Inovance H1U-0806MT, H1U-1410MT, H1U-0806MR, H1U-1410MR, H1U-1614MT User Manual

...
Page 1
Designation Rules
Ƶ
Basic Parameters
Ƶ
General Specifi cations
Ƶ
Product Information
Safety Precautions
Mechanical Design Reference
Data: 19010084 V0.0
User Manual
H
1U
Series PLC
Thank you for purchasing the PLC of Inovance control technology co., Ltd. Before using H
2U
series PLC, please read this manual carefully in order to use the products correctly.
This manual mainly describes specifi cations, features and usage of H
2U
series PLC, and there are PLC instructions set summaries for easy reference. For both the user program development environment usage and programming methods of this product, please refer to our company's “Auto-Shop programming software user's Guide "," H
2U
series PLC programming reference manual " and " H
2U
series communication manual”.
Features of H
1U
Series Programmable Controller: Building-in large program memory space without an external extension memory card, it can up to 8K steps. User program and all the power-down devices can be permanent backup in the power-off status, and the real­time clock can keep at least 20 days in power-down situations without batteries (power-on time is longer than 5 minutes). Provide high-speedmulti-channel and high frequency I/O ports as well as excellent operation and positioning control functions. Integrate two independent communication ports, providing excellent communication protocols and MODBUS instruction, which is convenient for system integration. Comprehensive encryption features can protect users’ intellectual property rights. With powerful networking and support CAN-BUS.
DESIGN PRECAUTIONS
Danger
Provide a safety circuit on the outside of the PLC so that the whole system operates to ensure the safety even when external power supply trouble or PLC failure occurs. To be considered in the design includes:
On the outside of the PLC, an emergency stop circuit, a protection circuit, an interlock circuit, or a positioning limit circuit may be necessary for preventing damage to the machine. Ensure the safe operation of equipment, please design external protection circuit and safety mechanics for the PLC output signals. When the PLC CPU detects the system abnormal, all outputs may be turned off. During the controller circuit failure, it may cause the output out of controlled. Design external circuits to ensure safe operations of the machine in such a case. When some sort of error occurs in a relay or transistor of the output unit, output may be kept on or off. PLC design is applied to the indoor electric environment, its power system-level should have lightning protection device, make sure that they will not lightning imposed on the PLC power input-side or signal input, control output terminal, avoid damage the device.
INSTALLATION PRECAUTIONS
Note
!
Do not use the PLC in the place of dust, oil smoke, conducting dust, corrosive gas, and combustible gas, exposure to the high temperature, dew, wind and rain, vibration and shock. Electric shock, fire, operator errors can also cause the product damage and deterioration. When processing for screw holes and wiring, do not make the metal fi lings and wires falling into the controller ventilation hole, this may cause a fi re, failure, and malfunction. When the installation work of the new PLC is over, it needs to ensure that there is no foreign body on the face of ventilation, including dust-proof and so on, otherwise, it may cause poor heat dissipation during running, a re, failure and malfunction. Avoid charged state for wiring and plugging the cable plug, otherwise easily cause electric shock, or cause damage to the circuit. The Installation and wiring should be fi xed and reliable, poor contact may cause incorrect operation. If there is serious interference, the communications and high-frequency signal cable should be shielded cables, to improve system anti-interference capacity.
WIRING PRECAUTIONS
Danger
Turn off all the power supply externally before installation or wiring work in order to avoid electric shock or damage of product. Please connect AC power supply to the special terminal. Make sure to attach the terminal cover offered as an accessory to the product before turning on the power or starting the operation after installation or wiring work. When processing for screw holes and wiring, do not make the metal fi lings and wires falling into the controller ventilation hole, this may cause a fi re, failure, and malfunction.
Note
!
For of the main unit terminal or the extension unit terminal
do not use external power supply. Do not wire
vacant terminals externally.
For applications where serious interference, high-frequency signal input or output cable selection shielded cables should be to enhance the system of anti-interference capacity. Please use the wire above 2mm2 to avoid connecting the grounding terminal at the same point as a heavy electrical system.
STARTUP AND MAINTENANCE PRECAUTIONS
Danger
Do not touch any terminal while the PLC is power on. Doing so may cause electrical shock or malfunctions
Before cleaning or retightening terminals, externally cut off all phases of the power supply. Failure to do so may expose you to shock hazard. Please connect or remove the wire, the extension module and control unit wire after cutting off all power supply, otherwise it may cause failures and malfunctions. For online modify, coercible output, RUN, STOP and so on, you should read the instruction manual, and operate the PLC after fully confi rm its safety.
Note
!
When handling extension card, be sure to cut off the power supply. Please follow the industrial wastes disposal for the waste products.
H1U-0806MRAX
1 2 3 4 5 6 7 8
Product Structure
Ƶ
System Expansion
Ƶ
Product Structure
ᅝ㺙ᄨ
Fig.1 Mounting Dimension Diagram
Fig2 Product Structure Diagram
Component names and Function descriptions:
Big foldaway1. Power supply, auxiliary power supply and removable terminal for input signal2. LEDs for indicating the input status3. Download port for user program4. Mounting screw holes(two)5. RUN/STOP switch6. Buckle for two DIN rail mounting7. System program download port (Do not operate for non-professional)8. Special function expansion card interface9. Special function expansion card fi xed bolts(Screw specifi cation: M2.6×6)10. Wiring terminal for RS485 communication port11. Special function expansion card(Available only after the user selection and installation)12.
Product Information
ķ
Series No.
ĸ
Input points
Ĺ
Output points
ĺ
Module classifi cation
Ļ
Output type
ļ
Power Supply type
Ľ
Special function identifi cation
ľ
H: Inovance controller 1U: 1U series controller 08: 8 points input 06: 6 points input M: Main module of general purpose controller;P: Positioning controller; N: Network controller;E: Expansion module R: Relay output type;T: Transistor output type A: AC 220V Input omitted default:AC220V;B: AC110V input; C: AC24V input;D: DC24V Such as high speed I/O and analog function, etc.
H1U series PLC supports only remote the expansion modules, do not support the local expansion modules. If you need to connect the remote expansion modules to conduct the function expansion, you need to install CAN­BUS communication expansion cards, and then conduct networking connection via CAN-BUS communication expansion cards and remote expansion modules. The model of CAN-BUS communications expansion card is H1U-CAN-BD which should be purchased separately, as well as making sure that the main module of the software version supports CAN-BUS functions. Otherwise the networking can not be performed. Please refer to the "H1U­CAN-BD user manual," for the application of H1U-CAN-BD, refer to "H2U series expansion module user manual" for the application of remote expansion modules, and refer to "H1/2U PLC instruction and programming manual." for CAN-BUS functions. System can be extended up to 64 points (support CAN-BUS devices), including the main module. As long as the CAN-BUS protocol meets any device that can be hung on the bus.
Table 1 Basic Parameters
Table 3 Mounting Dimension
Table 2 General Specifi cations
Terminal Block Defi nition Terminal block defi nition of H1U-0806MR, H1U-0806MT
Hardware Interface
Ƶ
LN
COM1COM0 COM2
Y1Y3Y2
S/S
X0
X1
X3
X2 X4X5X6
X7
24V
0V
Y0 Y4
Y5
COM3
Terminal block defi nition of H1U-1410MR, H1U-1410MT
Terminal block defi nition of H1U-1614MR, H1U-1614MT
LN
COM1COM0 COM 2
Y1 Y2
S/S
X0
X1
X3
X2 X4X5X6
X7
24V
0V
Y0 Y3
Y4
Y5
COM3 COM4
Y6Y7Y10
Y11
X10
X11
X12
X13
X14
X15
LN
COM1COM0 COM2
Y1 Y2
S/S
24V
0V Y0 Y4
Y5
Y7
Y10
Y11
Y3
COM3
Y6
COM4
Y12
Y13
Y14
Y15
X0
X1
X3
X2 X4X5X6X7X10
X11
X12
X13
X14
X15
S/S
S/S
X16
X17
Model Total I/Os
I/O Features
Total I/Ps Hi-speed I/Ps Input voltage Total O/Ps Hi-speed O/Ps Output Type
H
1U
-0806MR 14 8
Two 60 kHz Four 10 kHz
DC24V 6
/ Relay
H
1U
-0806MT Three 100 kHz Transistor
H
1U
-1410MR 24 14
Two 60 kHz Four 10 kHz
DC24V 10
/ Relay
H
1U
-1410MT Three 100 kHz Transistor
H
1U
-1614MR 30 16
Two 60 kHz Four 10 kHz
DC24V 14
/ Relay
H
1U
-1614MT Three 100 kHz Transistor
Environmental parameter
Ambient condition
Transport ambient
condition Type
Storage ambient
condition Parameter
Type Parameter Unit
Climatic- Condition
Ambient Temperature
Low Temperature
ć
Climatic- condition Ambient temperature Low temperature
High Temperature
ć
High temperature
Humidity Relative Humidity % Humidity Relative humidity
Atmospheric Pressure
Low Pressure kPa Atmospheric pressure Low pressure
High Pressure kPa High pressure
Mechanica-l Stress
Sine Vibration
Displacement mm Mechanica-l stress Sine vibration Displacement
Acceleration m/s
2
Acceleration
Random vibration
Acceleration Spectral Density
m
2/s3
(dB/Oct) Random vibration Acceleration spectral density
Frequency Range Hz Frequency range
Vibration Direction / Vibration direction
Shock
Type / Shock Type
Acceleration m/s
2
Acceleration
Dipping
Dipping Height
m Dipping
Dipping
height
Model
Total I/Os
Mounting Dimension
Physical Dimension
W×H×D˄mm
˅
A˄mm˅B˄mm
˅
H
1U
-0806M_ 14 62 80 70×90×75
H
1U
-1410M_ 24 83 80 93×90×75
H
1U
-1614M_ 30 100 80 110×90×75
Mounting Dimension
Ƶ
efesotomasyon.com
Page 2
Shenzhen Inovance Control Technology Co,.Ltd.
Address: Block E, Hongwei Industry Park, Liuxian Road, Baocheng No. 70 Zone, Bao’an District, Shenzhen
Fax: +86-755-29619897 Service Hotline: 400-777-1260
P.C.: 518101 Website: http://www.inovance.cn
Item High-speed inputs X0X5 General inputs
Signal input mode
Sink/Source mode.It is sink input when S/S terminal and 24V are shorted connection,it is source when s/s terminal and COM are shorted connection.
Electrical
parameters
Detection voltage DC24V
Input resistance 3.3k 4.3k
Input :ON Input current is more than 4.5mA. Input current is less than 3.5 mA.
Input : OFF Input current is less than 1.5mA Input current is less than 1.5mA.
Filter
function
Digital Filter X0 to X7 has digital filter function, the filter time can be set during the range of 0 to 60 msec.
Hardware Filter The other I/O port is hardware filter except X0 to X7, the filter time is about 10 msec.
High-speed Function
X0 to X5 can realize the function with high-speed counting,interrupt and pluse capture,etc. The maximum frequency of the X0 to X1 port counting up to 60kHz. The maximum frequency of the X2 to X5 port counting up to 10kHz.
Common connection terminal Only a common terminal˖S/S
Item Relay outputs Transistor outputs
Circuit Voltage Less than AC250V and DC30V DC5V to DC24V
Circuit Insulation Relay Mechanical Insulation Light coupling insulation
LED
When the relay output contacts close, the LED light is on.
When the light coupling is drove,the LED light is on.
Leakage current during open circuit
None Less than 0.1mA/DC30V
Min.load 2mA/DC5V 5mA˄DC5VDC24V
˅
Internal equivalent circuit PLC has a built-in power supply (DC24V) to detect user Xi input state, the user only needs to ON/OFF(dry-contact switch) signal between Xi and COM, if a transistor output signal form the active sensor, it should be OC output signal type. PLC signal input and internal equivalent circuit is shown in the following gure, users’ circuit and PLC internal circuit to connect via the terminal blocks. Figure 3-5 shows the SINK input method, “S/S” ” and “24V terminals are short connection.
In some special applications, you may need to adopt SOURCE input methods, its equivalent input circuit shown in Figure 6, "S/S" terminal and the "COM" terminals are short circuit. Figure 7 shows the internal equivalent circuit diagram of the relay output module, the output terminal is divided into several groups, each group is electrical isolation, and the contacts of different groups can connect with different power circuits.
Fig. 7 Relay Output Equivalent circuit
Fig. 5 Sink Input Connection
Fig. 8 Transistor Output Internal Equivalent circuit
Fig. 6 Source Input Connection
The internal equivalent circuit diagram of the transistor-output-type PLC as shown in Figure 8. In which we can see the output terminal is divided into several groups, and groups are electrical isolated each other. The transistor output level can only be used for DC-DC24V load circuit. For the inductive load in DC circuit, you should add a freewheeling diode, while the inductive load in AC circuit, and add a RC component instead. As shown in Figure 9.
Fig. 9 Diagram for Inductive Load Absorbing Circuit
Product Warranty Card
Customer
information
Add. of unit:
Name of unit:
P.C . :
Contact person:
Tel.:
Product
information
Product model:
Body barcode (Attach here):
Name of agent:
Failure
information
(Maintenance time and content):
Maintenance personnel:
Table 6 Input Specications
ľ
ķĸ
Ĺĺ Ļ
ļ
Ľ
COM1
485+
485-
Fig.3 COM0 Communication Port
Fig.4 COM1 Communication Port
Table 4 COM0 Port Denition
Pin No.
Signal Description
1 RXD- Receive negative data
2 RXD+ Receive positive data
3 GND Grounding, no electrical connections for 9 and 10
4 TXD-/RXD-
External transmit negative data. It can receive negative data if it is RS485.
5 +5V External power supply +5V, the same with the internal logic +5V.
6 CCS Communication direction control wire
7 TXD+/RXD+
External send positive data. It can receive negative data if it is RS485.
8 NC Non-pin
Terminal block specication: 22-14AWG wire. When loosen the screw at two sides, loosen both sides of the terminal screws alternately, pay attention not to completely one screw and then the other screw, just loosen the screw about half and then the other screw, two screws alternately until the whole screw are loosened, then you can gently raise up terminal head to nish the dismantling work of the terminal. When mounting terminals, put the terminal head into position, and then tighten a screw to conrm the screw will not fall off and then tighten the other screw, alternately tighten the screws on both sides until complete the process. Note that during the entire fixed process, insert two sides of the terminal as balance as possible, otherwise the terminals may damage by poor contact or short circuit. Communication Interface Denition The main PLC unit provides two communications ports.COM0 hardware has standard RS422 and RS485. COM1 hardware is standard RS485.The terminal interface is Mini-DIN8 socket.
Table 5 Power Supply Circuit Specication
Output3 in table 5 is the sensor power supply, and it can also provide external power supply to the special function module. Output2 provides power supply to the main module and the relay of IO expansion module. Output1 provides power to all modules. During the system configuration, make sure that power supply demand is not exceed its maximum capacity.
Item Unit
Min.
Value
Typical Value
Max.
Value
Remark
Rated operating voltage Vac 100 220 240 Normal startup and operating range
Limit input voltage Vac 85 / 264
Derating for usage When AC85 to100V and AC240 to 264V,see Figure 3-2.
Input current A / / 1 AC 85V input,full-loading output
Input power W/VA / / 15W/25VA
Output voltage
5V/GND V 4.5 5 5.5 Output1
24VDD/GND V 21.6 24 26.4 Output2
24VCC/COM V 21.6 24 26.4 Output3
Output current
5V/GND mA 50 500 500
The sum of capacity load is the internal consumption and the expansion module. The maximum output power shall be the sum of each full load . The cooling method is a natural cool.
24VDD/GND mA 10 200 200
24VCC/COM mA 10 200 200
Power Supply Circuit Specification
Ƶ
Input Specifications
Ƶ
Note: S/S connecting to 24V+ or COM determines the SINK or SOURCE input mode, the selection is effective to all the input points’ signals in main unit
Table 7 Output Specications
Output Specifications
Ƶ
Soft component arrangement and power-off r etentive
Ƶ
description
Table 8 Soft component arrangement
H1U-0806M H1U-1410M H1U-1614M
Input relay X
X000~X007
8 points
X000~X015
14 points
X000~X017
16 points
Output relay Y
Y000~Y005
6 points
Y000~Y011
10 points
Y000~Y015
14 points
Programming Reference
The soft components of H1U series PLC are permanent backup, which means that all soft components are not loss after the module power-down. The real-time clock can hold for 15 days, which means that the clock is still the current time after the module power-down and then restart within 15 days. The power-on time of the main module must be more than 1 minute, otherwise the power-down may abnormal. The longer the power-on time is, the longer the holding time will be, and the power-down time can hold up to 25 days.
Auxiliary Relay M
[M0~M383]
384 points
General
[M384~M1535]
1152 points
Latched
M8000~M8255
256 points
Special
State
[S0-S999]
1000 points
Retentive
Timer
T0~T199
200 points 100ms
General
T200~T245
46 points 10ms
General
[T246~T249]
4 points 1ms
Accumulative,
retentive
[T250~T255]
6 points 100ms Actuarial,
retentive
Counter
16 bit count-up counter 32 bit count-up/down counter High-speed counter
C0~C 15
16 points
General
[C16~C199]
168 points
Retentive
C200~C219
20 points
General
[C220~C234]
15 points
Retentive
[C235~C255]
21 points
Retentive
Data register D
ˈ
VˈZ
D0~D127
128 points
General
[D128~D7999]
7872 points
Retentive
[D1000~D7999]
Max.7000 points
It can be set to the
le register.
[D8000~D8255]
256 points
Special
V7~V0ˈZ7~Z0
16 points
Index
Nesting pointer
N0~N7
8 points
Master Control
P 0~P127
128 points
Jump subprogram
I00*~I50*
6 points
Input interrupt pointers
Countants
K 16 bit -32,768~32,767 32 bit -2,147,483,648~2,147,483,647
H 16 bit 0~FFFFH 32 bit 0~FFFFFFFFH
Item Relay outputs Transistor outputs
Max. output current
Resistive load
2A/1 point : 8A/4 points common port, 8A/8 points common port
Max. output current
Inductive load AC220Vˈ80VA
Lamp Load AC220Vˈ100W
ON response delay 20 msec Max.
High speed output: 10μs Others: 0.5msec
OFF response delay 20 msec Max.
High-speed output frequency None 100kHz per channel(Max.)
Output common ports Each group shared a common port, there is insulated gap between the groups.
Fuse protection None
efesotomasyon.com