Inspur 10GEM-001-FCOE Series Hardware Installation And Reference Manual

10GEM-001-FCOE Blade Switch Hardware Installation and Reference Guide V1.00
Documents
Description
Configuration Guide
Describes network protocols and related mechanisms that supported by the product, with configuration examples.
Command Reference
Describes the related configuration commands, including command modes, parameter descriptions, usage guides, and related examples.

Preface

Thank you for using our switches. This guide (Version: V1.00) will help you install and use the switches.
Scope
This manual describes the functions and physical features of the switches, and presents the installation procedure, troubleshooting procedure, technical specifications, and specifications and usages rules of cables and connectors. It is intended for the users that have some experience in installing and maintaining network hardware and want to learn the above information. At the same time, it is assumed that the users of this switch are already familiar with the related terms and concepts of Ethernet.
Document Structure
Chapter 1 "Product Overview" describes the main characteristics, technical specifications, and related modules
of this product.
Chapter 2 "Preparation before Installation" lists the safety, power supply, and site requirements that must be
met before the switch can be installed.
Chapter 3 "Product Installation" describes how to install the integrated switch and modules, and connect its
power cables and grounding lines.
Chapter 4 "System Debugging" describes the commissioning after the switch is powered on for the first time.
Chapter 5 Monitoring and Maintenance
Chapter 5 "Troubleshooting" describes possible problems met during the installation and use of the switch and
solutions for such problems.
Appendix A "Connector and Connection Media"
Appendix B " Mini-GBIC, 10G, 40G and FC Modules"
Appendix C Lightening Protection
Appendix D Cabling Recommendations in Installation
Related Documents
Documentation Conventions
The symbols used in this document are defined as follows:
- 1 -
This symbol brings your attention to some helpful suggestions and references. This symbol means that you must be extremely careful not to do some things that may damage the switch
or cause data loss.
- 2 -
Model
10G SFP+ Ethernet Port
10GBase-T Ethernet Port
40G QSFP+ Ethernet Port
2/4/8G SFP FC Interface
10GBA SE-KR
Expansio n Slot
Redundant Fan
Redundant Power Supply
10GEM-00 1-FCOE
16
N/A 4 8
16
N/A
N/A
N/A
Model
10GEM-001-FCOE
Expansion Module Slot
Unsupported
Expansion Module
Unsupported
Fan Slot
2
Power Module
Connected to the power connector on the back panel
Power Input
DC input Input voltage: 12 VDC
Power Consumption
<120 W
Optical Module
See Appendix B for details.
The supported modules may update at any time.
SFP+ Port
Supported
QSFP+ Port
Supported
FC Port
Supported by port 9-16 (SFP+ combo)
10Gbase-T Port
Unsupported
Temperature Warning
Support temperature warning and over-temperature protection.

Product Overview

The 10GEM-001-FCOE blade switch is a high-density 10G 3-layer IPv6 switch. It is mainly applicable to the data center to provide convergence and access for the server.
The 10GEM-001-FCOE series switch:
An SFP+ port supports both 10Gbase-R and 1000base-X. A QSFP+ port support both 40G mode and four 10G mode.
Specifications
- 1 -
Working Temperature
0°C to 35°C
Storage Temperature
-40°C to 55°C
Working Humidity
10% to 90% RH(non-condensing)
Weight
Net weight: 3kg
Dimensions (PCB)
461.0 mm x 226.4 mm (L x D)
The 10GEM-001-FCOE series switch is an A-class product which might cause radio interference in
living environment. Users need to take measures to deal with the interference.
The 10G or 40G Ethernet port of the 10GEM-001-FCOE switch supports direct attach copper (DAC)
cable. The SFP+ port supports 1-meter, 3-meter and 5-meter cable, and the QSFP+ port supports 3-meter cable. See Appendix B for details.
Product Appearance
Figure 0-1 Appearance of 10GEM-001-FCOE
Front Panel
Figure 0-2 Front Panel of 10GEM-001-FCOE
- 2 -
Notes:
10G SFP+ port Ejector lever 10G SFP+ port 40G QSFP+ port 10G QSFP+ port LED Fan 1 LED Fan
Fan 2 LED Console port System LED
Stack LED
The 10GEM-001-FCOE switch supports 10G SFP+ module and 1G SFP module. The 10G SFP+
module cannot be used as a 1G SFP module.
9-16 SFP+ ports can be configured as Fiber Channel ports.
Back Panel
Figure 0-3 Back Panel of 10GEM-001-FCOE
- 3 -
LED
Panel Identification
Status
Meaning
System LED
Status
Off
The system is not powered up.
Blinking green
The system is initializing.
Solid green
The system is operational.
Blinking orange
Warnings
Stack LED
STAT Off
The system is not powered up.
Blinking green
The stack module is operational in Master mode.
Solid green
The stack module is operational in Slave mode.
Fan 1 LED
FAN1 Off
The fan is not in position.
Solid green
The fan is operational.
Solid orange
The fan is faulty.
Fan 2 LED
FAN2 Off
The fan is not in position.
Solid green
The fan is operational.
Solid yellow
The fan is faulty.
SFP+ port LED
1-8 (Ethernet mode)
Off
The ports are not linked.
Solid green
The ports are linked at 10G/1G.
Blinking green
The ports are transceiving data at 10G/1G.
9-16 (FC mode)
Off
The ports are not linked.
Solid yellow
The ports are linked at 2/4/8G.
Blinking yellow
The ports are transceiving data at 2/4/8G.
9-16 (Ethernet mode)
Off
The ports are not linked.
Solid green
The ports are linked at 10G/1G.
Blinking green
The ports are transceiving data at 10G/1G.
QSFP+ port LED
17:x-20:x (Four 10G mode: 4 LEDs & 4 10G channels)
Off
The ports are linked.
Solid green
The ports are linked at 10G.
Blinking green
The ports are transceiving data at 10G.
17-20 (One 40G mode: 1 LED)
Off
The ports are not linked.
Solid green
The ports are linked at 40G.
Blinking green
The ports are transceiving data at 40G.
External Interface
The 10GEM-001-FCOE provides the following interfaces:
Console port: Use RS-232 interface electrical level and standard RJ-45 connector. This interface is connected with
the serial port of terminal PC to perform system debugging, configuration, maintenance, management, and host software uploading.
SFP+ port: There are 16 10G QSFP+ ports, which support optical modules and DAC copper cables, and are
compatible with 1000Base-X.
QSFP+ port: There are four 40G QSFP+ ports, which support optical modules and DAC copper cables. This port
can work in 4x10G mode.
FC port: There are eight 2G/4G/8G Fiber Channel ports (Port 9-16, SFP+ combo).
LEDs
Heat Dissipation
- 4 -
The switch fabric module is mounted at the rear of the blade server. Heat is dissipated by fans on the module panel..
Figure 0-4 Ventilation and Heat Dissipation of the 10GEM-001-FCOE
- 5 -

Preparation before Installation

Safety Precautions

To avoid body injury and device damage, please carefully read the safety precautions before you install
the 10GEM-001-FCOE series switch.
The following safety precautions do not cover all possible dangers.

Installation Safety

Keep the chassis clean and dust-free.  Do not place the device in walking areas.  Do not wear loose clothes, ornaments or any other things that may be hooked by the chassis during the
installation and maintenance.
Turn off all power supplies and unplug all power cords and cables before the installation or the dismantling.

Removal Safety

Avoid frequent removals after the device is installed.  Turn off all power supplies and unplug all power cords and cables before the installation or the dismantling.  When removing the device, pay attention to the balance and avoid hurting legs and feet or straining the back.
When the device is being removed, do not hold the power supply handle or the fan handle for these
parts are not designed for bearing the entire weight of the device. It will cause damage to the device or to your body if you hold these parts when removing the device.
To reduce the weight of the chassis during the removal, dismantle the expansion module, fan module
and the power supply module first.
Install and operate the device in places where removing is restricted.

Electric Safety

- 6 -
Observe local regulations and specifications when electric operations are performed. Relevant operators must be
qualified.
Carefully check any potential danger in the working area, such as ungrounded power supply, unreliable grounding
of the power supply, and damp/wet ground.
Find out the location of the emergency power supply switch in the room before installation. First cut off the power
supply in the case of an accident.
Be sure to make a careful check before you shut down the power supply.  Do not place the device in a damp location. Do not let any liquid enter the chassis.
Any nonstandard and inaccurate electrical operation can cause accidents such as fires or electrical
attacks, thus causing severe or even fatal damages to human bodies and the devices.
Direct or indirect touch through a wet object on high-voltage and mains supply can bring a fatal danger.

Electrostatic Discharge Damage Precautions

The 10GEM-001-FCOE designing gives a great consideration to prevent electrostatic discharge damage and adopts multiple measures. But if the electrostatic exceeds certain limit, it can still cause great damages to the circuitry and the device. In networks connected by the 10GEM-001-FCOE, the major sources of electrostatic induction are outdoor high voltage transmission cables, lightening, indoor floor materials and the machine structure.
Pay attention to the following tips:
The device and the floor are well grounded.  Take dust prevention measures in the room.  Maintain an appropriate humidity.  When the pluggable modules of the switch are being installed, wear antistatic wrist strap and make sure the
antistatic wrist strap is well grounded, as shown in figure 2-1.
Do not use bare hand to directly touch the components and the printed-circuit board (PCB) when the boards are
used.
Use an anti-static shielding bag to properly store the board.  Do not let any clothes touch a circuit board. An antistatic wrist strap can only prevent human static electricity from
damaging the circuit board, but cannot prevent any static electricity on clothes.
Figure 2-1 Wearing antistatic wrist strap
- 7 -
Model
Working Temperature
Working Humidity
10GEM-001-FCOE
0ºC to 35ºC
10% to 90%

Laser Safety

Among the modules supported by the 10GEM-001-FCOE, there are a great number of optical modules that are Class laser products.
Precautions
When a fiber transceiver works, ensure that the port has been connected with a fiber or has been covered by a
dust cap so as to keep out dust and prevent it from burning your eyes.
Do not stare at any fiber port.
Do not stare at any fiber port under any circumstances, as this may cause permanent damage to your
eyes.

Installation Site Requirements

Install the 10GEM-001-FCOE indoor. To ensure normal operation and a prolonged service life of the device, the installation site must meet the following requirements.

Ventilation Requirements

For the 10GEM-001-FCOE series switch, leave sufficient space in the front and at the back of the chassis (at least 20cm) for ventilation. After various cables are connected, bundle the cables or place them in the cable management bracket to avoid blocking the air intake.

Temperature and Humidity Requirements

To ensure the normal operation and a prolonged service life of the 10GEM-001-FCOE, maintain an appropriate temperature and humidity in the equipment room. The equipment room with too high or too low temperature and humidity for a long period of time may damage the equipment.
In an environment with high relative humidity, the insulating material may have bad insulation or even leak
electricity. And sometimes the materials may suffer from mechanical performance change and metallic parts may get rusted.
On the other hand, in an environment with low relative humidity, the insulating strip may dry and shrink, and static
electricity may occur easily and endanger the circuit on the device.
In an environment with high temperature, the equipment is subjected to even greater harm, as its performance
may degrade significantly and its service life may be shortened at high temperature for long that expedites the aging process.
Temperature and humidity requirements of the 10GEM-001-FCOE:

Cleanness Requirements

- 8 -
Substance
Concentration Limit (particles/m3)
Dust particles (diameter 0.5μm)
3.5×106
Dust particles (diameter 5μm)
3×104
Gas
Average (mg/m3)
Maximum (mg/m3)
SO2
0.2
1.5
H2S
0.006
0.03
NO2
0.04
0.15
N2
0.05
0.15
Cl2
0.01
0.3
Dust poses the top threat to the running of the device. The indoor dust falling on the device may be adhered by the static electricity, causing poor contact of the metallic joint. Such electrostatic adherence may occur more easily when the relative humidity is low, not only affecting the service life of the device, but also causing communication faults. The following table shows the requirements for the dust content and granularity in the equipment room.
Apart from dust, the salt, acid and sulfide in the air in the equipment room must also meet strict requirements; as such poisonous substances may accelerate the corrosion of the metal and the aging of some parts. The equipment room should be protected from the intrusion of harmful gases (for example, SO2, H2S, NO2 and Cl2), whose requirements are listed in the following table.

System Grounding Requirements

A good grounding system is the basis for the stable and reliable operation of the 10GEM-001-FCOE series switch. It is the key to prevent lightning stroke and resist interference. Please carefully check the grounding conditions on the installation site according to the grounding requirements, and perform grounding properly as needed.
Safety Grounding
The device using AC power supply must be grounded by using the yellow/green safety grounding cable. Otherwise, when the insulating resistance decreases between the power supply and the enclosure in the device, electric shock may occur.
The building installation shall provide a means for connection to protective earth, and the device is to be
connected to that means.
Lightning Grounding
The lightning protection system of the facility is an independent system that consists of the lightning rod, down lead conductor and the connector to the grounding system, which usually shares the power reference ground and yellow/green safety cable ground. The lightning discharge ground is for the facility only, not for the device.
For lightning protection, see Appendix C.