IS300 series servo driver is a servo driver which is specially desiged for Drive
permanent magnet synchronous servo motor (PMSM). IS300 series servo
driver has a wide capacity range(the rated current is 5A to 300A).It’s able to
provide not only servo pump control, but also the general functional
requirements.And it is a high-power servo driver which is value-for-money in
the present market.
This manual is a guide to the operations of IS300 series servo driver.
This manual provides the user with related precautions and instructions for the
prototyping, installation, parameter setup, and on-site commissioning, and
routine repair and maintenance of servo driver. In order to use this series of
driver correctly, please read this manual carefully prior to operation and keep it
properly for future using. The supporting equipment customers shall distribute
this manual together with the equipment to the final users.
Unpacking and inspection:
Please confirm carefully when unpacking the box:
1) If the model and driver rated values on the nameplate are the same as
your order. The box contains the equipment, certificate of conformity,
user manual and warranty card.
2) If the product is damaged during the transportation. If there is any
omission or damage, please contact our company or the supplier
immediately.
First time use:
The users who use this product for the first time shall read this manual
carefully. For any doubt on certain functions and performances, please contact
the technical support personnel of our company for help so as to use this
product properly.
With commitment to the constant improvement of the servo driver, our
company may change the information provided without additional notice.
i
Page 2
IS300 series servo driver complies with the following international standards,
and some products have passed the CE certification.
IEC/EN61800-5-1:2003 “Safety Regulations on Commissionable Electric Drive
System” and IEC/EN 61800-3:2004 Commissionable Electric Drive System:
The third Part: Electromagnetic Compatibility Standard and Specific Testing
Method for the Product (Comply with IEC/EN61800-3 standard under correct
installation and use as per Article 7.3.2 and 7.3.6).
ii
Page 3
Contents
FOREWORD .................................................................................................... I
CHAPTER 1 SAFETY AND PRECAUTIONS..............................................- 2 -
CHAPTER 9 FAILURE DIAGNOSIS AND SOLUTION...........................- 175 -
9.1 Failure Diagnosisi and Solution .........................................................- 175 -
9.2 Common Fault and Resolution ..........................................................- 190 -
APPENDIX 1: COMMON PARAMETERS TABLE..................................- 194 -
APPENDIX 2 SHORTCUT MENU PARAMETERS TABLE.....................- 201 -
Page 5
Safety and Precautions
- 1 -
Page 6
Chapter 1 Safety and Precautions
Safety definition:
In this manual, safety precautions are divided into two types below:
Danger arising due to improper operations may cause severe hurt or even
death.
Danger arising due to improper operations may cause moderate hurt or
light hurt or equipment damage.
1.1 Safety precautions
1.1.1 Before Installation:
zDo not use the damaged driver or driver with missing parts. Otherwise,
there may be risk of injury.
zUse the motor with Class B or above insulation. Otherwise, there may
be risk of electric shock.
1.1.2 During the Installation:
Danger
z Mount the driver on incombustible surface like metal, and keep away
from flammable substances. Otherwise it may cause fire.
z2. When more than two servo drivers are to be installed in one cabinet,
pay attention to the installation locations (refer to Chapter 3 Mechanical
and Electrical Installation) to ensure the cooling effect.
z3. Do not drop the lead wire stub or screw in the servo driver. Otherwise it
may damage the servo driver.
- 2 -
Page 7
1.1.3 During wiring:
Danger
zOperation shall be performed by the professional engineering technician.
Otherwise there will be danger of electric shock!
zThere shall be circuit breaker between the servo driver and power
supply. Otherwise, there may be fire!
zMake sure the power is disconnected prior to the connection.
Otherwise there will be danger of electric shock!
z The earth terminal shall be earthed reliably. Otherwise there may be
danger of electric shock.
z 6.Do not connect the input power cable to the output ends U, V and W.
Otherwise it may damage the servo driver.
z7. Ensure the wiring meet the EMC requirements and the local safety
standard. The wire size shall be determined according to the manual.
Otherwise, accident may be caused!
z8. The brake resistor cannot be directly connected between the DC bus
terminals (+) and (-). Otherwise it may cause fire.
1.1.4 Before Power-on:
Danger
z Before Power-on:
z Please confirm whether the power voltage class is consistent with the
rated voltage of the servo driver and whether the I/O cable connecting
positions are correct, and check whether the external circuit is short
circuited and whether the connecting line is firm. Otherwise it may
damage the servo driver!
z The cover must be well closed prior to the servo driver power-on.
Otherwise electric shock may be caused!
- 3 -
Page 8
zWhether all the external fittings are connected correctly in accordance
with the circuit provided in this manual. Otherwise accident may
occur!
1.1.5 Upon Power-on:
zDo not open the cover of the servo driver upon power-on. Otherwise
there will be danger of electric shock!
zDo not touch the servo driver and its surrounding circuit with wet hand.
Otherwise there will be danger of electric shock!
z Do not touch the servo driver terminals (including control terminal).
Otherwise there will be danger of electric shock!
zAt power-on, the servo driver r will perform the security check of the
external heavy-current circuit automatically. Thus, at this time please
do not touch the terminals U, V and W, or the terminals of motor,
otherwise there will be danger of electric shock.
z If parameter identification is required, please pay addtation to the danger
of injury arising from the rotating motor. Otherwise accident may occur!
zDo not change the factory settings at will. Otherwise it may damage the
equipment!
1.1.6 During the operation:
zDo not approach the mechanical equipment when selecting the restart
function. Otherwise it may cause injury!
z Do not touch the fan or discharge resistor to sense the temperature.
Otherwise, you may get burnt!
z3. Detection of signals during the operation shall only be conducted by
qualified technician. Otherwise, personal injury or equipment damage
may be caused!
- 4 -
Page 9
z4. During the operation of the servo driver, keep items from falling into
the equipment. Otherwise, it may damage the equipment!
z5. Do not start and stop the servo driver by connecting and disconnecting
the contactor. Otherwise, it may damage the equipment!
1.1.7 During Repair
Danger
z Do not repair and maintain the equipment with power connection.
Otherwise there will be danger of electric shock!
zbe sure to conduct repair and maintenance after the charge LED indictor
of the servo driver is OFF. Otherwise, the residual charge on the
capacitor may cause personal injury!
zThe servo driver shall be repaired and maintained only by the qualified
person who has received professional training. Otherwise, it may cause
personal injury or equipment damage!
1.2 Precautions
1.2.1 Motor Insulation Inspection
When the motor is used for the first time, or when the motor is reused after
being kept, or when periodical inspection is performed, it shall conduct motor
insulation inspection so as to avoid damaging the driver because of the
insulation failure of the motor windings. The motor wires must be
disconnected from the driver during the insulation inspection. It is
recommended to use the 500V megameter, and the insulating resistance
measured shall be at least 5MΩ.
1.2.2 Thermal Protection of the Motor
If the rated capacity of the servo motor does not match those of the driver,
especially when the rated power of the driver is higher than the rated power of
the motor, the relevant motor protection parameters in the driver shall be
adjusted, or thermal relay shall be mounted to protect the motor.
1.2.3 Motor Heating and Noise
Since the output voltage of servo driver is PWM wave and contains certain
- 5 -
Page 10
harmonics, the temperature rise, noise and vibration of the motor will be higher
than those when it runs at standard frequency.
1.2.4 Voltage-sensitive Device or Capacitor Improving Power Factor at the
Output Side
Since the servo driver output is PWM wave, if the capacitor for improving the
power factor or voltage-sensitive resistor for lightning protection is mounted at
the output side, it is easy to cause instantaneous over current in the servo
driver, which may damage the servo driver. It is recommended that such
devices not be used.
1.2.5 Switching Devices like Contactors Used at the Input and Output terminal
If a contactor is installed between the power supply and the input terminal of
the driver, it is not allowed to use the contactor to control the startup/stop of the
driver. If use of such contactor is unavoidable, it shall be used with interval of at
least one hour. Frequent charge and discharge will reduce the service life of
the capacitor inside the driver. If switching devices like contactor are installed
between the output end of the driver and the motor, it shall ensure that the
on/off operation is conducted when the driver has no output. Otherwise the
modules in the driver may be damaged.
1.2.8 Use under voltage rather than rated voltage
If the driver is used outside the allowable working voltage range as specified in
this manual, it is easy to damage the devices in the driver.
When necessary, use the corresponding step-up or step-down instruments to
change the voltage.
1.2.7 Change Three-phase Input to Two-phase Input
It is not allowed to change the IS300 series three-phase servo driver into
two-phase one. Otherwise, it may cause fault or damage to the servo driver.
1.2.8 Lightning Protection
Servo driver of the series has lightning over current protection device, and
has certain self-protection capacity against the lightning. In applications
where lightning occurs frequently, the user shall install additional protection
devices at the front-end of the driver.
1.2.9 Altitude and Derating
In areas with altitude of more than 1,000 meters, the cooling effect of the driver
may turn poorer due to rare air. Therefore, it needs to derate the driver for use.
Please contact our company for technical consulting in case of such condition.
- 6 -
Page 11
1.2.10 Certain Special Use
If the user needs to use the driver with the methods other than the
recommended wiring diagram in this manual, such as shared DC bus, please
consult our company.
1.2.11 Precaution of Driver Disposal
The electrolytic capacitors on the main circuit and the PCB may explode when
they are burnt. Emission of toxic gas may be generated when the plastic
parts are burnt. Please dispose the servo driver as industrial wastes.
1.2.12 Adaptable Motor
1) The standard adaptable Permanent-Magnet Synchronous Motor
2) Since the servo driver has built-in standard parameters of the adaptable
motors, it is necessary to perform motor parameter identification or modify
the default values so as to comply with the actual values as much as
possible, or it may affect the running effect and protection performance;
3) The short circuit of the cable or motor may cause alarm or explosion of the
driver. Therefore, please conduct insulation and short circuit test on the
newly installed motor and cable. Such test shall also be conducted during
routine maintenance. Please note that the servo driver and the test part
shall be completely disconnected during the test.
- 7 -
Page 12
Page 13
Product Information
- 1 -
Page 14
Chapter 2 Product Information
2.1 Designation Rules
MarkSeries
IS300 Servo Driver
Voltage Level
Mark
Three Phase
S
220V
Three Phase
T
380V
Corresponding Rated Output
Current
Corresponding
Relationship
Mark
Rated Output
Current
Mark
Rated Output
Current
9A
070
75A
2.2 Nameplate
IS300 T 005 – C
13A17A25A32A37A45A60A
080
100
140
170
91A
112A
150A
176A
Note: Standard built rotary transformer
PG card
210
250
300
210A
253A
304A
Fig. 2-1 Designation Specification
Mark
C
Interface Board Type
Motor temperature
overheating protection
PTC sensor with CAN
communication
Fig.2-3 Nameplate
- 8 -
Page 15
2.3 IS300 Servo Driver Series
(kgf)
system
(kVA)
Servo
Driver
Model
IS300T005 5.9 10.5 9.0 20
IS300T010 8.9 14.6 13.0 30
IS300T015 11.0 20.5 17.0 40
IS300T020 17.0 26.0 25.0 60
IS300T030 21.0 35.0 32.0 75
IS300T035 24.0 38.5 37.0 85
IS300T040 30.0 46.5 45.0 105
IS300T050 40.0 62.0 60.0 140
IS300T070 57.0 76.0 75.0 180
IS300T080 69.0 92.0 91.0 210
IS300T100 85.0 113.0 112.0 260
IS300T140 114.0 157.0 150.0360
IS300T170 134.0 180.0 176.0420
IS300T210 160.0 214.0 210.0500
IS300T250 192.0 256.0 253.0600
IS300T300
Input
voltage
Three-p
hase
380V
Range:-
15%~
20%
Table 2-1 IS300 Servo Driver Series Model and Technical Data
0.5k to 16kHz; the carrier frequency will be
automatically adjusted according to the load
characteristics.
Digital setting: 0.01Hz
Analog setting: maximum frequency ×0.1%
Close loop vector control (VC)
V/F control
Individualiz
ed function
Individualiz
ed function
Startup
torque
Speed
adjustment
range
Speed
stabilization
precision
Torque
control
precision
Overload
capacity
Auto voltage
regulation
(AVR)
Peripherals
self-detectio
n upon
power-on
0Hz/180%(VC)
1:1000 (VC)
±0.02%(VC)
±5%(VC)
150% rated current 60s; 180% rated current 5s.
It can keep constant output voltage automatically in
case of change of mains voltage.
It can conduct safety detections on the peripherals
upon power-on, including earth and short circuit
detections.
- 10 -
Page 17
Item Specifications
Shared DC
Bus
Function
QUICK key The user can freely define short-cut menus.
MF.K Key
It can realize the function that multiple drivers share
the DC bus.
Programmable key: Select the command channel
switching/forward and reverse rotations/jog
operation.
Run
Running
command
channel
Frequency
source
Auxiliary
Frequency
source
Input
terminal
Output
terminal
Three types of channels: operation panel setup,
control terminal setup,serial communication port
setup and CAN communication port setup . These
channels can be switched in various modes.
There are types of frequency sources, such as
analog voltage setup, analog current setup, serial
portsetup and CAN setup. These frequency sources
can be switched in various modes.
It can implement micro tuning and synthesis of
auxiliary frequency.
There are five digital input terminals, It can be
compatible with enabled PNP or NPN input mode.
One motor PTC overheating protection input
terminal.
There are three analog input terminals, two of which
can be used only as voltage input, while the other
can be used as voltage or current input.
There are three relay input terminals.One is NO/NC
with optional, the other two are NO.
Two analog output terminals, with optional 0//4mA to
20mA or 0/2V to 10V.
Communicat
ion terminal
CAN Communication terminal
RS485 Communication terminal
- 11 -
Page 18
Display and
Keyboard
Operation
Item Specifications
LED display It can display the parameters.
Envir
onm
ent
Key locking
and function
selection
Protection
function
Optional
parts
Using Place
altitude Lower than 1,000 meters
Ambient
temperature
Humidity Less than 95%RH, without condensing
Vibration Less than 5.9 m/s2(0.6g)
Storage
temperature
It can lock the keys partially or completely and define
the functional range of certain keys so as to prevent
error operations.
It can implement power-on motor short-circuit
detection, input/output phase loss protection, over
current protection, over voltage protection, under
voltage protection, over heat protection and overload
protection.
reakers components and PG card, etc.
Indoor, and be free from direct sunlight, dust,
corrosive gas, combustible gas, oil smoke, vapor,
drip or salt.
-10 ℃ Celsius to +40 ℃ Celsius (derated when used
in the ambient temperature of 40 ℃ Celsius to 50 ℃
Celsius)
-20 ℃ Celsius ~ +60 ℃ Celsius
- 12 -
Page 19
2.5 Physical Appearance and Dimensions of Mounting
Hole
2.5.1 Physical Appearance
Input and output hole
Fan
Fig.2-3 Physical Appearance of IS300 servo driver
Top-shellOperation Panel
Middle-shell
Bottom-shell
Driver nameplate
Bottom Mounting Hole
Fig.2-4 Schematic Diagram for Physical Dimensions and Mounting Hole
Dimensions
- 13 -
Page 20
Fig.2-5 Schematic Diagram for Physical Dimensions and Mounting Hole
Dimensions
2.5.2 Physical Dimensions and Mounting Hole Dimensions
Table 2-3 Physical Dimensions and Mounting Hole Dimensions (mm)
Model
IS300T005
IS300T010
Mounting
Hole
A B H H1 W D
148 236248/ 160 183φ5 2.5
Physical Dimensions
Diamete
r of
Mountin
g Hole
Weight
(kg)
IS300T015
IS300T020
IS300T030
IS300T035
190 305322/ 208 192φ6 6.5
235 447432463285 228Φ8 20
- 14 -
Page 21
Model
IS300T040
IS300T050
IS300T070
IS300T080
IS300T100
IS300T140
IS300T170
IS300T210
IS300T250
IS300T300
Mounting
Hole
A B H H1 W D
260 580549600385 265φ10 32
343 678660700473 307φ10 47
449 905880930579 375φ10 90
Physical Dimensions
Diamete
r of
Mountin
g Hole
Weight
(kg)
- 15 -
Page 22
1) Physical Dimensions of External Keyboard
Fig.2-6 Schematic Diagram for Physical Dimensions of External Keyboard
- 16 -
Page 23
2) Mounting Hole Dimensions of External Keyboard
Fig.2-7 Schematic Diagram for Mounting Hole Dimensions of External
Keyboard
- 17 -
Page 24
3) Schematic Diagram for Physical Dimensions of External reactor
Fig.2-8 Schematic Diagram for Physical Dimensions of External Reactor
Table 2-4 Physical Dimensions table of External Reactor(mm)
Servo Driver
Model
IS300T140
IS300T170
IS300T210
IS300T250
IS300T300
zFor special requirements, the user can customize non-standard products.
*External DC reactor installation mode:
IS300 series Servo Driver of over IS300T140 (included), all employs standard
external DC reactor, which is packed in independent wooden box and
A B C D E F G
190
190
12
16119225519510*15 φ12
5
12
16119225519510*15 φ12
5
16
0
16
0
Connec
Fixing
Hole
Copper
Platoon
ting
Diamet
er of
- 18 -
Page 25
delivered together with the Servo Driver. When mounting the Servo Driver, the
user needs to remove the short circuit bus between the terminals P and (+) of
the main circuit of the Servo Driver and then connect the DC reactor between
P and (+). There is no polarity between the reactor terminal and the Servo
Driver terminals P and (+) . After the DC reactor is mounted, the short circuit
bus between P and (+) will not be used.
2.6 Optional Parts
For detailed functions and usage instructions, see the related options
description.
If you require the following options, see description when ordering.
Table 2-5 IS300 Servo Driver Optional Parts
Name Model Function Remarks
Built-in brake unit
External brake
unit
Energy feedback
unit
External LED
operation panel
The letter
“B”
attached
behind the
product
model
MDBU
MDFB
MDKE
Built-in brake unit of
IS300T035 to
IS300T050
(optional)
External brake unit
of above
IS300T070
(included)
The servo driver is
a energy saving
product which can
feed the electric
energy back to
AC power grid.
External LED
display and
operation keyboard
Built-in brake unit
of IS300T005 to
IS300T030 is
standard
configuration.
If IS300T140
(included) or
above is required,
it can employ the
parallel mode.
It can employ the
parallel mode.
IS300 series
general-purpose
RJ45 interface
- 19 -
Page 26
Name Model Function Remarks
Extended cable MDCAB
Rectifier unit MFRU
Standard 8-core
network cable and it
can be connected
with MDKE.
It is used when the
driver shares the
bus and has energy
saving function.
1m, 3m,5m and
10m are
available.
2.7 Routine Repair and Maintenance of Servo Driver
2.7.1 Routine Repair
The influence of the ambient temperature, humidity, dust and vibration will
cause the aging of the devices in the servo driver, which may cause potential
fault of the servo driver or reducing the service life of the servo driver.
Therefore, it is necessary to carry out routine and periodical maintenance on
the servo driver.
It is not allowed to conduct repair and maintenance on the driver right after
power shutdown because there is still high voltage on the filter capacitor. The
repair or maintenance can be conducted only after the charge LED indictor is
OFF and the bus voltage measured with multimeter is less than 36V.
Routine inspection Items include:
1) Whether there is any abnormal change in the running sound of the motor;
2) Whether the motor has vibration during the running;
3) Whether there is any change to the installation environment of the servo
driver;
4) Whether the servo driver cooling fan works normally;
5) Whether the servo driver has over temperature;
Routine cleaning:
1) The driver shall be kept clean all the time.
2) The dust on the surface of the servo driver shall be effectively removed,
so as to prevent the dust entering the servo driver. Especially the metal
dust is not allowed.
3) The oil stain on the driver cooling fan shall be effectively removed.
- 20 -
Page 27
2.7.2 Periodic Inspection
Please perform periodic inspection on the places where the inspection is a
difficult thing.
Periodic inspection Items include:
1) Check and clean the air duct periodically;
2) Check if the screws are loosened;
3) Check if the driver is corroded;
4) Check if the wire connector has arc signs;
5. Main circuit insulation test
z When using the megameter (DC 500V megameter recommended) to
measure the insulating resistance, the main circuit shall be disconnected
with the servo driver. Do not use the insulating resistance meter to
control the insulation of the circuit. It is not necessary to conduct the
high voltage test (which has been completed upon delivery).
2.7.3 Replacement of Vulnerable Parts for Driver
The vulnerable parts of the driver include cooling fan and filter electrolytic
capacitor, whose service life depends on the operating environment and
maintenance status. General service life is shown as follows:
Part name Service Life
fan 2 to 3 years
electrolytic
capacitor
The user can determine the year of replacement according to the operating
time.
1) Cooling fan
Possible reason for damage: Bearing is worn and blade is aging.
Judging criteria: Whether there is crack on the blade and whether there is
abnormal vibration noise upon startup.
2) Filter electrolytic capacitor
Possible reason for damage: Input power supply in poor quality, high ambient
temperature, frequent load jumping, and electrolyte aging.
Judging criteria: Whether there is liquid leakage and whether the safe valve
has projected, and measure the static capacitance, and the insulating
resistance.
4 ~ 5 years
- 21 -
Page 28
2.7.4 Storage of Driver
Upon acquiring the driver, the user shall pay attention to the following points
regarding the temporary and long-term storage of the driver:
1) Pack the driver with original package and place back into the packing box
of our company.
2) Long-term storage will degrade the electrolytic capacitor. Thus, the
product shall be powered up once every 2 years, each time lasting at least
five hours. The input voltage shall be increased slowly to the rated value
with the regulator.
2.8 Instructions on Warranty of Driver
Free warranty only applies to the driver itself.
1) Our company will provide 18-month warranty (starting from the
leave-factory date as indicated on the barcode) for the failure or damage
under normal use conditions. If the equipment has been used for over 18
months, reasonable repair expenses will be charged.
2) Reasonable repair expenses will be charged for the following situations
within 18 months:
a) The equipment is damaged because the user fails to comply with
the requirements of the user’s manual;
b) Damage caused by fire, flood and abnormal voltage;
c) Damage caused when the driver is used for abnormal function.
The service expenses will be calculated according to the standard of the
manufacturer. If there is any agreement, the agreement shall prevail.
2.9 Prototyping Guide
Three control modes are available, namely, V/F and VC.
When selecting driver, it must firstly make clear the technical requirements of
the system for variable frequency speed adjustment and specific details
regarding the applications and load characteristics of the driver, and select the
model and determine the operating mode through taking into overall
consideration the adaptable motor, output voltage, rated output current and
other factors.
The basic principle is that the rated load current of the motor shall not exceed
the rated current of the inverter. Generally, the selection is based on the
adaptable motor capacity as specified in the instruction manual. Due attention
- 22 -
Page 29
shall be paid to the comparison between the rated currents of motor and
inverter. The overload capacity of the inverter only affects the startup and
brake process. In case short-time overload occurs during the running process,
variation of load speed may arise. If the requirement for the speed precision is
relatively high, it can consider increasing the level.
Constant torque load: Most of loads have constant toque characteristics, but
the requirements for rotation speed and dynamic performance are low.
Extruding machine, agitator, belt conveyer, transporting trolley in the factory,
and translational unit of crane are the examples. It can select MS V/F running
mode when performing prototyping test.
The controlled object has higher dynamic and static index requirements: It can
employ VC control mode in applications where the requirements for speed
adjustment precision and dynamic performance index are relatively high and
there is high precision synchronous control. Injection molding machine,elevator,
paper making and plastic thin film processing product line are the examples.
2.10 Guide to Prototyping of Brake Components
(*): Table 6 Driver Bake Components Prototyping Table provides data for
reference, and the user can select different resistance and power according to
the actual needs (but the resistance shall not be lower than the recommended
value, and the power may be higher than the recommened value). The
selection of brake resistor shall be determined in accordance with the power
generated by the motor in the actual application sytem and is associated with
the system inertia, speed-down time and energy of potential load. Thus, the
user needs to select based on the actual needs. The higher the system inertia,
the shorter the speed-down time required, and more frequent the brake is, and
then it needs to select higher power and lower resistance vlaue for the brake
resistor.
2.10.1Selection of resistance vlaue
Renewable electric energy consumption is almost the braking resistor when
braking.
Refer to the formula U*U/R=Pb,
In the formula, U refers to stable Braking system of Brake voltage. (Different
system has different brake voltage. The system 380VAC is 700V).Pb refers to
the Braking power.
- 23 -
Page 30
2.10.2 Selection of braking resistor Power
Theoretically, braking Power is consistent with braking Power.But in
consideration of the 70 percent derating,please refer to the formula
0.7*Pr=Pb*D, Pr refers to the resistor Power, D refers to braking
frequency(Which is the regeneration process accounting for the proportion of
the whole working process).For example, the braking frequency of elevator is
between 20% to 30%, the winding and unwinding is between 20% to 30%.The
centrifuge is between 50% to 60%, Occasional braking load is 5%. Injection
molding machine braking load is 10%.
Note: ×2 refers to two Braking unit paralleled with their respective brake
resistor; the meaning of ×3 is the same with ×2.
Recommended
Power of
Brake Resistor
6.5 kW×2
16kW
Recommended
Resistance
Value of Brake
Resistor
≥8Ω×2
≥2.5Ω Externally
Braking
Unit
Externally
connected
connected
MDBU-70-B×2
MDBU-210-B
Remarks
- 25 -
Page 32
Mechanical and Electric
- 26 -
Page 33
Chapter 3 Mechanical and Electric
Installation
3.1 Mechanical installation
3.1.1 Installation environment:
1) Ambient temperature: The ambient temperature exerts great
influences on the service life of the servo driver and is not allowed to
exceed the allowable temperature range (-10 Celsius to 50 ℃℃
Celsius).
2) The driver shall be mounted on the surface of incombustible articles,
with sufficient spaces nearby for cooling. The servo driver is easy to
generate large amount of heat during the operation. The servo
driver shall be mounted vertically on the base with screws.
3) The servo driver shall be mounted in the place without vibration or
with vibration of less than 0.6G, and shall be kept away from such
equipment as punching machine.
4) The servo driver shall be mounted in locations free from direct
sunlight, high humidity and condensate.
5) The servo driver shall be mounted in locations free from corrosive
gas, explosive gas or combustible gas.
6) The servo driver shall be mounted in locations free from oil dirt, dust,
and metal powder.
上
B
AA
Single Unit Installation Diagram Installation Diagram of
IS300
B
右
Upper and Lower Parts
- 27 -
Page 34
When the servo driver power is not higher than IS300T040, the A size can be
omitted. When the servo driver power is higher than IS300T040, the A size
shall be higher than 50mm.
When installing the upper and lower parts of the servo driver, the insulating
splitter is required.
IS300T035—IS300T050 ≥200mm ≥50mm
3.1.2 Cooling problem shall be taken into a ccount during the mechanical
installation. Pay attention to the following items:
1) Install the servo driver vertically so that the heat may be expelled
2) The mounting space shall be as indicated as the above figure, so as
3) The installation bracket must be flame retardant.
4) In the applications where there are metal dusts, it is recommended to
Power level
≤IS300T030 ≥100mm No requirements
≥IS300T070 ≥300mm ≥50mm
Fig.3-1 Servo Driver Installation Diagram
from the top. However, the equipment cannot be installed upside
down. If there are multiple servo drivers, parallel installation is a
better choice. In applications where the upper and lower parts of the
driver need to be installed, please refer to “Servo driver Installation
Diagram” and install an insulating splitter.
to ensure the cooling space of the Servo driver. However, the heat
dissipation of other devices in the cabinet shall also be taken into
account.
mount the radiator outside the cabinet. In this case, the space in the
sealed cabinet shall be large enough.
Physical Dimensions
B A
3.1.3 Removing and mounting the down cover plate:
The IS300T030 (included) employs plastic enclosure. Please refer to Figure
3-2 for removing the lower cover plate of the plastic enclosure. The hooker of
- 28 -
Page 35
the lower cover plate is easy to pull out with tools by forces inside.
Fig.3-2 Removing theDown Cover Plate of Plastic Enclosure
The servo driver above IS300T035 (included) employs sheet-metal enclosure.
Please refer to Figure 3-3 for removing the down cover plate of the sheet-metal
enclosure. It is easy to loosen the screws of the upper cover plate with tools.
zWhen removing the upper cover plate, be sure to avoid the falling of the
upper cover, which may cause human injury or damage to the equipment.
- 29 -
Page 36
Down Cover Plate
Fig.3-3 Removing the Down Cover Plateof Sheet-Metal Enclosure
3.1.4 The Installation of permanent-magnet sy nchronous serv o motor and
pressure transducer
Servo motors work process will appear to start and stop state from repeated
high-speed.It easily lead to motor vibration, causing system instability.Please
make sure that the electrical installation is fixed and reasonable.
Take the following one installation fixed way (the massive rubber cushion with
fixed bolts) as an example for reference.
screw bolt
rubber mat
Injection molding machine
supporting frames
screw nut
Fig.3-4 Permanent-magnet Synchronous Servo Motor Installation Diagram
- 30 -
Page 37
The Servo pump work process would lead to vacuum state,in order to prevent
air entering the pressure sensor intra-cavity that cause the pressure sensor
damaged,please ensure the pressure sensor cavity always retain hydraulic oil,
Please follow the oil pressure sensor installed vertically upward, as shown at
the fllowing.
Fig.3-5Pressure Sensor Installtion Mode
3.2 Electrical Installation
3.2.1 Guide to the external electrical parts:
Table 3-1 Guide to Prototyping of External Electrical Parts of IS300 servo
3.2.2 Using instruction of external electrical parts:
Table 3-2 Instruction for the Use of External Electrical Parts of IS300 Servo
Driver
Part
Name
Circuit
breaker
Contactor
AC input
reactor
Mounting Location Function description
Front end of input
circuit
Between the circuit
breaker and the servo
driver input side
Input side of the servo
driver
Disconnect the power supply when the
equipment at the lower part is over current.
Connection and disconnection of servo
driver. Frequent power-on and power-off
operations on the servo driver shall be
avoided.
1) Improve the power factor of the input
side;
2) Eliminate the higher harmonics of the
- 32 -
Page 39
Part
Name
EMC
Input
filter
DC
reactor
AC
output
reactor
Mounting Location Function description
input side effectively and prevent other
equipment from damaging due to
distortion of voltage wave.
3) Eliminate the input current unbalance
due to unbalance between the power
phases.
1) Reduce the external conduction and
radiation interference of the servo driver.
Input side of the servo
driver
IS300 series servo
driver adopts DC
reactor above
IS300T015 (included)
as standard.
Between the servo
driver output side and
the motor. Close to
the servo driver.
2) Decrease the conduction interference
flowing from the power end to the servo
driver and improve the anti-interference
capacity of the servo driver.
1) Improve the power factor of the input
side;
2) Improve the whole efficiency and
thermal stability of the servo driver.
3) Eliminate the impact of higher
harmonics of the input side on the servo
driver and reduce the external conduction
and radiation interference.
The servo driver output side generally
has higher harmonics. When the motor is far
from the servo driver, since there are many
distributed capacitors in the circuit, certain
harmonics may cause resonance in the
circuit and bring about the following two
impacts:
1) Degrade the motor insulation
performance and damage the motor for
the long run.
2) Generate large leakage current and
cause frequent servo driver protection.
In general, the distance between the
servo driver and the motor exceeds 100
meters. Installation of output AC reactor is
recommended.
- 33 -
Page 40
3.2.3 Connections of servo pump
Schematic Diagram for Servo Pump Connections
3.2.4 Main Circuit Terminals and Connections
zMake sure that the power switch is in OFF status prior to perform wiring
connection. Otherwise there may be danger of electric shock!
z
z Only the qualified and trained personnel can perform wiring connection.
Otherwise it may cause equipment and human injuries!
z It shall be earthed reliably. Otherwise there may be danger of electric
shock or fire!
zMake sure that the rated value of the input power supply is consistent
with that of the driver. Otherwise it may damage the driver!
zMake sure that the motor matches the driver. Otherwise it may damage
the motor or generate driver protection!
z Do not connect the power supply to the terminals of U, V and W.
Otherwise it may damage the driver!
zDo not directly connect the brake resistor between the DC bus terminals
(+) and (-). Otherwise it may cause fire!
- 34 -
Page 41
1)Description of main circuit terminals of single-phase servo driver:
Terminals Name Description
Input
R、S、T R、
S and T
(+)、 (-)(+)
and (-)
(+)、PB(+)
and PB
P、(+)P
and (+)
U、V、W U,
V and W
3) Precautions on Wiring:
terminal of
three-phase
power
supply
Negative
and positive
terminals of
DC bus
Connecting
terminal of
brake
resistor
Connection
terminal of
external
reactor
Output
terminal of
servo driver
Earth
terminal
a) Input power R, S and T:
The cable connection at the input side of the servo driver has no phase
sequence requirement.
b) DC bus (+) and (-) terminals:
Note that the (+) and (-) terminals of DC bus have residual voltage right
after power-on. It needs to wait until the CHARGE indictor is OFF and
make sure that the voltage is less than 36V prior to wiring connection.
Otherwise there may be danger of electric shock.
When selecting external brake unit for the driver of above IS300T07
(inculded), the poles of (+) and (-) shall not be connected reversely, or it
AC single-phase 220V power connection point
Shared DC bus input point (connection point of
external braking unit of above IS300T070
(included)
Connection point of Brake resistor of below
IS300T050(included)
Connection point of external reactor above
IS300T140(included)
Connect the three-phase motor
Earth terminal
- 35 -
Page 42
may damage the driver and even cause fire.
The wiring length of the brake unit shall not exceed 10 meters. Twisted
wires or pair wires shall be used and connected in parallel.
Do not connect the brake resistor directly to the DC bus, or it may
damage the servo driver and even cause fire.
c) Connecting terminals (+) and PB of brake resistor:
The connecting terminals of the brake resistor are effective only for the
servo driver of below IS300T050 (inculded) with built-in brake unit.
The prototype of brake resistor can refer to the recommended value and
the wiring length shall be less than 5 meters. Otherwise it may damage
the servo driver.
d) Connecting terminals P and (+) of external reactor:
For the servo driver of above IS300T140 (included)with external reactor,
when assembling, remove the connector between terminals P and (+)
and connect a reactor instead.
e) Terminals U, V, W at the output side of the servo driver:
The servo driver output side cannot connect to the capacitor or surge
absorber. Otherwise, it may cause frequent servo driver protection and
even damage the servo driver.
In case the motor cable is too long, it may generate electrical resonance
easily due to the impact of distributed capacitance, thus damaging the
motor insulation or generating higher leakage current to invoke over
current protection of the servo driver. When the length of motor cable is
longer than 100 meters, it needs to install a AC output reactor.
f) Earth terminal
This terminal shall be earthed reliably, with resistance of earth cable of
less than 0.1Ω. Otherwise, it may cause fault or damage the servo
driver.
Do not share the earth terminal and zero line of the power supply.
PE:
3.2.5 Control terminals and connection:
1)The control circuit terminals are arranged as follows:
- 36 -
Page 43
Fig.3-7 Layout of Control Circuit Terminals
2)Function description of control terminal:
Table 3-3 Description of Control Terminal Function of Servo Driver
Type Terminal Terminal name Func tio n de s cription
Provide 10V±10% power supply for
external- units, and the maximum
output current is 10mA.
+10V-GND 10V power supply
power supply
+13V-GND
Pressure sensor
power supply
It is generally used as the operating
power supply for the external
potentiometer.
The potentiometer resistance range
is 1kΩ~ 5kΩ.
Provide 13V±10% power supply for
external units.
The maximum output current is
10mA.
It is generally used as the operating
power supply for pressure sensor.
- 37 -
Page 44
Type Terminal Terminal name Func tio n de s cription
Provide +24V power supply for
external units. It is generally used as
the operating power supply for digital
input/output terminals.
24V±10%, no-load vitual
voltage can not exceed 30V.
The maximum output current is
200mA. It is internally insulated with
GND.
COM and 24V is internally
insulated .Connect to 24V by default
upon delivery.
When external signal is used to drive
DI1
~DI5, OP needs to connect to
the external power supply and
disconnect from the +24V power
terminal.(It is determined by the J4
jumper on the control board.)
1. Input range: ±10V/0 to 20mA,
which is determined by J3 jumper on
the control board. There is 12-bit
resolution, the correction
is 0.5 pensent.
2. Input impedance: It is 100kΩ at the
time of voltage input and 500Ω at the
time of current input.
precision is 0.5 pensent.
precision
Anal
og
Input
+24V-COM
OP
AI1-GND
AI2-GND
AI3-GND
+24V power
supply
External power
input terminal
Analog input
terminal 1
(The default
pressure setting)
Analog input
terminal 2
(The default flow
settup)
Analog input
terminal 3
(default
pressure sensor
signal input)
- 38 -
Page 45
Type Terminal Terminal name Func tio n de s cription
Digit
al
Input
Com
muni
catio
n
Termi
nal
Anal
og
Outp
ut
Real
y
DI1-COM Digital input 1
DI2-COM Digital input 2
DI3-COM Digital input 3
DI4-COM Digital input 4
DI5-COM Digital input 5
PTCP-PTCN
CANH
CANL
CGND
485B
485A
AO1-GND Analog output 1
AO2-GND Analog output 2
T/A1-T/B1
Motor overheating
protection input
CAN
Communication
terminal
485
Communication
terminal
Normally closed
terminal
1 、 Insulate drain-to-source input
programmable terminals,input
frequency is less than 100
2、 Input resistance:3.3kΩ;
3、Voltage range for level input :
9V
~ 30V。
Motor overheating protection PTC
sensor,support PTC130 、 PTC150
etc.
The higest communication speed is
1Mbps.Whether to connect terminal
resistance is determined by the J4
jumper on the control board.
Retain the terminal without the
funtion by default, the highest
communication speed is 230Kbps
with isolation.
The voltage or current output is
determined by the J3 jumper on the
control board.
Output range: 0V
20mA. There is 12-bit resolution, the
correction
the maximum load resistance value
is not less than 500Ω.
The voltage or current output is
determined by the J24 jumper on the
control board.
Output range: 0V
0mA
~ 20mA.
There is 12-bit resolution, the
correction
pensent,the maximum load
resistance value is not less than
500Ω.
Contact driving capacity:
~10V and 0mA~
precision is 1 pensent,
precision is 1
Hz;
~ 10V and
- 39 -
Page 46
Type Terminal Terminal name Func tio n de s cription
outp
ut
Auxil
ary
interf
ace
T/A1-T/C1
T/A2-T/C2
T/A3-T/C3
CNR1
Function Instructions of PG Card Terminal
Table 3-4
3) Description of Connection of control terminals:
interferences, it needs to employ shielded cable generally and the length shall
be no longer than 20 meters, as shown in Fig. 3-8. In case the analog signal
is subject to severe interference, and analog signal source side shall be
installed with filter capacitor or ferrite magnetic core, as shown in Fig.3-9.
Function Instructions of Servo Driver PG Card Terminal
Itemname Description
1 EXC
2 /EXC
3 SIN
4 SINLO
5 COS
9 COSLO
6 PTC-P
7 PTC-N
8 -- --
A. Analog input terminal:
Since the weak analog voltage signal is easy to suffer external
Normally open
terminal
Normally open
terminal
Normally open
terminal
External keyboard
interface
Excitation Signal
SIN Feedback Signal
COS Feedback Signal
Motor overheating protection PTC
sensor,support PTC130 、PTC150 ,etc.
AC250V,3A,COSφ=0.4。
DC 30V,1A。
External keyboard and parameter
copy unit interface
- 40 -
Page 47
Fig.3-8 Schematic Diagram for Connection of Input Terminal of Analog Signal
External
analog
source
0.22μF 50V
C
Shielded twisted-pa ir
cable
Ferrite bead (In the same
direction around two
circles)
IS300
AI1
GND
Fig.3-9 Schematic Diagram for Connection of Input Terminal of Analog Signal
B:Digital input terminal:
It needs to employ shielded cable generally, with cable length of no more
than 20 meters.
When enabled driving is adopted, necessary filtering measures shall be
taken to prevent the interference to the power supply.
It is recommended to use the contact control mode.
- 41 -
Page 48
C. DI Terminal Connection:
1、Connection with dry contact sharing the negative pole
Control board of servo driver
Fig.3-11 Connection with dry contact sharing the negative pole
This is one of the most commonly used connection mode. If external power
supply is used, it must remove the short circuit copper bars between +24V and
OP respectively,(which is determined by J11 jumper on the control board. )
and connect the positive pole of external power supply to OP and negative
pole to CME.
- 42 -
Page 49
2、Connection with dry contact sharing the positive pole
Control board of servo driver
Fig.3-11 Connection with dry contact sharing the positive pole
It must remove the short circuit copper bar between +24V and OP(which is
determined by J11 jumper on the control board.)and then connect OP with
CME.
- 43 -
Page 50
Operation and Display
- 44 -
Page 51
Chapter4 Operation and Display
4.1 Introduction to Operation and Display Interface
With the operation panel, it can perform such operations on the driver as
function parameter modification, driver working status monitoring and driver
running control (startup and stop). Refer to Fig.4-1 for the physical appearance
and functional zone of the operation panel.
Fig.4-1 Operation Panel Diagram
1) Description of Function LED Indictor:
RUN: When it is OFF, it indicates the driver is in stop status; when it is ON, it
indicates the driver is in rotation status.
LOCAL/REMOT: It is the LED indictor for keyboard operation, terminal
operation and remote operation (communication control). When it is OFF, it
indicates the keyboard operation control status; when it is ON, it indicates the
terminal operation control status; when it flashes, it indicates the remote
operation control status.
- 45 -
Page 52
FWD/REV: It is the LED indictor for forward/reverse rotation. When it is OFF, it
indicates the driver is in forward rotation status; when it is ON, it indicates the
driver is in reverse rotation status.
TUNE/TC: It is the LED indictor for tuning. When it is ON it indicates the torque
control status; when it is OFF, it indicates the speed control status.
2) Unit LED indictor description:
Hz refers to frequency unit.
A refers to current unit.
V refers to voltage unit.
RPM refers to rotation speed unit.
% refers to percentage
3) Digital display zone:
Five-digit LED display, able to display setup frequency, output frequency,
various monitoring datas and alarm codes.
- 46 -
Page 53
4) Keyboard button description
Button Name Function
PRG
ENTER
∧ Increase key
∨ Decrease key
>> Shift key
RUN Running key
STOP/RESET Stop/reset
QUICK Shortcut key
MF.K
Programming
key
Confirmation
key
Multi-function
selection key
Table 4-1 Keyboard Function
entry and exit of primary menu, deletion of
shortcut parameter
enter the menu interfaces level by level, and
confirm the set parameters.
increase of the data or function code
decrease of the data or function code
Select the displayed parameters in turn on
the stop display interface and running
display interface, and select the modification
digit of parameters when modifying
parameters.
It is used to start the running of the driver
under keyboard control mode.
Press this button to stop the running in the
running status and reset the operation in the
fault alarm status. These button
characteristics are limited by the function
code F7-02.
It can be used to enter or exit level 1 menu
of the shortcut menu. Refer to the QUICK
operation description for details.
In case F7-01=0, it has no function;
In case F7-01=1, it serves as the key
switching between local operation and
remote operation.
In case F7-01=2, it serves as
forward/reverse rotation switching key;
In case F7-01=3, it serves as forward
rotation Jog key;
Refer to F7-01 for the detailed operation.
- 47 -
Page 54
4.2 Description of Function Code Viewing and
Modification Methods
The operation panel of the IS300 servo driver adopts three-level menu
structure to carry out operations such as parameter setting.
The three-level menu includes function parameter set (level 1
menu)→Function code (level 2 menu)→Function code setup value (level 3
menu). Refer to Fig.4-2 for the operation procedure.
Parameter Set Modification
Function Code Modification
Function Code Modification
First-level Menu
Second-level Menu
Third-level Menu
Fig.4-2 Operation Procedure of Three-level Menu
Note: When operating on level 3 menu, press PRG key or ENTER key to return
to level 2 menu. The difference between PRG key and ENTER key is
described as follows: Pressing ENTER KEY will save the setup parameter and
return to the level 2 menu and then automatically shift to the next function code,
while pressing PRG key will directly return to level 2 menu without saving the
parameter, and it will return to the current function code.
Example: Modify the function code F3-02 from 10.00Hz to 15.00Hz. (The
bold-type work indicates the flashing bit.)
Fig.4-3 Example of parameter editing operation
In level 3 menu, if the parameter has no flashing bit, it indicates that the
function code cannot be modified. The possible reasons include:
1) The function code is an unchangeable parameter, such as actual
detection parameter, running record parameter, etc.
2) The function code cannot be modified in running status. It can be
modified only after the unit is stopped.
- 48 -
Page 55
4.3 Shortcut Menu Operation Mode
The shortcut menu is set to facilitate the user to quickly view and modify the
commonly used function parameters. In the shortcut menu, the parameter is
displayed in the form of “UA3-01”, which indicates the function parameter
A3-01. Parameter modification in the shortcut menu has the same effect as the
operation in the common programming status.
The shortcut menu can contain 16 function parameters at most. If there are 16
parameters and the user wants to add more, it will display “FULL”. If “NULL” is
displayed when entering the menu, it indicates that the shortcut menu is NULL.
The shortcut menu operation is limited by the function code F7-03. When F7-3
is set to “0”, addition or deletion operation can be performed on the shortcut
menu. When F7-03 is set to “1”, the parameter option is locked and addition or
deletion operation is inenabled.
The shortcut menu has stored the 16 common parameters by default for the
convenience of the user:
uA3-01 Maximum rotation speed
uA3-02 System oil pressure
uA3-03 Maximum oil pressure
uA3-04 Oil pressure command
risetime
uA3-05 Kp1Oil pressure control
Kp1
uA3-06 Ti1 Oil pressure control Ti1
uA3-07 Td1 Oil pressure control
Td1
uA3-08 Maximum reverse rotation
speed
uF4-32 AI3 Input filter time
uA3-09 Minimum flow
uA3-10 Minimum pressure
A3-20 AI zero drift auto correction
uF2-00 Speed loop proportional
gain 1
uF2-01 Speed loop integration
time 2
uF2-03 Speed loop proportional
gain 2
uF2-04 Speed loop integration
time 2
The user can edit the shortcut menu in accordance with the actual needs.
1) Add shortcut parameter item:
Flash Display
Stop Display
Stop Flashing
Fig.4-4 Example of Adding Shortcut Parameter Item
Note: When pressing QUICK key during the programming of level 2 menu, the
- 49 -
Page 56
display flashes and prompts whether to save the parameter into shortcut menu.
Press ENTER key for confirmation, the display stops flashing, and the
operation is completed. Press PRG key to cancel, the display stops flashing,
and the operation is cancelled.
2) Modification of shortcut parameters
Run or Stop
Display
Fig.4-5 Example of Modification of Shortcut Parameters
Run or Stop Desplay:
Note: In Stop or running display interface, press QUICK key to enter shortcut
key, and select different shortcut parameters with UP/DOWN key. Then press
ENTER key to enter next level of menu. At this time the modification method of
shortcut parameter is the same as that of the parameters in common level 3
menu. To return to the upper level display, press QUICK key, and the
modified parameters will not be saved.
3) Delete shortcut parameter item:
Flash display
Fig.4-6 Deletion of Shortcut Menu
Note: Press PRG key in shortcut menu, the display flashes and prompts
whether to delete the parameter. Press ENTER key for confirmation, the
display stops flashing and the deletion operation is completed. Press QUICK
key, the display stops flashing, and the deletion operation is canceled. If the
last shortcut parameter is deleted, “NULL” will be displayed upon deletion,
indicating that the shortcut menu is NULL.
- 50 -
Page 57
4.4 Method of Viewing Status Parameter
In stop or running status, it can display multiple status parameters.
It can select whether to display the parameter through the function
codes F7-04 (running parameter) and F7-05 (stop parameter) in
accordance with the binary bits. For the meanings of the binary bits,
refer to Chapter 6 F7-04 and F7-05 Function Codes for details.
In the
running status, five running status parameters are always displayed,
namely, setup frequency, bus voltage, output voltage , and output current, and
other sixteen parameters, namely, DI input status, DO output status, analog
input AI1 voltage, analog input Al2 voltage, analog input AI3 voltage and four
reserved parameters ,etc.They are displayed in accordance with the selection
of F7-04 (converted into decimal system). The displaying of the selected
parameters may be switched by the button sequence.
In the stop status, there are totally sixteen stop status parameters for selection,
namely, setup frequency, bus voltage, DI input status, DO output status,
analog input AI1 voltage, analog input Al2 voltage, analog input AI3 voltage(or
current) and five reserved parameters,They are displayed in accordance
with the selection of F7-05 (converted into decimal system).The displaying of
the selected parameters may be switched by the button sequence.
When the servo driver is restarted upon power shutdown, the displayed
parameters are the parameters selected before the power shutdown.
4.5 Password Setup
The driver provides user password protection function. When FP-00 is set to
non-zero value, it indicates the user password, and the password protection
turns valid after exiting the function code editing status. When pressing PRG
key again, “------“ will be displayed, and common menu cannot be entered until
user password is input correctly.
To cancel the password protection function, enter with password and set
FP-00 to “0”.
The user password protection for the parameter items in the shortcut men
depends on the status of F7-03, and is inenabled for the parameter values.
- 51 -
Page 58
4.6 Automatic Tuning of Motor Parameters
To select the vector control running mode, it must input the nameplate
parameter of the motor accurately prior to the running of the driver. The IS300
servo driver will select standard motor parameters matching the nameplate
parameter. Since the vector control mode relies highly on the motor
parameters, it must acquire the accurate parameters of the controlled motor to
ensure the good control performance.
The procedures for the automatic tuning of motor parameters are described
below:
First, select the command source (F0-02) as the command channel of the
operation panel.
Second, input the following parameters in accordance with the actual motor
parameters:
F1-01: Rated motor power
F1-02: Rated motor voltage
F1-03: Rated motor current
If the
back EMF of motor is unknown, please make the motor completely
disconnect from the load,and set F1-16=“2”(dynamic tuning),and press RUN
key on the keyboard panel, then the servo driver will automatically calculate
the following parameters:
F1-11: D axis inductors
F1-12: Q axis inductors
F1-13: Stator resistance
Finally, complete the dynamic tuning of motor parameters.
If the motor back-EMF is known, please set the parameter to F1-15
according to the motor back-EMF ,the motor can not be completely disconnect
from the load,and set F1-16=“2”(dynamic tuning),and press RUN key on the
keyboard panel, then the servo driver will automatically calculate the following
parameters:
F1-10: No-load current
F1-11: D axis inductors
F1-12: Q axis inductors
F1-13: stator resistor
F1-04: Rated motor frequency
F1-05: Rated rotation speed of
motor
F1-14: Unit
F1-15: Back EMF
A1-02: Encoder installation angle
F1-14: Unit
F1-15:
Back EMF
A1-02: Encoder nstallation angle
I
- 52 -
Page 59
Finally, complete the static tuning of motor parameters.
You can calculate motor
the motor basic parameters for calculation are rated-EMF coefficient of
V1000rpm (V/1000rpm) and the rated speed v (RPM):
Motor back EMFcalculation method as show follows:
Back EMF: Vemf = V1000 * v/1000
back-EMF according to the motor basic parameters,
- 53 -
Page 60
Function Parameter Table
- 54 -
Page 61
Chapter 5 Function Parameter Table
If FP-00 is set to non-zero value, it means parameter protection password is
set, and the parameter menu cannot be entered until correct password is input.
To cancel the password, it needs to set FP-00 to “0”.
The parameters in the shortcut menu are free from password protection.
The symbols in the function table are described as follows:
It indicates that the parameter setup value can be modified when the driver is
in stop status and running status.
It indicates that the parameter setup value cannot be modified when the driver
is in the running status.
It indicates that the numerical value of the parameter is the actually measured
value, which cannot be modified.
“*”: It indicates this parameter is “Factory default parameter” and can be set
only by the manufacturer.
- 55 -
Page 62
Function Parameter Table
(Common Parameter reference to appendix table)
Function
code
U0-00
U0-01 Setup frenquency
U0-02 Bus voltage Bus voltage 0V~ 830V - - ●
U0-03 Output voltage Output voltage
U0-04 Output Current Output Current 0.01A ~ 655.35A - - ●
U0-05
U0-06 Output torque Output torque
Name LED display Setup range
Group U0 Driver Parameter Viewing Group
Running
frenquency
Output
power
Running
frenquency
Setup
frenquency
Output
power
0.00Hz ~ maximum
frequency(F0-10)
0.00Hz ~T
maximum frequency
(F0-10)
0V ~ Motor rated
voltage(F1-02)
0.4kW ~1000.0kW- - ●
0.0% ~ Upper limit
torque(F2-10)
Minimu
m unit
Factory
default
- - ●
- - ●
- - ●
- - ●
value
descrip-t
Modific-
ation
ion
U0-07
U0-08
U0-09
U0-10
Local DI/DO
status
Expansion DI /
DO status
Voltage(after
corrected)
AI12 voltage after
corrected)
Local DI/DO
status
Expansion DI /
DO status
Voltage(after
corrected)
AI12 voltage
after corrected)
●
●
-10.00V~10.000V - - ●
-10.00V~10.000V - - ●
- 56 -
Page 63
Function
code
U0-11
U0-12~
U0-29
U0-30
U0-31
U0-32
A0-00
A0-01
A0-02
A0-03
A0-04
A0-05
Name LED display Setup range
AI3voltage after
corrected)
Reserved - - - - ●
AI11voltage
(before
corrected)
AI12voltage
before corrected)
AI13voltage
before corrected)
Weak magnetism
control mode
Weak
magnetismcurren
t coefficient
Weak magnetism
current upper
limit
Weak magnetism
Integral multiples
Weak magnetism
adjustment
coefficient
Output phase
failure PWM
detection time
AI3voltage after
corrected)
AI11voltage
(before
corrected)
AI12voltage
before corrected)
AI13voltage
before corrected)
Group A0 Weak Magnetism and SVC Control Group
Weak
magnetism
control mode
Weak
magnetism
current
coefficient
Weak
magnetismcurre
nt upper limit
Weak
magnetism
Integral multiples
Weak
magnetism
adjustment
coefficient
Output phase
failure PWM
detection time
-10.00V~10.000V - - ●
-10.00V~10.000V - - ●
-10.00V~10.000V - - ●
-10.00V ~10.000V- - ●
0: Direct calculation
1: Automatic
adjustment
80%~200% 1 100% ★
0~120 1 100% ★
200~1000 1 400 ★
0~100 1 4 ★
0~63000 1 0 ★
Group A1 PG Card
Minimu
m unit
Factory
default
value
1 0 ★
Modific-
ation
descrip-t
ion
- 57 -
Page 64
Function
code
A1-00~
A1-01
A1-02
A1-03
A1-04
A2-00
A2-01
A2-02
F0-00 Model display Model display
Name LED display Setup range
Reserved - - - - ★
Encoder
installation angle
Select the
reverse feedback
speed
Rotary
transformer
number of
pole-pairs
Baud rate
selection
CAN
communication
address
CAN
communication
continuous time
Encoder
installation angle
Select the
reverse feedback
speed
Rotary
transformer
number of
pole-pairs
Group A2 CAN Communication Group
Baud rate
selection
CAN
communication
address
CAN
communication
continuous time
Group F0 Basic Function Group
value
nt
Modific-
ation
descrip-t
ion
●
Minimu
m unit
0.0°~359.9° 0.1° 0.0° ☆
0~1 1 0 ☆
1~50 1 1 ★
0:20k
1:50k
2:125k
3:250k
4:500k
5:1M
1~255 1 1 ☆
0.0s(inenabled)
0.1s~5.0s
1: G model (heavy
load model)
2: P model (light load
model)
0.1s 0.0s ☆
Factory
default
1 4 ☆
Model
1
depende
- 58 -
Page 65
Function
code
F0-01 Control mode Control mode
F0-02
F0-03
Name LED display Setup range
Command source
selection
Main frequency
source X
selection
Command
source selection
Frequency
source X
selection
Minimu
0: Speed sensorless
vector control (SVC)
1: Speed sensor
vector control (VC)
2:V/F control
0: 0:Operation panel
running command
channel (LED OFF)
1: Terminal
command channel
(LED ON)
2: Serial port
command channel
(LED flashes)
0: Digital setup UP
and DOWN
adjustment
(non-recorded)
1: Digital setup UP
and DOWN
adjustment
(recorded)
2: Al1
3: Al2
4: Al3
5:Reserved
6: MS speed
7: Resvered
8: Resvered
9: Communication
setup
Factory
m unit
default
value
1 1 ★
1 0 ☆
1 1 ★
Modific-
ation
descrip-t
ion
- 59 -
Page 66
Function
code
F0-04
F0-05
F0-06
Name LED display Setup range
0:Digital setup UP
and DOWN
adjustment
(non-recorded)
1: Digital setup UP
and DOWN
Auxiliary
Frequency
source Y
selection
Auxiliary
Frequency
source Y range
selection
Auxiliary
Frequency
source Y
Auxiliary
Frequency
source Y
selection
Auxiliary
Frequency
source Y range
selection
Frequency
source Y range
adjustment
(recorded)
2: AI1
3: AI2
4: AI3
5:Reserved
6: MS speed
7: Reserved
8: Reserved
9: Communication
setup
0: Relative to
maximum frequency
1: Relative to
frequency source X
0%~100% 1% 100% ☆
Minimu
m unit
Factory
default
value
1 0 ★
1 0 ☆
Modific-
ation
descrip-t
ion
- 60 -
Page 67
Function
code
F0-07
F0-08 Preset frequency Preset frequency
F0-09 Running direction
F0-10
Name LED display Setup range
Frequency
source selection
Maximum
frequency
Frequency
source selection
Running
direction
Maximum
frequency
Minimu
m unit
0: Main frequency
source X
1: Main frequency
source X plus
auxiliary frequency
source Y
2: Switching
between main
frequency source X
and auxiliary
frequency source Y
3: Switching
between main
frequency source X
and (main
frequency source X
plus auxiliary
frequency source Y)
4: Switching
between main
frequency source Y
and (main
frequency source X
plus auxiliary
frequency source Y)
0.00Hz ~ the
maximum frequency
F0-10
0: Consistent
direction
1:Reverse direction
50.00Hz~300.00Hz1
1 0 ☆
0.01Hz50.00Hz ☆
1 0 ☆
Factory
default
value
200.00
Hz
Modific-
ation
descrip-t
ion
★
- 61 -
Page 68
Function
code
F0-11
F0-12
F0-13
F0-14
F0-15 Carrier frequency
Name LED display Setup range
Frequency
source upper limit
Frequency
upper limit
Frequency upper
limit offset
Frequency
lower limit
Frequency
source upper
limit
Frequency
upper limit
Frequency upper
limit offset
Frequency
lower limit
Carrier
frequency
Minimu
m unit
0: F0-12 setup
1: AI1
2: AI2
3: AI3
4: Reserved
5: Communication
setup
Frequency lower
limit F0-14 ~
maximum
frequencyF0-10
0.00Hz ~ The
maximum frequency
F0-10
0.00Hz ~ frequency
upper limit F0-12
0.5kHz~16.0kHz 0.1kHz
1 0 ★
0.01Hz
0.01Hz0.00Hz ☆
0.01Hz0.00Hz ☆
Factory
default
value
200.00H
z
Model
depende
nt
Modific-
ation
descrip-t
ion
☆
☆
- 62 -
Page 69
value
nt
Modific-
descrip-t
Function
code
F0-16
F0-17 Speed-up time 1 Speed-up time 1 0.0s~6500.0s 0.1s 20.0s ☆
F0-18
F1-00
F1-01 Rated power Rated power 0.4kW~1000.0kW 0.1kW
Name LED display Setup range
0: Fixed PWM,
carrier frequency
temperature
adjustment is
inenabled
1: Random PWM,
carrier frequency
Carrier frequency
adjustment
selection
Speed-down
time1
Motor type
selection
Carrier
frequency
adjustment
selection
Speed-down
time1
Group F1 Motor Parameters
Motor type
selection
temperature
adjustment
inenabled
2: Fixed PWM,
carrier wave
temperature
adjustment valid
3: Random PWM,
carrier frequency
temperature
adjustment enabled
0.0s~6500.0s 0.1s 20.0s ☆
0: Common
asynchronous motor
1: Variable
frequency
asynchronous motor
2: Permanent
magnetic
synchronous motor
Minimu
m unit
Factory
default
1 2 ☆
1 2 ★
Model
depende
ation
ion
★
- 63 -
Page 70
Function
code
F1-02 Rated voltage Rated voltage0V~440V 1V
F1-03 Rated current Rated current 0.01A~655.35A 0.01A
F1-04 Rated frequency Rated frequency 0.00~max 0.01Hz
status output
20: Communication
setup
21~22 Reserved
23: Swash Plate
Switching of Double
displacement
plunger pump (NO)
24: Pressure control
status output
25: Alarm output
from pump(NC)
Minimu
m unit
Factory
default
value
1 0 ☆
Modific-
ation
descrip-t
ion
F5-04~
F5-09
Reserved - - - - ☆
- 74 -
Page 81
value
Modific-
descrip-t
Function
code
F5-10
F5-11
F5-12~
F5-13
F5-14
F5-15 AO1 gain AO1 gain -10.00~10.00 0.01 1.00 ☆
F5-16
Name LED display Setup range
0: Running
1: Setup frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
6:Reserved
AO1 output
selection
AO2 output
selection
Reserved - - - - ☆
AO1 offset
coefficient
AO2 offset
coefficient
AO1output
selection
AO2 output
selection
AO1 offset -100.0%~100.0% 0.1% 0.0% ☆
AO2 offset -100.0%~100.0% 0.1% 0.0% ☆
7: AI1
8: AI2
9: Al3
10 : Feedback
frequency
11 : Feedback
voltage
12~16:
Reserved
11 ☆
Minimu
m unit
Factory
default
1 10 ☆
ation
ion
F5-17 AO2 gain AO2 gain -10.00~10.00
F5-18~
F5-22
Reserved - - - - ☆
Group F6 Start/Stop Control
- 75 -
0.01 1.00 ☆
Page 82
value
Modific-
descrip-t
Function
code
F6-00 Start mode Start mode
F6-01
F6-02
F6-03 Start frequency Start frequency 0.00 Hz~10.00Hz 0.01Hz0.00Hz ☆
F6-04
F6-05
F6-06
F6-07
F6-08
F6-09
F6-10 Stop mode Stop mode
Name LED display Setup range
0: Beginning from
stop frequency
1: Beginning from
zero speed
2: Beginning from
maximum frequency
0: Beginning from
stop frequency
Rotation speed
tracking mode
Rotation speed
tracking speed
Start frequency
retention time
DC brake current
at start
DC brake time at
start
Speed-up/speed-
down mode
Start segment
time of S curve
End segment
time of S curve
Rotation speed
tracking mode
Rotation speed
tracking speed
Start retention
time
DC brake current
at start
DC brake time at
start
Speed-up/
speed-down
mode
Start segment of
S curve
Start segment of
S curve
1: Beginning from
zero speed
2: Beginning from
maximum frequency
1~100 1 20 ☆
0.0s~36.0s 0.1s 0.0s ★
0%~100% 1% 0% ★
0.0s~36.0s 0.1s 0.0s ★
0: Straight
speed-up/speed-dow
n
1:S-cruve
speed-up/speed-dow
n
0.0%~40.0% 0.1% 30.0% ★
0.0%~40.0% 0.1% 30.0% ★
0:Speed-down to
stop
1: Free to stop
Minimu
m unit
Factory
default
1 0 ☆
1 0 ★
1 0 ★
1 0 ☆
ation
ion
- 76 -
Page 83
value
Modific-
descrip-t
Function
code
F6-11
F6-12
F6-13
F6-14
F6-15 Brake use ratio Brake use ratio 0%~100% 1% 100% ☆
F7-00
F7-01
Name LED display Setup range
DC brake
beginning
frequency at stop
DC brake waiting
time at stop
DC brake current
at stop
DC brake time at
stop
LCD Language
selection
MF.K Key
function selection
Brake frequency
at stop
Brake waiting at
stop
DC brake current
at stop
DC brake time at
stop
Group F7 Keyboard and Display
Language
selection
MF.K Key
function
selection
0.00Hz ~ maximum
frequency
0.0s~36.0s 0.1s 0.0s ☆
0%~100% 1% 0% ☆
0.0s~36.0s 0.1s 0.0s ☆
0: Chinese
1: English
0:MF.K inenabled
1: Switching
between operation
panel command
channel and remote
command channel
(terminal command
channel or serial port
communication
command channel)
2: Switching
between forward
rotation and reverse
rotation
3: Forward rotation
Jog
Minimu
m unit
0.01Hz0.00Hz ☆
Factory
default
1 0 ☆
1 0 ★
ation
ion
- 77 -
Page 84
Function
code
F7-02
F7-03
F7-04
F7-05
F7-06
F7-07
F7-08
Name LED display Setup range
0: Enabled only in
the keyboard control
mode
1: STOP key
enabled in the
terminal control
mode
STOP/RESET
key function
QUICK
parameter
lockout
LED operation
display
parameter
LED stop display
parameter
Load speed
display coefficient
Radiator
temperature 1
Radiator
temperature 2
STOP key
function
Parameter
lockout
Operation
display
Stop display
Load speed
coefficient
Radiator
temperature 1
Radiator
temperature 2
2: STOP key fault
reset function
enabled in the
terminal control
mode
3: STOP key stop
and fault reset
function enabled in
the terminal control
mode
0: QUICK parameter
lockout inenabled
1: QUICK parameter
lockout enabled
Reference to the last
paragraph of chapter
explaination
Reference to the last
paragraph of chapter
explaination
0.0001~6.5000 0.00011.0000 ☆
0.0℃~100℃ 1℃ - ●
0.0℃~100℃ 1℃ - ●
Minimu
m unit
Factory
default
value
1 0 ☆
1 0 ☆
1 624 ☆
1 1139 ☆
Modific-
ation
descrip-t
ion
- 78 -
Page 85
value
Modific-
descrip-t
Function
code
F7-09
F7-10
F7-11
F8-00
F8-01
F8-02
F8-03 speed-up time 2 speed-up time 2 0.0s~6500.0s 0.1s 20.0s ☆
F8-04
F8-05 Speed-up time 3 Speed-up time 3 0.0s~6500.0s 0.1s 20.0s ☆
F8-06
Name LED display Setup range
Accumulated
running time
Software version
No.1
Software version
No.2
Jog running
frequency
Jog speed-up
time
Jog speed-down
time
Speed-down time 2 Speed-down
Speed-down time 3 Speed-down
Accumulated
running time
Software
version No.1
Software
version No.2
Group F8 Auxiliary Function
Jog running
frequency
Jog speed-up
time
Jog speed-down
time
time 2
time 3
0h~65535h 1 - ●
- - - ●
- - - ●
0.00Hz ~ maximum
frequency
0.0s~6500.0s 0.1s 20.0s ☆
0.0s~6500.0s 0.1s 20.0s ☆
0.0s~6500.0s 0.1s 20.0s ☆
0.0s~6500.0s 0.1s 20.0s ☆
Minimu
m unit
0.01Hz2.00Hz ☆
Factory
default
ation
ion
F8-07 Speed-up time 4 Speed-up time 4 0.0s~6500.0s 0.1s 20.0s ☆
F8-08 Speed-up time 4 Speed-up time 4 0.0s~6500.0s 0.1s 20.0s ☆
F8-09 Skip frequency 1 Skip frequency 1
F8-10 Skip frequency 2 Skip frequency 2
F8-11
F8-12
Skip frequency
amplitude
Forward/reverse
rotation
dead-zone time
Skip frequency
amplitude
Forward/reverse
rotation
dead-zone time
0.00Hz ~ maximum
frequency
0.00Hz ~ maximum
frequency
0.00Hz ~ maximum
frequency
0.0s~3000.0s 0.1s 0.0s ☆
0.01Hz0.00Hz ☆
0.01Hz0.00Hz ☆
0.01Hz0.01Hz ☆
- 79 -
Page 86
value
Modific-
descrip-t
Function
code
F8-13 Reverse control Reverse control
F8-14
F8-15 Droop control Droop control 0.00Hz~10.00Hz 0.01Hz0.00Hz ☆
F8-16
F8-17
F8-18
F8-19
F8-20
F8-21
F8-22
Name LED display Setup range
0: Reverse rotation
enabled
1: Reverse rotation
inenabled
Set up frequency
lower than
frequency lower
limit action
Over modulation
enabled
Setup running
time
Start protection
selection
Frequency
detection value
(FDTlevel)
Frequency
detection
hysteresis (FDT-
hysteresis)
Frequency arrival
detection width
Earth short circuit
protection
detection upon
power-on
Frequency lower
limit action
Over modulation
enabled
Setup running
time
Start protection
selection
FDT level
FDT hysteresis
Frequency
arrival width
Earth short
circuit protection
detection upon
power-on
0: Run with
frequency lower limit
1: Stop
2: Zero speed
operation
0: Over modulation
inenabled
1: Over modulation
enabled
0h~65535h 1h 65535h ☆
0: No protection
1: Protection
0.00 ~ maximum
frequency
0.0% ~ 100.0%(FDT
level)
0.0 ~ 100.0%
(maximum
frequency)
0: Inenabled
1: Enabled
Minimu
m unit
0.01Hz50.00Hz ☆
0.1% 5.0% ☆
0.1% 0.0% ☆
Factory
default
1 0 ☆
1 0 ☆
1 1 ☆
1 0 ☆
1 1 ☆
ation
ion
- 80 -
Page 87
Function
code
F8-23
F9-00
F9-01
F9-02
F9-03
F9-04
F9-05
F9-06
F9-07
F9-08
F9-09
Name LED display Setup range
Running time to
action selection
Motor overload
protection
selection
Motor overload
protection gain
Motor overload
pre-warning
coefficient
Stall gain over
voltage
Stall protection
voltage over
voltage
Stall gain over
curren
Stall protection
current over
current
Transient stop/
non-stop function
Transient stop/
non-stop
frequency falling
rate
Fault auto reset
times
Running time to
action selection
Group F9 Fault and Protection
Overload
protection
selection
Overload
protection
coefficient
Overload
pre-warning
coefficient
Stall gain over
voltage
Stall point over
voltage
Stall gain over
curren
Stall point over
current
Transient stop/
non-stop function
Transient stop/
non-stop
frequency falling
rate
Fault auto reset
times
0: Continue running
1: Stop
0: Inenabled
1: Enabled
0.20~10.00 0.01 1.00 ☆
50%~100% 1% 80% ☆
0(No stall over
voltage)
120%~150% 1% 130% ☆
0~100 1 20 ☆
100%~200% 1% 150% ☆
0: Inenabled
1: Enabled
0.00Hz/s ~
maximum
frequency/s
0~3 1 0 ☆
Minimu
m unit
0.01Hz/s
Factory
default
value
1 0 ★
1 1 ☆
1 0 ☆
1 0 ☆
10.00Hz/
s
Modific-
ation
descrip-t
ion
☆
- 81 -
Page 88
Function
code
F9-10
F9-11
F9-12
F9-13
F9-14
F9-15
F9-16
F9-17
Name LED display Setup range
(T/A1-T/B1-T/C
1)Faulty rely
action selection
during the fault
auto reset
(T/A1-T/B1-T/C
1)
Fault auto-reset
interval
Input phase loss
protection
selection
Output phase
failure protection
selection
Velocity
protection
deviation
Velocity deviation
protection time
Motor temperture
protection
selection
Motor temperture
protection mode
Fault auto-reset
interval
Input phase loss
selection
Output phase
failure selection
Velocity
protection
deviation
Velocity
deviation
protection time
Motor temperture
protection
selection
Motor temperture
protection mode
0:No action
1: Action
0.1s~100.0s 0.1s 1.0s ☆
0: Inenabled
1: Enabled
0: Inenabled
1: Enabled
0.50Hz~50.00Hz 0.01Hz 10.00Hz ☆
0.0s Disable
0.0s Protection
inenabled 0.1s ~
20.0s
0: Inenabled
1: Enabled
0:D1 Signal input
1:A1 analog input
2-3:Reserved
Minimu
m unit
Factory
default
value
1 0 ☆
1 1 ☆
1 1 ☆
0.1 10.0s ☆
1 0 ☆
1 0 ☆
Modific-
ation
descrip-t
ion
- 82 -
Page 89
Function
code
F9-18 The first fault type
F9-19
Name LED display Setup range
The second
failure type
The second fault
type1
The second
failure type
0: No fault
1:Reserved
2: Speed-up over
current(Err 02)
3:Speed-down over
current(Err 03)
4: Constant speed
over current (Err 04)
5: Speed-up over
voltage (Err 05)
6: Speed-down over
voltage (Err 06)
7: Constant speed
over voltage (Err 07)
8: Reserved
9: Under voltage
failure (Err 09)
10: Servo driver
overload (Err 10)
11: Motor overload
(Err 11)
12: Input phase
failure (Err 12)
13: Output phase
loss (Err 13)
14: Radiator
overheating (Err 14)
15: External fault
(Err 15)
16: Communication
fault (Err 16)
17: Contactor fault
(Err 17)
18: Current detection
fault (Err 18)
19: Motor tuning fault
(Err 19)
Minimu
m unit
Factory
default
value
- - ●
- - ●
Modific-
ation
descrip-t
ion
- 83 -
Page 90
Function
code
F9-20
F9-21
F9-22
Name LED display Setup range
20: PG fault (Err 20)
21: Data overflow
(21)
22: Reserved
23: Motor earth short
circuit fault (23)
24~41: Reserved
42: CAN
communication fault
43: Encoder fault
(43)
44:Speed deviation
protection fault (Err
44)
45: Motor
The last failure
type
Frequency upon
fault
Current upon
fault
The third fault
type
Frequency upon
fault
Current upon
fault
temperature
protection
46: Oil pressure
sensor fault (Err46)
47~48:Relevant fault
of multi-pump in
parallel flow(Err47、
Err48)
- - - ●
- - - ●
Minimu
m unit
Factory
default
value
- - ●
Modific-
ation
descrip-t
ion
- 84 -
Page 91
Function
code
F9-23
F9-24
F9-25
FP-00 User password 1
FP-01
FP-02
FP-03
Name LED display Setup range
Bus voltage upon
fault
Input terminal
upon fault
Output terminal
upon fault
Parameter
initialization
Motor
specifications
solidification
Injection molding
machine fixed
specifications
Bus voltage
upon fault
Input terminal
upon fault
Output terminal
upon fault
Group FD Communication Parameters
Group FP User Password
Authorization for
all functions code
except FP-05
Parameter
initialization
Motor
specifications
Injection molding
machine
specifications
- - - ●
- - - ●
- - - ●
0~65535 1 0 ☆
0: No operation
1: Restore factory
default setup value
2: Clear the fault
record
3: Restore function
code setup value
saved by FP-05
0~65535 1 0 ★
0~65535 1 0 ★
Minimu
m unit
Factory
default
value
1 0 ★
Modific-
ation
descrip-t
ion
FP-04 User password 2
Authorization to
the FP-05
function code
0~65535 1 0 ★
- 85 -
Page 92
Function
code
FP-05
Name LED display Setup range
Function code
setting values in
real time saved
Save all the
present function
setup value code
0:No operation
1: Save all the
present function
setup value code
Minimu
m unit
Factory
default
value
1 0 ★
Modific-
ation
descrip-t
ion
- 86 -
Page 93
- 87 -
Page 94
Parameter Description and Solution
88
Page 95
Chapter 6 Parameter Description
Group U0 Driver parameters viewing group
Group A0 Weak magnetism and SVC control group
(SAV control reserved)
A0-00
A0-01
A0-02
A0-03
Weak
magnetism
control mode
Setup
range
Weak
magnetism
current
Coefficient
Setup
range
Weak
magnetism
current upper
limit
Setup
range
Weak
magnetism
Integral
multiples
Setup
range
0 Direct calculation
1 Automatic adjustment
80%~200%
0~120
200~1000
Factory
default value
Factory
default value
Factory
default value
Factory
default value
0
100%
100%
400
- 89 -
Page 96
Weak
magnetism
A0-04
When A0-00 =“0”, calculate the weak magnetism directly, the actual output of
weak magnetism current is to multiply the theoretical value by weak magnetic
current coefficient(A0-01), the greater setup value is,the greater the weak
magnetic current will be, the better the dynamic effect will be. But it may
cause speed and current oscillation if it is too large.
When A0-00=1, adjust weak magnetism current automaticlly, get the required
minimum weakening current. Adjustment speed is determined by weak
magnetism adjustment coefficient (A0-04), the bigger setup value is, the
faster the adjustment will be.But it may be caused by speed and current
oscillation if it is too large.
A0-05
Determine the phase failure detection time, the value is equal to zero that
does not do output phase failure detection, it can automaticlly set up after
motor parameter tuning.
adjustment
coefficient
Setup
range
Output phase
failure PWM
detection time
Setup
range
Factory
default value
0~1000
0~63000
Factory
default
value
4
0
Group A1 PG Card Group
A1-00~
A1-01
A1-02
The unit is 0.1 °, it is automatically set after the motor parameter tuning.
Reserved
Setup
range
Encoder
Installation
angle
Setup
range
Factory
default value
-
Factory
default value
0.0°~359.9°
- 90 -
-
0°
Page 97
Select the
Factory
default value
Select the forward direction of speed
0
direction
Select the reverse direction of speed
1
direction
Factory
default value
1~50
0
1
A1-03
A1-04
reverse of
feedback
speed
Setup
range
Rotary
transformer
number of
pole-pairs
Setup
range
Group A2 CAN Communication Group
A2-00
A2-01
A2-02
Baud rate
selection
0 20k
1 50k
Setup
range
CAN
communication
address
Setup
range
CAN
communication
continuous
time
2 125k
3 250k
4 500k
5 1M
1~255
Factory
default value
Factory
default value
Factory
default value
- 91 -
4
1
0.0
Page 98
0.0:
Setup
range
Set up detection CAN break time, if the driver did not receive data within the
setup time, then it will alarm 42.
Group A3 Servo oil pump control group
0.1s~5.0s
0.0:inenabled
0.1s~5.0s
oil pressure
control mode
A3-00
Setup
range
A3-00=“0”:Non-oil pressure control mode
A3-00=“1”:Driver oil pressure control mode 1.
Factory default
value
Non-oil pressure control mode
0
Driver oil pressure control mode 1
1
Driver oil pressure control mode 2
2
CAN oil pressure mode(For special use)
3
4 Reserved
0
CAN setup flow, oil pressure command and A13 analog channel
A13 analog channel provides oil pressure command, A12 analog
channel provides flow command, and A13 analog channel provides oil
pressure feedback command, driver conducts oil pressure control.
A3-00=“3”:CAN oil pressure contol mode (For special use), group A3 control group
parameters of the servo oil pump disabled.
A3-00=“4”:保留。Reserved.
Maximum rotation
speed
Factory default
value
2000rpm
A3-01
setup range
The corresponding system output flow sets motor running maximum speed, the
recommendations of the setup value is less than 1.4% of the motor rated speed (F1-05).
The maximum frequency of frequency lower limit
corresponding to rotation speed~30000rpm
- 92 -
Page 99
System oil
A3-02
Set the system maximum oil pressure value.
A3-03
pressure
Setup
range
Maximum oil
pressure
Setup
range
Factory default
value
0.0kg/cm2 to maximum oil pressure(A3-03)
Factory default
value
System oil pressure(A3-02) to 500.0kg/cm
175.0kg/cm2
250.0kg/cm2
2
Set the pressure scale of the oil pressure sensor. (Corresponding
voltage DC0~10V output pressure sensor)
A3-04
Oil pressure
command
risetime
Setup
range
Factory default
value
0ms~2000ms
20ms
Corresponding filter time of oil pressure command
Oil pressure
A3-05
The Oil pressure controls PID proportional gain of the first group. The greater setup
value is, the faster responses will be.Responding too fast that can easily lead to overshoot
and cause system instability and running oscillation. The smaller setting value is, the slower
response will be, responding too slow can easily lead to inefficient and product instability.
control Kp1
Setup
range
Factory default
value
0.0~800.0
210.0
A3-06
Oil pressure
control Ti1
Setup
range
Factory default
value
0.001s~10.000s
0.100s
The oil pressure controls PID integration time of the first group. The
smaller setup value is, the faster response will be.Responding too fast that
can easily lead to overshoot, cause system instability and running oscillation.
The greater setup value is, the slower response will be, responding too slow
can easily lead to inefficient and product instability.
- 93 -
Page 100
A3-07
Oil pressure
control Td1
Setup
range
Factory default
value
0.000s~1.000s
0.000s
The oil pressure controls PID derivative time of the first group. The
smaller setup value is, the faster response will be. Responding too fast that
can easily lead to overshoot, cause system instability and running oscillation.
The greater setup value is, the slower response will be, responding too slow
that can easily lead to inefficient and product instability.
A3-05、A3-06、A3-07:PID of the first group oil pressure
The switching methods of PID groups refer to the servo pump commissioning steps of
chapter seven.
PID of the first group oil pressure corresponding to terminals combination: DI2(OFF)、DI3(OFF)
Maximum
reverse rotation
A3-08
It is the maximum reverse rotation when pressure relief, which corresponds to the
percentage setup of the manimum rotation speed. It is used to set the maximum reverse
rotation speed. The greater setup value is, the faster pressure relief will be.But excessive
noise cause pump reversal.The smaller setting value is, the slower pressure relief will be.
speed
设定范围
Setup
range
Factory default
value
0.0%~100.0%
20.0%
Minimum flow
A3-09
The system running miximum flow,corresponding to the percentage setup of the
manimum rotation speed(A3-01).
A3-10
设定范围
Setup
range
Minimum
pressure
Factory default
value
0.0%~50.0%
Factory default
value
- 94 -
0.5%
0.5kg/cm2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.