E01 Wire Controller EEPROM Error A. Check EEPROM chip on wire controller PCB is
loose,; B. After step A, if unit still displays error
code E01, change the wire controller.
E02 Indoor Unit PCB EEPROM Error A. Check EEPROM chip on indoor unit PCB is
loose, the chip location on12KBUT/18KBTU model
PCB is IC11, on 24KBTU/36KBTU model PCB is
IC7; B. After step A, if unit still displays error code
E02, change the indoor unit PCB.
E03
SIGNAL COMMUNICATION
BETWEEN OUTDOOR UNIT MAIN
PCB AND INVERTER MODULAR
BOARD
A. Check the wiring on outdoor unit main PCB is
correct or loose; B. If step A is passed, then change
outdoor unit main PCB; C. If step A does not pass,
change outdoor unit inverter modular board.
E05 OUTDOOR UNIT FAN COIL
TEMPERATURE SENSOR
FAILURE
A. Connection location on outdoor unit main PCB
is: CN15 PO\PG\PQ for 12kbtu/18kbtu/
24kbtu/36kbtu, PO is for outdoor ambient
temperature sensor, PG is for outdoor fan coil
temperature sensor, PQ is for outdoor unit discharge
gas temperature sensor. Replace with new sensor; B.
after step A, if unit still displays error code E05,
change the outdoor unit main PCB.
E06
OUTDOOR UNIT AMBIENT
TEMPERATURE SENSOR
FAILURE
A. Connection location on outdoor unit main
PCB is: CN15 PO\PG\PQ for 12kbtu/18kbtu/
24kbtu/36kbtu, PO is for outdoor ambient
temperature sensor, PG is for outdoor fan coil
temperature sensor, PQ is for outdoor unit
discharge gas temperature sensor. Replace with
new sensor; B. after step A, if unit still displays
error code E06, change the outdoor unit main
PCB.