Innovative instruments i-therm AI-5441, i-therm AI-5841, i-therm AI-5741, i-therm AI-5941 User's Operating Manual

i
1. DISPLAY TYPE : 4-Digit 7 segment LED (RED)
STATUS LED’S : OP 1 : Main Control Output
2. INPUT Sensor Input : TC:J,K,R,S & RTD: Pt-100 Range : Refer below table
Sampling Time : 125 msec. Resolution : 1°C/0.1°C(Only for RTD) CJC for TC : Built in automatic LWC for Pt-100 : Built in upto 18E max. Digital Filter : 1 to 10 Sec.
3. RELAY OUTPUT Contact type : N/O, CM, N/C Contact Rating : 5A @ 250VAC or 30 VDC Life expectancy : > 5,00,000 operations Isolation : Inherent
4. SSR DRIVE OUTPUT Drive Capacity : 12V @ 30mA. Isolation : Non-Isolated.
5. FUNCTION Output 1 : Main Control output Control Action : ON-OFF/T.P (Select) Control Mode : Heat/Cool (Select) Compliance : ----
6. ENVIRONMENTAL Operating Range : 0 ~50°C, 5~90% Rh Storage Humidity : 95% Rh (Non-condensing)
7. POWER SUPPLY Supply Voltage : 90~270VAC, 50/60Hz. Consumption : 4W Maximum.
8. PHYSICAL Housing : ABS Plastic.
Model no.
Display height
AI-5441
AI-5841
AI-5741
AI-5941
0.36” 0.56”0.56”0.56”
USER’S OPERATING MANUAL FOR DIGITAL TEMPERATURE CONTROLLER
Model no.
Weight (gms.)
AI-5441
130 200 200 240
AI-5841 AI-5741
AI-5941
SPECIFICATIONS: -
(Models: AI 5441 / 5741 / 5841 / 5941)
SAFETY INSTRUCTION :
This controller is meant for temperature control applications. It is important to read the manual prior to installing or commissioning of controller. All safety related instructions appearing in this manual must be followed to ensure safety of the operating personnel as well as the instrument.
GENERAL
v The controller must be configured correctly for intended
operation. Incorrect configuration could result in damage to the equipment or the process under control or it may lead to personnel injury.
v The controller is generally part of control panel and in
such a case the terminals should not remain accessible to the user after installation.
MECHANICAL
v The Controller in its installed state must not come in
close proximity to any corrosive/combustible gases, caustic vapors, oils, steam or any other process by-
products. v The Controller in its installed state should not be exposed to carbon dust, salt air, direct sunlight or radiant heat v Ambient temperature and relative humidity surrounding
the controller must not exceed the maximum specified
limit for proper operation of the controller. v The controller in its installed state must be protected
against excessive electrostatic or electromagnetic
interferences. Ventilation slits provided on the chassis
of the instrument are meant for thermal dissipation hence
should not be obstructed in the panel.
ELECTRICAL v The controller must be wired as per wiring diagram & it
must comply with local electrical regulation. v Care must be taken not to connect AC supplies to low
voltage sensor input. v Circuit breaker or mains s/w with fuse (275V/1A) must be
installed between power supply and supply terminals to
protect the controller from any possible damage due to
high voltage surges of extended duration. v Circuit breaker and appropriate fuses must be used
for driving high voltage loads to protect the controller
from any possible damage due to short circuit on loads. v To minimize pickup of electrical noise, the wiring for low
voltage DC and sensor input must be routed away from
high current power cables. Where it is impractical to do
so, use shielded ground at both ends. v The controller should not be wired to a 3-Phase supply
with unearthed star connection. Under fault condition
such supply could rise above 264 VAC which will damage
the controller. v The Electrical noise generated by switching inductive
loads might create momentary Fluctuation in display,
alarm latch up, data loss or permanent damage to the
instrument. To reduce this use snubber circuit across
the load. v It is essential to install a over Temp. Protection device to
avoid any failure of heating system. Apart from spoiling
the product, this could damage the process being
controlled.
AI - 5441
(48 X 48)
AI - 5741
(72 X 72)
AI - 5941
(96 X 96)
AI - 5841
(48 X 96)
Fe-k(J) T/C
Cr-AL(K) T/C
Sensor Type
Accuracy
o
± 1 C
o
0 ~ 1700 C
o
0 ~ 1700 C
o
-100 ~ 450 C
Resolution
Range
o
1 C
o
1 C
o
1 C
}
(R) T/C
(S) T/C
Pt-100(RTD)
Pt-100(RTD 0.1)
o
0 ~ 760 C
o
-99 ~ 1300 C
o
-99.9 ~ 450.0 C
o
1 C
o
1 C
o
0.1 C
o
± 0.3 C
OP1
°C
SET
-therm
i
AI-5941
OP1
°C
-therm
i
AI-5741
SET
AI-544 1
OP1
SET
OP1
SET
-therm
i
AI-5841
°C
1
OIM AI-5X41 - V2.0 Page 1 of 4
i
ELECTRICAL INSTALLATION
The el ectrical conn ecti on dia gram is shown on th e cont roll er enclosure as b elow.
OVER ALL DIMENSIONS & PANEL CUT OUT (IN MM)
MECHANICAL INSTALLATION
The label on the controll er identifie s the serial number, wiring connections and batch number.
CAUTION: To prevent the risk of electrical shock, switch off the power before making/removing any connection or
removing the controller from its enclosure.
TABLE : 1
Model
Dim
48 72 96 48
48 72 96 96
8 10 10 10
75 65 45 45
44 68 92 92
44 68 92 44
9 9 9 9
A B
HC D F GE
43 66 89 43
AI-5441 AI-5741 AI-5941 AI-5841
INSTALLATION GUIDELINES
1. Prepare the cut-out with proper dimension as shown in figure.
2. Remove clamp from controller
3.Push the controller through panel cut-out and secure the controller in its place by tightening the side clamp.
A
B D
C
H
E
G
F
MODEL:-AI-5441/5741/5941
PANEL
CUTOUT
MODEL : AI - 5841
B
A
E
D
C H
G
F
PANEL
CUTOUT
AI - 5941
AI - 5841
FRONT PANEL LAYOUT
FRONT PANEL LAYOUT DESCRIPTION :
OP1 LED
DISPLAY
SET KEY
SHIFT
KEY
Sr.
NAME FUNCTION
Glo ws w hen OP1 is ON & flashes w hen del ay time (dly) is i n operation (if sel ect ed mode is ON- OFF )
It w ill display: (1) Mea sur ed v alu e of se lected inp ut o r Error ma ssa ges. (2 ) SP (Ma in set poi nt) value in r un m ode . (3) P ara met ers Value/code in p rog ram mode.
(1) Fo r S P pr og ra mming . ( 2) To ac ce ss Con tr ol mode a lo ng wit h D N K ey. (3) To a ccess Co nf igura ti on mode a lo ng wit h U P ke y. ( 4) To sc roll t he pa ramet er & to sto re it s valu e.
1
2
3
UP
KEY
DOWN
KEY
(1) To in cr ea se/al te r pa ra me ter va lu e in progr am mode. (2) To En te r in co nfigu ra ti on mode (w it h SE T key) . (3 ) To Set SP Of fset (w it h DO WN Key) .
(1) To inc rease /a lt er para me te r value i n pr ogram m od e wi th Up / Dn Ke y. (2) Pre ss f or 3 Sec in Pr og rammi ng t hi s will he lp t o go back t o pr ev ious pa ra meter.
(1) To d ecrea se /a lter p ar am eter v al ue in p ro gr am mod e. (2) To E nter c on tr ol mod e
4
5
6
AI - 5741
SUPPLY
L
N
1
2
3
4
5
6
7
8
9
10
11
12
15
16
13
14
NO NCCM
RELAY
SSR
AI - 5441
SUPPLY
L
N
1
2
3
4
5
6
7 8 9
10
11
13
14
15
16
12
NO NCCM
RELAY
SSR
1
2
3
4
5
6
10
11
12 13 14 15 16 17 18
7
8
9
NO NCCM
RELAY
SSR
SUPPLY
L
N
1
2
3
4
5
6
7
8
9
10
11
12 13 14 15 16 17 18
NO NCCM
RELAY
SSR
SUPPLY
L
N
OP1
SET
-therm
i
AI-5841
°C
1
3
4
5
6
2
AI - 5941
2
3
1
AI - 5441
1
2
3
5
4
6
AI - 5741
1
6
5
4
3
2
AI - 5841
OP1
°C
SET
-therm
i
AI-5941
AI-544 1
OP1
SET
OP1
°C
-therm
i
AI-5741
SET
6
5
4
2
OIM AI-5X41 - V2.0 Page 2 of 4
i
POWER UP :
At power on, following sequence will be prompted on the display till it reaches to Home display mode.
In home display mode, by pressing SET key once user can view SP value.
MODEL HOME
PV
VERSION INPUT
User can cha nge SP v alue using UP/ D OWN keys. Ho lding the key, will change the value at a faster rate. Press SET key to store the va lue & move on t o next param eter.
o
0 C
LSPL ~ HSPL
CONTROL
SET POINT
PROGRAMMING
USER LIST : To access the user list Press & Release SET key once.
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
PARA
METER
RANGE
DESCRIPTION
DEFAULT
DISPLAY
PARA
METER
RANGE
DESCRIPTION
DEFAULT
DISPLAY
CONTROL LIST : SET & DOWN key simultaneously To enter in this mode, press for 3 sec. User can then set
all the control related parameters as shown below.
0
1 ~ 9999
Set this paramet er to 15 (Default L OCK CODE) to access Control List. User has a choice t o set different Lock Code via USER LOCK CODE in Config . List.
0.5 to
99.9°C
o
1 to 25 C
0.5
to
100.0 Sec.
0
to
500 Sec.
-25 to
o
25 C
This parameter w ill appear only if selected control action is T.P. It sets bandwidth over w hich t he output power is adjusted depending upon the erro r (SV-PV).
This parame ter will appear only if selected control action is T.P. User can set this value base d on process being cont rolled & type of output bei ng selected. For Relay O/P, cycle ti me should be more than 12 Sec & for S SR O/P, cycle time should be less than 5 Sec .
This parameter wi ll appear only if selected control action is ON-OFF. It set s the main output restart time. If set to '0', O/P will be swi tched witho ut delay. Als o, Delay will be considered in case of every power ON.
This parameter wi ll appear only if selected control action is ON-OFF. It set s the dead band between ON & OFF switch ing of the Output. Larger value of hysterisis minimize the number of ON-OFF operation of t he loa d. Thi s increases life o f actuators like Relay but, also pr oduces large err ors.
o
5.0 C
16.0 Sec.
0 Sec.
2°C
P.BAND
CYCLE
TIME
CONTROL
HYS.
DELAY
LOCK CODE
CONFIGURATION LIST : key simultaneously (1) To enter in this mode, Press and hold SET & UP for 3 sec.
(2) Press UP or DOWN key to scroll between parameter options. (3) Press SET key to store the current parameter & move on to the next parameter.
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
J
INPUT TYPE
This parameter value is set according to the type of sensor (Thermoco uple or RTD Input) connected to the Controller's In put Terminals .
PARA METER
DESCRIPTION
DEFAULT
DISPLAY
0
LOCK CODE
Set this paramet er to 15 (Default L OCK CODE) to access Config. List. User has a choice t o set different Lock Code in the range via USER LOCK CODE in Config. List.
1 ~ 9999
MANUAL
OFF SET
o
0 C
This parameter will appear only i f sele cted C.A is time proportional . (For more details refer User guid e.)
Fe-k(J) T/C
Cr-AL(K) T/C
Sensor Type
Accuracy
o
± 1 C
o
0 ~ 1700 C
o
0 ~ 1700 C
o
-100 ~ 450 C
Resolution
Range
o
1 C
o
1 C
o
1 C
}
(R) T/C
(S) T/C
Pt-100(RTD)
Pt-100(RTD 0.1)
o
0 ~ 760 C
o
-99 ~ 1300 C
o
-99.9 ~ 450.0 C
o
1 C
o
1 C
o
0.1 C
o
± 0.3 C
3
OIM AI-5X41 - V2.0 Page 3 of 4
i
4
HIGHER SP LIMIT
o
400 C
Sets the maximum limit for set point adjustment. It can be set fr om L SPL value to maximum specified range of selec ted sensor.
PROCESS
VALUE
OFFSET
INPUT
FILTER
CONTROL
MODE
CONTROL
LOGIC
o
0 C
o
1 C
T.P
HEAT
Function of this parameter is to add/subtract a cons tant value to the measured PV to obtain Final PV for control applications. This pa rameter valu e needs to be altered for one of the following reaso n : (i) To com pensate for know n ther mal gradie nt. (ii)To match the display v alues with anoth er rec order or indicat or measuri ng the same PV.
Controller is equipped with an ad aptive digital filter which is us ed to filter out any extraneous pulses on the PV. Filtered PV Value is used for all PV dep endent func tions. If PV signal is fluctuati ng due to noise, in crease the filte r time constant value.
User can select between ON-O FF or T.P action algorithm to be adopted for output. (Refer User Guid e)
This parameter w ill appear only if selected control mode is ON-OFF. User can select heating logic in wh ich OP 1 will remain ON ti ll PV < SP. (PV increases wh en output is ON.)
This parameter w ill appear only if selected control mode is ON-OFF. User can select cooling logic in wh ich OP 1 will remain ON ti ll PV > SP. (PV decreases wh en output is ON.)
OUTPUT
TYPE
RELAY
User has to set thi s parameter very carefully in accordance with the o utput used. (Separate terminals for RELAY & SSR : - Re fer Electrical I nstallation) Select Relay if LOAD i s connected v ia Contactor. Whenever u ser selects R elay, Cycle time will automatically set to 16 sec. U ser can modify cycle time via Contr ol Lis t.
Select SSR if LOAD is connected via SSR (DC voltage pu lses). Whenever user s elects SSR , Cycle time wi ll automatically set to 1sec. User can modify cycle time via Control L ist.
15
Default USER LOC K CODE is 15 to access Control & Confi guration List. User has a choice t o set its own USER LOCK CODE between 1 to 9999, this is to p revent unauthorized access of Control & Confi guration L ist.
USER LOCK CODE
PARA
METER
DESCRIPTION
DEFAULT
DISPLAY
LOWER
SP
LIMIT
o
0 C
Sets the minimum limit for set point adjust ment. It can be set from minimum spec ified range of selecte d sensor to HSPL value.
SET
POINT 1
If Enabled, User can View & edit the Set point in USER list.
If disabled, User can only View the Set Point but Can not edit it in USER list.
ENABLE
2) TIME PROPORTIONAL ACTION: In this mode, ON & OFF time of output (Relay/SSR)varies proportionally in every cycle (cycle time settable by user) depending on the deviation of PV w.r.t. SP. This action Starts/continues only when PV enters or is within the band. (As shown in Fig : 3.3)
3) MANUAL RESET
(OFFSET ADJUSTMENT):
In some application, after adopting-Time proportionating action, system may stabilize at particular temperature over a period of time which can be different than the set value. This steady state (error) offset can be eliminated by setting this value equal and opposite to the existing offset. (As shown in Fig : 3.4)
TIME PROPORTIONAL ACTION
ACTIVE ZONE
Fig: 3.3
AMB
0
TEMP ( C)
SP
OUT PUT
ON
100 %
ON
100 %
OFF
100 %
PROPORTIONAL BAND (P.BND)
SET BY USER
time
AMB
0
TEMP ( C)
SP
Fig: 3.4
OFFSET
after offset adjustment
TIME
SP : Set Point Valu e(set temp. ) SSR : Solid State R elay T.P. : Time Pr oportional T/C : Ther mocouple
NC : Normally Close terminal of re lay NO : Normally Op en terminal o f relay OP1 : Output 1 PV : Process Value (actual tem p.)
C.A. : Control Action CJC : Cold juncti on compensa tion CM : Co mmon termin al of relay LWC : Lead wire (Le ngth) compensat ion
ABBREVIATION :
Innovative Instruments
On
Google Play
206, New Sonal Link Service Industrial Premises Co-op Society Ltd, Building No.2, Link Road, Malad (W), Mumbai - 400064. Tel: 022-66939916/17/18; E-mail : Website :
sales@innovativeinstruments.co.in
www.i nn ov at iv ei ns tr um en ts .c o. in
Mfgd by: I nnovative Instruments & Cont rol s LL P
i
OIM AI-5X41 - V2.0 Page 4 of 4