independent / series / parallel
OVP tripped
ng again turns Off the
range
OUT
ON / OFF
OUTPUT
ON / OFF
60V/3A
30V/6A
INDEP.
SERIES
PA
O.V.P.
SET
TRIP
SETUP
OUT
ON / OFF
OUTPUT
T
OPERATION
T
SPD-3606 User Manual
CH1/CH2 Independent Mode
ON / OFF
Background / Connection
G
.P.
SET
TRIP
Channel1 and Channel2 outputs work of each other and are separately controlled.
CH2
CH2
LOAD
CH1
CH1
LOAD
independent
O.V.P. SETNORMAL
CH3CH2CH1
Output ra
Setting step
ting
0 ~ 30V/0~6A or 0~60V/0~3A for each channel
1. Select the output rang V/3A or 30V/6A. Set the
60 CH1/CH3 me the CH1
positi
ter switch to
on.
e,
60V/3A
30V/6A
CH1
CH3
ote control
Rem
OVP SET
mode
When in remote control mode (page39), front panel output control is disabled.
Red CV/CC indicator when
CV/CC red
without output
output Off indicates internal error. Contact the service center.
C.V.
C.C.
+
ON / OFF
25
26
2. Set the tra
y
O
O
UTP
U
O
UTP
U
posi
tion to INDEP,
cking swit
ch
+ .
OPERATION
G
N
I
K
C
A
R
T
SPD-3606 User Manual
CH3 Independent Mode
P.
E
D
N
I
S
E
I
R
E
S
L
E
L
L
RA
A
P
3. Set the OVP details, see page
if necessar
22.
. For
.V.P.
SET
TRIP
4. Connect the load to the front panel terminal channel1 +/, chann
2
CH
A
3
,
V
0
6
A
6
,
0
V
0
3
0
5. Set the output V
oltage an Current using the control knobs fo
r each
channel.
el2 +/
D
N
.
1G
CH
A
3
,
V
0
6
A
6
,
0
V
0
3
0
CH1
d
MASTER
CH2
SLAVE
C.V.
C.C.
Background / Connection
Channel3 rating is 0.1 ~ 5V, maximum 3A. It works independently from Channel1 and 2, regardless of their modes.
s,
CH3
CH3
LOAD
Output ra
No Tracking
VOLTAGECURRENT
Series/Parallel
ting
0.1 ~ 5V, 3A maximum
Channel3 does not have Tracking Series/Parallel mode. Also, Channel3 output is not affected by Channel1 and 2 modes: independent/series/parallel.
Setting step
VOLTAGECURRENT
1. Set the CH1/CH3 tch to the CH3 positi
swi
meter
on.
CH1
C.V.
C.C. PAR.
ON / OFF
T
27
28
6. Press the Out Output i
ndica
ut key. The
p
tor turns
green.
T
ON / OFF
CH3
OPERATION
y
O
E
ge
D
g
SPD-3606 User Manual
CV CC
2. Set the OVP details, see page
if necessar
22.
. For
3. Connect the load to the fr panel channel3 terminal
.
4. Set the output V
he Channel3 Voltag
t
+/
oltage
using
e
control knob.
5. Press the Output key. The Output i
ndica
tor turns
green.
When the o
utput Current level exceeds 3A, the overload indicator turns red and Channel3 operation mode switches from Constant Volta to Constant Current.
ont
1
.
0
OUTPUT
ON / OFF
CH3
OVER LOAD
.V.P.
SET
TRIP
3
H
C
A
3
,
V
5
VOLTAG
OUTPUT
ON / OFF
CH3
OVER LOA
CH1/CH2 Tracking Series Mode
Background
Tracking series without common terminal
Connection
Tracking series operation doubles the Voltage capacity of SPD-3606 by internally connecting Channel1 (Master) and Channel2 (Slave) in serial and combining the output to a single channel. Channel1 (Master) controls the combined Voltage output level.
The followin
describes two types of configuration
depending on the common ground usage.
CH2
CH1
Note: “overload” in this case
LOAD
does not mean abnormal operation.
Output ra
Setting step
29
30
ting
0 ~ 120V/0 ~ 3A or 0 ~ 60V/0 ~ 6A
1. Select the output rang 6
0V(120V)/ 0V(60V)/6
3 CH1
/CH3 me
the CH1
3A or A. Set the
positi
ter switch to
on.
e,
60V/3A
30V/6A
CH1
CH3
2. Set the tra
M
OUT
PUT
OUT
PUT
posi
tion to Series,
cking swit
ch
+ .
OPERATION
G
N
I
K
C
A
TR
.
P
DE
N
I
S
E
RI
E
S
L
E
L
L
A
PAR
SPD-3606 User Manual
7. Refer to the Channel1 (Master) meter an i
ndicator for the output setting level an
CV/CC status.
CH1
ASTER
d
d
3. Set the OVP cking seri
tra
if necessar
es mode, set the Channel2 (Slave) the ma OVP t
ximum level, so that
rips if the Channel1 (Master) setting is violat OVP setup
details, see page
y. In
OVP setting
the
ed. For
22.
to
O.V.P.
SET
TRIP
4. Connect the load to the front panel terminal
channel1+ & channel2 (Single supply).
1
H
C
D
N
G
2
H
C
A
3
,
V
0
6
A
6
,
0
V
0
3
0
5. Turn up C
urrent knob to maximum.
the
Channel2
A
3
,
V
0
6
A
6
,
0
V
0
3
0
CURRENT
SLAV E
CH2
CH1 / CH3
Current level
Channel1 meter reading shows the output Current. (Channel2
C.V.
C.C.
Current control must be in the Maximum position).
Voltage level
s,
Double the reading on the Channel1 Voltage meter. (In the above case, the actual output is
23.6 x 2 = 47.2V).
8. Press the Outp Output i green.
ndica
ut key. The
tor turns
ON / OFF
ON / OFF
CH1
VOLTAGECURRENT
6. Set the output V
oltage an
d
Current using the Channel1
aster) knob
(M
.
MASTER
C.V.
C.C.
31
32
OPERATION
SPD-3606 User Manual
Tracking series with common terminal
Connection
CH2
LOAD
Output ra
Setting step
ting
0~60V/0~3A or 0~30V/0~6A for CH1 ~ COM
0~–60V/0~3A or 0~–30V/0~6A for CH2 ~ COM
1. Select the output rang 0V(120V)/
6 3
0V(60V)/6
/CH3 me
CH1 the CH1
3A or A. Set the
positi
ter switch to
on.
COM
e,
CH1
60V/3A
30V/6A
CH1
CH3
3. Set the OVP if necessar cking seri
tra Channel2 (Slave) the ma OVP t
es mode, set the
OVP setting
ximum level, so that
rips if the Channel1 (Master) setting is violat OVP setup
details, see page
y. In
to
the
ed. For
22.
O.V.P.
SET
TRIP
4. Connect the load to the front panel terminal
channel1+ & channel2. Us terminal
5. Set the output V the Cha Volt Cha
he output setting leve
t
as the common line
2
CH
A
3
,
V
0
6
A
6
,
0
V
0
3
0
oltage
nnel1 (Mas
ter)
age knob. Refer to th
nnel1 (Master)
D
N
meter for
e Channel1 (
connection.
0 0
using
e
l.
1G
CH
A
3
,
V
0
6
A
6
,
V
0
3
Common
CH1
MASTER
C.V.
C.C.
)
s,
VOLTAGECURRENT
2. Set the tra tion to Series,
posi
cking swit
ch
+ .
R
T
PARA
G
N
I
K
C
A
.
EP
D
N
I
S
E
I
ER
S
L
E
L
L
CH1(+)~COM Voltage = 23.6V in the above case
CH1 / CH3
CH2(–)~COM Voltage = –23.6V in the above case
33
34
6. Set the output Current
OUT
PUT
OUT
PUT
C
S
sepa
rately, usin
hannel1 (Master)
C Channel
2 (Slave) Current
g both the
and
knob.
OPERATION
CH1
VOLTAGECURRENT
MASTER
C.V.
C.C.
CH2
VOLTAGECURRENT
SLAVE
C.V.
C.C. PAR.
SPD-3606 User Manual
CH1/CH2 Tracking Parallel Mode
Background / Connection
Tracking parallel operation doubles the Current capacity of SPD-3606 by internally connecting Channel1 (Master) and Channel2 (Slave) in parallel and combining the output to a single channel. Channel1 (Master) controls the combined output.
CH2
CH1 / CH3
CH1(+)~COM Current = 1.84A in the above case
CH2(–)~COM Current = 2.18A in the above case
ndica
ut key. The
tor turns
r
ON / OFF
CH1
MASTER
7. Press the Outp
Output i green.
8. Refer to the Channel1
(Master) indicator fo CH1(+) ~ COM CV/CC st
atus, and the Channel2
(Slave) indicator
(–) ~ CO
CH2 status.
for
M CV/CC
C.V.
.C.
ON / OFF
CH2 LAVE
C.V.
C.C. PAR.
Output ra
ting
Setting step
CH2
CH1
LOAD
0 ~ 30V/0 ~ 12A or 0 ~ 60V/0 ~ 6A
1. Select the output rang V/3A(6
60 30
V/6A(12A). Set th
CH1 the CH1
2. Set the tra
posi
A) or
/CH3 me
positi
ter switch to
on.
cking swit
tion to Parallel,
e,
e
ch
+ .
60V/3A
30V/6A
CH1
CH3
G
N
I
K
C
A
R
T
.
P
E
D
N
I
S
E
I
R
E
S
L
E
L
L
A
R
A
P
35
36
OPERATION
OUT
PUT
OUT
PUT
M
SPD-3606 User Manual
3. Set the OVP if necessary. In
tracking parallel mode, set the Channel2 (Slave) OVP setting to the maximum level, so that the OVP trips if the Channel1 (Master) setting is violated. For OVP setup details, see page22.
4. Connect the load to the front panel terminals,
channel1 +/−.
2
H
C
A
3
,
V
0
6
A
6
,
0
V
0
3
0
5. The Channel2 (Slave)
indicator turns red, indicating Tracking Parallel (PAR). The CV/CC status of tracking parallel mode is displayed in the Channel1 (Master) indicator.
O.V.P.
SET
TRIP
7. Refer to the Channel1 meter for the output
setting level.
CH1 / CH3
Current level
Double the reading on the Channel1 meter. In the above case, the actual output is 1.84 x 2 = 3.68A.
1
H
C
D
N
G
A
3
,
V
0
6
A
6
,
0
V
0
3
0
Voltage level
Channel1 meter reading shows the actual output Voltage.
8. Press the Output key. The
Output indicator turns
CH1
ASTER
C.V.
C.C.
ON / OFF
C.V.
C.C. PAR.
C.V.
C.C. PAR.
green.
9. Refer to the Channel1
(Master) indicator for the
ON / OFF
CV/CC status.
CH1
VOLTAGECURRENT
6. Set the output Voltage and
Current using the Channel1 (Master) control knobs. Channel2 control knobs are
MASTER
C.V.
C.C.
disabled.
37
38
REMOTE OUTPUT CONTROL
SPD-3606 User Manual
REMOTE OUTPUT
CONTROL
Background
Wire connecti
Remote control Off (front panel control)
The remote c rear panel can turn the output On/Off, just like the Output key on the front panel. This feature is useful for automated measurement and testing using externally connected control device, such as in production line or incoming quality inspection.
on
Connect the terminals using bare wires. Use a minus driver to push the orange part, insert the wire, then release the orange part.
When there is no connection, Output On/Off is entirely controlled from the front panel.
ontrol terminal on the
OUTPUT
2
ON / OFF
3
PERFORMANCE
VERIFICA
Overview
Background
Verification item
1
Equipment
Digital Multimeter
TION
Performance verification checks SPD functionality before the operation or at the incoming inspection. Recording tables are attached at the end of this chapter.
Output Voltage
Tracking Series Voltage
Output Current
OVP
DCV Accuracy < 0.1%
DCA Accuracy < 0.5%
Output always Off
Output always On
When the left two terminals are connected, the Output is always Off. The front panel Output key is disabled.
When the right two terminals are connected, the Output is always On. The front panel Output key is disabled.
39
Multimeter
PD ca
– S
Philips screw driver
40
ble
DCA range: 12A
Resolution 4 ½ digit
Recommended model: GDM-8245, GDM-8246
Voltage rating > 70V
Current rating > 12A
< 3mm (for OVP adjustment)
PERFORMANCE VERIFICATION
OLT
A
CURRENT
CURRENT
SPD-3606 User Manual
Default SPD-3606 setting
The following is the required front and rear panel setting before running each verification.
Range
OVP setting SW
Channe
l1/3 meter
SW
60V/3A
60V/3A
30V/6A
Output Voltage
Tracking Series
OVP
Normal pos
ition
CH1 position
30
V/6A
Output Current
Tracking Parallel
60V/3A
30V/6A
O.V.P. SETNORMAL
CH1
Output Voltage Verification
Check item
Connection
CH3CH2CH1
Verification step
Minimum output Voltage accuracy
Maximum output Voltage accuracy
Voltage meter accuracy (Output On)
Voltage meter accuracy (Output Off)
SPD-3606
Digital Multimeter
V
A
1. Set the SPD panel according to the Default
setting list, page41.
CH1
0 60V , 3A 0 30V , 6A
acking SW
Tr
Channe
l1/2/3
Voltage knob
Channe
l1/2
Independent position,
Minimum position
Minimum position
+ .
CH3
2. Connect SPD Digit
G
N
I
K
C
A
R
T
.
P
E
D
N
I
S
E
I
SER
L
E
L
L
A
PAR
V
GE
3. Power up SPD and Digital Multimeter.
4. Turn up the SPD Current knob to
al Multimeter Voltag
nal
termi
the ma
ximu
Channel 1 an
.
m.
d
e
Current knob
41
42
PERFORMANCE VERIFICATION
UTPUT
UTPUT
VOLTA
g
0
6
A
A
SPD-3606 User Manual
5. Turn On the SPD output.
Minimum output Vol tag e
6. Record the Multimeter reading as the Minimum output Voltage. Here is the acceptance range.
Channel1/2
Channel3
7. Turn up the ma Mult
the SPD Voltage kn
m. Switch the
ximu
imeter Voltage terminal if
necessary.
Maximum output Vol tag e
8. Record the Multimeter readin output Voltage. Here is the acceptance range.
Channel1/2
Channel3
Vol tage meter accuracy
9. Compare and record the difference betw
Voltage meter and the Multimeter read
SPD as t
he Voltage meter accuracy (Out On).
Then turn the output Off, and check the SPD reading again (Out Off).
O
< 0V
< 100mV
61.5V ~ 62.5V
5.20V ~ 5.30V
OUTPUT
O
ON / OFF
ON / OFF
ob to
as the Maximum
een the
OUTPUT
ON / OFF
GE
ing
ON / OFF
Example:
Multimeter (Out On) = 30.00V
Tolerance = ±(0.005*30 + 0.2) ±0.4V
Accepted SPD reading(Out On)= 29.6V~30.4V
Accepted SPD reading (Out Off)=29.6V~30.4V
Channel2
10. Connect the Multimeter to
SPD Channel2 and repeat step 4 to 9.
Channe
l3
11. Switch the CH1/CH
meter swi positi Mult
tch to CH3
on. Connect the
imeter to Channel3
and repeat step 5 to
*
Skip step 4 since Channel 3 does not ha Current knob.
CH2
0 60V , 3A
30V,
3
CH1
CH3
CH3
0.1 5V , 3
9.
ve
Here is the acceptance range and example.
Channel1/2/3
difference < ±(0.5% of reading + 2 digits) of Multimeter
43
44
PERFORMANCE VERIFICATION
CURRENT
UTPUT
UTPUT
VOLTA
0
A
VOLTA
0
A
SPD-3606 User Manual
Tracking Series Voltage Verification
Check item
C
onnection
Verification step
Minimum output Voltage accuracy
Maximum output Voltage accuracy
SPD-3606
Digital Multimeter
V
A
1. Set the SPD panel according to the Default setting
list, page41, except for the tracking switch (see below).
2. Set the tracking switch position to Series,
3. Connect SPD Digit termi
+ .
Channel 1 an
al Multimeter Voltag
.
nal
d
e
4. Power up SPD and Digital Multimeter.
NG
CKI
RA
T
.
P
E
D
N
I
S
E
I
R
E
S
L
E
L
L
ARA
P
CH1
0 60V , 3A 0 30V , 6A
Minimum tracking series output voltage
Maximum tracking series output voltage
5. Turn up the SPD Curr knob, both Channel
ent
1 and
Channel2, to the maximum.
6. Turn On the SPD output.
7. Turn up Volt Mult
the SPD Channel1
age knob until th
e
imeter reading shows
1.000V.
8. Connect the Multimeter to SPD Channel2 the
reading. Here is the
acceptance
Channel2
and record
range.
0.985V ~ 1.015V
9. Connect Digital Multimeter back
to SPD Channel1.
. Turn up
10
Volt Mult
60.00V
the SPD Channel1
age knob until th
e
imeter reading shows
.
11. Connect the Multimeter to SPD Channel2 the
reading. Here is the
acceptance
Channel2
and record
range.
59.69V ~ 60.31V
O
ON / OFF
GE
CH2
0 60V , 3A
30V, 6
CH1
0 60V , 3A 0 30V , 6A
GE
CH2
0 60V , 3A
30V, 6
O
ON / OFF
(1.000V)
(60.00V)
45
46
PERFORMANCE VERIFICATION
V
OLT
OUTPU
T
OUTPU
T
g
RRENT
g
0
A
SPD-3606 User Manual
Output Current verification
Check item
C
onnection
Verification step
Minimum output Current accuracy
Maximum output Current accuracy
Current meter accuracy (Output On)
Current meter accuracy (Output Off)
Digital Multimeter
1. Set the SPD panel according to the Default
setting list, page41.
2. Connect SPD Digit
al Multimeter Current
terminal
Channel 1 an
.
3. Power up SPD and Digital Multimeter.
4. Turn up the ma
the SPD Voltage kn
m.
ximu
SPD-3606
V
A
d
ob to
CH1
0 60V , 3A 0 30V , 6A
AGE
Minimum output Current
6. Record the Multimeter readin output Current. Here is the acceptance range.
Channel1/2
7. Turn up the SPD Current knob to
Maximum output Current
the ma
imeter Current terminal to
Mult high cu
8. Record the Multimeter readin output Current. Here is the acceptance range.
Channel1/2
m. Switch the
ximu
rrent range.
Channel3
Current meter accuracy
9. Compare and record the difference betw
urrent meter and the Multimeter read
SPD C as the
Current meter accuracy (Out On
Then turn the output Off, and check the SPD reading again (Out Off).
is the acceptance range and example.
Here
Channel1/2/3
Example:
Multimeter (Out On) = 3.000A
Tolerance = ±(0.005*3 + 0.02) ±0.04A
Accepted SPD reading(Out On)= 2.96A~3.04A
Accepted SPD reading (Out Off)= 2.96A~3.04A
as the Minimum
< 0A
CU
as the Maximum
6.15A ~ 6.25A
3.05A ~ 3.15A
een the
ing
).
OUTPUT
ON / OFF
OUTPUT
ON / OFF
difference < ±(0.5% of reading + 2 digits) of Multimeter
CH2
5. Turn On the
SPD output.
10. Connect the Multimeter to SPD Channel2 and repeat step 4 to 9.
0 60V , 3A
ON / OFF
ON / OFF
47
48
30V, 6
PERFORMANCE VERIFICATION
O.V
SPD-3606 User Manual
. Connect the Mult
11
t
o SPD Channel3 an
eat step 4, 5, 8, 9.
rep
Skip step 6 and 7 since Channel 3 does no
*
imeter
minimum current verific
CH1
d
CH3
ation and Current knob.
CH3
0.1 5V, 3A
t have
OVP verification
Check item
C
onnection
Verification step
OVP setting accuracy (Minimum)
OVP functionality (Minimum)
OVP setting accuracy (Maximum)
OVP functionality (Maximum)
1. Set the SPD panel according to the Default
setting list, page41.
2. Power up SPD.
3. Set the OVP setti the “O.
SPD-3606
(No connection)
ng switch
V.P. SET” position.
to
O.V.P. SETNORMAL
CH3CH2CH1
.P.
SET
TRIP
CH1
ng
O.V.P.
SET
TRIP
DECREASE
4. The O.V.P. i f
ront panel
5. Turn down t termi
nal to minimum.
49
50
tor on the
ndica
turns green.
he OVP setti
PERFORMANCE VERIFICATION
j
g
U
TPU
T
U
TPU
T
VOL
T
O.V.P
O.V
j
g
SPD-3606 User Manual
Minimum OVP
g
settin
6. Record the SPD Voltage meter readin nimum OVP setting accuracy. Here is
Mi acceptance range.
Channel1/2
Channel3
ust the OVP settin
7. Ad
terminal until the SPD meter shows
ollowing value.
f
Channel1/2
Channel3
8. Set the OVP setti
the “
Normal” positi
P indica
OV panel t
urns
9. Turn On the
10
. Slowly
turn up the SPD Voltage knob unt
il the OVP
indica
tor turns red
1.0V
0.50V
DECREASE
the exac
t
1.0V
0.50V
ng switch
on. The tor on the front Off.
SPD output.
to
AGE
CH1
O
ON / OFF
O.V.P.
SET
TRIP
(tripped).
g as the
the
INCREASE
O.V.P. SETNORMAL
CH3CH2CH1
O
ON / OFF
SET
TRIP
OUTPUT
ON / OFF
O.V.P. SETNORMAL
CH3CH2CH1
.P.
SET
TRIP
INCREASE
g as the
the
Maximum OVP
g
settin
ng
OUTPUT
ON / OFF
to
O.V.P.
SET
TRIP
CH1
12. Turn Off the SPD output.
13
. Set the OVP setting switch
the “O.
14
. The O.V.P. indica
f
15
. Turn up the OVP setti
V.P. SET” position.
ront panel
turns green.
tor on the
terminal to maximum.
16. Record the SPD Voltage meter readin
Ma
ximum OVP setting accuracy. Here is
acceptance range.
Channel1/2
Channel3
ust the OVP settin
. Ad
17
.
terminal until the SPD meter shows
ollowing value.
f
Channel1/2
Channel3
65.0 ~ 68.0V
6.00 ~ 7.00V
the exac
t
60.0V
5.0V
DECREASE
CH1
INCREASE
Minimum OVP functionality
11
. Record the SPD Voltage meter readin
Minim
um range OVP functionality.
acceptance range.
Channel1/2
Channel3
0.5V ~ 1.5V
0.00V ~ 1.00V
g as the
Here is the
51
52
. Set the OVP setting switch
18
the “
Normal” positi
P indica
OV panel t
urns
tor on the front
Off.
on. The
to
O.V.P. SETNORMAL
CH3CH2CH1
PERFORMANCE VERIFICATION
P
U
P
U
VOL
T
O.V.P
. Turn On the SPD output.
19
OUT
SPD-3606 User Manual
OUT
T
T
Recording Tables
Maximum OVP functionality
ON / OFF
20
. Slowly
turn up the
AGE
SPD Voltage knob
il the OVP
unt indica
tor turns red
(tripped).
21
. Record the SPD Voltage meter readin
Ma
ximum range OVP functionality.
acceptance range.
Channel1/2
Channel3
. Turn Off the SPD output.
22
. Repeat step 3 to 22 for
23
24
. Repeat step 3 to 22 for
59.2V ~ 60.8V
4.47V ~ 5.53V
OUTPUT
ON / OFF
Channel2.
Channel3.
O.V.P.
SET
TRIP
ON / OFF
.
SET
TRIP
g as the
Here is the
OUTPUT
ON / OFF
Output voltage verification (Minimum/Maximum)
Item Channel Min. limit Result Max. limit
Minimum Output Voltage
CH1 –3 CH2 –30mV 0mV
0mV 0mV
CH3 0mV 100mV CH1 61.5V 62.5V Maximum
Output Voltage
CH2 61.5V 62.5V CH3 5.2V 5.3V
Output voltage verification (Meter accuracy)
Tolerance = ± (0.5%*Multimeter +0.2) V
Channel Multimeter Tolerance SPD (On)
Channel1
~
SPD (Off)
Channel2 ~ Channel3 ~
Tracking series voltage verification
Item Channel Min. limit Result Max. limit
acking Serie s
Tr
CH2 0.985V 1.015V Minimum Tracking Seri e s
CH2 59.69V 60.31V Maximum
53
54
PERFORMANCE VERIFICATION
Output current verification (Minimum/Maximum)
Item Channel Min. limit Result Max. limit
SPD-3606 User Manual
Minimum Output Current
Output Current
CH1 –1m CH2 –1mA 0mA CH1 6.15A 6.25A Maximum CH2 6.15A 6.25A CH3 3.05A 3.15A
A 0mA
Output current verification (Meter accuracy)
Tolerance = ± (0.5%*Multimeter +0.02) A
Channel Multimeter Tolerance SPD (On)
Channel1 Channel2 ~ Channel3 ~
~
SPD (Off)
OVP verification
Item Channel Min. limit Result Max. limit
Minimum OVP Setting
Functionality
Setting
Functionality
CH1 0. CH2 0.0V 1.0V CH3 0.0V 0.1V CH1 0.5V 1.5V Minimum OVP CH2 0.5V 1.5V CH3 0.00V 1.00V CH1 65.0V 68.0V Maximum OVP CH2 65.0V 68.0V CH3 6.0V 7.0V CH1 59.2V 60.8V Maximum OVP CH2 59.2V 60.8V CH3 4.47V 5.53V
0V 1.0V
FAQ
Q1. I cannot turn On the output (the Output key does not respond).
A1. The following scenarios are possible.
The rear panel remote control terminal is in the Off position. In
s case, set it to the On position or deactivate remote control.
thi details,
The OVP setting switch on the rear panel is on the SET side. In
this c
The OVP indicator is red. In this case, change the OVP setting to
higher v
Note that in several conditions, the Output key automatically turns Off to avoid harmful condition. For details, see page25.
Q2. The CV/CC indicator is red (Constant Current) while the output is Off.
A2. This indicates there is an internal error. Contact the service center.
Q3. The meter does not match the real value.
A3. The following scenarios are possible.
Make sure the rear panel OVP setting is in the “Normal” position.
If the OV
If you are using Channel1 or Channel3, make sure the meter
swi share the same
see page
ase, set the switch to the Norm
alue or remove the over voltage condition.
the OVP switch is in the “SET” position, the meter mi
P setting, not the output value. For OVP details, see page22
tch on the right side is in the correct position. Channel1 and 3
39.
al side.
meter.
For
ght show
.
For more information, contact your local dealer
55
56
APPENDIX
g
SPD-3606 User Manual
Volume Guard (Optional)
APPENDIX
Fuse Replacement
Step
1. Take off the power cord and remove the socket
using a minus driver
E
S
U
F
E
C
A
D
L
E
P
I
E
F
I
R
C
E
P
S
S
A
G
N
I
T
A
R
E
S
U
F
V
A
5
0
1
1
1
T
V
0
5
2
V
0
3
2
S
T
T
A
W
X
A
0
5
M
5
A
V
0
0
9
z
H
0
6
/
0
5
2. Replace the
E
S
U
F
E
C
A
D
L
E
P
I
E
F
I
R
C
E
P
S
S
A
G
N
I
T
A
R
E
S
U
F
V
A
5
0
1
1
1
T
V
0
5
2
V
0
3
2
S
T
T
WA
X
A
0
5
M
5
A
V
0
0
9
z
H
0
6
/
0
5
D
R
O
C
R
E
W
E
O
S
P
U
T
F
C
G
E
N
N
I
N
C
O
A
L
C
P
S
I
E
D
R
E
R
O
F
E
B
fuse in the ho
D
R
O
C
R
WE
E
O
S
P
U
T
F
C
G
E
N
N
I
N
C
O
A
L
C
P
S
I
E
D
R
E
R
O
F
E
B
.
lder.
fuse
Background
Applicable knobs
ch volume
Atta guard
The volume guard is an optional item which replaces the Channel 1 and 2 output knobs to prevent accidentally changing the output level. This feature is useful for automated testin
at fixed
output level, such as assembly line inspection.
Channel 1 Voltage and Current knob
Channel2 Voltage and Current knob
CH2
1. Pull out the original knob (Chann current knob for example).
2. Insert and screw the volume
guard to fix its
position.
3. To change the output level
, use a minus screwdriver from opening o
f the volume
guard.
el2
CH1
the
E
G
A
T
L
O
V
2
H
C
E
V
A
L
T
S
N
E
R
R
U
C
.
V
.
C
.
C
.
C
.
R
A
P
E
G
A
T
L
O
V
2
H
C
E
V
A
L
T
S
N
E
R
R
U
C
.
V
.
C
.
C
.
C
.
R
A
P
E
G
A
T
L
O
V
H2
C
E
V
A
L
T
S
N
E
R
R
U
C
.
V
.
C
.
C
.
C
.
R
A
P
Ra
ting
T10A/250V
57
58
APPENDIX
SPD-3606 User Manual
Specification
Output Ratings CH1/CH2
Independent
CH1/CH2 Series
CH1/CH2 Parallel
CH3
Vol tag e Regulation
Current Regulation
Tr ac k in g Operation
Line
Load
Ripple & Noise
Recovery
Line
Load
Ripple & Noise
Tracking Error
Series Regulation
ple & Noise
Rip
0 ~ 30V / 0 ~ 6A
0 ~ 60V / 0 ~ 3A
60V / 0 ~ 6A
0 ~
0 ~ 120V / 0 ~ 3A
0 ~ 30V / 0 ~ 12A
0 ~ 60V / 0 ~ 6A
0.
1 ~ 5V / 3A
0.01% + 3mV
0.01% + 5mV (rating current 6A)
0.01% + 8mV (rating current 12A)
5mVrms (5Hz ~ 1MHz)
50mV
Time
100µs (50% load change, minimum load 0.5A)
0.2% + 3mA
0.
3mArms
0.5% + 10mV of Master
300mV
10mVrms (5Hz ~ 1MHz)
100mVpp (20Hz ~ 20MHz)
(20Hz ~ 20MHz)
P-P
2% + 3mA
Output On/Off Response Time
OVP
Meter Type
Insulation
Temperature Coefficient
Remote Control
Fan Nois e
Operation Environment
Storage Environment
Power Source
Accessories
Dimensions
Weight
Vol tage Up
(10% ~ 90%)
Vol tage Down
(90% ~ 10%)
Accuracy
Accuracy
Resolu
Chassis and Te rm i na l
Chassis and AC cord
Vol tag e
Current
Output On/Off
50dB
Ambient temperature 0 ~ 40°C
Relative humidity 80%
Ambient temperature –10 ~ 70°C
Relative humidity 70%
AC 115V/230V±15%, 50/60Hz
User manual x 1, Power cord x 1
Test lead GTL-104 x 2, GTL-105 x 1
255 (W) x 145 (H) x 265 (D) mm
Approx. 6kg
100ms (95% rating load)
100ms (10% rating load)
± (0.5% of reading + 0.5V)
digits 0.5" LED display
3 ½
± (0.5% of reading + 2 digits)
tion
100mV/10mA
100M or above (DC 1000V)
100M or above (DC 1000V)
100ppm/°C+3mV
150ppm/°C+3mA
59
60
APPENDIX
Declaration of Conformity
We
GOOD WILL INSTRUMENT CO., LTD.
(1) No.7-1, Jhongsing Rd., Tucheng City, Taipei County, Taiwan (2) No. 69, Lu San Road, Suzhou City (Xin Qu), Jiangsu Sheng, China declare, that the below mentioned product
Type of Product: Power Supply Model Number: SPD-3606
are herewith confirmed to comply with the requirements set out in the Council Directive on the Approximation of the Law of Member States relating to Electromagnetic Compatibility (2004/108/EC, 89/336/EEC, 92/31/EEC, 93/68/EEC) and Low Voltage Directive (73/23/EEC, 93/68/EEC). For the evaluation regarding the Electromagnetic Compatibility and Low Voltage Directive, the following standards were applied: EMC
EN 61326-1: 2006 Electrical equipment for measurement, control and laboratory use –– EMC requirements
Conducted Emission Radiated Emission
ClassA
EN 55011: 1998 + A1:1999 + A2:2002 Current Harmonics EN 61000-3-2: 2000 + A2:2005 Voltage Fluctuations EN 61000-3-3: 1995 + A1:2001
Electrostatic Discharg
EN 61000-4-2: 1995 + A1:1998 + A2:2001 Radiated Immunity EN 61000-4-3: 2002 + A1:2002 Electrical Fast Transients EN 61000-4-4: 2004
+A2:2005
------------------------- Surge Immunity EN 61000-4-5: 1995 + A1:2001
------------------------- Conducted Susceptibility EN 61000-4-6: 1996 + A1:2001
------------------------- Power Frequency Magnetic Field EN 61000-4-8: 1993 + A1:2001
------------------------- Voltage Dip/ Interruption EN 61000-4-11: 2004
Safety
Low Voltage Equipment Directive 73/23/EEC & amended by 93/68/EEC
Safety Requirements IEC/EN 61010-1: 2001
e
INDEX
block diagram, system.............. 11
caution symbol............................. 5
cleaning the instrument.............. 7
constant current mode.............. 18
constant voltage mode.............. 18
cooling fan.................................. 20
noise level spec ............................. 60
safety instruction ............................ 6
CV/CC
indicator overview ....................... 16
overview ........................................ 18
default setting for verification . 41
EN 55011..................................... 61
EN 61000..................................... 61
EN61010
declaration of conformity............ 61
measurement category .................. 6
pollution degree.............................. 7
environment
operation.......................................... 7
specification................................... 60
storage .............................................. 7
front panel diagram .................. 14
fuse
SPD-3606 User Manual
rating .............................................. 57
replacing ........................................ 57
safety instruction ............................ 6
socket overview ............................ 17
ground symbol............................. 5
list of features............................. 10
load connection
independent mode ....................... 26
procedure....................................... 24
tracking parallel............................ 36
tracking series ......................... 30, 33
wire type ........................................ 24
meter
ch1/ch3 switch.............................. 28
faq.................................................... 56
OVP mode ..................................... 22
multimeter for verification ....... 40
output current
recording table ........................54, 55
specification................................... 59
verification..................................... 47
output on/off
faq.................................................... 56
key overview................................. 14
61
62
INDEX
manual............................................ 25
remote............................................. 39
response time spec ....................... 60
output range
independent mode ....................... 26
specification................................... 59
switch overview............................ 14
tracking parallel............................ 36
tracking series ......................... 30, 33
output voltage
recording table ........................54, 55
specification................................... 59
technical background................... 13
verification............................... 42, 45
overload indicator
description ..................................... 29
overview ........................................ 15
OVP
automatic output off .................... 25
indicator overview ....................... 14
recording table .............................. 55
setting terminal overview ........... 17
setup ............................................... 22
verification..................................... 50
when activated.............................. 23
power supply
power on/off................................. 21
safety instruction ............................ 6
socket overview ............................ 17
specification................................... 60
switch overview............................ 14
rear panel diagram.....................17
remote output control
disable manual control ................ 25
setup ............................................... 39
terminal overview ........................ 17
service operation
about disassembly .......................... 6
contact point.................................. 56
tracking mode
parallel............................................ 36
parallel indicator overview......... 16
series ............................................... 30
specification................................... 59
tracking series
common ground ........................... 33
tracking switch
automatic output off .................... 25
independent mode ....................... 27
overview ........................................ 15
tracking parallel............................ 36
tracking series ................... 31, 33, 45
UK power cord.............................8
ventillation space requirement.20
volume guard .............................58
warning symbol ...........................5
63
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
Loading...