54
Installation [All Models]
a) Positioning the unit
The boiler should be positioned in a convenient
place, on a wall that is capable of supporting it
safely (refer to section “Technical Specication”
for weight of boiler). Use the mounting template
and tting kit provided.
Position the boiler so that the tap is
approximately 400mm above a draining board.
Leave sufcient space around the unit to enable
access for servicing, paying particular attention
to the position of the top-centre xing screw that
holds the case in place.
When mounting on wall, screw in the top two
screws leaving about 6mm protruding and hang
the machine using the keyhole slots provided.
Once the machine is positioned, tighten the top
screws and insert the bottom screw.
b) Electrical Connection
3.0kW Units: (WM3, WM3SS, WM7, WM7SS,
WM15-3SS)
Supply: 230V, 50/60Hz (3.0kW).
The circuit should be protected by its own
13amp double pole connection unit with ex
outlet to BS5733, alternatively the circuit should
have means of disconnection incorporated in
xed wiring, having a contact separation of a
least 3mm in all poles. Minimum cable size is
1.5mm2. The use of an ELCB is recommended.
Base Entry of Cable: Use the cable gland.
Loosen cable-gripping nut and pass cable
through gland, leaving enough free cable to
connect to terminal block. Tighten cable gland
grip nut.
Alternative Rear Entry Installation (Electrical):
The xed or exible cable is connected direct
to the terminal block – the cable gland is not
utilised.
DO NOT SWITCH ON UNTIL THE
INSTALLATION IS COMPLETE AND THE
CASE AND TAP ARE IN PLACE
6.0kW Unit: (WM15-6SS)
Supply: 230V, 50/60Hz (6.0kW).
This unit is 6KW so must be connected to a
30amp isolator tted with a suitable ELCB.
Electrical installation should conform to current
I.E.E. wiring regulations.
3.0 or 6.0kW Unit: (WM25SS) - Optional on
installation
The 25 litre unit can be congured to either
3KW or 6KW.
As it leaves the factory it is congured to 3KW.
This can be changed to 6KW by tting the link
wire (supplied) to the second heating element.
NOTE:
If the unit is congured to 6KW then the unit
must be connected to a 30amp isolator tted
with a suitable ELCB. Electrical installation
should conform to current I.E.E. wiring
regulations.
In addition, the “Heater Rating” must be
changed in the Program Mode, from 3KW to
6KW (select “Set Heater Rating”). To access
Program Mode, follow instructions as on page 6
- WARNING: This appliance must be earthed.
- Electrical installation should conform to
current I.E.E. wiring regulations.
ONLY A QUALIFIED ELECTRICIAN SHOULD
CARRY OUT THIS WORK
c) Water Connection
The water supply must have a pressure not
exceeding 7bar and no lower than 2bar.
If the mains water pressure is below 2bar, a fault
situation could arise.
If the water pressure exceeds 7bar a suitable
water pressure reducing valve will need to be
tted to the water supply to bring it to a level
that the machine can cope with. Failure to do so
could result in the boiler overlling.
THE MANUFACTURERS CANNOT BE
HELD RESPONSIBLE FOR ANY MACHINE
MALFUNCTION IF THE WATER PRESSURE
IS NOT WITHIN THE RANGE STATED. IF IN
DOUBT, CONSULT YOUR WATER SUPPLY
COMPANY.
- Connect to a suitable cold water drinking
supply using 15mm copper pipe and using
“T” piece supplied.
- Push the “T” piece rmly onto the water
inlet solenoid pipe with the brass plug
facing forward (Note: the “T” has been
blanked off using a brass plug – leave the
plug in-place).
- Push the 15mm cold water supply rmly
into the bottom of the tting.
Alternative Rear Entry Installation (Water
Connection):
Remove the brass plug from “T” piece and
re-t into the bottom of the “T” piece instead.
Push rmly onto the inlet solenoid pipe with the
“T” facing the wall. Push the 15mm cold water
supply rmly into the “T” tting.
NOTE: To avoid damage to the appliance, do
not use any solder connections whilst pipes
are connected to the boiler.
- A 15mm stop valve must be tted between
the water supply and the boiler so that it
can be isolated.
- Water purication lters are available from
Instanta to ensure fresh tasting water.
In hard water areas, scale can cause
problems. Fitting a scale reducer will help
minimise scale but will not eliminate scale
completely.
d) Overow/Drain
The tting kit includes a 15mm, straight push-t
coupling with a small piece of 15mm copper
pipe pushed into it. NOTE: This connector
must be pushed onto the corresponding
brass overow connection on the services-
bracket (along side the solenoid).
If the overow is to be extended, remove the
copper pipe (supplied) and replace with 15mm
pipe of your chosen length. The pipe must have
a continuous fall and should not be longer than
300mm (if a longer run is required, use 22mm
pipe to avoid airlocks). The overow pipe should
have no more than four right angle bends and
should discharge to a safe, visible position.
Alternative Rear Entry Installation
(Overow/Drain):
If rear entry has been chosen, the straight
push-on coupling must be replaced with a
15mm push-t elbow (available from plumber’s
merchants). Push the elbow onto the brass
overow connection on the services bracket
(alongside the solenoid). As described above,
the pipe must have a continuous fall etc.
Under certain conditions the overow
pipe could vent steam, hot water or cold
water. The manufacturers cannot be held
responsible should damage occur from
such discharge, if the overow pipe has not
been directed to a suitable position where
overowing water can run away safely.
VENT PIPE:
A small silicone rubber tube connects the tanklid to the back panel. Ensure this is connected
(and hasn’t come off in transit) and that the
outlet tting in the back-panel is not obstructed.
e) Fitting Case:
- Stainless Steel Case Units Only: Attach
the Earth wire connection to the bottom of
the boiler-case (screw & washer supplied).
- Position the boiler-case close to the
wall-mounted boiler assembly and plug-in
the communications lead (located on inside
of boiler-case) into the circuit board.
- With the communications lead connected,
offer up the case to the wall-mounted boiler
assembly, aligning the tap and plastic
spring-mounted tap moulding with the
cut-out in the boiler-case.
- Secure case in position using M4 screws
(supplied) at top and bottom of the case.
- Slide the grey tap collar along the chromed
tap assembly so that it ts snugly against
the plastic tap moulding.
Operation
First use (once water and electrical connections
have been made):
NOTE: If the “7-day Timer” or “Filter Monitor”
features are not required, the boiler can be
used without any program set-up.
Simply switch the machine on by pressing the
small button at the top of the LCD window.