Error
Code
Error Code Indication TROUBLE SHOOTING
01 Wire Controller EEPROM Error A. Check EEPROM chip on wire controller PCB is
code E01, change the wire controller.
02 Indoor Unit PCB EEPROM Error A. Check EEPROM chip on indoor unit PCB is
loose, the chip location on12KBUT/18KBTU model
PCB is IC11, on 24KBTU/36KBTU model PCB is
IC7; B. After step A, if unit still displays error code
E02, change the indoor unit PCB.
03
SIGNAL COMMUNICATION
BETWEEN OUTDOOR UNIT MAIN
PCB AND INVERTER MODULAR
BOARD
A. Check the wiring on outdoor unit main PCB is
correct or loose; B. If step A is passed, then change
outdoor unit main PCB; C. If step A does not pass,
change outdoor unit inverter modular board.
05 OUTDOOR UNIT FAN COIL
TEMPERATURE SENSOR
FAILURE
A. Connection location on outdoor unit main PCB
is: CN15 PO\PG\PQ for 12kbtu/18kbtu/
24kbtu/36kbtu, PO is for outdoor ambient
temperature sensor, PG is for outdoor fan coil
temperature sensor, PQ is for outdoor unit discharge
gas temperature sensor. Replace with new sensor; B.
after step A, if unit still displays error code E05,
change the outdoor unit main PCB.
06
OUTDOOR UNIT AMBIENT
TEMPERATURE SENSOR
FAILURE
A. Connection location on outdoor unit main
PCB is: CN15 PO\PG\PQ for 12kbtu/18kbtu/
24kbtu/36kbtu, PO is for outdoor ambient
temperature sensor, PG is for outdoor fan coil
temperature sensor, PQ is for outdoor unit
discharge gas temperature sensor. Replace with
new sensor; B. after step A, if unit still displays
error code E06, change the outdoor unit main
PCB.
Page 24
07
OUTDOOR UNIT DISCHARGE
GAS PIPE TEMPERATURE
SENSOR FAILURE
A. Connection location on outdoor unit main PCB
is: CN15 PO\ PG\PQ for 12kbtu/18kbtu/
24kbtu/36kbtu, PO is for outdoor ambient
temperature sensor, PG is for outdoor fan coil
temperature sensor, PQ is for outdoor unit discharge
gas temperature sensor. Replace with new sensor; B.
after step A, if unit still displays error code E07,
change the outdoor unit main PCB.
E08 SINGAL COMMUNICATION
BETWEEN INDOOR AND WIRE
CONTROLLER FAILURE
A. Check the wiring between indoor unit and
wire controller; B. If not work, change wire controller
OR wire between wire controller and indoor unit PCB;
C. if not work, change indoor unit PCB.
09 SINGAL COMMUNICATION
BETWEEN INDOOR AND
OUTDOOR UNIT FAILURE
A. Check the wiring sequence between indoor unit
and outdoor unit, if wired incorrect this will cause
damage to the PCB for both indoor unit and outdoor
unit; B. Check the status of LED4 lamp on outdoor
unit main PCB, if it’s dark or flashing, check the
wiring on outdoor unit main PCB, if wiring is
correct, change the outdoor unit main PCB; C. if
LED4 lamp is lit, change indoor unit PCB; D. If step
C does not work, change outdoor unit main PCB.
10 DISCHARGE GAS TEMPERATURE
OR COMPRESSOR
TEMPERATURE OVERHEAT
PROTECTION
Check that the refrigerant charge is correct, if
refrigerant charge is low test system for leaks.
12 INVERTER MODULAR BOARD
FAILURE
A. Check the voltage of input AC power is correct;
B. Check the wiring on outdoor unit main PCB is
correct, or loose; C. If step A & B are passed but
unit is still not functional, change the inverter
modular board; D. if step C does not work, then
change the outdoor unit main PCB.
Page 25
13
OVER CURRENT OR LOW
CURRENT PROTECTION
A. Check the voltage of input AC power is within
normal range. B. Check DC power voltage on
outdoor unit main PCB, if the voltage is lower than
150VDC, then replace the outdoor unit main PCB;
if the volt age is higher than 400VDC, then change
PFC modular board, or change the inverter modular
board.
14
INDOOR UNIT FAN COIL
TEMPERATURE SENSOR
FAILURE
A. Connection location on indoor unit PCB is:
CN8/T2_PIPE for 12kbtu/18kbtu, CN19/PIP E/PT
for 24kbtu/36kbtu, replace with new sensor; B. after
step A, if unit still displays error code E3, change
the indoor unit PCB.
16
INDOOR UNIT AMBIENT
TEMPERATURE SENSOR
FAILURE
A. Connection location on indoor unit PCB is:
CN11/ T1_ROOM for 12kbtu/18kbtu,
CN20/ROOM/RT for 24kbtu/36kbtu, replace with
new sensor; B. after step A, if unit still displays
error code E2, change the indoor unit PCB.
17
ANTI-FROSTING IN COOLING
MODE
A. Check if indoor unit fan motor is operating;
B. Check if unit is in the cooling mode when ambient
temperature is too low; C. Check if the resistance
data of indoor unit fan coil temperature sensor is
correct according to resistance data table of sensors
in this manual.
18 ANTI-OVERHEATING IN
HEATING MODE
A. Check if indoor unit fan motor is operating;
B. Check if unit is in the heating mode when
ambient temperature is too hot; C. Check if the
resistance data of indoor unit fan coil temperature
sensor is correct according to resistance data table
of sensors in this manual.
E21 OUTDOOR CONDENSER
OVERHEAT IN COOLING MODE
A. Check if outdoor unit fan motor is operating;
B. Check if unit is in the cooling mode when ambient
temperature is too hot; C. Check if the resistance
data of outdoor unit fan coil temperature sensor is
correct according to resistance data table of sensors
in this manual.