INOR IPAQ-LPlus Operating Manual

Output load diagram
Dimensions
()
4
Load
R
Load
at 23 mA output
8
12
Supply voltage U (VDC)
=(U-7)/0.023
363228242016
Permissible R
Load
R 1600
1200
800
400
0
Ordering table
Item Part No. Transmitter
PLUS
IPAQ-L IPAQ-LX IPAQ-LX
Options
Configuration 70CAL00001 Configuration with 5-point calibration certificate 70CAL00051
Software and cable
IPRO-X (IPRO with cable) 70IPRX0001 IPRO+ 70IPRS0001 (IPRO with IPRO+ cable) Software IPRO upgrade 70IPRS0001
PLUS
(Cenelec) 70IPLPX001
PLUS
(FM) 70IPLPX101
70IPLP0001
17.5/0.69
35/
1.38
58/2.28
45/
1.77
mm/inches
Short form data:
Power supply 7 - 36 VDC Ambient temperature -20 to + 70 °C
Isolation input/output/PC 3750VAC Mounting DIN Rail
- 4 to +158 °F
90/
3.54
User
Instructions
Intelligent Precision
Temperature
Transmitter
Measurably better transmitters
http://www.inor.com
E-mail:support@inor.se
The manual must be read prior to adjustment and/or installation.
All information subject to change without noticeMade in Sweden
LIMITED WARRANTY
INOR Process AB, or any other affiliated company within the Inor Group (hereinafter jointly referred to as ”Inor”), hereby warrants that the Product will be free from defects in materials or workmanship for a period of five (5) years from the date of delivery (”Limited Warranty”). This Limited Warranty is limited to repair or replacement at Inor’s option and is effective only for the first end-user of the Product. Upon receipt of a warranty claim, Inor shall respond within a reasonable time period as to its decision concerning:
1 Whether Inor acknowledges its responsibility for any asserted defect in materials or workmanship; and, if so,
2 the appropriate cause of action to be taken (i.e. whether a defective product should be replaced or repaired by Inor).
This Limited Warranty applies only if the Product: 1 is installed according to the instructions furnished by Inor; 2 is connected to a proper power supply; 3 is not misused or abused; and 4 there is no evidence of tampering, mishandling, neglect, accidental damage, modification
or repair without the approval of Inor or damage done to the Product by anyone other than Inor.
This Limited Warranty is provided by Inor and contains the only express warranty provided.
INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE OR REPRESENTATION AS TO SUITABILITY FOR ANY PARTICULAR PURPOSE, PERFORMANCE, QUALITY AND ABSENCE OF ANY HIDDEN DEFECTS, AND ANY REMEDY FOR BREACH OF CON­TRACT, WHICH BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION, OP­ERATION OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING, INCLUDING IM­PLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED HEREIN, INOR FURTHER DISCLAIMS ANY RE­SPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL, DIRECT, SEC­ONDARY OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE OF THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or replaced at the option of Inor. Customer pays freight to Inor, and Inor will pay the return freight by post or other “normal” way of transport. If any other type of return freight is requested, customer pays the whole return cost.
PO Box 9125, S-200 39 MALMÖ, Sweden.
Phone:
Domestic 040-31 25 60 International +46-40-31 25 60
Fax:
Domestic 040-31 25 70 International +46-40-31 25 70 E-mail: support@inor.se
Postfach 1410, D-64836 Münster, Germany.
Phone:
Domestic 06071-61 20 08 International +49-6071-61 20 08
Fax:
Domestic 06071-61 20 07 International +49-6071-61 20 07
E-mail:
1860 Renaissance Blvd., Suite 203 Sturtevant, WI 53177, USA
Phone:
Domestic 1-888-430-INOR International +1-414-884-4535
Fax:
Domestic (414) 884-4537 International +1-414-884-4537 E-mail: inor@ols.com
86BIQ00013 1098
inor.gmbh@t-online.de
(414) 884-4535
Introduction
PLUS
IPAQ-L precision temperature transmitter. The size and versatillity makes an ideal choice for all industrial instrumentation. The transmitter give you the possibility to use a customized linearization using 40 points, or 8 third de­gree polynimials to give you the best possi­ble precision.
IPAQ-L gent way to monitor the isolation resitance.
is a loop-powered intelligent
PLUS
also have SmartSense, an intelli-
INPUTS
Pt100, Pt1000, Ni100, Ni1000
4-wire connection
3-wire connection
RTD
3-wire connection
with ”SmartSense”
Pt100
Pt100
Diff temperature T1>T
2
General information
PLUS
IPAQ-L
is a two-wire precision rail­mounted transmitter intended to be used in industrial environment.
The transmitter is configured from a stand­ard IBM compatible PC by using the IPRO software (version 4.1 or later). When the transmitter is reconfigurated by a PC no recalibration is needed.
You can connect a digital display to the transmitter for a local readings. The display is connected to the communication port and is powered from the transmitter.
The transmitter will update the display every second once it is connected.
Connection
1. Power supply and output signal are con-
nected according to figures to the right. Power supply IPAQ-L
PLUS
with 7 - 36V.
2. Input signal is connected according to
figures to the right.
3. Communication cable and the digital
display are connected according to figures to the right.
Configuration
The IPAQ-L be externally powered when you configure with the IPRO+ communication cable. If you use the IPRO-X communication cable you need to power the transmitter. To con­figure the transmitter you need IPRO (the IPAQ software). If IPRO is not installed in your PC, install the software following the instructions in ”IPRO User instructions”.
Configuration from PC is "on-line", that is, the transmitter can be installed in the proc­ess with the input connected during configu­ration. The output is frozen while transmis­sion from PC to IPAQ takes place. When the transfer is done, the transmitter uses the new parameters.
PLUS
transmitter do not have to
Jack for connecting PC
and digital display
Potentiometer
4-wire connection
*
*Max input
OUTPUT
4-20 mA Output
+
Power Supply
-
R
Load
3-wire connection
*
*Max input
Connections
Power supply
+
*
-
Test (mA)
+
Input
SmartSense:
The transmitter continuously supervises the isolation resistance in thermocouples and 3-wire-connected Pt100/D100 including the connection wires. If the isolation resistance is low it causes error in the measurements and consequently a faulty output. The transmitter indicates low isolation resistance by forcing the output to a preprogrammed value. This function requires setting by the PC-program IPRO and the use of a temperature sensor with an extra wire.
-
78 56
-Test
7 45
+Out -
mV
- +
12 34
12 3
4
T
2
*SmartSense lead
Voltage
millivolt
- +
Thermocouple
AE,B,E,J,K,L,N,R,S,T,U
or customer specific
- +
*SmartSense lead
SmartSense
R
LOAD
I
OUT
PC/Display Connection
Pt100/D100
*
T/C
*
SmartSense lead
Calibration
Since IPAQ-L recommended checking the calibration once a year. Use equipment with an inaccuracy of at least 5 times better than the checked one, e.g. if you are checking a transmitter with an inaccuracy of 0.05% use instrument with an inaccuracy of maximum 0.01%.
You can either perform a full recalibration of the transmitters stored calibration param­eters (Basic Calibration) or make a System Error Correction (recommended). In each case use the IPRO software and follow the instructions on the screen. When performing a System Error Correction, please note that this is only a compensation for errors at the measuring range in use.
PLUS
is a precision instrument it´s