INOR LCD-H11X Specifications

LCD-H11X
Loop Powered Heavy-duty LCD Field Indicator
LCD-H11X
LCD-H11X is a digital, heavy-duty LCD indicator for installation directly in a 4-20 mA loop without need for external power.
The indicator is equipped with high-contrast, easy-to-read LCD digits. The scale is easily programmable, without reference signal, by three push buttons for any values between - 1999 and 9999.
• Can be used with any DIN B transmitter or as display only
• Installation directly in a 4-20 mA loop without need for power supply
• Only 1.5 V voltage drop
• High-contrast, 4-digit LCD display
• Simple push button scaling without reference signal
• Any range between -1999 to 9999 for 4 to 20 mA input
• Labels for different engineering units are included
• Typical accuracy of 0.05 % allows for high precision read-outs
• HART transparent
• Designed for ambient temperatures between -25 to +70 °C / -13 to +158 °F
• Field mounting in rugged IP 66 / NEMA 4X housing
• 90° indexing of display orientation
Indicator Connections
Specifi cations:
Input Current 4-20 mA Maximum current 30 mA Minimum current for operation ~3.5 mA
Voltage drop ~1.5 V Indication
Display Black LCD with 4 digits including minus sign Digit height 12.7 mm / 0.5 ” Indication range Any range between -1999 to 9999 Decimals Selectable, 0 to 3 Under range / Over range Flashing symbols LO/HI Engineering units Set of labels included (including blanks)
Response time Appr. 0.5 s Scale setting 3 pushbuttons inside the housing Operation temperature -25 to +70 °C /-13 to +158 °F Typical accuracy ±0.05 % FS ±1 digit Connections Stranded, ≤ 1.5 mm
Enclosure
Material Pressure Die Cast Aluminium; Silicone Rubber gasket; Glass window Paint Spray Epoxy Primer with Polyurethane Top Coat. Color: RAL 5005 Signal Blue Protection NEMA 4X / IP66 FM/CSA Class 1, Div 1 & 2 [FM Cert 3019264] [CSA Cert 1717515] Conduit Connections 3 x ¾” NPT Threaded ports Mounting Wall mount or optional 2” Conduit 316 SS bar clamp
2,
AWG 16
Dimensions
108/4.25
104/4.09
106/4.17
mm/inches
110/4.33 O.A
Ordering information
LCD-H11X 70LCDH11X Confi guration 70CAL00001 SS Bar clamp 70PMB-2-SS316
For indicator only (without housing), contact Inor
SPECIALISTS IN INDUSTRIAL TEMPERATURE MEASUREMENT
37
37