INOR ISOPAQ-41P GB User Manual

USER INSTRUCTIONS English
Isolation Transmitter
www.inor.com
Read these instructions before using the product and retain for future information.
When operating the isolating transmitter, certain parts
When operating the isolating transmitter, certain parts of the module can carry dangerous voltage! Ignoring the
of the module can carry dangerous voltage! Ignoring the warnings can lead to serious injury and/or cause
warnings can lead to serious injury and/or cause damage!
damage!
The isolation transmitter should only be installed
The isolation transmitter should only be installed and put into operation by qualified staff. The staff
and put into operation by qualified staff. The staff must have studied the warnings in these operating
must have studied the warnings in these operating instructions thoroughly.
instructions thoroughly.
The transmitter may not be put into operation if the
The transmitter may not be put into operation if the housing is open.
housing is open.
In applications with high operating voltages
In applications with high operating voltages sufficient distance and isolation as well as shock
sufficient distance and isolation as well as shock protection must be ensured.
protection must be ensured.
Safe and trouble-free operation of this device can
Safe and trouble-free operation of this device can only be guaranteed if transport, storage and
only be guaranteed if transport, storage and installation are carried out correctly and operation
installation are carried out correctly and operation an maintenance are carried out with care.
an maintenance are carried out with care.
Appropriate safety measures against electrostatic
Appropriate safety measures against electrostatic discharge (ESD) should be taken during range selection
discharge (ESD) should be taken during range selection and assembly on the transmitter.
and assembly on the transmitter.
2. Short description 2. Short description
The 3-way isolation transmitter is used for electrical isolation and
The 3-way isolation transmitter is used for electrical isolation and conversion of 0 - 20 mA, 4 - 20 mA and 0 - 10 V signals. For
conversion of 0 - 20 mA, 4 - 20 mA and 0 - 10 V signals. For applications where normally only one signal combination is used,
applications where normally only one signal combination is used, IsoPAQ-41P offers a cost-effective alternative. The signal
IsoPAQ-41P offers a cost-effective alternative. The signal combination is selected by the Part No.
combination is selected by the Part No.
The 3-way isolation guarantees reliable decoupling of the sensor
The 3-way isolation guarantees reliable decoupling of the sensor circuit from the processing circuit and prevents linked measurement
circuit from the processing circuit and prevents linked measurement circuits from influencing each other. The Protective Separation with
circuits from influencing each other. The Protective Separation with high isolation level provides protection for personnel and
high isolation level provides protection for personnel and downstream devices against impermissibly high voltage.
downstream devices against impermissibly high voltage.
3. Functioning 3. Functioning
The input signal is modulated and then electrically decoupled using
The input signal is modulated and then electrically decoupled using a transformer. The isolated signal is then made available at the
a transformer. The isolated signal is then made available at the output, demodulated, filtered and amplified.
output, demodulated, filtered and amplified.
4 Equipment 4 Equipment
A screwdriver with a width of 2.5 mm is required to connect the
A screwdriver with a width of 2.5 mm is required to connect the wires to the screw clamp terminals.
wires to the screw clamp terminals.
5. Mounting, electrical connection 5. Mounting, electrical connection
The isolation transmitter is mounted on standard 35 mm DIN rail. The isolation transmitter is mounted on standard 35 mm DIN rail.
Terminal assignments Terminal assignments
1 Input + Current 2 Input - Curr ent 3 Input + Voltage 4 Input - Voltage
5 Output + 6 Output ­7 Power supply≅ 8 Power supply≅
6. Order information
Product Input / Output Part No.
IsoPAQ-41P 0 - 20 mA / 0 - 20 mA 70ISP41012 4 - 20 mA / 0 - 20 mA 70ISP41032 0 - 10 V / 0 - 20 mA 70ISP41052 0 - 20 mA / 4 - 20 mA 70ISP41014 4 - 20 mA / 4 - 20 mA 70ISP41012 0 - 10 V / 4 - 20 mA 70ISP41054 0 - 20 mA / 0 - 10 V 70ISP41016 4 - 20 mA / 0 - 10 V 70ISP41036 0 - 10 V / 0 - 10 V 70ISP41056
7. Technical Data

Input

Input signal (factory set as ordered) Input resistance
Input capacitance Overload

Output

Output signal (factory set as ordered) Load
Linear transmission range - 2 ... + 110 % Ripple < 10 mV

General data

Transmission error Temperature coefficient Cut-off frequency (-3 dB) > 1 kHz Test voltage 4 kV, 50 Hz
Working voltage2) (Basic insulation)
Protection against dangerous body currents
Ambient temperature
Powe r supp ly 20 to 253 V AC/DC AC 4 8 ... 62 Hz, approx. 2 VA
EMC3) EN 61326 -1 Construction 12,5 mm (0.5’’) housing, protection t ype: IP 20 Connection Weight Approx. 100 g
1) Average T C in specified operating temperature rang e
2) As far as relevant the standards and rules m entioned above are considered by development and production of our devices. In ad dition relevant assembly rules are to be considered by insta llation of our devices in other e quipments. For applications with high working volta ges, take measures to prevent accidental contact and make sure that there is suff icient distance or insulation between adjacent situated devices.
3) Minor deviations possible during int erference
8. Block diagram
9. Dimensions
0 - 20 mA 4 - 20 mA 0 - 10 V
Current input Voltage input
Approx. 1 nF Current input Voltage input
0 - 20 mA 4 - 20 mA 0 - 10 V
Current output Voltage output
± 0,1 % of end value
1)
± 0,005 %/K of end value
Input against output against power supply 600 V AC/DC for overvoltage category II a nd
contamination class 2 acc. to EN 61010 par t 1 Protective Separation by reinforc ed insulation acc.
2)
to EN 61010 part 1 up to 300 V AC/DC for overvoltage category II and contam ination class 2 between input and output and power suppl y.
Operation Transport and storage
2.5 mm2, AWG 14
22 1 M
200 mA Voltage limitation via 30 V Z-Diode, max. continuous current 30 mA
≤ 600 Ω ≤ 1 kΩ
rms
- 20 °C to + 70 °C (-4 to 158 °F)
- 35 °C to + 85 °C (-31 to 185 °F)
DC approx. 1,0 W
LIMITED WARRANTY
INOR Process AB, or any other affiliated company within the Inor Group (hereinafter jointly referred to as ”Inor”), hereby warrants that the Product will be free from defects in materials or workmanship for a period of five (5) years from the date of delivery (”Limited Warranty”). This Limited Warranty is limited to repair or replacement at Inor’s option and is effective only for the first end-user of the Product. Upon receipt of a warranty claim, Inor shall respond within a reasonable time period as to its decision concerning:
1. Whether Inor acknowledges its responsibility for any asserted defect in materials or workmanship; and, if so,
2. the appropriate cause of action to be taken (i.e. whether a defective product should be replaced or repaired by Inor).
This Limited Warranty applies only if the Product:
1. is installed according to the instructions furnished by Inor;
2. is connected to a proper power supply;
3. is not misused or abused; and
4. there is no evidence of tampering, mishandling, neglect, accidental damage, modification or repair without the approval of Inor or damage done to the Product by anyone other than Inor.
This Limited Warranty is provided by Inor and contains the only express warranty provided.
INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND ANY IMPLIED WARRANTY, GU ARANTEE OR REPRESENTATION AS TO SUITABILITY FOR ANY PARTICULAR PURPOSE, PERFORMANCE, QUALITY AND ABSENCE OF ANY HIDDEN DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT, WHICH BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION, OPERATION OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED HEREIN, INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL, DIRECT , SECONDARY OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE OF THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or replaced at the option of Inor. Customer pays freight to Inor, and Inor will pay the return freight by post or other “normal” way of transport. If any other type of return freight is requested, customer pays the whole return cost.
INOR Process AB
PO Box 9125 200 39 MALMÖ SWEDEN
Phone: +46 40 31 25 60 Fax: +46 40 31 25 70 E-mail: support@inor.se Internet: www.inor.com
86BIS00027 2005-05
Loading...