INOR MESO-L GB User Manual

1
2
4
3
5
6
7
USER INSTRUCTIONS
INTRODUCTION
The MESO transmitters are Smart and universal 2-wire transmitters for temperature and other measurement applications.
Smart HART 2-wire
Transmitter
ATEX
The user instruction must be read prior to adjustment and/or installation.
All information subject to change without notice.
MEA S URE O F S U CCE S S
MESO-H is the standard In-head transmitter and MESO-L is the DIN Rail transmitter. MESO-HX is the Intrinsic Safe In-head version for use in Ex-applications. MESO-H, MESO-L and MESO-HX are fully HART-compatible, with communication through the HART protocol, directly on the 4-20 mA output loop.
CONFIGURATION
Conguration of the MESO transmitter is performed by using either a general hand-held HART Communicator or a PC with the Inor Windows
software, MePRO 2, installed. Also Emerson AMS and Siemens PDM can
be used for conguration since the MESO transmitters are integrated into
them. The MESO transmitter uses all HART
Common Practice Commands
the following numbers are used: 34, 35, 38,
40, 41, 42, 48, 49 and 59. These commands can be reached from a stan-
dard HART Handheld Communicator or a universal HART PC software and HART PC modem. Several
Transmitter Specic Commands
be read/written by a HART Handheld Communicator with the INOR MESO DD included or via the Emerson AMS or Siemens PDM with the MESO DD included. To address all the features in MESO including the
tion
and the
Basic Calibration
the MePRO software must be used. The latest version of the INOR PC software MePRO can be downloaded from http://
www.inor.com. Also a HART PC modem connected to the serial port or the
USB port of the PC is needed. For connection of the HART PC modem to the transmitter see gures 10 – 12. The modem is connected over the load (B-C) or over the transmitter (A-B). For HART communication to work properly the MESO transmitters must be powered and there must be at least 250 ohm in the current loop. To communicate with the transmitter when it is installed in the eld, load re-
sistance, cable resistance and cable capacitance must be considered. See diagram 3.
PLEASE NOTE! For MESO-HX make sure to follow the
instructions for maintaining intrinsic safety during con-
guration, installation and operation.
!
Universal Commands
. Among the
are also implemented. They can
Customized Lineariza-
INOR Process AB, PO Box 9125, SE-200 39 Malmö, Sweden,
Phone: +46-(0)40-312560, Fax: +46-(0)40-312570, E-mail: info@inor.se
INOR Transmitter OY, Unikkotie 13, FI-01300 Vantaa, Finland,
Phone:+358-(0)10-4217900, Fax: +358-(0)10-4217901, E-mail: jari.stadig@inor.
INOR Transmitter GmbH, Rodenbacher Chaussee 6,
Phone: +49-(0)6181-582940, Fax: +49-(0)6181-582944, E-mail: inor.gmbh@t-online.de
INOR Transmitter Inc, 7 Dearborn Road, Peabody, MA 01960, USA,
Fax: +1 978 535 3882, +1 262 670 9001, E-mail: service@inor.com
DE-63457 Hanau-Wolfgang, Germany,
Phone: +1 978 826 6900, +1 262 670 9050,
www.inor.com, www.inor.se
This product should not be mixed with other kind of scrap, after usage.
It should be handled as an electronic/electric device.
MEA S URE O F S U CCE S S
DIMENSIONS
LIMITED WARRANTY
INOR Process AB, or any other afliated company within the Inor Group (hereinafter jointly referred to as
”Inor”), hereby warrants that the Product will be free from defects in materials or workmanship for a period
of ve (5) years from the date of delivery (”Limited Warranty”). This Limited Warranty is limited to repair or replacement at Inor’s option and is effective only for the rst end-user of the Product. Upon receipt of
a warranty claim, Inor shall respond within a reasonable time period as to its decision concerning:
1 Whether Inor acknowledges its responsibility for any asserted defect in
materials or workmanship; and, if so,
2 the appropriate cause of action to be taken (i.e. whether a defective
product should be replaced or repaired by Inor).
This Limited Warranty applies only if the Product:
1 is installed according to the instructions furnished by Inor; 2 is connected to a proper power supply; 3 is not misused or abused; and
4 there is no evidence of tampering, mishandling, neglect, accidental damage, modica-
tion or repair without the approval of Inor or damage done to the Product by anyone other than Inor.
This Limited Warranty is provided by Inor and contains the only express warranty provided.
INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE OR REPRESENTATION AS TO SUITA­BILITY FOR ANY PARTICULAR PURPOSE, PERFORMANCE, QUALITY AND ABSENCE OF ANY HIDDEN DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT, WHICH
86BME00002 2010-03
BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION, OPERATION OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING, INCLUDING IMPLIED WARRANTIES OF MER-CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED HEREIN, INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL, DIRECT, SECONDARY OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE OF THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or replaced at the option of
Inor. Customer pays freight to Inor, and Inor will pay the return freight by post or other “normal” way of transport. If any other type of return freight is requested, customer pays the whole return cost.
DATA (shortform)
Load
Load
Load
l
l
l
Power supply1): Meso-H 10 - 42 VDC
Meso-HX 12 - 30 VDC/max 100 mA/0.9W
1)
When communicating acc to HART the load must be more than 250 ohm.
2)
Supply voltage over 36V demands at least 250 ohm´s load
Meso-L 11 - 42 VDC
2)
2)
MESO-HX Ex-DATA
Approval Demko 03 ATEX 134077X II 1G Ex ia IIC T4/T5/T6 Control Drawing 88DRW00053
Approval FM, J.I. 6D9A4.AX, CSA 2007 Certicate 1863602
Class I, II and III, Division 1, Group A, B, C, D and G Control Drawing 3-7967
Output (current loop) Ui : 30 VDC
Ii : 100 mA Pi : 900 mW Li : 1 mH Ci : 1 nF
MESO-HX must be powered from an certied isolating power supply or
zener barrier, placed outside the hazardous area. MESO-HX shall be mounted in an Ex-compatible housing having protection IP20 or better.
Ambient temperature: T4: -40 oC Tamb +85 oC
T5: -40 oC Tamb ≤ +65 oC
T6: -40 oC Tamb +50 oC
Service temperature ≤ max ambient temperature
INPUTS
MESO-HX may only be connected to transducers complying with ”Simple Apparatus” acc. to
EN 60079-11:2007 § 5.7
Fig 9.
MESO-HX must be installed in an enclosure having
!
an Ingress Protection suitable for the actual use but at least IP20. If MESO-HX is mounted in a housing (head) made of light metals and installed in hazardous area make sure the content of magnesium (Mg) in the light metal is less than 6%.
If MESO-HX is mounted in a housing which is isolated from ground and can be charged to an ignition capable level, then the housing shall be
electrostatically grounded when installed in hazardous area.
CABLE LENGTH
To cal cu late maximum length of the cable for reliable communication, add load resistance and approximated cable re­sistance. Please note that the loop resistance for relia ble commun ication must be in the range 230
– 1100 Ohm, 250 Ohm is
a commonly used value.
In the data-sheet for the cable you get the cable capacitance/meter. Use the
R value you calculated and the cable capacitance/meter together with the
diagram above to get the maximum length of the cable. For multidrop mode,
use the formula below. The cable length can also be calculated according to the formula:
L = 65*106 / (R * C) – (Cn*5000 +10 000) / C Where: L: is the cable length (m) R: is load resistance (including resistance of barrier)+cable resistance (ohm) C: is cable capacitance/m (pF/m) Cn: is the number of Meso transmitters in the loop.
L can also be changed to ft, if so C is given in pF/ft.
For Ex-version MESO-HX also the restrictions on cable capacitance Ci
and inductance Li stated in the Certicates and Approval documents
must be observed. Also national and regional standards and regulations must be consulted.
ORDERING TABLE
Item Part No.
Meso-H, isolated 70MEH00001 Meso-HX, isolated (ATEX) 70MEHX0001 Meso-HX, isolated (FM, CSA) 70MEHX1001 Meso-L 70MEL00001
Software and cable
HART PC modem RS232 70MEM00001 HART PC modem USB 70MEM00003 Software CD 70CDSOFT01
Accessories
Surface mounting box 70ADA00008 Rail mounting box 70ADA00009 Head mounting kit 70ADA00012 Rail mounting kit 70ADA00013
CONNECTIONS
Meso-H
Fig10
Meso-HX
Meso-L
1)
R
10
i
12-30 VDC
Fig12
1)
Fig11
see ”Cable Length”
1. Power supply, load and output signal are connected according
to gure above
2. Input signal is connected according to one of the gures 1-9
Loading...