innovair BLUTEC VEM60C3SS1, BLUTEC VEM60C2SS1, BLUTEC VEM48C2SS1, BLUTEC VEM36C2HR1 Installation Instructions Manual

Page 1
WARNING
These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjust­ment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference by a serviceman.
NOTE: Appearance of unit may vary.
INSTALLATION INSTRUCTIONS
Split System Air Conditioner Condenser
3-5 Tons
R410A
BLUTEC
Page 2
Outdoor Units
2 Outdoor Units
Outdoor Units
1. Dimensions ....................................................................... 3
2. Service Space ................................................................... 4
3. Piping Diagrams ............................................................... 5
4. Wiring Diagrams .............................................................. 6
5. Electric Characteristics ................................................... 9
6. Operation Limits............................................................... 9
7. Sound Levels ................................................................. 10
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 3
Dimensions
Outdoor Units 3
1. Dimensions
Unit Model
(Btu/h)
Dimensions (Inches)
Refrigerant Connection Service
Valve Size
"H" in [mm] "W" in [mm] "L" in [mm] Liquid in Vapor in
VEM36C2HR1 29-7/8[759] 23-5/8[600] 23-5/8[600] 3/8 3/4
VEM48C2SS1
29-7/8[759] 28[710] 28[710] 3/8 3/4
VEM60C2SS1
33-3/16[843] 28[710] 28[710] 3/8 3/4
VEM60C3SS1
33-3/16[843] 28[710] 28[710] 3/8 3/4
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 4
Outdoor Units
4 Outdoor Units
2. Service Space
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 5
Piping Diagrams
Outdoor Units 5
3. Piping Diagrams
VEM36C2HR1
INDOOR OUTDOOR
LIQUID SIDE
GAS SIDE
HE
AT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
T2 Evaporator temp. sensor
T1 Room temp. sensor
Throttle orifice
VEM48C2SS1 ,VEM60C2SS1, VEM60C3SS1
INDOOR OUTDOOR
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
T2 Evaporator temp. sensor
T1 Room temp. sensor
Throttle orifice
T5 Discharge temp. sensor
High pressure switch
Low pressure switch
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 6
Outdoor Units
6 Outdoor Units
4. Wiring Diagrams
VEM36C2HR1,VEM60C2SS1
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 7
Wiring Diagrams
Outdoor Units 7
VEM48C2SS1
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 8
Outdoor Units
8 Outdoor Units
VEM60C3SS1
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 9
Electric Characteristics
Outdoor Units 9
5. Electric Characteristics
Model
Power Supply
Hz Phase Voltage Min. Max.
VEM36C2HR1
60 1 220-230V 198V 242V
VEM48C2SS1
60 1 220-230V 198V 242V
VEM60C2SS1
60 1 220-230V 198V 242V
VEM60C3SS1
60 3 220-230V 198V 242V
6. Operation Limits
Temperature
Mode
Cooling operation
Room temperature
17℃~32
Outdoor temperature
18℃~43
(-7℃~43℃:
For the
models with low
temperature cooling
system)
10 15 25 30 3520
15
20
25
30
35
40
45
Indoor temperature(℃ WB)
Outdoor temperature(
DB)
STD
Cooling
43
17 32
10
5
0
-5
-10
18
-7
With Low
Ambient
Cooling System
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 10
Sound Levels
10 Outdoor Units
7. Sound Levels
Model
Noise level dB(A)
VEM36C2HR1
65
VEM48C2SS1
65
VEM60C2SS1
64
VEM60C3SS1
64
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 11
Installation
Installation 11
Installation
1. Installation Procedure ............................................... 12
2. Location select ion ..................................................... 13
3. Indoor unit installation .............................................. 17
4. Outdoor unit installation (Top Discharge Unit) ....... 22
5. Refrigerant pipe installation ..................................... 25
6. Drainage pipe installation ......................................... 28
7. Vacuum Drying and Leakage Checking .................. 32
8. Additional refrigerant charge ................................... 33
9. Engineering of ins ulation ......................................... 34
10. Engineering of electrical wiring ............................... 35
11. Test operation ............................................................ 36
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 12
Installation Procedure
12 Installation
1. Installation Procedure
Vacuum drying and leakage checking
Additional refrigerant charge
Insulation the joint part of refrigerant pipe
Wiring connection and elec t r ic safety checking
Test operation
Refrigerant pipe
installation and insulation
Drainage pipe installation
and insulation
Indoor unit installation
location selection
Outdoor unit installation
location selection
Indoor unit installation
Outdoor unit inst al lation
Refrigerant pipe
installation and insulation
Drainage pipe installation
and insulation
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 13
Locatio n selection
Installation 13
2. Location select ion
2.1 Indoor unit location selection
The place shall easily suppor t t he indoor unit’s weight. The place can ensure the ind oor unit installation and inspection. The place can ensure the indoor unit horizontally installed. The place shall allow easy w ater drainage. The place shall easily connect with the outdoor unit. The place where air circulat ion i n t he r oom should be good. There should not be any heat source or steam near the unit. There should not be any oil gas near t he unit There should not be any corrosive gas near t he unit There should not be any salty air neat the unit There should not be strong electromagnetic wave near the unit There should not be inflamm able materials or gas near the unit There should not be strong voltage vibration.
2.2 Outdoor unit location selection
The place shall easily suppor t t he outdoor unit’s weight. Locate the outdoor unit as close to indoor unit as possib le The piping length and height dr op can not exceed the allowable value. The place where the noise, vibration and outlet air do not disturb the neighbors. There is enough room for inst allation and maintenance. The air outlet and the air inlet are not i m peded, and not face the strong wind. It is easy to install the connecting pipes and cables. There is no danger of fire due to leakage of inflammable gas. It should be a dry and well ventilation place The support should be flat and horizontal D o not install the outdoor unit in a dirty or severely polluted place, so as to avoid blockage of the heat
exchanger in the outdoor unit.
If is built over the unit to pr event direct sunl ight, rain exposure, d irect str ong we nd, snow a nd other scr aps
accumulation, make sure that heat radiation from the condenser is not restricted.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 14
Indoor unit installation
14 Installation
3. Indoor unit installation
3.1 Ceiling & floor indoor unit installation
3.1.1 Service space for indoor unit
3.1.2 Bolt pitch
Ceiling installation
Capacity (Btu/h)
D E
36K 1200 220
48K, 60K 1565 220
Wall-mounted installation
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 15
Indoor unit installation
Installation 15
3.1.3 Install t he pendant bolt
Ceiling installation Select the position of inst allation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings).
Wall-mounted installation Install the tapp in g s cr ew s onto the wall.(Refer to picture below)
3.1.4 Install t he m ain body
Ceiling installation (The only installation method for the unit with drain pump) Remove the side board and the grille.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 16
Indoor unit installation
16 Installation
Locate the hanging arm on t he hanging screw bolt. Prepare the mountin g bolts on the unit.
Put the side panels and gril les b ack.
Wall-mounted installation Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit. (The bottom of body can touch with floor or suspended, but the body must install vertically.)
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 17
Indoor unit installation
Installation 17
3.2 Duct indoor unit installation
3.2.1 Service space for indoor unit
3.2.2 Bolt pitch
Capacity (KBtu)
Size of outline dimension mounted plug
L M
36 1180 490
48/60 1240 500
3.2.3 Install the pendant bolt
Select the position of inst allation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings).
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 18
Indoor unit installation
18 Installation
3.2.4 Install the main body
Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on the four installation h ooks evenly, t o ens ure the balance of the body. Use a leveling instrument to make sure the levelness of the main body is within ±1°.
3.2.5 Install the air filter
Insert the air filter through t he fi lter slot and fix it with 2 screws.
3.2.6 Install the air du ct
Please design the air duct as bel ow recommended picture
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 19
Indoor unit installation
Installation 19
3.3.7 Change the air inlet di r ect i on
Take off ventilation panel and flange, cut off the staples at side rail.
Stick the attached seal sponge as per the indicating place in the following fig, and then change the
mounting positions of air ret ur n panel and air return flange .
When install the filter mesh, please plug it into flange inclined from air retur n opening, and then push up.
The installation has finish, upon filter mesh which fixing blocks have been insert to the flange positional
holes.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 20
Indoor unit installation
20 Installation
3.3 Air handler indoor unit installation
3.3.1 Service space for indoor unit
Refrigerant piping and connect ions- minimum12" recommended. Maintenance and servicing access - minimum36" from front of unit recommended for blower motor/coil replacement. Filter removal - minimum 36" recommended.
Plenum Clearances:
3.3.2 Install the main body
You can choose vertical or horizontal installation in accordance w it h t he applications.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 21
Indoor unit installation
Installation 21
Note: For drain the condensate out of the unit smoothly, please place the unit with a small angle when horizontal instal lation.
3.3.3 Install the air duct
Ty pica l air duct design:
Vertical Installation
Horizontal Inst al lat i on
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 22
Outdoor unit installation (Top Discharge Unit)
22 Installation
4. Outdoor unit installation (Top Discharge Unit)
4.1 Location selection
Before starting the inst al lat ion, select and chec k the suit a bility of the locat ion fo r bot h the indoor and outdoor unit. Observe all limit at io ns and clearance requirements. The outdoor unit must have sufficient clearance for air entrance to the condenser coil, for air discharge and for service access.
Note: For multiple unit installations, units must be spaced a minimum of 18 inches apart. (Coil face to coil face.) If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit. Provide an adequate struct ur al support.
4.2 Service space for outdoor unit
4.3 Install the Unit
On ground installation
The unit may be installed at ground level on a solid base that will not shift or settle, causing strain on the refrigerant lines and possible leaks. Maintain the clearances shown in Fig.5 and install the unit in a level position.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 23
Outdoor unit installation (Top Discharge Unit)
Installation 23
Normal operating sound levels may be objectionable if the unit is placed directly under windows of certain rooms (bedrooms, study, etc.). Top of unit discharge area must be unrestricted for at least 6 feet above the unit. Warning: The outdoor unit should not be installed in an area where mud or ice could cause per sonal injury. Elevate the unit sufficie ntly to prevent any bloc kage of the air entra nces by sno w in areas wher e there will be snow accumulation. Check the local weather bureau for the expected snow accumulation in your area. Isolate the unit from rain gutt er s t o avoid any possible wash out of the foundation.
On roof installation
When installing units on a roof, the structure must be capable of supporting the total weight of the unit, including a padded frame unit, rails, etc., which should be used to minimize the transmission of sound or vibration into the condition ed space.
Factory preferred tie-down method (Optional) Note:
These instructions are intended as a method to tie-down system to cement slab as a securing procedur e for high and areas. It is recommended to check Local codes for tie-down methods and protocols. Step 1: Pr ior t o installing clear pad of debris. Step 2: Ensur e cement pad is level. IMPORTANT: Then cement pad must be made of HVAC-approved materials and must be the proper thickness to accommodate fasteners. Step 3: Cent er unit onto pad. Step 4: Fasten 4 L-shaped stainless steel braces onto cabinet base using 4 1/4” * 1/2” Hex washer head stainless steel self-ta ppi ng screws where indicated in following pictur e.
IMPORTANT: Do not use screws longer than indicated 1/4” * 2/3” and make sure that the brace is attached on center of base ban where indic at ed in Fig.7. Damage will occur to system. Step 5: Dr ill 4 holes into cement base ensuring holes are 2 1//2”dp. Step 6: Assemble unit to cement pad using 4 1/4” * 2” Hex washer head cement screws make sure not to over tighten. Step 7:Finish unit assembly process as indicated in i ns tallation manual.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 24
Outdoor unit installation (Top Discharge Unit)
24 Installation
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 25
Refrigerant pipe installat ion
Installation 25
5. Refrigerant pipe installation
5.1 Maximum pipe length and height drop
Considering the allowable pipe length and height drop to decide the installation position. Make sure the distance and height dr op bet w een indoor and outdoor unit not exceeded t he date in the following table.
Model Max. Length Max. Elevation
36,000Btu/h 30m 20m
>36,000Btu/h
50m
25m
5.2 The procedure of connecting pipes
5.2.1 Choose the pipe size according to the specification table.
5.2.2 Confirm the cross way of the pi pes.
5.2.3 Measure the necessary pipe length.
5.2.4 Cut the selected pipe with pi pe cutter
Make the section flat and smoot h.
90
Lean
Crude
Burr
o
5.2.5 Insulate the copper pipe
Before test operation, t he joi nt par t s should not be heat insulated.
5.2.6 Flare the pipe
Insert a flare nut into the pipe befor e f laring the pipe According to the following t able t o f lare t he pipe
Pipe diameter
Flare dimension A (mm)
Flare shape
Min Max
1/4" (6.35) 8.3 8.7
R0.4~0.8
A
45
¡ã
90°
4
-
+
3/8" (9.52) 12.0 12.4
1/2" (12.7) 15.4 15.8
5/8" (15.9) 18.6 19.1
3/4" (19) 22.9 23.3
After flared the pipe, the opening p art must be seal by end cover or adhesive tape to avoid duct or
exogenous impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pip es so t hat it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 26
Refrigerant pipe installat ion
26 Installation
5.2.10 Set the wall conduit
5.2.11 Set the supporter for the pi pe.
5.2.12 Locate the pipe and fix it by supporter
For horizontal refrigerant pipe, the distance between supporters should not be exce ed 1m. For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners (Side discharge outdoor u nit).
Be sure to use two spanners and proper torque to f ast en t he nut, too large torque will damage the flare,
and too small torque may cause lea kage. Refer the following table for different pipe connection.
Pipe Diameter
Torque Sketch map
(kgf.cm) (N.cm) 1/4" (6.35) 144~176 1420~1720 3/8" (9.52) 333~407 3270~3990 1/2" (12.7) 504~616 4950~6030 5/8" (15.9) 630~770 6180~7540
3/4" (19) 990~1210 9270~11860
5.2.14 Connect the pipe to indoor unit and outdoor unit by brazing (Top discharge outdoor unit and Air Handler indo or units)
Top discharge outdoor unit and air handler indoor units connections are copper-to-copper and should
be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. The total system refrigerant charge is retained within the outdoor unit during shipping and installation. The reusable service valves are pr ovided to evacuate and charge per this instruct i on.
Serious service problems can be avoided by taking adequate precautions to assure an internally clean
and dry system.
CAUTION: Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is hi gh eno ugh to c aus e oxidat ion o f the c opper unless a n inert atmosphere is provide. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and pr event oxidation.
Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it
as shown in following picture. Also, prot ect all paint ed sur faces, insulat ion, du ring braz ing. A fter braz ing cool joint with wet rag.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 27
Refrigerant pipe installat ion
Installation 27
Valve can be opened by removing the plunger cap and fully inserting a hex wrench into the stem and
backing out counter-clockwise until valve stem just touches the chamf er ed r etaining wall.
5.2.15 Connect the throttle part
If the throttle part of indoor unit is separate design, it must be c onnected before connecting the pipe to
indoor unit. Make sure the thr ottle part is horizontally installed.
Connect to the pipe
Connect to indoor unit
Horizontal
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 28
Drainage pipe installation
28 Installation
6. Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
Ensure at least 1/100 slope of the drainage pipe Adopt suitable pipe diame t er Adopt nearby condensate w at er discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeli ne route and elevation
Before installing condensate water pipeline, det ermine its route and elevation to avoid intersec t io n with
other pipelines and ensure slop e is st r aight.
6.2.2 Drainage pipe selectio n
The drainage pipe diamet er shall not small than the drain hose of indoor unit According to the water flow r at e and dr ai nage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu) Water flowrate (l/h)
12 2.4 18 4 24 6 30 7 36 8 42 10 48 12 60 14
According to the above table t o calculate the total water flowrate for the confluence pipe selection. For horizontal drainage pipe (The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
Slope 1/50 Slope 1/100
PVC25 20 39 27
For branch pipe
PVC32 25 70 50 PVC40 31 125 88
Could be used for confluence pipe
PVC50 40 247 175 PVC63 51 473 334
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe (The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h) Remark
PVC25 20 220
For branch pipe
PVC32 25 410 PVC40 31 730
Could be used for confluence pipe
PVC50 40 1440 PVC63 51 2760 PVC75 67 5710 PVC90 77 8280
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 29
Drainage pipe installation
Installation 29
6.2.3 Individual design of drainage pipe system
The drainage pipe of air conditioner shall be insta lle d separat e ly w ith other sewage pip e, rainw ater pipe
and drainage pipe in building.
The drainage pipe of the indoor unit with wat er pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
In general, the supporter gap of the drainage pipe horizontal pipe and vert ical pipe is respectively
1m~1.5m and 1.5m~2.0m.
Each vertical pipe shall be equipped with not less than two hangers. Overlarge hanger gap for horizontal pipe shall create bending, thus lea di ng to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
W
ater flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
The correct installation wil l not cause converse water flow and the slope of the br anch pipes can be
adjusted freely
The false installation will cause converse water flow and the slope of the branc h pipe can not be
adjusted.
6.2.6 Water storage pipe setting
If the indoor unit has high extra static pressure an d without water pump to elevate the condensate water,
such as high extra stat ic pressure duct unit , the wat er storage pipe shou ld be set to avoid converse flow or blow water phenomena.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 30
Drainage pipe installation
30 Installation
Indoor unit
More than 50mm
More than 25mm
Plug
Water storage pipe
6.2.7 Lifting pipe setting of indoor unit with water pu mp
The length of lifting pipe s hould not exceed the pump head of indoor unit w ater pump.
Pump head of big four way cass et t e: 750mm Pump head of compact fo ur w ay cassette: 500mm
The drainage pipe should be set dow n i nc l ined after the lifting pipe immediately t o av oid wrong
operation of water level sw itch.
Refer the following picture for installation reference.
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipe≤150mm B: Lift height
the pump head of water pump
Down incline pipe
B
6.2.8 Blowhole setting
For the concentrated dr ainage pipe system, there should design a blowhole at the hi ghest point of main
pipe to ensure the condensate wat er discharge smoothly.
The air outlet shall face down to pr event dirt entering pipe. Each indoor unit of the syst em s hould be installed it. The installation should be cons idering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
6.2.9 The end of drainage pipe shall not contact with ground directly.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 31
Drainage pipe installation
Installation 31
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural draina ge mode(t he indoor unit with outdoor drainage pump) Infuse above 600ml water through water test hole slowly into the water collector, observe whether the water can discharge through the transparent hard pipe at drainage out let.
2. Pump drainage mode
2.1 Disconnect the plug of water level swit ch, r emove the cover of water test hole and slow ly infuse about 2000ml water through the w ater test hole, be sure that the water will not touch the motor of drainage pump.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and then connect the plug of water level switch, check the operation sound of water pum p and observe whether the water can dischar ge t hr ough the transparent hard pipe at dra ina ge outlet. (In light of the
length of drainage pipe, wat er shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole back to the original place.
a. After stopped the air condit ioner 3 minutes, check whether there is anyt hing a bnor mal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at remote-controlled receiving board a nd even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pu mp co ul d
discharge water at once. If wat er level does not decline under warning water lev el 3 minutes later, it shall cause shutdown o f unit. When this situat ion ha ppen s, the normal startup only can be recovered by turning down power suppl y and eliminating accumulated water.
Note: Drain plug at the main water -containing plate is used for eliminat ing accumulated water in water-containing plat e w hen maintaining air conditioner fault. During normal operation, the plug shall be filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to t he i nsulat i on engineering parts.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 32
Vacuum Drying and Leakage Checking
32 Installation
7. Vacuum Drying and Leakage Checking
7.1 Purpose of vacuum drying
Eliminating moisture in sy st em to pr event the phenomena of ice-blockage and copper oxidation.
Ice-blockage shall cause abnormal operation of system, while copper oxid e shall damage compressor.
Eliminating the non-condensable gas (air) in system to prev ent the components oxidizing, pressure
fluctuation and bad heat exchange during the operation of system.
7.2 Selection of vacuum pump
The ultimate vacuum degree of v ac uum pump shall be -756mmHg or above. Precision of vacuum pump shall reach 0. 02mmHg or above.
7.3 Operation procedure for vacuum drying
Due to different construction environment, two kinds of vacuum drying ways could be chosen, namely ordinary vacuum drying a nd special vacuum drying.
7.3.1 Ordinary vacuum drying
1. When conduct first vacuum drying, co nnect pressure gauge to the infusing mouth o f gas pipe and liquid pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached
-755mmHg).
2 If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates
that there is moisture or leakag e in p ipeline system and need to go on with drying for half an hour.
3 If the vacuum degree of vacuum pump still could not reach -755mmHg after 1.5 hours of drying, check
whether there is leakage s our ce.
4 Leakage test: After the vacuum degree reac hes -755mmHg, stop vacuum drying and keep t he pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it ind icat es that there is moisture or leak source.
7.3.2 Special vacuum drying
The special vacuum drying method shall be adopted when:
1. Finding moisture during flushing refrigerant pipe.
2. Conducting construction on rainy day, because r ain wat er m ight penetrated into pipeline.
3. Construction period is long, and rain wat er might penetrated into pipeline.
4. Rain water might penetrate into pipel ine during construction.
Procedures of special vac uum drying are as follows:
1. Vacuu m drying for 1 hour.
2. Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could achieve the effect of vacuum drying, but this method could not achieve drying thoroughly when there is too much moisture. Therefore, special attention shall be drawn to prevent the entering of water and the formation of condensate water .
3. Vacuu m drying again for half an hour.
If the pressure reached -755mmHg, start to pressure leakage test. If it can not r eached the value, repeat vacuum damage and vacuum drying again for 1 hour.
4 Leakage test: After the vacuum degree reac hes -755mmHg, stop vacuum drying and keep t he pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it ind icat es that there is moisture or leak source.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 33
Additional refrigerant charge
Installation 33
8. Additional refrigerant charge
After the vacuum drying pr ocess is carried out, the additional refrigerant c harge process need to be
performed.
The outdoor unit is factory charged with refrig erant. The add itiona l refrigerant charge volume is decided
by the diameter and length of the l iq uid pipe between indoor and outdoor unit. Refer the follow ing formula to calculate the charge volume.
Diameter of liquid pipe (mm) Φ6.35 Φ9.52 Φ12.7 Formula V=20g×(L-5) V=40g×(L-5) V=60g×(L-5)
V: Additional refrigerant charge volume (g). L : The length of the liquid pipe (m).
Note:
Refrigerant may only be charged after performed the vacuum drying process. Always use gloves and glasses to protect your hands and eyes during the charge work. Use electronic scale or flui d in fusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexib l e pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be c harged in liquid state. Before recharging, The air in the flexible pipe and manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is re fr igerant lea kage at the connection
joint part.(Using gas leakage detector or soap water to detect).
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 34
Engineering of insulation
34 Installation
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe → insulation (except joint section) f lare t he pipe piping layout and connectio n vacuum drying → insulate t he joi nt par t s
9.1.2 Purpose of refrigerant pipe insulation
During operation, tempera t ur e of gas pipe and liquid pipe shall be ov er -heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwi s e it shall debase the performance of unit and burn compressor.
Gas pipe temperature is v ery low during coolin g. I f insulation is not enough, it shal l form dew an d cause
leakage.
Temperature of gas pipe is very high (generally 50-100) d ur in g heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
The burning performance should over 120 According to the local law to choose insulation materials The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thic ker accor dingly.
9.1.4 Installation highlights of insulation construction
Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner .
Liquid pipe Insulation meterial
Gas pipe
The insulation material at the joint pipe shall be 5~10cm longer than the gap of the insulation material. The insulation material at the joint pip e s hall be inserted into the gap of the insulation material. The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly.
The linking part should be use gl ue to paste together Be sure not bind the insulation material over-tight, it may extrude out the a ir i n t he material to cau se b ad
insulation and cause easy agin g of the material.
9.2 Insulation of drainage pipe
9.2.1 Operational procedure of refrigerant pipe insulation
Select the suitable pipe → insulation (exce pt joint section) pipi ng layout and connectiondrainag e test insulate the joint parts
9.2.2 Purpose of drainage pipe insulation
The temperature of condensate drainage water is very low. I f insulat ion i s not enough, it shall form dew and cause leakage to damage t he house decoration.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 35
Engineering of electrical wiring
Installation 35
9.2.3 Insulation material selection for drainage pipe
The insulation material should be fla me retarda nt m ateria l, the flam e retardant of the material should be
selected according to the local law.
Thickness of insulation layer is usually above 10mm. Use specific glue to paste t he seam of insulation material, and then bind w it h adhesive tape. The width
of tape shall not be less than 5cm. Make sure it is firm and avoid dew.
9.2.4 Installation and highlights of insulation construction
The single pipe should be insulated before c onne ctin g to an other p ipe, th e joint part sho uld be insul ate d
after the drainage test.
There should be no insulat ion ga p bet ween the insulation material.
10. Engineering of electrical wiring
10.1 Highlights of electrical wiring installation
All field wiring construction should be finished by qualified electrician. Air conditioning equipment should be grounded according to the local electrical regulations. Current leakage protectio n sw it ch should be installed. Do not connect the power wire to t he terminal of signal wire. When power wire is parall el with signal w ire, put w ires to t heir own w ire tube and re main at least 30 0mm
gap.
According to table in indoor par t na med “the sp ec ificat ion of the p ow er” to choose the wiring, make sure
the selected wiring not small tha n t he dat e showing in the table.
Select different colors for differ ent wire according to relevant regulations. Do not use metal wire tub e at t he place with acid or alkali corrosion, adopt plastic wire tube to replace it. There must be not wire connec t joi nt in the w ire tube If joint is a must, set a connection box at the place . The wiring with different voltage should not be in one wire tube. Ensure that the color of the wires of outdoor and the terminal No. are same as t hose of indoor unit
respectively.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 36
Test operation
36 Installation
11. Test operation
11.1 The test operation must be carried out after the entire installation has been
completed.
11.2 Please confirm the following points before the test operation.
The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed. The refrigerant pipe syste m is le akage-checked. The drainage is unimpeded. The ground wiring is connect ed cor r ectly. The length of the tubing and t he added stow capacity of the refrigerant hav e been recorded. The power voltage fits the r at ed voltage of the air conditioner. There is no obstacle at the outlet an d inlet of the outdoor and indoor units. The gas-side and liquid-si de st op values are both opened. The air conditioner is pre-heated by turning on the power.
11.3 Test operation
Set the air conditioner under t he mo de of "COOLING" by remote controller, and check the following points.
Indoor unit
Whether the switch on the remote controller works well. Whether the buttons on the rem ote controller works well. Whether the air flow louver mov es normally. Whether the room temperature is adjusted well. Whether the indicator lights normally. Whether the temporary but t ons works well. Whether the drainage is norm al. Whether there is vibration or abnormal noise during operation.
Outdoor unit
Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your
neighborhood.
Whether any of the refrigerant is le aked.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 37
Electrical Control System
Electrical Control System 37
Electrical Control System
1. Electrical Control Function .......................................... 38
2. Electrical Control Function (Air Handler) ................... 43
3. Troubleshooting ............................................................ 46
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 38
Electrical Control Function
38 Electrical Control System
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 3 minutes Delay at restart for compressor.
1.2.2 Sensor protect ion at open ci r cuit and breaking disconnecti on.
1.2.3 Phase check function
If the phase sequence is detected wrong or lack of 1 or 2 phase, the unit won’t start and there is error code displayed on outdoor P CB.
1.2.4 Low pressure check function
The low pressure switch should be always closed. If it is open, the system will stop until the fault is cleared. During defrosting procedure , 4 minutes after defrosting ends and 5 minutes after compressor is on in heating mode, low pressure sw itc h w on’t be checked. Note: The system will not check if the protection could be cleared in 30 seconds after the protection occurs. If this protection occurs 3 times, it won’t recover automatically unti l the main power is cut off.
1.2.5 Over-current protection
When compressor is running, if the curr ent is over twice of the rated for 3 seconds, the compress or w i ll st op and an error code will be displayed on the outdoor PCB. If the current becomes normal, the compressor w ill restart after 3 minut es. Note: The current won’t be chec ked withi n 3 secon ds after the co mpress or st a rt s. The sy st em will not chec k if the protection could be cleared in 30 seconds after the protection occurs.
1.3 Operation Modes and Functions
1.3.1 Fan mode
(
1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan:
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 39
Electrical Control Function
Electrical Control System 39
27
T1
26
High
Low
24
Medium
1.3.2 Cooling Mode
1.3.2.1 Compressor running rules
Once the compressor starts up, it will follow the below r ules: When indoor room temperatureT1 is lower than Ts, the compressor and outdoor fan will shut off. When T1 is higher than Ts+1, the compressor and outdoor fan will start up.
Ts+1
Ts
On
Off
1.3.2.2 Outdoor fan running rules
The On-off outdoor units have single fan speed. The outdoor fan will run following the compressor except when AC is in evaporator high temperature protection in heating mode, condenser high temperature protection in cooling mode, defrosting mode and the current protection.
1.3.2.3 Indoor fan running rules
In cooling mode, indoor fan runs al l the time and the speed can be selected as high, medium, low and auto. The auto fan:
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 40
Electrical Control Function
40 Electrical Control System
4
T1-Ts
3
High
Low
1
Medium
1.3.2.4 Low evaporator coil temperature T2 protection
For ceiling& floor: AC will enter T2 protection if any of the following conditions is satisfied. Condition 1:
TE6
T2
On
Off
TE5
When the evaporator coi l temp.T2 keeps lower than TE 5 for 30 minutes, the compressor and outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
Condition 2:
TE6
T2
On
Off
TE5-2
When the evaporator coil temp.T2 keeps lower than TE5-2 for 20 minutes, the compressor and outdoor fan will shut off. When T2 is higher than TE6, the compr essor and outdoor fan will restart up.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 41
Electrical Control Function
Electrical Control System 41
Condition 3:
TE6
T2
On
Off
TE5-4
When the evaporator coil temp.T2 keeps lower than TE5-4 for 8 minutes, the compressor and outdoor fan will shut off. When T2 is higher than TE6, t he compressor and outdoor fan will restart up.
For A5 duct:
TE6
T2
On
Off
TE5
When.T2
TE5 for Time0, the compressor and outdoor fan will shut off. When T2>TE6, the compressor
and outdoor fan will restart up.
1.3.3 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between 17~30℃. In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts). For ceiling &floor:
ΔT=T1-Ts
Running mode
ΔT
>2℃
Cooling
-1<ΔT≤2℃
Fan-only
ΔT≤-1
Heating
For A5 duct:
ΔT=T1-Ts
Running mode
ΔT
>2℃
Cooling
-1≤ΔT≤2℃
Fan-only
ΔT<-1
Heating
Indoor fan will run at auto fan of the relevant mode.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 42
Electrical Control Function
42 Electrical Control System
The louver operates same as in rel evant mode. If the machine switches mode between heating and cooling, the compressor will keep stopping for 15 minutes and then choose mode according to T1-Ts. If the setting temperature is modified, the machine will choose running function again.
1.3.4 Drying mode
1.3.4.1 The indoor fan wil l keep running at low speed.
1.3.4.2 All protections are active and the same as that in cooling mode.
1.3.4.3 The louver oper ates the same as in cooling mode.
1.3.5 Timer function
1.3.5.1 Timing ra nge i s 24 hours.
1.3.5.2 Timer on. The machine will turn on automatically when reaching the setting ti me.
1.3.5.3 Timer off. The machine will turn off automat ically when reaching the setting time.
1.3.5.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then turn off automatical ly when reaching the setting “off” time.
1.3.5.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then turn on automatically whe n r eac hing the setting “on” time.
1.3.5.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be off and the AC running mode has not been chan ged.
1.3.5.7 The setting time is relativ e time.
1.3.6 Economy function
1.3.6.1 It is valid in cooling, heating and auto mode.
1.3.6.2. Turning off, changing mode or setting fan speed wi ll ca ncel economy function.
1.3.6.3 Operation process in sleep mode is as follow: After pressing ECONOM IC or SLEEP button on the controller, the machine will go into economy mode. When cooling, the setting temperature rises 1(be lower than 30) every hour, 2 hours later the setting
temperature stops rising. For heat pump models, when they are in heating, the setting temperature reduces 1(be higher than 17) every hour, 2 hours later the setting temperature stops reducing.
1.3.6.4 In this mode, the fan speed is forc ed int o AUTO mode.
1.3.7 Auto-Restart function
The indoor unit is equippe d w ith auto-r es t art fu nctio n, w hich is carr ied out t hro ugh an aut o-res t ar t modu le. In case of a sudden power failure, the module memorizes the setting conditions before the power failure. The unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes when power returns.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 43
Electrical Control Function (Air Handler)
Electrical Control System 43
2. Electrical Control Function (Air Handler)
2.1 Definition
T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature
2.2 Cooling Mode
2.2.1 When low level input from the wired controller portals G and Y, the system goes into cooling mode. Now on the wired controller, mode switch is in “Cool” and fan switch is in “ON” or “AUTO” position.
2.2.2 The compress or is c ontrolled by the wired controller and the cont r ol s ketch is as following:
Mechanical or Electronic Switch K
FAN
ON AUTO
(When the temperature reac hes t he setting, switch K is open)
2.2.3 The indoor fan motor works as following rules: When the fan switc h of the w ire d cont rol ler is in “ON” position, the fan signal G is low so th at t he in door fan is always on; When the fan switch of the w ired cont r ol ler is i n “AUTO” position, the fan signal G and the compress or signal Y is synchronal.
2.2.4 Evaporator low-temper ature protection
If T22 for 3 minutes, the compressor will stop and the indoor fan will works as usual; if T2>8, the protection is invalid and the compressor will restart.
T2
Compressor On
8 2
After 3 minutes
Compressor off
R Y G
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 44
Electrical Control Function (Air Handler)
44 Electrical Control System
2.3 Heating Mode
2.3.1 In heating mode, the four-way valve is on
2.3.2 The compressor and the four-way valve are controlled by the wired controller. As long as the four-way valve signal B and compressor signal Y is low level, the system goes into heating mode. Now on the wired controller, mode switch is in “Heat” and fan switch is in “ON” or “AUTO” position.
2.3.3 The control sketch is as following picture:
Mechanical or Electronic Switch K
FAN
ON AUTO
Mechanical or Electronic Switch
(When the temperature reac hes the setting, switch K is open)
2.3.4 Anti-cold wind protection (Optional) This function can be active by set the jumper JR1 on the indoor PCB
When T2TE4, indoor fan will stop; when T2TE3, indoor fan will re-start. In this protection, compressor and outdoor fan still wor k.
2.3.5 Indoor coil high-temperature protection
The temperatures in bracket is the setting temper ature w hen JR1 is connecte d (the anti-col d wind functio n is
indoor fan on
TE3 TE4
Indoor fan of f
Compress or off TE8
TE9
TE7 Outdoor fan off TE10
Compressor and
Out door fan on
R
Y G B
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 45
Electrical Control Function (Air Handler)
Electrical Control System 45
active).
2.4 Fan Only Mode
2.4.1 When the unit is in fan only mode, the outdoor fan and compressor ar e off.
2.4.2 On the wired controller, “Mode” switch is in “OFF” position and “Fan” switch is in “ON” position.
2.4.3 The control sketch is as following:
2.5 Indoor PCB Dis play
There are 3 LEDs on indoor PCB, which can display some information.
2.5.1 When the unit is initial electrified, all LED will flash for 1 second. When the unit is standby, LED1 will flashes at 0.5 Hz. When the unit is running normally, LED1 will be always on and LED2, LE D3 are off.
2.5.2 When there is an error, these LEDs will display as following:
No
Information LED1 LED2 LED3 Recover when
1 T2 sensor fault X
X T2 is normal
2 Input signal of wired controller error
X
Input is right
X means “OFF”, means “flash at 5 Hz”
R
G
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 46
Troubleshooting
46 Electrical Control System
3. Troubleshooting
LEDs’ for the indication of outdoor trouble
Type Contents LED1 LED2 LED3
Trouble Phase sequence(Only for VEM60C3SS1) Flash Off Off Trouble
Lack of phase(A,B) (Only for
VEM60C3SS1)
Flash Off Off
Trouble
Lack of phase(Only for VEM60C3SS1)
Off
Off
Off
Trouble
Protection of Low pressure(for 48k-60k
models)
Flash Flash Off
Trouble Overload of current Off Off Flash Trouble Communication malfunction Flash Off Flash
Trouble
Open-circuit and short-circ uit trouble of T5
or protection of high pressure(for 48k-60k
models)
Off Flash Off
Note:
1. If the LED1-LED3 are flashing slowly, means the system is stand-by.
2. T3: Outdoor condenser temperature sensor
3. T4: Outdoor ambient temperature sensor
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 47
Troubleshooting
Electrical Control System 47
Lack of phase
Check the power supply, is it 3 phase,
Check the connection betw een pow er supply and terminal,
is the voltage in outdoor terminal is 3 phase, 220-230V?
Outdoor PCB is defectiv e
Yes
Yes
3.3. Solving steps for typical malfunction
a. Phase sequence error:
b. Overload of curr ent
c. Lack of phase
Phase sequence error
Change the order of two of the wires to power supply.
Switch on the unit again.
If the problem cannot be solved, t he outdoor PCB is defective
Overload of current
Check the current, normally
Is the current in rated range?
The outdoor PCB is defective
Possible reason
1. Outdoor f an is defective
2. The compressor is defective
3. Refrigerant is over charged
4. Air enter the re frigerant system
Yes
No
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 48
Troubleshooting
48 Electrical Control System
d. Protection of pressure or temp.
e. Open-circuit and short-circuit trouble of T5
Is connection to connector of temp. sensor good?
Check the resistance o f t he temp. sensor according to Appendix 2
Repair connector
No
Yes
Is it the resistance is nor m al?
Indoor PCB is defective.
Replace the sensor
Yes
No
Protection of pressure or temp.
Is it k1 or K2 open ?
Is temp. protective switch K1 ope n
Possible reason
1. The wires is loose to K1
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is defective
5. Outdoor unit is in bad ventilation
Is pressure protective switch K2 open
Yes
Yes
Yes
Possible reason
1. The wires is loose to K2
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor motor or fan blade is defective
5. Outdoor unit is in bad ventilation
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 49
Troubleshooting
Electrical Control System 49
Appendix 1 Temperature Sensor Resistance Value Table (--K)
K Ohm
K Ohm
K Ohm
K Ohm
-20
115.266
20 12.6431 60 2.35774 100 0.62973
-19
108.146
21
12.0561
61
2.27249
101
0.61148
-18
101.517
22
11.5000
62
2.19073
102
0.59386
-17
96.3423
23
10.9731
63
2.11241
103
0.57683
-16
89.5865
24
10.4736
64
2.03732
104
0.56038
-15 84.2190 25 10.000 65 1.96532 105 0.54448
-14
79.3110
26
9.55074
66
1.89627
106
0.52912
-13
74.5360
27
9.12445
67
1.83003
107
0.51426
-12
70.1698
28
8.71983
68
1.76647
108
0.49989
-11
66.0898
29
8.33566
69
1.70547
109
0.48600
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9
58.7079
31
7.62411
71
1.59068
111
0.45957
-8
56.3694
32
7.29464
72
1.53668
112
0.44699
-7
52.2438
33
6.98142
73
1.48481
113
0.43482
-6
49.3161
34
6.68355
74
1.43498
114
0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4
44.0000
36
6.13059
76
1.34105
116
0.40060
-3
41.5878
37
5.87359
77
1.29078
117
0.38991
-2
39.8239
38
5.62961
78
1.25423
118
0.37956
-1
37.1988
39
5.39689
79
1.21330
119
0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1
33.3269
41
4.96392
81
1.13604
121
0.35042
2
31.5635
42
4.76253
82
1.09958
122
0.3413
3
29.9058
43
4.57050
83
1.06448
123
0.33246
4
28.3459
44
4.38736
84
1.03069
124
0.32390
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6
25.4954
46
4.04589
86
0.96681
126
0.30754
7
24.1932
47
3.88673
87
0.93662
127
0.29974
8
22.5662
48
3.73476
88
0.90753
128
0.29216
9
21.8094
49
3.58962
89
0.87950
129
0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.27770
11
19.6891
51
3.31847
91
0.82643
131
0.27078
12
18.7177
52
3.19183
92
0.80132
132
0.26408
13
17.8005
53
3.07075
93
0.77709
133
0.25757
14
16.9341
54
2.95896
94
0.75373
134
0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16
15.3418
56
2.73823
96
0.70944
136
0.23916
17
14.6181
57
2.63682
97
0.68844
137
0.23338
18
13.9180
58
2.53973
98
0.66818
138
0.22776
19
13.2631
59
2.44677
99
0.64862
139
0.22231
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Page 50
Troubleshooting
50 Electrical Control System
Appendix 2
Unit: ℃---K Discharge temp. sensor tabl e
-20 542.7 20 68.66 60 13.59 100 3.702
-19 511.9 21 65.62 61 13.11 101 3.595
-18 483 22 62.73 62 12.65 102 3.492
-17 455.9 23 59.98 63 12.21 103 3.392
-16 430.5 24 57.37 64 11.79 104 3.296
-15 406.7 25 54.89 65 11.38 105 3.203
-14 384.3 26 52.53 66 10.99 106 3.113
-13 363.3 27 50.28 67 10.61 107 3.025
-12 343.6 28 48.14 68 10.25 108 2.941
-11 325.1 29 46.11 69 9.902 109 2.86
-10 307.7 30 44.17 70 9.569 110 2.781
-9 291.3 31 42.33 71 9.248 111 2.704
-8 275.9 32 40.57 72 8.94 112 2.63
-7 261.4 33 38.89 73 8.643 113 2.559
-6 247.8 34 37.3 74 8.358 114 2.489
-5 234.9 35 35.78 75 8.084 115 2.422
-4 222.8 36 34.32 76 7.82 116 2.357
-3 211.4 37 32.94 77 7.566 117 2.294
-2 200.7 38 31.62 78 7.321 118 2.233
-1 190.5 39 30.36 79 7.086 119 2.174 0 180.9 40 29.15 80 6.859 120 2.117 1 171.9 41 28 81 6.641 121 2.061 2 163.3 42 26.9 82 6.43 122 2.007 3 155.2 43 25.86 83 6.228 123 1.955 4 147.6 44 24.85 84 6.033 124 1.905 5 140.4 45 23.89 85 5.844 125 1.856 6 133.5 46 22.89 86 5.663 126 1.808 7 127.1 47 22.1 87 5.488 127 1.762 8 121 48 21.26 88 5.32 128 1.717 9 115.2 49 20.46 89 5.157 129 1.674
10 109.8 50 19.69 90 5 130 1.632 11 104.6 51 18.96 91 4.849 12 99.69 52 18.26 92 4.703 13 95.05 53 17.58 93 4.562 14 90.66 54 16.94 94 4.426 15 86.49 55 16.32 95 4.294 B(25/50)=3950K 16 82.54 56 15.73 96 4.167 17 78.79 57 15.16 97 4.045
R(90℃)=5KΩ±3%
18 75.24 58 14.62 98 3.927 19 71.86 59 14.09 99 3.812
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com
Loading...