GE N E RAL INF O RMA T ION
MinIPAQ-L is a two-wire temperature transmitter intended to be used in industrial environment.
The transmitter is congured from a PC via a USB port, connected via the INOR USB interface ICON, by using the ConSoft program together with the MinIPAQ Soft program. When the transmitter is set from a PC no calibration is needed. The manual is on-line. ConSoft is compatible with Windows 2000 (SP3),
Windows XP and Windows Vista.
USER INSTRUCTIONS
The user instruction must be read prior to adjustment and/or installation.
All information subject to change without notice.
MEASURE OF SUCCESS
This product should not be mixed with other kind of scrap, after usage.
It should be handled as an electronic/electric device.
www.inor.com, www.inor.se
INOR Process AB, PO Box 9125, SE-200 39 Malmö, Sweden,
Phone: +46(040)31 25 60, Fax: +46(040)31 25 70, E-mail: info@inor.se
INOR Transmitter OY, Unikkotie13, FI-01300 Vantaa, Finland,
Phone:+358-10-4217900, Fax: +358-10-4217901, E-mail: jari.stadig@inor.
INOR Transmitter GmbH, Rodenbacher Chaussee 6,
DE-63457 Hanau-Wolfgang, Germany,
Phone: +49(0)6181-582940, Fax: +49(0)6181-582944, E-mail: inor.gmbh@t-online.de
INOR Transmitter Inc, 7 Dearborn Road, Peabody, MA 01960, USA,
Phone: +1(978) 826-6900/(262) 670-9050,
Fax: +1(978) 535-3882/(262) 670-9001, E-mail: service@inor.com
CO N F IGU R ATI O N
Before making a conguration of MinIPAQ-L you need to do
following:
1. Install the PC conguration software ConSoft in your PC. The soft­ware is included in the PC Conguration Kit 70CFGUS001 and can also be downloaded from the web site www.inor.com.
2. Install the PC conguration software MinIPAQ Soft, version 1.23.01 or later, in your PC. The software is included in the PC Conguration Kit 70CFGUS001 and can also be downloaded from the web site www.inor.com.
3. Install the drivers for the INOR USB Interface. The drivers are included in the PC Conguration Kit 70CFGUS001.
Conguration procedure:
The help le in MinIPAQ Soft contains complete information about the conguration procedure. Here is a short-form guide:
1. Connect the MinIPAQ-L to the PC via the USB Interface. Conguration can be performed with or without connected power supply.
2. In ConSoft, click on “Connect”, and the software will automatically recognize the connected transmitter.
3. Click on the highlighted “MinIPAQ” in the menu tree of ConSoft and the “MinIPAQ Soft” conguration window will open.
4. Be sure to set the Communication port in MinIPAQ Soft (under Op­tions) to the same port No. as indicated in the lower left corner of the ConSoft window, e.g. COM8.
5. In the conguration window you can set the following parameters: a. Input (RTD or Thermocouple type) b. 3- or 4-wire connection (for RTD input) c. Activation of Cold Junction Compensation (for T/C input) d. Measuring range in three different engineering units e. Upscale or downscale action at sensor break or short-circuit f. Compensation for known sensor errors g. Activation of a Low pass lter
6. The selected conguration is downloaded to the transmitter by click­ing the button “Transfer to transmitter”. If the transmitter is in operation during transmission from the PC, the transmitter output is frozen. When the transfer is complete, the transmitter begins using the new parameters directly.
DATA (shortform)
Input See ”Input Connections” Sensor failure Upscale, downscale or off Adjustments - Zero Any value within range limits Adjustments - Minimum spans
Pt100, Pt1000, Ni100, Ni120, Ni1000 10°C / 18°F Cu10 100°C / 180°F T/C 2 mV
Output 4-20 mA, temperature linear Operating temperature -20 to +70°C / -4 to +158°F
Galvanic isolation No
Power supply 8 to 32 VDC Typical accuracy ±0.15 % of temperature span Mounting Rail acc. to DIN EN 50022, 35 mm
CA L I BR A T IO N
CO N N ECT I ONS
OUTPUT LOAD DIAGRAM
It is recommended to check the calibration once a year. Use equipment with an inaccuracy of at least 5 times better than the checked transmitter, e.g. if you are checking a transmitter with an inaccuracy of maximum
0.1% use instrument with an inaccuracy of maximum 0.02%. Use the MinIPAQ Soft Basic Calibration function in the Options menu, and follow the instructions on the screen.
INP U T CONNECTIONS
DI M E NSI O NS
MO U N TI N G
RTD
T/C
RTD
RTD, 3-wire connection
Pt100, α =0.00385, Pt1000, α=0.00385 Pt100, α =0.003902, Pt100, α=0.003916 Ni100, Ni120, Cu10, Ni1000, Pt(Spec), α=0.00385
Thermocouple
B, C, E, J, K, L, N, R, S, T, U
RTD, 4-wire connection
Pt100, α=0.00385, Pt1000, α=0.00385 Pt100, α=0.003902, Pt100, α=0.003916 Ni100, Ni120, Cu10, Ni1000 Pt(Spec), α=0.00385
1
2 3
Output
PC Connection
Input
4
21
22 23
Out
In
23
22
2
3
1
21
4
OR D E RI N G IN F ORM A TIO N
LI M I TE D WA R R ANT Y
INOR Process AB, or any other afliated company within the Inor Group (hereinafter jointly referred to as ”Inor”), hereby warrants that the Product will be free from defects in materials or workmanship for a period of ve (5) years from the date of delivery (”Limited Warranty”). This Limited Warranty is limited to repair or replace­ment at Inor’s option and is effective only for the rst end-user of the Product. Upon receipt of a warranty claim, Inor shall respond within a reasonable time period as to its decision concerning: 1 Whether Inor acknowledges its responsibility for any asserted defect in materials or workmanship; and, if so, 2 the appropriate cause of action to be taken (i.e. whether a defective product should be replaced or repaired by Inor). This Limited Warranty applies only if the Product: 1 is installed according to the instructions furnished by Inor; 2 is connected to a proper power supply; 3 is not misused or abused; and 4 there is no evidence of tampering, mishandling, neglect, accidental damage, modication or repair without the approval of Inor or damage done to the Product by anyone other than Inor.
This Limited Warranty is provided by Inor and contains the only express war­ranty provided.
INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE OR REPRESENTATION AS TO SUITABILITY FOR ANY PARTICULAR
PURPOSE, PERFORMANCE, QUALITY AND ABSENCE OF ANY HIDDEN
DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT, WHICH BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION, OPERATION OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING, INCLUDING IMPLIED WARRANTIES OF MER-CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED HEREIN, INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL, DIRECT, SECONDARY OR
CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE
OF THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or replaced at the option of Inor. Customer pays freight to Inor, and Inor will pay the return freight by post or other “normal” way of transport. If any other type of return freight is requested, customer pays the whole return cost.
MinIPAQ-L 70MQL00003
Conguration 70CAL00001 PC conguration kit (USB-conn.) 70CFGUS001
+
-
RTD
T/C
RTD
Input connections
Output connections
35/1.38
17.5/0.69
68/2.68
63/2.48
98/3.86
45/1.77
mm/inches
Mounting of MinIPAQ-L on rail DIN EN 50022, 35 mm.
1. Fix the upper part of the transmitter onto the rail.
2. Press the lower part of the transmitter against the rail.
3. To remove the transmitter, use a screwdriver and bend the locking under the transmitter downwards.
R
LOAD
I
OUT
Test
1)
1)
Ri ≤ 10 Ω