USER’S OPERATING M AN UA L FOR PID DIGITAL TEMPERATURE CONTROLLER
(Models: AI 7481 / 7781 / 7981 / 7681 / )7881
1. DISPLAY TYPE : Dual 4- Digit 7 segment LED
4 Digit Bright Red (PV) 4 Digit Luminous Green (SV)
STATUS LED’S : OP 1 : Main Control Output
2. INPUT Sensor input : TC : J,K,R,S,N,T,B
RTD : Pt-100
Range : Refer below table.
Sampling Time : 125 msec. Resolution : 1°C/0.1°C(Only for RTD) CJC for TC : Built in automatic LWC for Pt-100 : Built in upto 18E max. Digital Filter : 1 to 10 Sec.
3. RELAY OUTPUT Contact type : N/O, CM, N/C Contact Rating : 5A @ 250VAC or 30 VDC Life expectancy : > 5,00,000 operations Isolation : Inherent
4. SSR DRIVE OUTPUT Drive Capacity : 12V @ 30mA. Isolation : Non-Isolated.
5. FUNCTION Output 1 : Main Control output Control Action : ON-OFF/PID (Select) Control Mode : Heat/Cool (Select)
6. ENVIRONMENTAL Operating Range : 0 ~50°C, 5~90% Rh Storage Humidity : 95% Rh (Non-condensing)
7. POWER SUPPLY Supply Voltage : 90~270VAC, 50/60Hz. Consumption : 4W Maximum.
8. PHYSICAL Housing : ABS Plastic.
SPECIFICATIONS : -
SAFETY INSTRUCTION :
This controller is meant for temperature control applications. It is important to read the manual prior to installing or commissioning of controller. All safety related instruction appearing in this manual must be followed to ensure safety of the operating personnel as well as the instrument.
GENERAL
v The controller must be configured correctly for intended
operation. Incorrect configuration could result in damage to the equipment or the process under control or it may lead personnel injury.
v The controller is generally part of control panel and in
such a case the terminals should not remain accessible to the user after installation.
MECHANICAL
v The Controller in its installed state must not come in
close proximity to any corrosive/combustible gases, caustic vapors, oils, steam or any other process by­products.
v The Controller in its installed state should not be
exposed to carbon dust, salt air, direct sunlight or radiant
heat.
v Ambient temperature and relative humidity surrounding
the controller must not exceed the maximum specified limit for proper operation of the controller.
v The controller in its installed state must be protected
against excessive electrostatic or electromagnetic interferences. Ventilation holes provided on the chassis of the instrument are meant for thermal dissipation hence should not be obstructed in the panel.
ELECTRICAL
v The controller must be wired as per wiring diagram & it
must comply with local electrical regulation.
v Care must be taken not to connect AC supplies to low
voltage sensor input.
v Circuit breaker or mains s/w with fuse (275V/1A) must be
installed between power supply and supply terminals to protect the controller from any possible damage due to high voltage surges of extended duration.
v Circuit breaker and appropriate fuses must be used
for driving high voltage loads to protect the controller from any possible damage due to short circuit on loads.
v To minimize pickup of electrical noise, the wiring for low
voltage DC and sensor input must be routed away from high current power cables. Where it is impractical to do this, use shielded ground at both ends.
v The controller should not be wired to a 3-Phase supply
with unearthed star connection. Under fault condition such supply could rise above 264 VAC which will damage the controller.
v The Electrical noise generated by switching inductive
loads might create momentary Fluctuation in display, alarm latch up, data loss or permanent damage to the instrument. To reduce this use snubber circuit across the load.
v It is essential to install a over Temp. Protection device to
avoid any failure of heating system. Apart from spoiling the product, this could damage the process being controlled.
Model no.
Display height (PV)
Display height (SV)
AI-7481
0.30” 0.56”
0.80” 0.36”
0.36”
0.36”0.36”0.24”
0.39”
0.56”
AI-7881AI-7781 AI -79 81 AI -76 81
Fe-k(J) T/C
Cr-AL(K) T/C
Sensor Type
Accuracy
o
± 1 C
o
0 ~ 1700 C
o
0 ~ 1700 C
o
0 ~ 1800 C
o
-100 ~ 450 C
Resolution
Range
o
1 C
o
1 C
o
1 C
}
(R) T/C
(S) T/C
TC - N
TC - T
TC - B
Pt-100(RTD)
Pt-100(RTD 0.1)
o
0 ~ 760 C
o
-99 ~ 1300 C
o
-99 ~ 1300 C
o
-99 ~ 400 C
o
-99.9 ~ 450.0 C
o
1 C
o
1 C
o
1 C
o
1 C
o
1 C
o
0.1 C
o
± 0.3 C
OP1
PV
SV
TUNE
SET AT
-therm
i
AI-7981
OP1
PV
SV
-therm
i
AI-7781
SET AT
AI-748 1
OP1
PV
SV
SET AT
SET
AT
PV
SV
AI-768 1
OP1
PV
SV
AI-788 1
OP1
SET
AT
1
OIM AI-7X81 V2.0 Page 1 of 6
i
OVER ALL DIMENSIONS & PANEL CUT OUT (IN MM)
TABLE : 1
Model
Dim
48 72 96 96 48
48 72 96 48 96
8 10 10 10 10
75 65 45 45 45
44 68 92 44 92
44 68 92 92 44
9 9 9 9 9
A B
HC D F GE
43 66 89 89 43
AI-7481 AI-7781 AI-7981 AI-7681 AI-7881
MECHANICAL INSTALLATION
The label on the controller identifies the serial number, wiring connec tions and batch number.
INSTALLATION GUIDELINES :
1. Prepare the cut-out with proper dimension as shown in Figure.
2. Remove clamp from controller
3. Push the controller through panel cut-out and secure the controller in its place by tightening the side clamp.
C H
MODEL : AI - 7681
E
D
C
H
A
B
F
G
PANEL
CUTOUT
CAUTION: To prevent the risk of electrical shock, switch off the power before making/removing any connection or removing
the controller from its enclosure.
ELECTRICAL INSTALLATION :
The el ectri cal connection diagr am show n on the controller encl osure i s as below.
A
B D
E
G
F
MODEL:-AI-7481/7781/7981
PANEL
CUTOUT
MODEL : AI - 7881
B
A
E
D
C
H
G
F
PANEL
CUTOUT
4
5
6
7
1
2
3
AI - 7481
6 7
4
5
1
2
3
AI - 7781
6 7
4
5
1
2
3
AI - 7981
FRONT PANEL LAYOUT
1
2
4
3
6
7
5
AI - 7881
AI - 7681
1
5
3
2
6
4
7
AI - 7981
AI - 7681 / AI - 7881
AI - 7781
SUPPLY
L
N
1
2
3
4
5
6
7
8
9
10
11
12
15
16
13
14
NO NCCM
SSR
AI - 7481
SUPPLY
L
N
1
2
3
4
5
6
7
8 9
10
11
13
14
15
16
12
NO NCCM
SSR
1
2
3
4
5
6
10
11
12 13 14 15 16 17 18
7
8
9
NO NCCM
RELAY
RELAY
RELAY
SSR
SUPPLY
L
N
1
2
3
4
5
6
7
8
9
10
11
12 13 14 15 16 17 18
NO NCCM
RELAY
SSR
SUPPLY
L
N
OP1
PV
SV
TUNE
SET AT
-therm
i
AI-7981
OP1
PV
SV
-therm
i
AI-7781
SET AT
AI-748 1
OP1
PV
SV
SET AT
SET
AT
PV
SV
AI-7681
OP1
PV
SV
AI-7881
OP1
SET
AT
Glows when OP1 is ON & flashes when delay time (dly1) is in operation(if selected mode is ON-OFF)
( ( ( along with UP k ey. (4) To scroll the pa ram ete r & to st ore i ts value.
1) For SP pro gramming. 2) To ac ces s C ontrol mod e. 3) To ac ces s Co nfi gur ati on m ode
( ( (with SET key ) . (3) To acknow led ge Ala rm. ( 4) To enter in tu ne mo de (w ith D OWN K ey).
1) To in crease/alt er param ete r val ue in program mode . 2 ) To Ente r in co nfi gur ati on mo de
( ( To ente r in tune m ode (wi th UP Ke y).
1) To d ecr eas e / alter paramete r value in pro gram mo de. 2)
It will displ ay (1 ) Mea sur ed va lue of selecte d inp ut or E rro r massages in ru n mod e. (2) Paramet ers Va lue in program m ode .
It will display (1) (Main s ) / SP2 ( Aux ili ary /Al arm) set value / Set Soa k tim e value/ bala nce o r ela pse d soa k time in run mode . (2) P ara met er co de in program mo de.
SP et point
1
2
3
4
5
6
7
OP1 LED
UPPER
DISPLAY
LOWER
DISPLAY
SET KEY
SHIFT
KEY
Sr.
NAME FUNCTION
UP
KEY
DOWN
KEY
(1) To in crease/alt er pa ram ete r val ue in program mo de wi th Up / D n Key. (2) Press for 3 Sec i n Pro gra mmi ng this will hel p to go b ack t o pre vious parame ter.
FRONT PANEL LAYOUT DESCRIPTION :
2
OIM AI-7X81 V2.0 Page 2 of 6
Model no.
Weight (gms.)
AI-74 81 AI-77 81 AI-79 81 AI-78 81AI-76 81
130 200 240 200 200
i
DELAY 1
0
to
500 Sec.
This parameter will be prompted only if selected control action is ON-OFF. It sets the main output restart time where O/P once turned off will turn ON only after restart time, regardless difference between PV & SP in Heat or Cool mode. If set to '0', O/P will be switched without delay. Also, Delay will be applicable in case of every power ON.
90 Sec.
CONTROL
HYS
o
1 to 25 C
This parameter will be prompted only if selected control action is ON-OFF. It sets the dead band between ON & OFF switching of the Output. Larger value of hysterisis minimize the number of ON-OFF operation to the load. This increases life of actuators like contactors but, also produces large errors (between PV & SV).
2°C
OUTPUT
OFF
1 to 10
This parameter will be prompted only if selected control action is PID. With this parameter O/P will be Completely OFF after the Set Point + Offset Value. If Disable, O/P will act Depending upon the PID Value after Set Point achieved.
Disable
This parameter will be available only if Enabled in Configuration List. User can set ramp rate/min for SP1 (Set Point) to minimize overshoot.
RAMP RATE
o
0.0 C to
o
25.0 C
Disable
POWER UP :
At power on, f ol lo wi ng sequence will be prompted on the display for 1 sec. till it reaches to Home display mode.
User can change SP value using UP/ DOWN keys. Holding the key, will change the value at a faster rate. Press SET key to store the desired value & move on to the next parameter.
o
0 C
LSPL ~ HSPL
CONTROL
SET
POINT
PROGRAMMING
USER LIST : To access the user list press SET key once.
LOWER
DISPL AY
UPPER
DISPL AY
PARA
METER
RANGE
DESCR IPT ION
DEFAULT
UPPER
DISPL AY
LOWER
DISPL AY
MODEL VERS ION INPUT HOME
PV
SV
LOWER
DISPL AY
UPPER
DISPL AY
PARA
METER
RANGE
DESCR IPT ION
DEFAULT
PROPORTIONAL
BAND
0.5
to
99.9°C
This parameter will be prompted only if selected control action is PID. It sets bandwidth over which the output power is adjusted depending upon the error (SV-PV). The value of this parameter is automatically set by Auto tune function.
o
5.0 C
INTEGRAL
TIME
0
to
9999 Sec.
This parameter will be prompted only if selected control action is PID. It sets the time taken by PID algorithm to remove steady state error. The value of this parameter is automatically set by Auto tune function. If set to ‘0’, this function will be disabled.
240
DERIVATIVE
TIME
0
to
300 Sec.
This parameter will be prompted only if selected control action is PID. It defines how strongly the controller will react to the rate of change of PV. The value of this parameter is automatically set by Auto tune function. If set to ‘0’, this function will be disabled.
60
CYCLE
TIME
0.5
to
100.0 Sec.
This parameter will be prompted only if selected control action is PID. User can set this value based on process being controlled & type of output being selected. For Relay O/P, cycle time should be more than 12sec & for SSR O/P, cycle time should be less than 10sec.
16.0 Sec.
0
Set this parameter to 15 (Default LOCK CODE) to access Control List. User has a choice to set different Lock Code via USER LOCK CODE in Config. List.
1 ~ 9999
LOCK CODE
CONTROL LIST : SET & DOWN key simultaneously To enter in this mode, press for 3 sec. User can then set
the control parameters.
50 %
to
100 %
100 %
TUNE
OFFSET
This parameter will be prompted only if selected control action is PID. This parameter allows the User to carry out Auto Tuning function below set point.(If tune offset is 50 %, tuning will be carried out at 50 % of set point and if 100 %, tuning will be carried out at 100% of the set point.)
100 %
OUTPUT POWER
LIMIT
0.0 % TO
100.0 %
This parameter will be prompted only if selected control action is PID. This parameter will decide the Max. output power in % applied to the load.
3
OIM AI-7X81 V2.0 Page 3 of 6
i
CONTROL
LOGIC
FOR O/P
HEAT
This parameter will be prompted only if selected control mode is ON-OFF. User can select heating logic in which OP1 will remain ON till PV < SP. (PV increases when output is ON.)
This parameter will be prompted only if selected control mode is ON-OFF. User can select cooling logic in which OP1 will remain ON till PV > SP. (PV decreases when output is ON.)
0
Set this parameter to 15 (Default LOCK CODE) to access Config. List. User has a choice to set different Lock Code via USER LOCK CODE in Config. List.
LOCK CODE
LOWER
DISPL AY
UPPER
DISPL AY
PARA
METER
DESCR IPT ION
DEFAULT
CONTROL
MODE
FOR O/P 1
PID
User can select between PID or ON-OFF action algorithm to be adopted for output.
INPUT
FILTE R
o
1 C
Controller is equipped with an adaptive digital filter which is used to filter out any extraneous pulses on the PV. Filtered PV Value is used for all PV dependent functions. If PV signal is fluctuating due to noise, increase the filter time constant value.
PROCESS
VALUE
OFFSET
o
0 C
Function of this parameter is to add/subtract a constant value to the measured PV to obtain Final PV for control applications. This parameter value needs to be altered for one of the following reason : (i) To compensate for known thermal gradient. (ii) To match the display values with another recorder or indicator measuring the same PV.
LOWER
SET
POINT
LIMIT
o
0 C
Sets the minimum limit for set point adjustment. It can be set from minimum specified range of selected sensor to HSPL value.
HIGHER
SET
POINT
LIMIT
o
400 C
Sets the maximum limit for set point adjustment. It can be set from LSPL value to maximum specified range of selected sensor.
Fe-k(J) T/C
Cr-AL(K) T/C
Pt-100(RTD)
Sensor Type
Accuracy
1
±o
C
o
0 ~ 760 C
o
-99 ~ 1300 C
o
-99 ~ 1300 C
o
-99 ~ 400 C
o
0 ~ 1800 C
o
-100 ~ 450 C
Resolution
Range
o
1 C
o
1 C
o
1 C
}
(R) T/C
(S) T/C
TC - N
TC - T
TC - B
Pt-100(RTD 0.1)
o
-100.0 ~ 450.0 C
o
0 ~ 1700 C
o
0 ~ 1700 C
o
1 C
o
1 C
o
1 C
o
1 C
o
0.1 C
o
1 C
o
0.3 C
±
TC - J
INPUT
TYPE
This parameter value is set according to the type of sensor (Thermocouple or RTD input) connected to the controller's input terminals.
CONFIGURATION LIST : (1) key simultaneously To enter in this mode, press and hold SET & UP for 3 sec.
(2) Press UP or DOWN key to scroll between parameter options. (3) Press SET key to store the current parameter & move on to the next parameter.
4
OIM AI-7X81 V2.0 Page 4 of 6
i
OUTPUT
TYPE
RELAY
User has to set this parameter very carefully in accordance with the output used. (Separate terminal for RELAY & SSR, Refer electrical installation ) Select Relay if LOAD is connected via contactor. Whenever user selects Relay, Cycle time will automatically get set to 16 sec. User can modify cycle time via control list.
Select SSR if LOAD is connected via SSR (DC voltage pulses). Whenever user selects SSR, Cycle time will automatically get set to 1sec. User can modify cycle time via control list.
OVERSHOOT
CONTROL
POINT
DISABLE
This parameter will be prompted only if selected control action is PID. Setting this parameter on higher side will proportionally slows down the rate of rise of PV to minimize overshoot(this may cause delay to reach SP). Setting on lower side will proportionally or disabling this parameter will increase the rate of rise of PV( which may cause overshoot). Disable this option if delay is not required to reach SP.
PARA METER
DESCRIPTION
DEFAULT
This function will be executed only if selected control action is PID & Auto tune is Enable. Auto-tuning function can be initiated by setting this parameter to ‘YES’. The decimal of LSB flashes till Auto Tuning function is in progress. During Auto-tuning, Controller learns the process characteristics by itself & calculates required P, I & D values. User can cancel or abort this feature by setting this parameter to ‘NO’.
AUTO
TUNING
MODE
NO
LOWER
DISPL AY
LOWER
DISPL AY
UPPER
DISPL AY
UPPER
DISPL AY
PARA
METER
DESCR IPT ION
DEFAULT
AUTO TUNING MODE : To enter in this mode, Press & hold SHIFT key for minimum 3 sec.
15
Default USER LOCK CODE is 15 to access Control & Configuration List. User has a choice to set its own USER LOCK CODE between 1 to 9999, this is to prevent unauthorized access of Control & Configuration List.
USER LOCK CODE
AUTO TUNE
Enable
If Disabled, this parameter will not be prompted if user press Up & Down keys Simultaneously for 3Sec.
SET
POINT 1
Enable
If Enabled, User can View & edit the Set point in USER list.
If disabled, User can only View the Set Point but Can not edit it in USER list.
This parameter will be prompted only if selected control action is PID. If Enabled, this parameter will be prompted if user press Up & Down keys Simultaneously for 3Sec.
5
OIM AI-7X81 V2.0 Page 5 of 6
RAMP RATE
Disable
This parameter will be prompted only if OCP (over shoot control point) is disabled. When enabled, User can set the desired RAMP rate in USER list.
When disabled, this parameter will not be prompted in USER list.
Toggle
This parameter will be prompted only if RATE (Ramp Rate) is Enabled. By pressing DOWN key, Lower display will Toggle between Actual Set point Value i.e. Target Set Point (T-SP) & Ramping Set point (R-SP).
By this parameter Lower display will only show the Target Set Point T-SP Value.
By this parameter Lower display will only show the Ramping Set Point R-SP.
LOWER
DISPLAY
MESSAGE
i
6
OIM AI-7X81 V2.0 Page 6 of 6
Innovative Instruments
On
Google Play
338, Ne w Son al Link Serv ice I ndustria l Pre mises Co-o p Soc iety Ltd, Build ing N o.2, Link Ro ad, M alad (W), Mu mba i - 400064. Tel: 022-66 939 916/17/1 8; E-mai l : Website :
sales @in novative ins truments .co .in
www.in novative ins truments .co .in
Mfgd by: Innovative Instruments & Controls LLP
i
NC : Normally Close terminal of Relay NO : Normally Open terminal of Relay OP1 : Output 1 PV : Process Value (actual temp.)
C.A. : Control Action CJC : Cold junction compensation CM : Common terminal of relay LWC : Lead wire (Length) compensation
SP : Set Point Value(set temp.) SSR : Solid State Relay T/C : Thermocouple
ABBREVIATION :
Adjus t
Proportional Band
Integral Time
Derivative Time
Slow Response Over Shoot or Oscillations Slow Response Instability or Oscillation Slow Response or Oscillation High Over Shoot
Decrease PB Increase PB Decrease Int Increase Int Decrease Dt Increase Dt
Sympt om
Solut ion
Fig: 3.1
HEAT LOGIC / ON-OFF
TIME
0
TEMP ( C)
HYSTERISIS
SP
ON ON ON
AMB
O/P
OFF OFF
Fig: 3.2
TIME
COOL LOGIC / ON OFF
O/P
O/P
0
TEMP ( C)
AMB
HYSTERISIS
ON ON ON
SP
OFF OFF
ON-OFF ACTION : In this mode, Output (Relay/SSR) remains ON till actual temperature reaches to the set point value. On
reaching SP, Output turns OFF & remains OFF till actual temperature drops down (in Heat logic) or raises (in Cool logic) equal to hysterisis set by User. (As shown in Fig : 3.1 & 3.2)
USER GUIDE :
AUTO TUNING MODE : In this mode, Controller learns the process characteristics by itself and calculates the required P,I &
D values. It can be performed at any time after power ON but, it is best to start it when the process is at Ambient temperature in order to minimize overshoot & undershoot. Auto tuning is applied in case of : (1) Initial set up for a new process. (2) Substantial change in SP from previous auto tuning value. (3) Control accuracy is not satisfactory. If the control performance by using auto-tuning is still unsatisfactory, User can apply the further adjustments of P,I & D values as shown below