Innovative instruments AI-5481, AI-5781, AI-5681, AI-5881, AI-5981 User's Operating Manual

USER’S OPERATING MANUAL FOR DIGITAL TEMPERATURE CONTROLLER
(Models: AI 5481 / 5881 / 5781 / 5981 / 5681)
1. DISPLAY TYPE : Dual 4- Digit 7 segment LED 4 Digit Bright Red (PV) 4 Digit Luminous Red (SV)
:
Sampling Time : 200 msec. Resolution : 1°C CJC for TC : Built in automatic
LWC for Pt-100 : Built in up to 18E max. Digital Filter : 1 to 10 Sec.
3.
Contact type : N/O, CM, N/C Contact Rating : 5A @ 250VAC or 30 VDC Life expectancy : > 5,00,000 operations Isolation : Inherent
4.
Drive Capacity : 12V @ 30mA. Isolation : Non-Isolated.
5.
1:
STATUS LED’S
RELAY OUTPUT
SSR DRIVE OUTPUT
FUNCTION
OP 1 : Main Control Output
2.
Sensor Input : J/K/Pt-100 Range : Refer below table
Output Main Control output Control Action : ON-OFF/T.P (Select) Control Mode : Heat/Cool (Select) Compliance : ----
6.
Operating Range : 0 ~50°C, 5~90% Rh Storage Humidity : 85% Rh (Non-condensing)
7.
Supply Voltage : 90~270VAC, 50/60Hz. Consumption : 4W Maximum.
8.
Housing : ABS Plastic.
INPUT
ENVIRONMENTAL
POWER SUPPLY
PHYSICAL
SPECIFICATIONS : -
:SAFETY INSTRUCTION
This controller is meant for temperature control applications. It is important to read the manual prior to installing or commissioning of controller. All safety related instruction appearing in this manual must be followed to ensure safety of the operating personnel as well as the instrument.
The controller must be configured correctly for intended operation. Incorrect configuration could result in damage to the equipment or the process under control or it may lead personnel injury. The controller is generally part of control panel and in such a case the terminals should not remain accessible to the user after installation.
The Controller in its installed state must not come in close proximity to any corrosive/combustible gases, caustic vapors, oils, steam or any other process by-products. The Controller in its installed state should not be exposed to carbon dust, salt air, direct sunlight or radiant heat. Ambient temperature and relative humidity surrounding the controller must not exceed the maximum specified limit for
proper operation of the controller. The controller in its installed state must be protected against excessive electrostatic or electromagnetic interferences. Ventilation holes provided on the chassis of the instrument are meant for thermal dissipation hence should not be obstructed in the panel.
The controller must be wired as per wiring diagram & it must comply with local electrical regulation. Care must be taken not to connect AC supplies to low voltage sensor input. Circuit breaker or mains s/w with fuse (275V/1A) must be installed between power supply and supply terminals to protect the controller from any possible damage due to high voltage surges of extended duration. Circuit breaker and appropriate fuses must be used for driving high voltage loads to protect the controller from any possible damage due to short circuit on loads. To minimize pickup of electrical noise, the wiring for low voltage DC and sensor input must be routed away from high current power cables. Where it is impractical to do this, use shielded ground at both ends. The controller should not be wired to a 3-Phase supply with unearthed star connection. Under fault condition such supply could rise above 264 VAC which will damage the controller. The Electrical noise generated by switching inductive loads might create momentary Fluctuation in display, alarm latch up, data loss or permanent damage to the instrument. To reduce this use snubber circuit across the load.
It is essential to install a over Temp. Protection device to avoid any failure of heating system. Apart from spoiling the Product, this could damage the process being controlled.
GENERAL
MECHANICAL
ELECTRICAL
v
v
v
v
v
v
v
v
v
v
v
v
v
v
Model no.
Display height (PV)
Display height (SV)
AI-5481
0.39” 0.39” 0.56” 0.8” 0.39”
0.39” 0.39” 0.39” 0.56” 0.39”
AI-5881 AI-5781 AI-5981 AI-5681
1
Document Name : OIM AI-5X81 (Ver 1.2) Page 1 of 4
Model no.
Weight (gms.)
AI-5481 AI-5781 AI-5981 AI-5881 AI-5681
200240 200200130
(48 X 48)
(72 X 72)
(96 X 96)
(48 X 96)
(96 X 48)
Fe-K(J) T/C
Cr-AL(K) T/C
Pt-100 (RTD)
Pt-100 (RTD 0.1)
Sensor Type
Accuracy
±1 C
o
± 0.3 C
o
0 760 C~
o
-99 ~ 1300 C
o
-100 450 C~
o
-100.0 450.0 C~
o
Resolution
Range
1C
o
1C
o
1C
o
0.1 C
o
}
-therm
i
AI-5881
SET
1
2
43
6
5
OP1
-therm
i
AI-5681
SET
1
3
2
6
4
5
OP1
-therm
i
AI-5981
SET
6
4
5
1
2
3
PV
SV
OP1
-therm
i
AI-5781
SET
6
4
5
1
2
3
PV
SV
OP1
MODEL : AI - 5881
B
A
E
D
CH
MODEL : AI - 5681
E
D
C
H
A
B
F
G
A
B
D
C
H
E
G
F
G
F
MODEL:-AI-5481/5781/5981
OVER ALL DIMENSIONS & PANEL CUT OUT (IN MM)
TABLE : 1
Model
Dim
48 72 96 48 96
48 72 96 96 48
8 10 10 10 10
110
65
65 110 110
44 68 92 92 44
44 68 92 44 92
9 9 9 9 9
AB
HCD FGE
43 66 89 43 89
AI-5481 AI-5781 AI-5981 AI-5881 AI-5681
MECHANICAL INSTALLATION
The label on the controller identifies the serial number, wiring connections and batch number.
INSTALLATION GUIDELINES
1. Prepare the cut-out with proper dimension as shown in figure.
2. Remove clamp from controller
3. Push the controller through panel cut-out and secure the controller in its place by tightening the side clamp.
PANEL
CUTOUT
CAUTION: To prevent the risk of electrical shock, switch off the power before making/removing any connection or removing
the controller from its enclosure.
PANEL
CUTOUT
PANEL
CUTOUT
AI - 5481 AI - 5781 AI - 5981
AI - 5881
FRONT PANEL LAYOUT
AI - 5681
2
Document Name : OIM AI-5X81 (Ver 1.2) Page 2 of 4
ELECTRICAL INSTALLATION
The electrical connection diagram is shown on the controller enclosure as below.
SUPPLY
L
N
1
2
3
4
5
6
7
8
9
10
11
12
15
16
13
14
SSR1
NO NCCM
RELAY1
1
2
3
4
5
6
10
11
12 13 14 15 16 17 18
7
8
9
NO NCCM
RELAY1
SSR1
SUPPLY
L
N
NO NCCM
RELAY1
SSR1
SUPPLY
L
N
AI-5481
AI-5781 AI - 5981 AI - 5681/5881
SUPPLY
L
N
1
2
3
4
5
6
789
10
11
13
14
15
16
12
NO NCCM
RELAY1
1234
5
10
9
11 1 2
131415 16
6
78
SSR
NO. NAME FUNCTION
Î Ï
Ð
Ñ
Ò
Ó
OP1 LED
UPPER
DISPLAY
LOWER
DISPLAY
SET KEY
UP
KEY
DOWN
KEY
Glows whenOP1 is ON & flasheswhen delay time (dly1) isin operation & selected mode isON-OFF.
It will display : (1) Measured value of selected input or Error messages in run mode. (2) Parameters Value in program mode.
It will display : (1) (Main s ) / SP2 (Auxiliary) set value / Set Soak time value/ balance or elapsed soak time in run mode. (2) Parameter code in program mode.
SP1 et point
(1) For SP programming. (2) To access Control mode. (3) To access Configuration mode alongwith UP key. (4) To scroll the parameter & to store its value.
(1) To increase/alter parameter value in program mode. (2) To Enter in configuration mode (alongwith SET key) . (3) To acknowledge Alarm. (4) To enter in tune mode (alongwith DOWN Key).
(1) To decrease / alter parameter value in program mode. (2)
. (3) To start Soak timer.
To enter in tune mode
(alongwith UP Key)
4
SET
-therm
i
AI-5481
5
6
1
2
3
PV
SV
OP1
MANUAL OFF SET
0C
o
This parameter will appear only if selected C.A is time proportional. (For more details: refer user guide.)
-25 to
25
o
C
DELAY 1
0
to
500 Sec.
This parameter will be prompted only if selected control action is ON-OFF. It sets the main output restart time where O/P once turned OFF will turn ON only after restart time, regardless difference between PV & SP in Heat or Cool mode. If set to '0', O/P will be switched without delay. Also, Delay will be applicable in case of every power ON.
120 Sec.
PROGRAMMING :
At power on, following sequence will be prompted on the display for 1 sec. till it reaches to Home Display mode.
USER LIST : To access the user list press SET key once.
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
RANGE
DESCRIPTION
DEFAULT
CONTROL LIST :
SET keyTo enter in this mode press for 3 sec. User can set the control parameters as shown below.
User can change SP1 value using UP/ DOWN keys. Holding the key, will change the value at a faster rate. Press SET key to store the value & move on to the next parameter.
0C
o
LSPL ~ HSPL
CONTROL
SET POINT
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
RANGE
DESCRIPTION
DEFAULT
PROPORTIONAL
BAND
CYCLE
TIME
CONTROL
HYS.
0.5 to
99.9°C
1to25 C
o
0.5
to
100.0 Sec.
This parameter will be prompted only if selected control action is PID. It sets bandwidth over which the output power is adjusted depending upon the error (SV-PV). The value of this parameter is automatically set by Auto tune function.
This parameter will be prompted only if selected control action is PID. User can set this value based on process being controlled & type of output being selected. For Relay O/P, cycle time should be more than 12sec & for SSR O/P, cycle time should be less than 10sec.
This parameter will be prompted only if selected control action is ON-OFF. It sets the dead band between ON & OFF switching of the output. Larger value of hysterisis minimize the number of ON-OFF operation to the load. This increases life of actuators like contactors but, also produces large errors (between PV & SV)
5.0 C
o
16.0 Sec.
2°C
3
Document Name : OIM AI-5X81 (Ver 1.2) Page 3 of 4
UPPER
DISPLAY
LOWER
DISPLAY
MODEL VERSION HOME
PV
SV
POWER UP :
0
LOCK CODE
1 ~ 9999
Set this parameter to 15 (Default LOCK CODE) to access Control List. User has a choice to set different Lock Code via USER LOCK CODE in Config. List.
In home display mode, by pressing SET key once, user can view SP value.
CONFIGURATION LIST :
key simultaneously(1) To enter in this mode, Press and hold SET & UP for 3 sec. (2) Press UP or DOWN key to scroll between parameter options. (3) Press SET key to store the current parameter & move on to the next parameter.
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
DESCRIPTION
DEFAULT
Set this parameter to 15 (Default LOCK CODE) to access Config. List. User has a choice to set different Lock Code via USER LOCK CODE in Config. List.
0
LOCK CODE
0C
o
Sets the minimum limit for set point adjustment. It can be set from minimum specified range of selected sensor to HSPL value.
LOWER
SP
LIMIT
J
INPUT TYPE
This parameter value is set according to the type of sensor (Thermocouple or RTD Input) connected to the Controller's Input Terminals.
Fe-k(J) T/C
Cr-AL(K) T/C
Pt-100(RTD)
Pt-100(RTD 0.1)
Sensor Type
Accuracy
± 0.3 C
o
0 760 C~
o
-99 1300 C~
o
-100 450 C~
o
-100.0 450.0 C~
o
Resolution
Range
1C
o
1C
o
1C
o
0.1 C
o
±1 C
o
}
.
1) In this mode, output (Relay/SSR) remains ON till actual temperature reaches to the set point. On reaching SP, output turns OFF & remains OFF till actual temperature drops down (in heat logic) or raises (in cool logic) equal to hysterisis set by user. (As shown in Fig : 3.1 & 3.2)
ON-OFF ACTION:
Fig: 3.1 Fig: 3.2
TIME
COOL LOGIC / ON OFF
HEAT LOGIC / ON-OFF
TIME
TEMP ( C)
0
HYSTERISIS
SP
ON ON ON
AMB
O/P
OFF OFF
O/P
O/P
TEMP ( C)
0
AMB
HYSTERISIS
ON ON ON
SP
OFF OFF
USER GUIDE:
Fig: 3.3
AMB
TEMP ( C)
0
SP
OUT PUT
ON
100 %
ON
100 %
OFF
100 %
PROPORTIONAL BAND (P.BND)
SET BY USER
TIME PROPORTIONAL ACTION
ACTIVE ZONE
TIME
AMB
TEMP ( C)
0
SP
Fig: 3.4
OFFSET
after offset adjustment
TIME
2) In this mode, ON & OFF time of Output (Relay/SSR) varies proportionally in every cycle (cycle time settable by User) depending on the deviation of PV w.r.t. SP. This action starts/continues only when PV enters or is within the band. (As shown in Fig : 3.3)
TIME PROPORTIONAL ACTION:
3) In some
application, after adopting-Time proportionating action, system may stabilize at particular temperature over a period of time which can be different than the set value. This steady state (error) offset can be eliminated by setting this value, equal and opposite to the existing offset. (As shown in Fig : 3.4)
MANUAL RESET
(OFFSET ADJUSTMENT) :
4
Document Name : OIM AI-5X81 (Ver 1.2) Page 4 of 4
338, New Sonal Link Service Ind. Est. no.2 , Link Road, Malad (W), Mumbai - 400064. Tel: 022-66939916/17. Fax: 022-66939918 E-mail:sales@innovativeinstrument.com ; Website: innovativeinstrument.com
: Innovative InstrumentsMfgd by :-Dealer
SP : Set Point Value(set temp.) SSR : Solid State Relay T.P. : Time Proportional T/C : Thermocouple
NC : Normally Close terminal of relay NO : Normally Open terminal of relay OP1 : Output 1 PV : Process Value (actual temp.)
C.A. : Control Action CJC : Cold junction compensation CM : Common terminal of relay LWC : Lead wire (Length)
compensation
ABBREVIATION
INPUT
FILTER
CONTROL
MODE
FOR O/P 1
CONTROL
LOGIC
FOR O/P 1
2.5 C
o
PID
HEAT
The controller is equipped with an adaptive digital filter which is used to filter out any extraneous pulses on the PV. Filtered PV Value is used for all PV dependent functions. If PV signal is fluctuating due to noise, increase the filter time constant value.
User can select between TP or ON-OFF action algorithm to be adopted for output.
This parameter will appear only if selected control mode is ON-OFF. User can select heating logic in which OP1 will remain ON till PV < SP. (PV increases when output is ON.)
This parameter will appear only if selected control mode is ON-OFF. User can select cooling logic in which OP1 will remain ON till PV > SP. (PV decreases when output is ON.)
PROCESS
VALUE
OFFSET
0C
o
Function of this parameter is to add/subtract a constant value to the measured PV to obtain Final PV for control applications. This parameter value needs to be altered for one of the following reason : ­(i) To compensate for known thermal gradient (ii)To match the display values with another recorder or indicator measuring the same PV.
OUTPUT
TYPE
RELAY
User has to set this parameter very carefully in accordance with the output used. (Separate terminals for RELAY & SSR : - Refer Electrical Installation ) Select Relay if LOAD is connected via contactor. Whenever user selects Relay, Cycle time will be automatically set to 16 sec. User can modify cycle time via control list.
Select SSR if LOAD is connected via SSR (DC voltage pulses). Whenever user selects SSR, Cycle time will be automatically set to 1sec. User can modify cycle time via control list.
15
Default USER LOCK CODE is 15 to access Control & Configuration List. User has a choice to set its own USER LOCK CODE between 1 to 9999, this is to prevent unauthorized access of Control & Configuration List.
USER LOCK CODE
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
DESCRIPTION
DEFAULT
HIGHER
SP
LIMIT
Sets the maximum limit for set point adjustment. It can be set from LSPL value to maximum specified range of selected sensor.
400 C
o
Loading...