Output load diagram
Dimensions
(Ω)
4
Load
R
Load
at 23 mA output
8
12
Supply voltage U (VDC)
=(U-7)/0.023
363228242016
Permissible R
Load
R
1600
1200
800
400
0
Ordering table
Item Part No.
Transmitter
PLUS
IPAQ-L
IPAQ-LX
IPAQ-LX
Options
Configuration 70CAL00001
Configuration with 5-point
calibration certificate 70CAL00051
Software and cable
IPRO-X (IPRO with cable) 70IPRX0001
IPRO+ 70IPRS0001
(IPRO with IPRO+ cable)
Software IPRO upgrade 70IPRS0001
PLUS
(Cenelec) 70IPLPX001
PLUS
(FM) 70IPLPX101
70IPLP0001
17.5/0.69
35/
1.38
58/2.28
45/
1.77
mm/inches
Short form data:
Power supply 7 - 36 VDC
Ambient temperature -20 to + 70 °C
Isolation input/output/PC 3750VAC
Mounting DIN Rail
- 4 to +158 °F
90/
3.54
User
Instructions
Intelligent Precision
Temperature
Transmitter
Measurably better transmitters
http://www.inor.com
E-mail:support@inor.se
The manual must be read prior to adjustment and/or installation.
All information subject to change without noticeMade in Sweden
LIMITED WARRANTY
INOR Process AB, or any other affiliated company within the Inor Group (hereinafter jointly
referred to as ”Inor”), hereby warrants that the Product will be free from defects in materials or
workmanship for a period of five (5) years from the date of delivery (”Limited Warranty”).
This Limited Warranty is limited to repair or replacement at Inor’s option and is effective only
for the first end-user of the Product. Upon receipt of a warranty claim, Inor shall respond
within a reasonable time period as to its decision concerning:
1 Whether Inor acknowledges its responsibility for any asserted defect in materials or
workmanship; and, if so,
2 the appropriate cause of action to be taken (i.e. whether a defective product should be
replaced or repaired by Inor).
This Limited Warranty applies only if the Product:
1 is installed according to the instructions furnished by Inor;
2 is connected to a proper power supply;
3 is not misused or abused; and
4 there is no evidence of tampering, mishandling, neglect, accidental damage, modification
or repair without the approval of Inor or damage done to the Product by anyone other
than Inor.
This Limited Warranty is provided by Inor and contains the only express warranty provided.
INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED
HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE OR REPRESENTATION AS TO
SUITABILITY FOR ANY PARTICULAR PURPOSE, PERFORMANCE, QUALITY AND
ABSENCE OF ANY HIDDEN DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT, WHICH BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION, OPERATION OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE. EXCEPT AS PROVIDED HEREIN, INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL, DIRECT, SECONDARY OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE OF
THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or replaced at the
option of Inor. Customer pays freight to Inor, and Inor will pay the return freight by post or
other “normal” way of transport. If any other type of return freight is requested, customer pays
the whole return cost.
PO Box 9125,
S-200 39 MALMÖ, Sweden.
Phone:
Domestic 040-31 25 60
International +46-40-31 25 60
Fax:
Domestic 040-31 25 70
International +46-40-31 25 70
E-mail: support@inor.se
Postfach 1410,
D-64836 Münster, Germany.
Phone:
Domestic 06071-61 20 08
International +49-6071-61 20 08
Fax:
Domestic 06071-61 20 07
International +49-6071-61 20 07
E-mail:
1860 Renaissance Blvd., Suite 203
Sturtevant, WI 53177, USA
Phone:
Domestic 1-888-430-INOR
International +1-414-884-4535
Fax:
Domestic (414) 884-4537
International +1-414-884-4537
E-mail: inor@ols.com
86BIQ00013 1098
inor.gmbh@t-online.de
(414) 884-4535

Introduction
PLUS
IPAQ-L
precision temperature transmitter. The size
and versatillity makes an ideal choice for all
industrial instrumentation. The transmitter
give you the possibility to use a customized
linearization using 40 points, or 8 third degree polynimials to give you the best possible precision.
IPAQ-L
gent way to monitor the isolation resitance.
is a loop-powered intelligent
PLUS
also have SmartSense, an intelli-
INPUTS
Pt100, Pt1000, Ni100, Ni1000
4-wire connection
3-wire connection
RTD
3-wire connection
with ”SmartSense”
Pt100
Pt100
Diff temperature T1>T
2
General information
PLUS
IPAQ-L
is a two-wire precision railmounted transmitter intended to be used
in industrial environment.
The transmitter is configured from a standard IBM compatible PC by using the IPRO
software (version 4.1 or later). When the
transmitter is reconfigurated by a PC no
recalibration is needed.
You can connect a digital display to the
transmitter for a local readings. The display
is connected to the communication port and
is powered from the transmitter.
The transmitter will update the display
every second once it is connected.
Connection
1. Power supply and output signal are con-
nected according to figures to the right.
Power supply IPAQ-L
PLUS
with 7 - 36V.
2. Input signal is connected according to
figures to the right.
3. Communication cable and the digital
display are connected according to
figures to the right.
Configuration
The IPAQ-L
be externally powered when you configure
with the IPRO+ communication cable. If
you use the IPRO-X communication cable
you need to power the transmitter. To configure the transmitter you need IPRO (the
IPAQ software). If IPRO is not installed in
your PC, install the software following the
instructions in ”IPRO User instructions”.
Configuration from PC is "on-line", that is,
the transmitter can be installed in the process with the input connected during configuration. The output is frozen while transmission from PC to IPAQ takes place. When
the transfer is done, the transmitter uses
the new parameters.
PLUS
transmitter do not have to
Jack for connecting PC
and digital display
Potentiometer
4-wire connection
*
*Max input
OUTPUT
4-20 mA Output
+
Power
Supply
-
R
Load
3-wire connection
*
*Max input
Connections
Power supply
+
*
-
Test
(mA)
+
Input
SmartSense:
The transmitter continuously supervises the
isolation resistance in thermocouples and
3-wire-connected Pt100/D100 including the
connection wires. If the isolation resistance is
low it causes error in the measurements and
consequently a faulty output. The transmitter
indicates low isolation resistance by forcing
the output to a preprogrammed value. This
function requires setting by the PC-program
IPRO and the use of a temperature sensor
with an extra wire.
-
78
56
-Test
7
45
+Out -
mV
- +
12
34
12
3
4
T
2
*SmartSense lead
Voltage
millivolt
- +
Thermocouple
AE,B,E,J,K,L,N,R,S,T,U
or customer specific
- +
*SmartSense lead
SmartSense
R
LOAD
I
OUT
PC/Display
Connection
Pt100/D100
*
T/C
*
SmartSense lead
Calibration
Since IPAQ-L
recommended checking the calibration once
a year. Use equipment with an inaccuracy of
at least 5 times better than the checked one,
e.g. if you are checking a transmitter with an
inaccuracy of 0.05% use instrument with an
inaccuracy of maximum 0.01%.
You can either perform a full recalibration
of the transmitters stored calibration parameters (Basic Calibration) or make a System
Error Correction (recommended). In each
case use the IPRO software and follow the
instructions on the screen. When performing
a System Error Correction, please note that
this is only a compensation for errors at the
measuring range in use.
PLUS
is a precision instrument it´s
T
1
*