INNOVATIVE CIRCUIT TECHNOLOGY ICT200-LVD Instruction Manual

ICT200-LVD LOW VOLTAGE DISCONNECT SWITCH
This automatic LVD switch is designed to protect your battery from excessive discharge that may cause permanent degradation of the cells. The ICT200-LVD disconnect switch may be wired in series with the battery positive or negative lead for use with any dc grounding configuration.
The intelligent back-lit LCD display makes set up simple. Selecting your nominal battery voltage at first power up will automatically set the disconnect and reconnect voltages to standard levels for the battery voltage chosen. Custom voltage thresholds may be set for specialized applications, and the internal contactor may be manually set to an open or closed state if required. The display also shows the battery voltage and the current drawn by the load, along with the operating state of the LVD and any alarm conditions.
CONNECTION DIAGRAM
WARNINGS
Risk of personal injury or damage to equipment and property! Always observe the following:
Use an appropriate over-current protection device in line
with the battery sense connection, and in line with the main load battery connection
Use a disconnect switch or circuit breaker in series with the
main load battery connection, for installation and service
Use wire and connectors rated for the maximum load
current, and size of fuse or circuit breaker. Tighten all connections
Ensure load current does not exceed max rating of unit
INSTALLATION
Mount the unit in a standard 19” equipment rack using the
front panel mounting ears (included).
With the main battery service disconnect switch open; connect the LVD LOAD and BATTERY terminals using appropriately sized wire, disconnect, and an over-current protection device rated for the application. Bond the chassis to ground using the ground stud located on the back panel.
Installation (continued) Connect the alarm output contacts (if desired) to an external monitoring system, using the REMOTE connector (P10) terminals 1, 2, and 3 as shown in the REMOTE table, below. Use the mating 7 pin REMOTE connector plug (included).
Connect the battery sense lines using 22 AWG or larger wire and an over current protection device (5A fuse or circuit breaker) to the battery terminals. These lines provide power to the unit, and allow the control circuitry to sense the battery voltage. The internal display should then power up, allowing the nominal battery voltage to be set (see Initial Set Up section).
REMOTE Connector P10: (pins 4, 5 not used)
CONTROL PANEL MENUS
FRONT PANEL CONTROL
Use the front panel scroll knob, ENTER, and BACK buttons to navigate the interface menus and set up the following parameters:
Nominal battery SYSTEM VOLTAGE (set to 12/24/48V
to correctly scale factory default LVD points)
Restore to FACTORY SETTINGS (default values, 12V
system, AUTO mode, contactor open)
LVD SETTINGS (set custom disconnect and reconnect
voltage levels, set mode for AUTO disconnect or MANUAL-OPEN/MANUAL-CLOSED configuration)
SECURITY SETTINGS (set a four digit password and
lock-out timer to prevent unauthorized adjustment of LVD settings, if desired) (default is no password)
Use the scroll knob to cycle between the top-level menus, press ENTER to select a menu for adjustment, and then use the scroll knob to select the parameter for adjustment, press ENTER to select.
Adjust the selected parameter with the scroll knob; press ENTER to activate the setting. Use the BACK button to return to a higher level menu
Pin Number
Name
Note 1 Common
Alarm out common
2
NC
Alarm NC (alarm state)
3
NO
Alarm NO (alarm state)
6
BATT POS
Battery sense Positive
7
BATT NEG
Battery sense Negative
SET SYSTEM VOLTAGE
NOMINAL BATT V: 12V FACTORY SETTINGS
BATTERY: 13.6V 83A
LVD MODE: AUTO DISCONN VOLTAGE: 10.5V
RECONN VOLTAGE: 12.5V
LVD SETTINGS
DISCONN VOLTAGE: 10.5V RECONN VOLTAGE: 12.5V
LVD MODE: AUTO
SET SECURITY SETTINGS
PASSWORD CLEAR PASSWORD
SET LOCKOUT TIMER
SET SYSTEM VOLTAGE
NOMINAL BATT V: 24V <SCROLL> TO CHANGE
PUSH <ENTER> TO SET
LVD SETTINGS
DISCONN VOLTAGE: 11.2V <SCROLL> TO CHANGE
PUSH <ENTER> TO SET
ENTER PASSWORD
0***
<SCROLL> TO CHANGE
PUSH <ENTER> TO SET
Press ENTER to
activate setting
after adjustment
Press ENTER to
activate setting after adjustment
Press ENTER to
activate setting after adjustment
Scroll
Scroll
Scroll
Press ENTER to
select desired parameter to adjust
Press ENTER to
select desired parameter to adjust
Press ENTER to
select desired parameter to adjust
Home Screen
System Voltage Setting (Nominal)
LVD (min)
LVD (default)
LVD (max)*
Reconnect (min)*
Reconnect (default)
Reconnect (max)
12V (default)
10.5
11.5
12.5
12.0
12.5
13.8
24V
21.0
23.0
25.0
24.0
25.0
27.6
48V
42.0
46.0
50.0
48.0
50.0
55.2
ADJUSTABLE LVD SETTINGS:
*Note: The disconnect voltage setting cannot be set higher than the reconnect voltage setting, less a 1.0V guard band. Likewise the reconnect voltage cannot be set lower than the LVD point plus 1.0V.
e.g. for a 12V system with the reconnect V set to 12.6V the LVD set point cannot exceed 11.6V
INITIAL SET UP
Wire the unit per the installation instructions and connect power to the battery sense terminals. The SET SYSTEM VOLTAGE screen should be displayed on the front panel. Press ENTER to select that screen, then use the scroll wheel to select the NOMINAL BATT V line, press ENTER to select, and then adjust the encoder knob to select 12, 24 or 48V as required. Press ENTER to select. The unit disconnect and reconnect thresholds will now be set to the factory default levels for that battery voltage.
Normally this is the only setting required on the unit unless custom disconnect or reconnect points are desired, or the internal LVD contactor is to be manually set to open or closed. The external battery service disconnect switch may now be closed, allowing the load to be powered through the LVD unit.
ALARMS
The Form-C alarm contact on the back panel is triggered for LVD trip, Over Current trip, or internal Over Temperature trip. The main LVD contactor will open for all alarm conditions, and must be manually re-set for an Over Current event by setting the LVD Mode back to AUTO.
Alarm Screens: (any button press will return to home screen)
SPECIFICATIONS
Battery Voltage: 10 to 65V Maximum Load Current: 200A (12/24V), 100A (48V) Auto Overload Disconnect Current: (+/- 5%) 12/24V System setting 220A 48V System setting 110A Display Accuracy (V): +/- 2% (Amps): +/- 5% LVD Delay (approx. time to switch state) 3s Operating power (Tare loss): < 1W Alarm Contact (Form-C): 0.5A, 125Vac/dc max Dimensions: (inches)
LIMITED WARRANTY
ICT Ltd. warrants to the original consumer purchaser that this product shall be in good working order, free from defects in materials and workmanship, for a period of three (3) years from the date of purchase. Should failure occur during the above stated time period, then ICT will, at its option, repair or replace this product at no additional charge except as set forth below. All parts, whether for repair or replacement, will be furnished on an exchange basis. All exchange pieces become the property of ICT. This limited warranty shall not apply if the ICT product has been damaged by unreasonable use, accident, negligence, disaster, service, or modification by anyone other than the ICT factory.
Limited warranty service is obtained by delivering the product during the above stated three (3) years warranty period to an authorized ICT dealer or ICT factory and providing proof of purchase date. If this product is delivered by mail, you will insure the product or assume risk of loss or damage in transit, and prepay shipping charges to the factory.
Every reasonable effort has been made to ensure that ICT product manuals and promotional materials accurately describe ICT product specifications and capabilities at the time of publication. However, because of ongoing improvements and updating of ICT products, ICT cannot guarantee the accuracy of printed materials after the date of publication and disclaims liability for changes, errors or omissions.
If this ICT product is not in good working order, as outlined in the above warranty, your sole remedy shall be repair or replacement as provided above. In no event will ICT be liable for any damages resulting from the use of or the inability to use the ICT product, even if an ICT employee or an authorized ICT dealer has been advised of the possibility of such damages, or for any claim by any other party.
ICT reserves the right to make changes without further notice to any products or documentation for improvement of reliability, function, or design.
ICT Ltd. does not recommend use of its products in life support applications wherein a failure or malfunction of the product may directly or indirectly threaten life or cause injury. The user of ICT products, which are to be used in life support applications as described above, assumes all risks of such use and indemnifies ICT against all damages.
INNOVATIVE CIRCUIT TECHNOLOGY LTD.
26921 Gloucester Way
Langley, British Columbia, Canada V4W 3Y3
T 604.856.6303 F 604.856.6365 www.ict-power.com
ALARM BATT LOW 10.5VDC BATT DISCONN BY LVD
ICT200-LVD
LOW VOLTAGE DISCONNECT
INSTRUCTION MANUAL
855-341-000
INNOVATIVE CIRCUIT TECHNOLOGY LTD.
ALARM OVER CURRENT BATT DISCONN BY LVD
Loading...