Innovative Technology ICT22012-100, ICT22012-140, ICT22012-70, ICT22024-35, ICT22024-70 Instruction Manual

...
Page 1
THEPOWEROFRELIABILITY
INNOVATIVE CIRCUIT TECHNOLOGY LTD.
855-080-005
ICT N+1 REDUNDANT SERIES
INSTRUCTION MANUAL
Incorrect wiring, such as reverse battery connection, may result in serious damage to both the N+1 system and equipment connected to the system.
Servicing of the unit should be done by ICT.
Ensure that the two voltage selector switches are both set correctly and to the same position. If the switches are incorrectly set it will result in module failure.
The system must be operated from an outlet with a proper grounding connection.
If replacing modules, disconnect power from any external source including the AC cord and any connected batteries.
WARNING: High leakage current, use only cord set provided with this equipment.
ICT N+1 REDUNDANT SERIES
SETUP SAFETY + WARNINGS
The ICT N+1 Redundant Series is a high reliablity, expandable DC power system. The system is designed with active current sharing technology to distribute the load current among the modules, reducing stress on individual components and increasing reliability. Each module is equipped with a high power shottky output diode for true redundancy.
This series comes standard with system monitoring functions through a D-Sub connector, with signals such as module ok, over temperature warning, analog DC output current, fan failure, and AC fail. Battery backup terminals are provided for float charging an external lead acid battery and providing battery revert capability.
These instructions should be read before using the product and it should be saved for future reference. A more detailed manual is available on request from ICT.
For 120V operation, set both voltage selection switches to the 120V position. For 220V operation, set both to the 220V position.
After the system has been mounted, connect the load to the terminal block at the rear of the unit. If desired, connect a 12V or 24V lead acid battery (matching the N+1 system voltage) to the battery terminals for float charging.
A disconnect device must be provided for both the DC power output circuit and the battery backup circuit if used. The backup battery (if used) should be provided with an overcurrent device suitable for the available short circuit current of the batteries used.
Connect the AC power cord to the unit and then to the available outlet. Alternate AC cord types are available.
Turn the power switch on the front of the unit to the on position.
4
4
4
4
4
4
4
4
4
4
4
4
Input
Voltage
Range
Configs.
Output
Voltage
Output
Current
(Cont.)
Output
Current
(Peak)
Current
Limiting
Line
Regulation
Load
Regulation
Output Ripple
(Max)
Efficiency
(Typical)
# of
Modules
N NM
N - Standard NM - with LCD Meter
105-130/
205-250 VAC
13.8 VDC
+/- 300 mV
34.0 Amps 70.0 Amps 80.0 Amps 2.20% 1.00% 40 mV RMS 79%
ICT22012-70
2
105-130/
205-250 VAC
13.8 VDC
+/- 300 mV
105.0 Amps 105.0 Amps 120.0 Amps 2.20% 1.00% 40 mV RMS 79%
ICT22012-100
3
105-130/
205-250 VAC
13.8 VDC
+/- 300 mV
83.0 Amps
(90A @ 240 VAC)
127.0 Amps 160.0 Amps 2.20% 1.00% 40 mV RMS 77% (80% @ 240 VAC)
4
105-130/
205-250 VAC
27.6 VDC
+/- 600 mV
17.0 Amps 36.0 Amps 40.0 Amps 2.20% 1.00%
40 mV RMS 83%
ICT22024-35
2
105-130/
205-250 VAC
27.6 VDC
+/- 600 mV
34.0 Amps 54.0 Amps 60.0 Amps 2.20% 1.00%
40 mV RMS 83%
ICT22024-50
3
105-130/
205-250 VAC
27.6 VDC
+/- 600 mV
41.0 Amps
(51A @ 240 VAC)
56.0 Amps4 80.0 Amps 2.20% 1.00%
40 mV RMS 83%
(84% @ 240 VAC)
ICT22024-70
105-130/
205-250 VAC
13.8 VDC 34.0 Amps 35.0 Amps-- 36.0 Amps 2.20% 1.00% 35 mV RMS 80%
ICT12-30
105-130/
205-250 VAC
27.6 VDC 17.0 Amps 18.0 Amps-- 19.0 Amps
Redundant
Current
34.0 Amps
34.0 Amps
34.0 Amps
17.0 Amps
17.0 Amps
17.0 Amps
--
-- 2.20% 1.00% 40 mV RMS 80%
ICT24-17
Modules
All complete systems are CSA C22.2 No 107.1, UL 1012 Approved
& FCC class A Compliant
SPECIFICATIONS
ICT22012-140
Page 2
LIMITED WARRANTY
INNOVATIVE CIRCUIT TECHNOLOGY LTD.
26921 GLOUCESTER WAY LANGLEY, BRITISH COLUMBIA, CANADA V4W 3Y3
T 604.856.6303 F 604.856.6365 www.ictcorporate.com
ICT Limited Warranty is only intended for the benefit of the original Purchaser of this product. This Warranty is not transferable or assignable without the prior written permission of ICT. ICTʼs sole obligation and liability under this warranty is limited to either repairing or replacing defective products at the sole discretion of ICT. When repairing or replacing the products, ICT may use products or parts that are new, equivalent to new or re-conditioned. Parts repaired or replaced during the warranty period will be under warranty for the remainder of the warranty period.
The warranty period on ICT products purchased new from ICT is two years. The warranty period for a repaired product or part thereof is ninety (90) days or the remainder of the unexpired term of the new product warranty period, whichever is greater. Repair or replacement of a defective product or part does not extend the original warranty coverage period.
No claim will be accepted unless written notice of the claim is received by ICT in accordance with ICTʼs Return Material Authorization (RMA) procedure, as soon as reasonably possible after the defect is discovered. A valid product serial number must be provided with the RMA claim to prove eligibility. The RMA form is available on the ICT website at www.ict-power.com/support/warranty-repair/.
The Purchaser shall at their own risk and cost return the defective product to ICTʼs factory or designated repair center once an RMA is issued by ICT. Return of the products to the customer after repair is completed shall be prepaid by ICT unless otherwise mutually agreed between the parties. Products shipped to ICT which have incurred freight damage will not be covered by this Warranty and any repairs or replacement parts, components or products needed will be invoiced in the full current price amount and returned freight collect to Purchaser. It is the Purchaserʼs responsibility to check the product upon receipt for any damage during shipping and to contact the carrier or shipper regarding such damage. Product that is returned as defective, which is determined to operate within published specifications will be returned to the Purchaser freight collect.
This Warranty will be void if the product has been subjected to misuse, neglect, accident, exposure to environmental conditions not conforming to the productsʼ limits of operation, improper installation or maintenance, improper use of an electrical source, defects caused by sharp items or by impact pressure, a force majeure event, has been modified or repaired by anyone other than ICT or its authorized representative, has been subjected to unreasonable physical, thermal or electrical stress, improper maintenance, or causes external to the unit including but not limited to general environmental conditions such as rust, corrosive atmospheres, sustained temperatures outside the specified operating range of the equipment, exposure to power surges and/or electrical surges, improper grounding, mould or dust, animal or insect damage, water damage or immersion in liquid of any kind.
ICT does not control the installation and use of any ICT product. Accordingly, it is understood this does not constitute a warranty of performance or a warranty of fitness for a particular purpose.
STANDARD FEATURES AND OPTIONS (continued)
Input Fuse Protection protects against over current at the input of each module and on the backplane.
13 12 11 10 9 8 7 6 5 4 3 2 1
25 24 23 22 21 20 19 18 17 16 15 14
STATUS
FUNCTION
+15V supply AC Power Good Signal (5 VDC = good) Not Connected Fan Fail (5 VDC = ok, 0 VDC = fail) Not Connected System current (0 VDC to 5 VDC = 0A to maximum system current) Module 1 check (5 VDC = good) Module 2 check (5 VDC = good) Module 3 check (5 VDC = good) Module 4 check (5 VDC = good) Not Connected Over-temperature sense (5 VDC = fail) System output voltage sense Signal Ground
PIN
1 2 3 4 5 6 7 8
9 10 11 12 13
14-25
The N+1 is equipped with a 25 pin D-Sub female connector (behind “STATUS CONNECTOR” panel on the rear of the unit) with the following pinout:
The unit features protection in the event of faults, transients and other abnormalities.
LED Status Display (Standard)
A green LED status indicator is provided in the top right to indicate that there is a DC voltage present at the output terminals of the power supply.
Protection Features (Standard)
A green LED is provided in the top left for indication of the presence of AC voltage.
Two LED indicators are provided for each of the four internal modules. A green LED will be lit to indicate that there is a voltage present at the output of the module. A yellow LED will be lit if the module voltage is not present, either due to a fault or absence of the module.
Current Limit and Foldback protection are present on each module to prevent the load from drawing current above the maximum allowable value. If an excessive load is drawn the output voltage will start to fold back, and in the case of a hard short the current will be reduced as well.
Surge protection is provided on the backplane and each module to protect against input voltage transients.
DESCRIPTION OF OPERATION
The N+1 redundant power system consists of a backplane and up to 4 modules. Each module is a 400+ watt DC power supply. They are highly efficient current mode power supplies with electronic current and voltage foldback protection.
For true N+1 operation, each module includes a redundant OR-ing diode. This diode ensures that no matter what type of failure occurs in one of the power modules, it will not affect the DC bus. Each one of these highly reliable power modules is connected through the system backplane.
Through the backplane, each module is connected to create an active load sharing network. This feature forces all of the modules to share the load evenly.
ADJUSTMENT AND SERVICING
Remove the three screws located on the top of the system cover using a Phillips screwdriver. Then loosen the four screws on the sides of the case. You can now remove the lid. Each module is secured with 3 screws. Remove the screws using a Phillips screwdriver. To remove a module, pull the module away from the backplane until it is disconnected from the quick connector and then lift the end up carefully.
STANDARD FEATURES AND OPTIONS
Battery Backup (Standard)
During normal operation, the power supply will provide power to the output while float charging the battery that is connected at the battery backup output. In the event that the AC power source is interrupted, the battery will supply power to the load through an isolation diode; however, the load voltage will be
0.4V lower than the battery voltage. The power resistors used to float charge the battery limit the charging current to about 5 Amps. During battery operation the fans are thermally controlled to conserve power.
Removal of Module
Installation of Module
To install a module, follow the steps to remove a module in reverse. Pay special attention to the five spring clips in the metal heat sink of the module. These should be tight and care should be taken not to dislodge them.
Before opening the cover, be sure to turn off the unit and unplug any power sources entering the unit. This includes both the AC power souce and any battery connections. A full manual with more detailed instructions is available on request.
An optional LCD display is available for the system. This display shows the output voltage, current, and module status. A plug symbol indicates that AC power is available, while a battery symbol indicates that the unit is running on the backup batteries. The display is backlit for better contrast in a wide range of ambient light conditions.
LCD Display (M Option)
Protection Features (Continued)
Loading...