Innotech ICS01, ICS02 User Manual

Page 1
© MASS ELECTRONICS Pty Ltd 2008
DS 13.01
September 2013
Overview
The ICS series Control Stations form par t of the Maxim & Genesis Direct Digital Controller range and provide a simple unitary Human Machine Interface (HMI). The HMI oers on/o, setpoint and fan speed control. The HMI is powered by 24VAC and connect s directly to the Globals Comms network.
Each ICS can communicate with a designated controller on the network. The ICS units are configured via the Keypad, are compatible with most existing Innotech digital produc ts and are capable of operating at both fast or slow comms.
The interface to the controller is via global transmit and receive blocks, the configuration simply uses the ICS address to form part of the unique point name.
Features
• One numerical value input
• One numerical value output
• One momentary push button digital input
• One LED indication digital output
• One fan speed input (ICS02 only)
• Housed in a switchplate that mounts in standard electrical wall plates
• Isolated RS485 interconnection between Innotech Controllers
• Adjustable user input range
• Adjustable decimal place
• Configurable power on settings
Applications
The Innotech Control Station extends the capabilities of Innotech controllers by providing a numerical value output, numerical value input, push button digital input and a single LED display output for distributed control via RS-485.
The Innotech Control Station provides a visual display of a control value and a means to set a parameter. It is not intended for use on a large controller network as this aects the operation.
Installation
• Strictly follow the guidelines when installing the Comms wiring as outlined in the Genesis System Comms Wiring Recommendations.
• Mount the Innotech Control Station in a dry and clean location free of excess vibration.
Wiring
• DO NOT connect 240VAC to any terminals.
• The cable used for RS485 Comms must be shielded single twisted pair, 120 ohms character impedance, 36 to 45pF per metre capacitance between conductors.
• The Comms cable must be organised as a bus topology. That is, starting at one end, devices are connected to it until the other end of the cable is reached. No “stubs” are allowed. To connect a device to the cable, a cut is made in the cable at the point where the device is to be situated along it. Then, the two new ends of the cable are wired into the device. The shields from the two new ends are then terminated into the terminals marked SHLD1.
• Refer to the Genesis Network Installation Instructions and DS99.04 Cabling Manual for more information.
Approvals
The Innotech Control Station conforms to the requirement s for RCM labelling.
ICS0x
Innotech Control Station
MODEL:
ICS01: ON/OFF, Set Point ICS02: ON/OFF, Set Point and 3 Speed Fan
Model Number Designations
Innotech Control Station - ICS0x
Model
On/O
Temp.
Display
Setpoint
Adjust
Run Status Fan Speed
ICS01
ICS02
Page 2
© MASS ELECTRONICS Pty Ltd 2008
Page 2 DS 13.01 - ICS0x - Innotech Control Station September 2013
Specifications
Power Supply
• Voltage: 24VAC ±10% @ 50/60Hz
• Power Consumption: 3VA max
Inputs
• Push buttons for adjusting control values
• Push button for momentary input of “digital function”
Outputs
• No physical outputs
• Display of Temperature and Setpoint
Terminal Identification
1 24VAC Supply 2 0VAC Supply 3 Earth
Terminal 3 is for the protection of the Comms circuitr y and must be connected to a good electrical bonded Earth.
COMMS Connection
S1 Shield from incoming Comms Cable. + RS485 (+) signal.
- RS485 (-) signal. S2 Shield from outgoing Comms Cable. Do not connect. Only used on REM Networks
Temperature Ratings
• Storage 0 to 50°C non-condensing
• Operating 0 to 40°C non-condensing
Enclosure
The Innotech Control Stations are housed in switchplate that mounts in standard electrical wall plates. Colour: White Mounting: Wall mounted
Innotech Controller Configuration
The interface to the Innotech Control Station is with the use of Global Blocks in the configs executed on Innotech Controllers (Genesis and Maxim families). The Innotech Control Stations have the following pre-defined Global Blocks:
• CS:xxx AI Set Point Adjust
• CS:xxx AO Temperature Display
• CS:xxx DI On/O
• CS:xxx DO Run Status
• CS:xxx FS (ICS02 Only) Fan Speed (0, 1, 2, 3)
xxx represents the three digit address. (ie. Address 10 is 010, Address 5 is 005)
To access the points on the Innotech Control Station, Global Blocks with names corresponding to the above names need to be placed in the config. The figure below provides an example for an ICS02 at network address 2:
Page 3
© MASS ELECTRONICS Pty Ltd 2008
Page 3
DS 13.01 - ICS0x - Innotech Control Station
September 2013
Program Functions Of The Innotech Control Station
To enter Programming mode depress and hold the and
buttons for 5 seconds. The display will become blank indicating that you are in the Programming Mode. Release both keys and the display will show parameter 0.
Whilst in the programming mode the following buttons are active:
Change to the next parameter
Increase the current parameters value
Decrease the current parameters value
Parameter 0 - Global Address
The display will show the current GLOBAL Address of the device.
• The range of address is 2 to 127. The default address is 2.
Parameter 1 - Maximum Input Value
The display will show the Maximum Input Value to which the module’s input can be set.
• The range of Maximum Input Value is 0.0 to 99.9
• The factory default setting is 30.0
Parameter 2 - Minimum Input Value
The display will show the Minimum Input Value to which the module’s input can be set.
• The range of Minimum Input Value is 0.0 to 99.9
• The factory default setting is 15
Parameter 3 - Decimal Places
The display will show the number of decimal places which will be displayed for both the input and output values.
• The range of Decimal Places is 0 to 2
• The factory default setting is 1
Parameter 4 - Baud Rate
The display will show an indication of the communications Baud Rate:
• 0 4800 Baud
• 1 38400 Baud
• The factory default setting is 38400 Baud
To exit the Programming Mode depress the and buttons and the new setting will be saved.
IF PARAMETER 4 IS CHANGED, POWER TO THE ICS0x MUST BE RECYCLED, AFTER EXITING PROGRAMMING MODE.
Start Up Default Settings
The Innotech Control Station Module can be set to start with default settings for Set Point, Run Status and Fan Speed (ICS02 only). To set the start up default settings adjust the Innotech Control Station to the desired Set Point, Run Status and Fan Speed (ICS02 only) and then press and hold the and buttons for 5 seconds.
The display will become blank indicating that the new default start up settings have been saved.
Operating Functions Of The Control Station
Numerical Output
The Innotech Control Station will display a 4-digit value with up to 3 decimal places.
Numerical Input
The Innotech Control Station will provide a 4- digit value with up to 3 decimal places to Innotech controllers on the global network. The value can be modified by pressing the button to increment by the least significant digit or the button to decrement by the least significant digit.
Digital Input Value
The button on the Innotech Control Station provides a digital input value to the Innotech Controllers. This operates as a standard momentar y switch, i.e. Pressing the button produces a short period ON value to the controller.
Digital Output LED
The Innotech Control Station displays a digital state via the system LED during normal operation. This LED, however, cannot be overridden whist the Digital Input Value is in a transitional state.
Fan Speed Button (ICS02 Only)
The button provides means of set ting a fan speed. Pressing the
button cycles bet ween low/medium/high fan speeds. This is indicated on the LEDs above the button. The button and LEDs are disabled whilst the Control Station is o (ie. there is no ventilation only mode).
Page 4
© MASS ELECTRONICS Pty Ltd 2008
Page 4 DS 13.01 - ICS0x - Innotech Control Station September 2013
S1
S2
+
-
1 2 3
24V 0V EARTH
24V
EAR T H
0V
TX
RX
Global Comms Wiring
Daisy Chained
End Device
From Previous Controller
From Last Controller
To Next Controller
R 485(+)S
R 485(+)S
R 485(+)S
R 485( - )S
R 485( - )S
R 485( - )S
S1
S2
+
S1
S2
+