Innotech Genesis II Digital Controller User Manual

Genesis II Direct Digital Controller
INSTALLATION INSTRUCTIONS
Proprietary
No part of this technical manual may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of Mass Electronics Pty Ltd.
Trademark
Disclaimer
While great eorts have been made to assure the accuracy and clarity of this document, Mass Electronics Pty Ltd assumes no liability resulting from any omissions in this document, or from misuse of the information obtained herein. The information in this document has been carefully checked and is believed to be entirely reliable with all of the necessary information included. Mass Electronics Pty Ltd reserves the right to make changes to any products described herein to improve reliability, function and design, and reserves the right to revise this document and make changes from time to time in content hereof with no obligation to notify any persons of revisions or changes. Mass Electronics Pty Ltd does not assume any liability arising out of the application or any use of any product or circuit described herein; neither does it convey licence under its patent rights or the rights of others.
Some information in this document relates to products which are obsolete but still relevant for consumers who may have not upgraded their devices or who are using obsolete but still functional equipment.
Page 2 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Document Management
Document Title:
Genesis II Installation Instructions
Revision History
Version Number
1.0 June 2010 Document first edition
2.0 December 2013 Contact Details update, style update
Date Summary of Changes
Page 3 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
This page has been le intentionally blank.
Page 4 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Contents
Chapter 1 - Preliminary Information .............................................................11
1-1 Introduction ............................................................................................................. 12
1-1.1 Systems Covered by this Manual ............................................................................ 12
1-1.2 Scope of this Technical Manual...............................................................................13
1-2 Special Considerations ............................................................................................14
1-3 Unpacking Instructions ........................................................................................... 14
1-4 Installation Plans ..................................................................................................... 14
1-5 Tools and Test Equipment ....................................................................................... 14
Chapter 2 - Mechanical Information .............................................................. 15
2-1 Introduction ............................................................................................................. 16
2-2 Physical Descriptions .............................................................................................. 16
2-2.1 Genesis II Series Controllers .................................................................................... 16
2-2.2 Remote Expansion Modules .................................................................................... 19
2-3 Installation Instructions .......................................................................................... 26
2-3.1 DIN Rails ................................................................................................................... 26
2-3.2 General Installation Instructions ............................................................................28
2-4 Dierence Data......................................................................................................... 29
2-4.1 REM Limitations ....................................................................................................... 29
2-4.2 Installation of GENII WMI Wireless Module Interface ............................................. 29
Chapter 3 - Electrical Installation .................................................................31
3-1 Introduction ............................................................................................................. 32
3-2 Electrical Installation Practices .............................................................................. 32
3-3 Digital Controller Wiring .......................................................................................... 33
3-3.1 Genesis II Direct Digital Controller .........................................................................35
3-3.2 MPCII Mid Points Controller ....................................................................................43
Page 5 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Contents (Continued)
3-4 Wiring of Remote Expansion Modules .................................................................... 50
3-4.1 REM Power Connections .........................................................................................50
3-4.2 REM Comms Connections ....................................................................................... 51
3-4.3 GENII AI REM Analogue Input Module ..................................................................... 52
3-4.4 GENII AO REM Analogue Output Module ................................................................53
3-4.5 GENII DI REM Digital Input Module ..........................................................................54
3-4.6 GENII DO REM Relay Output Module .......................................................................56
3-4.7 GENII IDI REM Opto Isolated Digital Input Module ................................................. 57
3-4.8 GENII PI REM Pulse Input Module ...........................................................................58
3-4.9 GENII MZS REM Multi Zone Station Module ............................................................ 59
3-4.10 GENII MZSAH REM Multi Zone Station A/H Module .............................................. 60
3-4.11 GENII CS REM Control Station Module ..................................................................61
3-4.12 GENII CSAH REM Control Station A/H Module ......................................................62
3-4.13 GENII CSFCAH REM Control Station Fan Control A/H Module .............................. 63
3-4.14 GENII MP405 REM Multipoint Module ................................................................... 64
3-4.15 GENII MP414 REM Multipoint Module ................................................................... 66
3-4.16 GENII MP423 REM Multipoint Module ................................................................... 68
3-4.17 GENII MP432 REM Multipoint Module ................................................................... 70
3-4.18 GENII WMI Wireless Module Interface ................................................................... 72
3-4.19 SENRx Series Wireless Temperature Sensors .......................................................73
Chapter 4 - Commissioning ..........................................................................75
4-1 Introduction ............................................................................................................. 76
4-1.1 Inspect the Installation ...........................................................................................76
4-1.2 Check Input and Output Wiring ..............................................................................77
4-1.3 Install AISCs ............................................................................................................. 90
4-1.4 Set Jumper Plugs .....................................................................................................91
4-1.5 Load Soware and Configure the Controller(s) ..................................................... 96
4-1.6 Initial Tests .............................................................................................................. 97
4-1.7 Final System Check ................................................................................................. 99
Page 6 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Contents (Continued)
Chapter 5 - Network Installation ................................................................101
5-1 Overview ................................................................................................................ 102
5-2 Genesis II Products ................................................................................................ 102
5-2.1 Definitions .............................................................................................................. 103
5-3 Installation ............................................................................................................. 104
5-3.1 Network Specifications .........................................................................................104
5-3.2 Cable Specifications .............................................................................................. 104
5-3.3 Wiring Topology ..................................................................................................... 105
5-3.4 REM Network End of Line Termination (EOL) ....................................................... 108
5-3.5 Genesis II System Comms Wiring Considerations ................................................ 110
5-4 Cable Connection Procedures ..............................................................................121
Customer Assistance ................................................................................. 124
Innotech Support ............................................................................................................124
Page 7 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
List of Illustrations
Figure 2-1:  Figure 2-2:  Figure 2-3:  Figure 2-4:  Figure 2-5:  Figure 2-6:  Figure 2-7:  Figure 2-8:  Figure 2-9:  Figure 2-10:  Figure 2-11:  Figure 2-12:  Figure 3-1:  Figure 3-2:  Figure 3-3:  Figure 3-4:  Figure 3-5: 
Genesis II Direct Digital Controller Dimensions ..................................................... 17
Genesis II DDC Plastic Lid Clamping Details ..........................................................18
MPCII Mid Point Controller Dimensions ................................................................. 19
GenII AI REM Analogue Input Module ..................................................................... 20
GenII CS REM Control Station Module ....................................................................21
GenII MZS REM Multizone Station Module .............................................................22
GenII MP405 REM Multipoint Module ..................................................................... 23
GenII WMI Wireless Module Interface ..................................................................... 24
GenII SENRx Wireless Temperature Sensors ..........................................................25
DIN Rail Dimensions ................................................................................................ 26
Typical Enclosure and Example Remote System Layout ...................................... 27
Genesis II DDC Optimum Display Viewing Angle ...................................................28
Computer Generated Wiring Diagram Example ....................................................34
Genesis II DDC Input / Output Terminals ...............................................................35
Genesis II DDC Driving Multiple Solid State Relays ................................................ 40
MPCII Mid Points Controller Input / Output Terminals ..........................................43
MPCII Mid Points Controller Driving Multiple Solid State Relays .......................... 48
Figure 3-6:  Figure 3-7:  Figure 3-8:  Figure 3-9:  Figure 3-10:  Figure 3-11:  Figure 3-12:  Figure 3-13:  Figure 3-14:  Figure 3-15:  Figure 3-16:  Figure 3-17:  Figure 3-18:  Figure 3-19:  Figure 3-20:  Figure 3-21:  Figure 3-22: 
RS485 Comms Cable Connections .........................................................................51
GenII AI REM Analog Input Module ......................................................................... 52
GENII AO REM Analogue Output Module ................................................................ 53
GENII DI REM Digital Input Module ......................................................................... 54
GENII DO REM Relay Output Module ...................................................................... 56
GENII IDI REM Opto Isolated Digital Input Module.................................................57
GENII PI REM Pulse Input Module ........................................................................... 58
GENII MZS REM Multizone Station Module .............................................................59
GENII MZSAH REM Multizone Station A/H Module .................................................60
GENII CS REM Control Station Module ...................................................................61
GENII CSAH REM Control Station A/H Module ........................................................62
GENII CSFCAH REM Control Station Fan Control, A/H Module ..............................63
GENII MP405 REM Multipoint Module .....................................................................64
GENII MP414 REM Multipoint Module .....................................................................66
GENII MP423 REM Multipoint Module .....................................................................68
GENII MP432 REM Multipoint Module .....................................................................70
GENII WMI Wireless Module Interface .....................................................................72
Page 8 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
List of Illustrations (Continued)
Figure 3-23:  Figure 4-1:  Figure 4-2:  Figure 4-3:  Figure 4-4:  Figure 4-5:  Figure 4-6:  Figure 4-7:  Figure 4-8:  Figure 4-9:  Figure 4-10:  Figure 5-1:  Figure 5-2:  Figure 5-3:  Figure 5-4:  Figure 5-5:  Figure 5-6: 
SENRx Wireless Temperature Sensor (Back View) .................................................73
Checking Power Input ............................................................................................. 79
Checking Digital Input Wiring ................................................................................. 81
Checking Dry Contact Inputs .................................................................................. 83
Checking Digital Output Wiring .............................................................................. 85
Analogue Input Signal Conditioner (AISC) Locations ............................................ 87
Address Jumpers, Typical Settings ........................................................................92
End of Jumper, Typical Location ............................................................................93
Setting Analogue Output Jumpers.........................................................................94
Setting Frequency Jumpers on the GENII WMI ......................................................95
Setting Frequency Jumpers on the SENRx Module ............................................... 95
Correct and Incorrect Bus Topology.....................................................................105
Adding Modules to a Network ..............................................................................106
Linking Networks in Dierent Locations ..............................................................107
Multi-Network Arrangement .................................................................................108
Example of a Simple REM Network ......................................................................108
Example of REM Network with an Innotech Repeater IR11 ................................109
Figure 5-7:  Figure 5-8:  Figure 5-9:  Figure 5-10:  Figure 5-11:  Figure 5-12:  Figure 5-13:  Figure 5-14:  Figure 5-15:  Figure 5-16:  Figure 5-17:  Figure 5-18:  Figure 5-19:  Figure 5-20:  Figure 5-21: 
REM Network with Digital Controller in the middle of a run ...............................109
REM Network with Innotech Repeater IR11 in the middle of a run ....................110
Use of Repeaters to expand the Primary Network .............................................. 111
Example of Comms Screen Connection ............................................................... 112
Typical Comms Network Connections ................................................................. 112
Innotech Repeater IR11 and IR12 .........................................................................114
Networking and Earthing the Innotech Repeater IR12 .......................................115
GENII MPI Modem and Printer Interface ..............................................................116
Hazardous Connection Example, Circuit 1 ..........................................................117
Hazardous Connection Example, Circuit 2 ..........................................................118
Use of GENII MPI, Circuit 1 ....................................................................................119
Use of GenII MPI, Circuit 2 ..................................................................................... 120
Voltage Check, Isolated/Non-Isolated Digital Controller .................................... 122
Voltage Check, GENII MPI with Isolated/Non-Isolated RS485 ............................. 122
Voltage Check, Innotech Repeater .......................................................................123
Page 9 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
List of Tables
Table 1-1:  Table 3-1:  Table 3-2:  Table 3-3:  Table 3-4:  Table 3-5:  Table 3-6:  Table 3-7:  Table 3-8:  Table 3-9:  Table 3-10:  Table 3-11:  Table 3-12:  Table 3-13:  Table 3-14:  Table 3-15:  Table 3-16: 
Document Chapters ................................................................................................ 13
Nominal Resistance for Wire Sizes at 20°C .............................................................33
Genesis II DDC Power Input Signal Conditions ...................................................... 36
Genesis II DDC Input Signal Conditions .................................................................37
Genesis II DDC Output Signal Conditions ..............................................................38
Genesis II DDC Analogue Inputs .............................................................................39
Genesis II DDC Analogue Outputs ..........................................................................41
Genesis II DDC Pulse Counter Input Terminals ...................................................... 42
MPCII Mid Points Controller Power Input Signal Conditions ................................44
MPCII Mid Points Controller Digital Input Signal Conditions ................................45
MPCII Mid Points Controller Digital Output Signal Conditions .............................46
MPCII Mid Points Controller Analogue Inputs ........................................................ 47
MPCII Mid Points Controller Analogue Outputs ..................................................... 49
GenII AI REM Analog Input Signal Conditions ........................................................ 52
GENII AO REM Analogue Output Signal Conditions ............................................... 54
GENII DI REM Digital Input Signal Conditions ........................................................55
GENII DO REM Relay Output Signal Conditions ..................................................... 56
Table 3-17:  Table 3-18:  Table 3-19:  Table 3-20:  Table 3-21:  Table 3-22:  Table 3-23:  Table 3-24:  Table 3-25:  Table 3-26:  Table 4-1:  Table 4-2:  Table 4-3:  Table 4-4: 
GEN II IDI REM Opto Isolation Digital Input Signal Conditions ..............................57
GENII PI REM Pulse Input Signal Conditions .......................................................... 58
GENII MP405 REM Input Signal Conditions ............................................................ 65
GENII MP405 REM Output Signal Conditions ......................................................... 65
GENII MP414 REM Input Signal Conditions ............................................................ 67
GENII MP414 REM Output Signal Conditions ......................................................... 67
GENII MP423 REM Input Signal Conditions ............................................................ 69
GENII MP423 REM Output Signal Conditions ......................................................... 69
GENII MP432 REM Input Signal Conditions ............................................................ 71
GENII MP432 REM Output Signal Conditions ......................................................... 71
Genesis II System Power Inputs .............................................................................78
Digital Input Signal Voltages ................................................................................... 80
Analogue Input Checks ........................................................................................... 86
Units Requiring Jumper Settings ...........................................................................91
Page 10 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Direct Digital Controller
INSTALLATION INSTRUCTIONS

Chapter 1 - Preliminary Information

Genesis II Installation Instructions

1-1 Introduction

This manual is intended to provide qualified technical personnel with complete and easy-to-follow instructions for the installation, checkout and commissioning of the Innotech Genesis II Direct Digital Controller and MPCII Mid Points Controller.
Although the intent of this manual is to simplify the installation task, instructions contained in this manual are based on the assumption that installation of a Genesis II System will be accomplished by technically qualified personnel. Also, these instructions presuppose that installation personnel are familiar with local regulations, codes and safety requirements.
Installers should familiarise themselves with the content of this manual before attempting installation of the Genesis II Direct Digital Controller or MPCII Mid Points Controller.
Throughout this manual there are icons to illustrate notes and points of caution, as illustrated below:
NOTE
Notes contain useful information, which should be read.
IMPORTANT
Important Notes contain information, which is important for ensuring success.
CAUTION
Caution Notes contain critical information, which MUST be read.

1-1.1 Systems Covered by this Manual

Systems are intended for use in a variety of applications, the systems are designed on a modular basis. Modularity provides the most economical and eicient means of adapting the system to the customer’s specific requirements. Also, in seeking to improve customer satisfaction through product improvement, Innotech oen provides updates and revisions to its Genesis product line. The modularity concept and equipment revisions result in a large array of dierent types of hardware available to the customer.
The manual covers the Genesis II System. This system is based on one or more controllers as the major control units interconnected with several ancillary units. These major control units included in this manual are:
• Genesis II Direct Digital Controller
• MPCII Mid Points Controller
For purposes of explanation, a System is defined as one or more controller units interconnected with various ancillary units for the purpose of performing specific functions. A Genesis II System consists of one or more Genesis II Direct Digital Controllers and/or MPCII Mid Points Controllers as the major control unit(s).
Page 12 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
Some of the ancillary units included in the Genesis II System are (refer to the System Description Manual for descriptions of these units):
• Several types of Remote Expansion Module (REM)
• Miscellaneous Ancillary Units
The purpose of this manual is to provide clear and complete instructions for all phases of the installation of the units that comprise your Genesis II System. In order to provide the clearest instructions possible with minimum confusion, instructions in this manual are based on the following approach:
• For simplicity of explanation, installation instructions in this manual are based on the assumption the system to be installed is a typical Genesis II System containing a single Genesis II Direct Digital Controller and a selection of REMs.
• Specific information on the installation and wiring of ancillary units can be located in the Datasheet and Product Paperwork associated with each device.
• Basic electrical wiring information is provided in the Electrical Installation chapter, and wiring instructions for network systems is contained in the Network Installation chapter.

1-1.2 Scope of this Technical Manual

This technical manual contains:

Table 1-1:  Document Chapters

Heading Heading
Chapter 1 ­Preliminary Information
Contains installation related information of a general nature such as general safety considerations and pre-installation requirements.
Contains instructions and related data to facilitate the mechanical
Chapter 2 -
Mechanical Installation
installation of components of the Genesis II System. It also includes information such as physical descriptions of the units, mounting dimensions and mechanical installation guidelines.
Contains electrical wiring information useful for installation of a Chapter 3 -
Electrical Installation
basic “standalone” system. Chapter 3 is augmented by network
wiring information in Chapter 5 - Network Installation. Appropriate
references are provided between Chapter 3 and Chapter 5 for
installation of network wiring.
Chapter 4 -
Commissioning
Provides instructions for post-installation inspection and checkout
of the Genesis II System, power application and initial setup of the
various units that comprise the system.
Provides detailed information for interconnecting various units in a
network configuration. This appendix should be used in conjunction Chapter 5 -
Network Installation
with Chapter 3 when network installation is involved. The two
electrical installation areas: Chapter 3 and Chapter 5 are purposely
separated from each other in the interest of clarity and to simplify the
use of this manual.
Page 13
© Mass Electronics Pty Ltd 2010Chapter 1 – Preliminary Information
Genesis II Installation Instructions

1-2 Special Considerations

The following precautions and installation considerations must be observed to ensure personal safety and to prevent damage to equipment:
• Local safety regulations, building codes and ordinances must be complied with during installation. In cases of conflict with procedures in this manual, contact Innotech or its authorised representative for clarification.
• To prevent damage to equipment, avoid applying electrical power to the equipment prior to checkout, unless specifically instructed to do so in this manual.
• The Genesis II System can be installed using common tools and test equipment. Only qualified personnel familiar with local codes and practices should install the system. Wiring should only be performed by someone knowledgeable of electronics and wiring installation practices. Refer to the appropriate documentation when installing items provided by other manufacturers.

1-3 Unpacking Instructions

The following unpacking instructions should be followed as soon as possible aer the equipment is delivered to the installation site:
1. Carefully unpack each item and set packing materials aside for future use.
2. Check the inventory against the packing list to make sure nothing is missing.
3. Inspect each item for damage.
4. Report any shortages or damaged items.
5. Collect all factory inspection sheets and similar data; place in an equipment history file.
6. Any items which are not installed immediately should be carefully returned to its shipping
container and stored in a safe place until it is time for it to be installed.

1-4 Installation Plans

The following installation data should be gathered and made available to the installation team:
• This technical manual.
• Computer-Generated Wiring Diagram: the Innotech Gen2Config soware can be used to print a wiring diagram for the specific application. A copy of this wiring diagram is usually provided at the time of hardware delivery. Procedures for printing additional copies of the wiring diagram are contained in the Gen2Config Online Help.
• Computer-Generated Materials List: the Materials List is also provided at the time of hardware delivery. The list is printed out from the Innotech Gen2Config soware. The Materials List shows all the items of hardware required for the specific application.
• For non-Innotech equipment, gather the manufacturer’s installation-related data such as schematics, wiring diagrams, dimension diagrams, etc.
• Any other data source as it becomes known.

1-5 Tools and Test Equipment

No special tools are required for installation of the Genesis II Systems. Only common hand tools are needed. A high impedance digital Volt-Ohm-Milliammeter is the only item of electronic test equipment required.
Page 14 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Direct Digital Controller
INSTALLATION INSTRUCTIONS
Chapter 2 - Mechanical Installation
Genesis II Installation Instructions

2-1 Introduction

This section of the manual contains instructions and related data to facilitate the installation of components of the Genesis II System.
It is recommended that the main units of the Genesis II System, such as the Genesis II Direct Digital Controller (DDC), MPCII Mid Points Controller and standard Innotech Remote Expansion Modules (REM) be mounted in steel cabinets to minimise the eects of electromagnetic interference (EMI).
Innotech Control Station Module REMs and Wireless Sensor REMs have specific recommendations for installation described in this section. Networking components, such as computers, printers and modems, should be installed in accordance with standard computer installation practises.
Because of the designed-in flexibility of the Genesis II System, digital controllers and associated devices can be installed in a wide variety of configurations, depending on the user’s preference. For this reason it is not possible to include all the various installation configurations in this manual. Instead, this manual provides examples of installations that are considered typical.
Innotech recognises that the installation examples described in this manual may not be in total agreement with the user’s requirements. However, information in this document should be used as a guide for all installations, regardless of whether the specific circumstances match the examples given. In all cases, installation personnel should familiarise themselves with the information contained in this section.
NOTE
If required, additional installation recommendations can be provided from Innotech Control Systems Australia upon request.

2-2 Physical Descriptions

The following paragraphs contain physical descriptions, including dimensions and installation­related information, for the main units of the Genesis II System. These paragraphs are intended to provide the installer with suicient information to permit proper installation of the various units.
For units of equipment not included in the following paragraphs, refer to the appropriate product datasheet.

2-2.1 Genesis II Series Controllers

Controllers are the main processing units that provide overall control of the Genesis II Systems. Controllers are housed in a rectangular case made from flame retardant polycarbonate / ABS plastic listed under UL94-V0. The types of controller units included in this manual are:
• Genesis II Direct Digital Controller
• MPCII Mid Points Controller
Page 16 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
ALLDIMENSIONS ARE IN MILLIMETRES
Mounting Hole
2-2.1.1 Genesis II Direct Digital Controller
The Innotech Genesis II Direct Digital Controller is a state-of-the-art processing system that has the capability of controlling various types of industrial systems.
The Genesis II Direct Digital Controller is housed in a rectangular case suitable for Switchboard Mounting. The housing is made from flame retardant plastics recognised by UL as UL 94-V0. Refer to Figure 2-1.

Figure 2-1:  Genesis II Direct Digital Controller Dimensions

4mm
Typical of 8
Page 17
© Mass Electronics Pty Ltd 2010Chapter 2 – Mechanical Installation
Genesis II Installation Instructions
Plastic Lid Piece
RELEASE
The unit’s circuit boards are mounted inside the case, which consists of a base and a lid. The plastic base has eight mounting holes; each hole is 4mm in diameter. Not all of the eight holes are required for mounting, provided the unit is securely installed.
There are four slots in the bottom circuit board (motherboard), two slots at each end. These slots facilitate the clamping of the case’s plastic lid to the motherboard. To remove the plastic lid from the motherboard, press firmly inwards at each end of the plastic lid, which disengages the clip-in fittings, and li away simultaneously. Refer to Figure 2-2.
Top Circuit Board
TO
Motherboard
Plastic Base Piece

Figure 2-2:  Genesis II DDC Plastic Lid Clamping Details

Installation of the plastic lid is similar to the removal procedure; insert the clip-in fitting at one end of the plastic lid into the slots provided on the motherboard. Then, clip the opposite end of the plastic lid into the slots at that end of the motherboard. Pressing the two ends of the plastic lid together can assist in the operation.
Page 18 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
2-2.1.2 MPC II Mid Points Controller
The Innotech MPCII Mid Points Controller is a state-of-the-art processing system that has the capability of controlling various types of industrial systems. The MPCII Mid Points Controller can be used in a Genesis II System as the main controller.
It is housed in a case suitable for Switchboard Mounting. The housing is moulded from flame retardant plastics recognised by UL as UL 94-V0. The MPCII Mid Points Controller does not have any external controls or indicators. Refer to Figure 2-3.
188
GENESIS MPC
163

Figure 2-3:  MPCII Mid Point Controller Dimensions

DIGI TALCONTROLLER
65

2-2.2 Remote Expansion Modules

Remote Expansion Modules increase the capability of a controller by allowing more input and output devices to be connected to it.
The term Remote Expansion Module (REM) is the collective term applied to several types of units used to configure the hardware to the customer's requirements. The following paragraphs contain wiring information for the following categories of REMs used in the Genesis II System:
• REM I/O Expansion Modules (2-2.2.1)
• REM Control Station Modules (2-2.2.2)
• REM Multi Zone Station Modules (2-2.2.3)
• REM Multipoint Modules (2-2.2.4)
• REM Wireless Sensor Modules (2-2.2.5)
The system imposes restrictions on the total number and types of REMs that can be used with a controller. These requirements are explained in section 2-4.1.
Page 19
© Mass Electronics Pty Ltd 2010Chapter 2 – Mechanical Installation
Genesis II Installation Instructions
2-2.2.1 REM I/O Expansion Modules
REM I/O Expansion Modules increase the Input and/or Output capabilities of a Genesis II Series digital controller.
There are a total of six dierent REM I/O Expansion Modules.
• GENII AI REM Analogue Input Module
• GENII AO REM Analogue Out Module
• GENII DI REM Dry Contact Digital Input Module
• GENII DO REM Relay Output Module
• GENII IDI REM Opto Isolated Digital Input Module
• GENII PI REM Pulse Input Module
Common Enclosure Information
The above listed REM I/O Expansion Modules are housed in a rectangular case made from flame retardant polycarbonate / ABS plastic listed under UL94. ( GENII AO REM is listed under UL94-VO)
Colour: Grey Dimensions (max): 75mm(w) x 155mm(h) x 57mm(d) Mounting: DIN Rail Mounted
The cable run between the digital controller and the REM I/O Expansion Modules should not exceed 600 metres. However, the maximum cable length can be increased through the use of Innotech Repeater IR11 module. (See 5-3.3.3 for more information)
Below is a schematic of the GENII AI REM Analogue Input Module. The above listed REM I/O Expansion Modules feature the same dimensions and similar appearance. Refer to Figure 2-4.
75
57
TX
123
RX
GENESI S ANALOG I NPUT
Re mote Expansio nModule
155
+A1- +A2- +A3- +A4- +A5- +A6-
A CB DFE G H IJ LK
SCREEN
SCREEN

Figure 2-4:  GenII AI REM Analogue Input Module

Page 20 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
2-2.2.2 REM Control Station Modules
REM Control Station Modules are housed in a switchplate that mounts in standard electrical wall plates at a remote location. Mechanical installation instructions for the REM Control Station Modules are not applicable; electrical installation instructions for these modules are contained in the
Electrical Installation Chapter.
There are a total of three dierent REM Control Station Modules.
• GENII CS REM Control Station Module
• GENII CSAH REM Control Station A/H Module
• GENII CSFCAH REM Control Station Fan Control, A/H Module
Common Enclosure Information
Colour: White Mounting: Wall Mounted
The cable run between a digital controller and GENII CS REM Control Station Modules should not exceed 600 metres. However, the maximum cable length can be increased through the use of Innotech Repeater IR11 module. (See Paragraph 5-3.3.3 for more information)
Below is a schematic of the GENII CS REM Control Station Module. The above listed REM Control Station Modules feature the same dimensions and similar appearance. Refer to Figure 2-5.
Off
On
Run
Timer

Figure 2-5:  GenII CS REM Control Station Module

Page 21
© Mass Electronics Pty Ltd 2010Chapter 2 – Mechanical Installation
Genesis II Installation Instructions
2-2.2.3 REM Multi Zone Station Modules
REM Multi Zone Station Modules are housed in a switchplate that mounts in standard electrical wall plates at a remote location. Mechanical installation instructions for the REM Multi Zone Station Modules are not applicable; electrical installation instructions for these modules are contained in the
Electrical Installation chapter.
There are a total of two dierent REM Multi Zone Station Modules.
• GENII MZS REM Multi Zone Station Module
• GENII MZSAH REM Multi Zone Station A/H Module
Common Enclosure Information
Colour: White Mounting: Wall Mounted
The cable run between a digital controller and REM Multi Zone Station Modules should not exceed 600 metres. However, the maximum cable length can be increased through the use of Innotech Repeater IR11 module. Refer to Paragraph 5-3.3.3 for more information.
Below is a schematic of the GENII MZS REM Multi Zone Station Module. The above listed REM Control Station Modules feature the same dimensions and similar appearance. Refer to Figure 2-6.
Off
On
1
2
3
Select
4
5
6
Run

Figure 2-6:  GenII MZS REM Multizone Station Module

Page 22 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
2-2.2.4 REM Multipoint Modules
REM Multipoint Modules provide additional Analogue/Digital output capabilities for a Genesis II Series digital controller.
There are a total of three dierent REM Multipoint Modules.
• GENII MP405 REM Multipoint Module
• GENII MP423 REM Multipoint Module
• GENII MP432 REM Multipoint Module
Common Enclosure Information
The above listed REM Multipoint Modules are housed in a rectangular case suitable for DIN Rail mounting. The housing is moulded from flame retardant plastics recognised by UL as UL 94-V0.
Colour: Grey Dimensions(max): 107mm(w) x 100mm(h) x 65mm(d) Mounting: DIN Rail Mounted
The cable run between a digital controller and REM Multipoint Modules should not exceed 600 metres. However, the maximum cable length can be increased through the use of Innotech Repeater IR11 module. Refer to Paragraph 5-3.3.3 for more information.
Below is a schematic of the GENII MP405 REM Multi Zone Station Module. The above listed REM Multipoint Modules feature the same dimensions and similar appearance. Refer to Figure 2-7.
36
107
7
EOL
24V
A2A1A0
Jumpers
0V
SHLD2
SHLD1
+
-
Comms
DO 1 DO 2 DO 3
E
Co mNO
TH1
TH2
Co mNO Co mNO
-
-
+
+
DI
DI
2
1
AO
1
+
-
-
+
+
DI
DI
3
4
AO
2
+
-
-
65
50
36
12
90
100

Figure 2-7:  GenII MP405 REM Multipoint Module

Page 23
© Mass Electronics Pty Ltd 2010Chapter 2 – Mechanical Installation
Genesis II Installation Instructions
2-2.2.5 REM Wireless Sensor Modules
Wireless Temperature Sensor REMs increase the capability of a Genesis II System by allowing wireless temperature sensor’s to interface with the digital controller. The use of Wireless Temperature Sensor REMs is facilitated through the Wireless Module Interface, with connects directly to the REM socked on the digital controller.

GENII WMI Wireless Module Interface

The Wireless Module Interface can be located up to 600 metres from the host digital controller, however the cable length joining the GENII WMI to the controller must not exceed 600 metres. The maximum cable length can be increased through the use of Innotech Repeater IR11 module.
Up to 15 Wireless Temperature Sensor REMs can be wirelessly connected to a Wireless Module Interface, and can be located up to 20 metres from the Wireless Module Interface.
The GENII WMI Wireless Module Interface is housed in a rectangular case made from flame resistant Astrene M650 IR plastic in accordance with IEC695-2-1 (HD444-2-1) as of EN6355-1,A2 and IEC707 (AS/ NZS2420).
Colour: Grey Dimensions(max): 75mm(w) x 155mm(h) x 57mm(d) Mounting: DIN Rail Mounted
The GENII WMI should be mounted within a 20 metre radius (depending on obstructions) of all SENRx modules (see below) from which it will be receiving data. The location should be dry, clean and free of excess vibration. Below is an image of the GENII WMI Wireless Module Interface. Refer to Figure 2-8.
IMPORTANT
Do not install the GENII WMI inside a fully enclosed metal switchboard, as this may interfere with quality of the wireless signal.
Figure 2-8:  GenII WMI Wireless Module Interface
Page 24 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions

GENII SENRx Wireless Temperature Sensors

The GENII SENRx Wireless Temperature Sensors are housed in a square case manufactured from an ignition resistant grade of ABS, which meets the requirements of AS2420.
There are four models of the GENII SENRx modules:
• SENR1 Wireless Temperature Sensor
• SENR2 Wireless Temperature Sensor with Set Point
• SENR5 Wireless Temperature Sensor with Aer Hours
• SENR6 Wireless Temperature Sensor with Set Point and Aer Hours
Colour: O white Dimensions(max): 80mm(w) x 80mm(h) x 37mm(d) Mounting: Wall Mounted
The GENII SENRx modules should be mounted within a 20 metre radius (depending on obstructions) of the GENII WMI Wireless Module Interface. The location should be dry, clean and free of excess vibration. Refer to Figure 2-9.
5
30
7
UP
MOUNTING
HOLES
80
Figure 2-9:  GenII SENRx Wireless Temperature Sensors
80
Page 25
© Mass Electronics Pty Ltd 2010Chapter 2 – Mechanical Installation
Genesis II Installation Instructions

2-3 Installation Instructions

A steel enclosure is recommended to contain the system with the aim of minimizing EMI from surrounding equipment. To allow for the number of cables to enter and leave the enclosure, the minimum dimensions of slotted cable ducts should be 45mm x 45mm with 65mm clearance from the cable ducts to the terminals of the units.
The communications cable between the Genesis II Direct Digital Controller and REMs, or MPCII Mid Points Controller and REMS, is through the integrated RS485 REM Comms port in the digital controller.
NOTE
Unless otherwise noted, Installation Instructions are based on the assumption that the system to be installed is a local Genesis II System consisting of one Genesis II Direct Digital Controller and three types of REMs. Installation instructions for other types of hardware, such as the MPCII Mid Points Controller or GENII WMI Wireless Module Interface, is contained in section 2-4 - Dierence Data.

2-3.1 DIN Rails

The DIN rail is an industry-standard item and is available from a large number of commercial sources. The rail is usually manufactured from galvanised steel and may be provided with a finish. It is typically available in 2 metre lengths. DIN rail cutters are available commercially and are recommended; however, for smaller installations, a hacksaw may be used to cut the rails to the required length.
Figure 2-10 shows the dimensions of a typical DIN rail section.
15
35
Mounting Slot
18 X 5.2
ALLDIMENSIONS ARE IN MILLIMETRES
25

Figure 2-10:  DIN Rail Dimensions

Page 26 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
Figure 2-11 shows an example of a typical Genesis II System layout in an equipment enclosure.

Figure 2-11:  Typical Enclosure and Example Remote System Layout

Page 27
© Mass Electronics Pty Ltd 2010Chapter 2 – Mechanical Installation
Genesis II Installation Instructions
Side View
90 Degrees
Degrees

2-3.2 General Installation Instructions

To ensure continued reliable operation of the Genesis II System, the following installation guidelines should be observed:
• The Genesis II Direct Digital Controller or MPCII Mid Points Controller should be installed in a position that provides easy access to the front panel and suicient room for power, and input/ output cabling. Also, the Digital Controller should be mounted such that the controls are in easy reach of the user. This requirement does not apply to the MPCII Mid Points Controller which has no external controls or indicators.
• Placement of the Genesis II Direct Digital Controller should take into account the optimum viewing angle of the Liquid Crystal Display (LCD), which is approximately 45° vertically and 90° horizontally (see Figure 2-12).
• Do not mount any unit of the system near high voltage, high current cables or sources of strong radio frequency emissions such as transmitter antenna cables.
• The ambient temperature of the digital controller and REMs at the installation site should not exceed the 0-40 °C temperature range.
• Mount the units in an area with minimum vibration and minimum exposure to mechanical damage.
• The REMs must be installed within 600 metres of the Genesis II Direct Digital Controller or MPCII Mid Points Controller.
Top View
45

Figure 2-12:  Genesis II DDC Optimum Display Viewing Angle

Page 28 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
2-4 Dierence Data
This paragraph contains dierence data unique to installation of the MPCII Mid Points Controller, Genesis II System REMs and related devices. Installation instructions provided in Section 2-3 are applicable except where stated otherwise.

2-4.1 REM Limitations

The following limitations apply to the installation of REMs:
• A Genesis II Direct Digital Controller must have Version 4 firmware or greater installed to support REM Modules.
• For pre-version 5 controllers, a GENII RMI Remote Module Interface is required to connect REM Modules. Refer to datasheet DS15.01 GENII RMI Remote Module Interface for more information.
• Gen2Config v4.0 or greater must be used to configure a Genesis II Direct Digital Controller that has REM Modules connected to it.
• REM units designed for DIN rail mounting should be mounted on DIN rails in cabinets approved for switchgear or industrial control equipment, with the exception of the GENII WMI (See 2-4.2).
NOTE
Gen2Config V4.0 or greater automatically configures the Genesis II Series digital controller, and produces a printout which lists the types and quantities of REMs that can be used with a given Genesis II Series digital controller. The following information provides generalised REM type/quantity requirements that can be used for planning purposes.
• Up to 15 REMs can be connected to a single Genesis II Direct Digital Controller or MPCII Mid Points Controller, with one exception – the MP REMs. The MP REM can only be addressed between 1 and 8 and only 8 MP REMs can be used.

2-4.2 Installation of GENII WMI Wireless Module Interface

Follow the General Installation Guidelines (2-3.2) except:
• Do not install the GENII WMI inside a fully enclosed metal switchboard.
• The GENII WMI should be mounted within a 20 metre radius of all SENRx Modules from which it will be receiving data.
Page 29
© Mass Electronics Pty Ltd 2010Chapter 2 – Mechanical Installation
Genesis II Installation Instructions
This page has been le intentionally blank.
Page 30 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Direct Digital Controller
INSTALLATION INSTRUCTIONS

Chapter 3 - Electrical Installation

Genesis II Installation Instructions

3-1 Introduction

This section of the manual contains instructions and related data to facilitate the electrical installation of the Genesis II System. Because of the designed-in flexibility of the Genesis II System, it can be installed in a wide variety of configurations, depending on the user’s preference. For this reason, it is not possible to include all the various installation configurations in this manual. Instead, this manual provides examples of typical installations.
Innotech recognises that the installation examples described in this manual may not be in total agreement with the user’s requirements. However, information in this document should be used as a guide for all installations, regardless of whether the specific circumstances match the examples given. In all cases, installation personnel should familiarise themselves with the information contained in this section.
NOTE
If required, additional installation recommendations can be provided from Innotech Control Systems Australia upon request.
This section of the technical manual contains the following specific information:
• Electrical Installation Practices of a general nature
• Wiring information for digital controllers (Genesis II Direct Digital Controller, MPCII Mid Points Controller)
• Wiring information for Remote Expansion Modules

3-2 Electrical Installation Practices

This paragraph provides general information which is intended to assist qualified personnel installing the Genesis II Systems. More detailed information for wiring of controllers and expansion modules is contained in subsequent paragraphs. All wiring between the controller/expansion modules and system input/output devices, such as sensors, fans and compressors, must be in accordance with the instructions in the applicable instruction manual or datasheet.
CAUTION
Electrical power to the system must be turned o throughout the installation process. Do not apply power to any part of the system until ready for Commissioning (see Commissioning).
NOTE
If any data presented in this manual disagrees with information in the applicable instruction manual, information in the manufacturer’s instruction manual takes precedence. Customers are encouraged to contact Innotech Control Systems Australia for further information or clarification of information presented herein via the contact details at the back of this document.
Page 32 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
Cabling plays an important role in the installation of Genesis II Systems. The following general cabling guidelines should be observed:
• In all cases, use electromagnetic-shielded cable for sensor wiring.
• When necessary to protect cabling from physical damage, both shielding and physical protection may be provided by running the cable in a metal conduit. Alternatively, use steel wire armoured (SWA) cable, which also contains an electromagnetic shield.
• Avoid running cables in the vicinity of high voltage power cables or cables carrying switching voltages/currents. This especially applies to sensor signal cables.
• Interconnecting cables must have multi-strand conductors with a cross-sectional area of 1mm² for each conductor.
• The earth cable to a Genesis II System enclosures must be a minimum of 2.5mm², and wired in accordance with local electrical regulations.
• For Analogue Inputs to the controller, a 16 conductor (0.5mm²) shielded cable is required.
Table 3 -1 provides assistance in determining the cabling requirements for various installation configurations. It shows the dimensions, wire gauge designations and resistance values per unit length for common wire sizes. Use this table to determine specific cabling requirements for your installation.

Table 3-1:  Nominal Resistance for Wire Sizes at 20°C

Conductor Area (mm²) Diameter (mm)
0.5 0.80 21 20 3.44
1.0 1.13 18 17 1.72
1.5 1.38 17 15 1.15
2.0 1.60 16 14 0.86
2.5 1.78 15 13 0.69
NOTE
• 1. SWG = Standard Wire Gauge, BWG = British Wire Gauge, AWG = American Wire Gauge.
• 2. All SWG, BWG and AWG numbers are for the largest wire if a direct equivalent to the mm² wire size is not available.
Nearest SWG or
BWG
Nearest
AWG
Ohms per 100

3-3 Digital Controller Wiring

The following paragraphs contain input/output connection information for the Genesis II Direct Digital Controller and the MPCII Mid Points Controller. The GEN2Config Soware, which is used to configure and program the digital controller, automatically produces a wiring diagram and materials list for the specific application. The wiring diagram and materials list can be easily printed and used for reference.
metres
Page 33
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
Below is an example of a typical computer-generated wiring diagram. A printout of the wiring diagram and materials list is usually provided at the time of hardware delivery. Refer to Figure 3-1.

Figure 3-1:  Computer Generated Wiring Diagram Example

Page 34 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions

3-3.1 Genesis II Direct Digital Controller

Figure 3-2 shows the input/output connection groups for the Genesis II Direct Digital Controller. The controller uses Phoenix type plug-in terminal strips located around the controller’s perimeter. Both single row and double row terminals are used. Terminals are grouped by function as follows:
• Power Input (3-3.1.1)
• Digital Inputs (3-3.1.2)
• Digital Outputs (3-3.1.3)
• Analogue Inputs (3-3.1.4)
• Analogue Outputs (3-3.1.5)
• Pulse Input (3-3.1.6)
• Remote Expansion Modules (REM) Connector (3-3.1.7)
• RS232 Serial Communications (Comms) Port (Network Installation)
• Optional Ethernet Communications Port (Network Installation)
• Net & Global Commmunications (Comms, RS485) Terminal (Network Installation)

Figure 3-2:  Genesis II DDC Input / Output Terminals

Page 35
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
3-3.1.1 Power Input
The Genesis II Direct Digital Controller's power requirements are one of the following:
• 24VAC ±10%, 50/60 Hz, Power Consumption: 15 VA.
• 24VDC ±10%, Power Consumption: 8 Watts.
The operating voltage must meet the requirements of Safety Extra Low Voltage (SELV) to EN60730. The transformer used must be a safety transformer in compliance with EN60742 and be designed for 100% duty. It must also be sized and fused in compliance with local safety regulations.
A single transformer may be used to supply voltage to more than one unit (such as a Genesis II Direct Digital Controller and associated Remote Expansion Modules) providing the planned load is well within the transformer’s rating. The transformer output terminal designated as AC Neutral must be solidly earthed to the enclosure’s main earth link.
Power input terminals are Terminals 1, 2 and 3 and are detailed below in Table 3-2 .

Table 3-2:  Genesis II DDC Power Input Signal Conditions

Ter minal AC Supply DC Supply
1 24VAC +24VDC 2 0VAC (Neutral) 0VDC 3 Earth Earth
NOTE
Resistance between Terminal 2 and Earth must be 3 or less.
Page 36 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
3-3.1.2 Digital Inputs
The Genesis II Direct Digital Controller’s eight Digital Input channels (Terminals 4 to 19) provide the capability of directly interfacing to digital input signal sources such as pushbutton switches and relay contacts.
Because each Digital Input channel is isolated, the power source for the signal must be external to the controller. This signal source can be AC or DC. If the source is AC, it can be provided by the auxiliary transformer.
Digital input signal power requirements are one of the following:
• 24VAC ±15%
• 24VDC ±15%
There are two terminals associated with each Digital Input channel. If an external DC signal source is used, the even-numbered (le) terminal must be wired as positive and the odd-numbered (right) terminal as negative.
Refer to Table 3 -3 for Digital Input terminal number assignments. Signal names assigned to the terminals are DI 1+/- through to DI 8+/-. DI stands for Digital Input, the numeral value represents the channel number and the + or - sign indicates the signal polarity when using a DC signal power source.

Table 3-3:  Genesis II DDC Input Signal Conditions

Positive Side Negative Side
Ter minal Signal Terminal Signal
4 DI 1+ 5 DI 1-
6 DI 2+ 7 DI 2-
8 DI 3+ 9 DI 3-
10 DI 4+ 11 DI 4-
12 DI 5+ 13 DI 5-
14 DI 6+ 15 DI 6-
16 DI 7+ 17 DI 7-
18 DI 8+ 19 DI 8-
Page 37
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
3-3.1.3 Digital Outputs
Each of the Genesis II Direct Digital Controller’s twelve digital output channels (Terminals 42–65) consists of a single-pole, double-throw (SPDT) relay. The two terminals assigned to each channel represent the associated relay’s Normally Open (NO) and Common (COM) contacts.
Digital output relay contacts are rated at 24VAC, 2A. Good practice is to use pilot relays for the actual switching functions, particularly when it applies to inductive loads such as coils, solenoids and motors. This protects the relays of the Digital Output channel and has the advantage of allowing the pilot relays to be installed adjacent to the controlling switch-gear.
Refer to Table 3 -4 for Digital Output terminal number assignments.

Table 3-4:  Genesis II DDC Output Signal Conditions

Normally Open (NO) Common (COM)
Ter minal Signal Terminal Signal
42 DO 1 NO 43 DO 1 COM
44 DO 2 NO 45 DO 2 COM
46 DO 3 NO 47 DO 3 COM
48 DO 4 NO 49 DO 4 COM
50 DO 5 NO 51 DO 5 COM
52 DO 6 NO 53 DO 6 COM
54 DO 7 NO 55 DO 7 COM
56 DO 8 NO 57 DO 8 COM
58 DO 9 NO 59 DO 9 COM
60 DO 10 NO 61 DO 10 COM
62 DO 11 NO 63 DO 11 COM
64 DO 12 NO 65 DO 12 COM
Page 38 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
3-3.1.4 Analogue Inputs
The Genesis II Direct Digital Controller’s eight Analogue Input channels (Terminals 22-37) allow the direct interface of various analogue inputs, such as Thermistor, 0-10VDC, 0-5VDC and 4-20 mA signals. Each Analogue Input channel is configured to the type of input by the use of Analogue Input Signal Conditioners (AISCs). These are small plug inserts installed during system commissioning (see
Commissioning).
IMPORTANT
Special consideration must be made when using loop-powered 4-20 mA inputs. As this type of input draws 20 mA from the Digital Controller, a maximum of two inputs of this type may be used. This type of input must not be used on Remote Expansion Modules.
NOTE
Terminals 20 and 21 are provided for terminating Analogue Cable Screens.
There are two terminals associated with each of the eight Analogue Input channels. Normally, the even-numbered (positive) terminal is used for the active Analogue Input signal from the sensor. The odd-numbered (negative) terminal is used to provide the stimulation for the sensor or a voltage reference (such as 0 Volts) for an active transducer.
Due to the sensitivity of the Analogue Input signals, screened cable must be used. The screens should be terminated at Terminals 20 or 21.
Refer to Table 3 -5 for Analogue Input terminal number assignments. Signal names assigned to the terminals are AI1+/- through AI8+/-. AI stands for Analogue Input; the numeral represents the channel number. The + indicates the active signal and the - indicates the signal reference/return.

Table 3-5:  Genesis II DDC Analogue Inputs

Active Reference
Ter minal Signal Terminal Signal
22 AI 1+ 23 AI 1-
24 AI 2+ 25 AI 2-
26 AI 3+ 27 AI 3-
28 AI 4+ 29 AI 4-
30 AI 5+ 31 AI 5-
32 AI 6+ 33 AI 6-
34 AI 7+ 35 AI 7-
36 AI 8+ 37 AI 8-
Page 39
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
3-3.1.5 Analogue Outputs
Sixteen Analogue Output channels are provided. Each channel can be configured, through the Gen2Config soware, to operate in either the Variable Mode or the Heat Valve Mode.
In the Variable Mode, the output is a voltage-analogue signal varying from 0 to +10 Volts with a maximum current rating of 5mA. In the Heat Valve Mode, the output signal consists of Pulse-Width Modulated (PWM), 0-10V, high-speed pulses at 5mA.
For a description of PWM as it applies to Heat Valve Operation, refer to the Innotech Genesis II Direct Digital Controller User Manual.
When using PWM outputs, up to three solid state relays, connected in series, may be used on each Heat Valve-configured analogue output channel. See Figure 3-3.
A maximum of eight Analogue Output channels can be applied to Heat Valve operation. For more than eight Heat Valve outputs, it is recommended that Models IHV4002 or IHV4004 for Heat Valves for Solid State Relays or IHV4212, IHV4224 or IHV4214 Staging Heat Valves for Solid State Relays be used. These heat valves are driven by the Digital Controller’s Analogue Output channel in the Variable Mode.
For more information on these devices, refer to:
• Datasheet DS3.31 for Type IHV Heat Valves.
• Datasheet DS3.32 for Type IHV42 Heat Valves.
L3
12
3+ve
ANALOGUE
OUTPUT
TERMINALS
-
+
L1 L2
TO
HEATERS
12
3+ve
4
HEATERS
12
3+ve
4
TO

Figure 3-3:  Genesis II DDC Driving Multiple Solid State Relays

TO
HEATERS
4
Page 40 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
Refer to Table 3 -6 below for Analogue Output terminal numbers. There are 16 Analogue active signal terminals (AO1 through AO16), one for each channel and eight return (Common) terminals. The fewer number of Common terminals is intended to reduce the overall number of terminals.
Cable screening may be terminated into the Screens Terminals (20 and 21), space permitting. Alternatively, all cable screens can be combined by soldering within the slotted cable-routing ducts with a common 1mm2 earth lead connected to Terminals 20 or 21.

Table 3-6:  Genesis II DDC Analogue Outputs

Ter minal Signal Terminal Signal
66 AO1 78 AO5
67 AO2 79 AO6
68 AO3 80 AO7
69 AO4 81 AO8
70 Common 82 Common
71 Common 83 Common
72 Common 84 Common
73 Common 85 Common
74 AO9 86 AO13
75 AO10 87 AO14
76 AO11 88 AO15
77 AO12 89 AO16
Page 41
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
3-3.1.6 Pulse Counter Inputs
A single, high-speed Digital Input is provided to facilitate the counting of rectangular wave signals (0-10VDC up to 0-24VDC, for pulse frequencies up to 1 kHz). Refer to Table 3-7 for terminal number assignments.
Terminals 38 and 39 provide 24VDC power to the pulse source, if required. Terminals 40 and 41 are the pulse-input terminals. The input is polarity sensitive so it is important that correct polarity be observed.

Table 3-7:  Genesis II DDC Pulse Counter Input Terminals

Ter minal Signal
38 +24VDC to Pulse Signal
39 -24VDC to Pulse Signal
40 + Pulse Input
41 - Pulse Input
3-3.1.7 REM Connector
The Genesis II Direct Digital Controller has the facility for I/O expansion using Remote Expansion Modules (REMs). Each REM provides an array of points which can be connected to a sub-network up to 600 metres in length.
The fieen REMs can be made up of any mix of the available types with one exception - the MP REM. The MP REM can only be addressed between 1 and 8 and only 8 MP REMS can be used.
The REM connector is a 4 way terminal connection that provides access between the Genesis II Direct Digital Controller and the expansion modules.
The individual REMs are connected to the device by means of an RS485 Comms cabling arrangement, as explained in 3-4 - Wiring of Remote Expansion Modules.
Page 42 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
DIGI
RS232
T
OUTPUTS

3-3.2 MPCII Mid Points Controller

Figure 3-4 shows the input/output connection groups for the MPCII Mid Points Controller. The MPCII Mid Points Controller uses terminal strips located around the controller’s perimeter. Terminals are grouped by function as follows:
• Power Input (3-3.2.1)
• Digital Inputs (3-3.2.2)
• Digital Outputs (3-3.2.3)
• Analogue Inputs (3-3.2.4)
• Analogue Outputs (3-3.2.5)
• Remote Expansion Modules (REM) Connector (3-3.2.6)
• RS232 Serial Communications (Comms) Port (Network Installation)
• Net & Global Communications (Comms, RS485) Terminal (Network Installation)
TALINPUTS
POWER
ANALOGUE INPUTS
SCREENS
CONNECTOR
REM
POR
RS-232 COMMS
REM
MPC
Cobar
DIGITAL OUTPUTS
GLOBAL
COMMS
ANALOGUE
COMMS
NET
COMMS
RS485
COMMS

Figure 3-4:  MPCII Mid Points Controller Input / Output Terminals

Page 43
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
3-3.2.1 Power Input
The MPCII Mid Points Controller's power requirements are one of the following:
• 24VAC ±10%, 50/60Hz, Power Consumption: 7 VA
• 24VDC ±10%, Power Consumption: 4 Watts
The operating voltage must meet the requirements of Safety Extra Low Voltage (SELV) to EN60730. The transformer used must be a safety transformer in compliance with EN60742 and be designed for 100% duty. It must also be sized and fused in compliance with local safety regulations.
A single transformer may be used to supply voltage to more than one unit (such as a MPCII Mid Points Controller and associated Remote Expansion Modules) providing the planned load is well within the transformer’s rating. The transformer output terminal designated as AC Neutral must be solidly earthed to the enclosure’s main earth link.
Power input terminals are Terminals 1, 2 and 3 and are detailed below in Table 3-8:

Table 3-8:  MPCII Mid Points Controller Power Input Signal Conditions

Ter minal AC Supply DC Supply
1 24VAC +24VDC
2 0VAC (Neutral) -24VDC
3 Earth Earth
NOTE
Resistance between Terminal 2 and Earth must be 3 or less.
Page 44 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
3-3.2.2 Digital Inputs
The MPCII Mid Points Controller’s four Digital Input channels (Terminals 4 to 11) provide the capability of directly interfacing to digital input signal sources such as pushbutton switches and relay contacts.
Because each Digital Input channel is isolated, the power source for the signal must be external to the controller. This signal source can be AC or DC. If the source is AC, it can be provided by the auxiliary transformer.
Digital input signal power requirements are one of the following:
• 24 VAC ±15%
• 12 VDC ±15%
There are two terminals associated with each Digital Input channel. If an external DC signal source is used, the even-numbered (le) terminal must be wired as positive and the odd-numbered (right) terminal as negative.
The MPCII Mid Points Controller's Digital Input terminals are not assigned numbers; however, each Digital Input terminal is clearly labelled as to its polarity and signal name. Signal names assigned to the terminals are DI 1+/- through DI 4+/-.
Refer to Table 3 -9 for the MPCII Mid Points Controller's Digital Input Signal Conditions:

Table 3-9:  MPCII Mid Points Controller Digital Input Signal Conditions

Positive Side Negative Side
Ter minal Signal Terminal Signal
DI 1 DI 1+ DI 1 DI 1-
DI 2 DI 2+ DI 2 DI 2-
DI 3 DI 3+ DI 3 DI 3-
DI 4 DI 4+ DI 4 DI 4-
Page 45
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
3-3.2.3 Digital Outputs
Each of the MPCII Mid Points Controller’s eight digital output channels consists of a single-pole, double-throw (SPDT) relay. The two terminals assigned to each channel represent the associated relay’s Normally Open (NO) and Common (COM) contacts.
Digital output relay contacts are rated at 24VAC, 2A (to be supplied by a Class 2 Transformer).
Good practice is to use pilot relays for the actual switching functions, particularly when it applies to inductive loads such as coils, solenoids and motors. This protects the relays of the Digital Output channel and has the advantage of allowing the pilot relays to be installed adjacent to the controlling switch-gear.
The MPCII Mid Points Controller's Digital Output terminals are not assigned numbers; however, each Digital Output terminal is clearly labelled as to its polarity and signal name. Signal names assigned to the terminals are DO 1(NO/COM) through DO 8(NO/COM).
Refer to Table 3 -10 for Digital Output terminal number assignments:

Table 3-10:  MPCII Mid Points Controller Digital Output Signal Conditions

Normally Open (NO) Common (COM)
Ter minal Signal Terminal Signal
DO 1 DO 1 NO DO 1 DO 1 COM
DO 2 DO 2 NO DO 2 DO 2 COM
DO 3 DO 3 NO DO 3 DO 3 COM
DO 4 DO 4 NO DO 4 DO 4 COM
DO 5 DO 5 NO DO 5 DO 5 COM
DO 6 DO 6 NO DO 6 DO 6 COM
DO 7 DO 7 NO DO 7 DO 7 COM
DO 8 DO 8 NO DO 8 DO 8 COM
Page 46 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
3-3.2.4 Analogue Inputs
The MPCII Mid Points Controller’s four Analogue Input channels allow the direct interface of various analogue inputs, such as Thermistor, 0-10VDC, 0-5VDC and 4-20mA signals. Each Analogue Input channel is configured to the type of input by the use of Analogue Input Signal Conditioners (AISCs). These are small plug inserts installed during system commissioning (Mechanical Installation).
There are two terminals associated with each of the four analogue input channels. Normally, the even-numbered (positive) terminal is used for the active Analogue Input signal from the sensor. The odd-numbered (negative) terminal is used to provide the stimulation for the sensor or a voltage reference (such as 0 Volts) for an active transducer.
Due to the sensitivity of the Analogue Input signals, screened cable must be used. The screens should be terminated at the Screen Terminals, located between the Digital Input and Analogue Input terminals on the MPCII Mid Points Controller.
The MPCII Mid Points Controller's Analogue Input terminals are not assigned numbers; however, each Analogue Input terminal is clearly labelled as to its polarity and signal name. Signal names assigned to the terminals are AI 1+/- through AI 4+/-. Refer to Table 3 -11 for Analogue Input terminal number assignments.
IMPORTANT
Special consideration must be made when using loop-powered 4-20mA inputs. As this type of input draws 20mA from the Digital Controller, a maximum of two inputs of this type may be used. This type of input must not be used on Remote Expansion Modules.
NOTE
Screen Terminals, located between the Digital Input and Analogue Input terminals on the MPCII Mid Points Controller, are provided for terminating Analogue Cable Screens.

Table 3-11:  MPCII Mid Points Controller Analogue Inputs

Active Reference
Ter minal Signal Terminal Signal
AI 1 AI 1+ AI 1 AI 1-
AI 2 AI 2+ AI 2 AI 2-
AI 3 AI 3+ AI 3 AI 3-
AI 4 AI 4+ AI 4 AI 4-
Page 47
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
3-3.2.5 Analogue Outputs
The MPCII Mid Points Controller has four Analogue Output channels. Each channel can be configured, through the Gen2Config Soware, to operate in either the Variable Mode or the Heat Valve Mode.
In the Variable Mode, the output is a voltage-analogue signal varying from 0 to +10 Volts with a maximum current rating of 5mA. In the Heat Valve Mode, the output signal consists of Pulse-Width Modulated (PWM), 0-10V, high-speed pulses at 5mA.
For a description of PWM as it applies to Heat Valve Operation, refer to the Innotech MPCII Mid Points Controller User Manual.
When using PWM outputs, up to three solid state relays, connected in series, may be used on each Heat Valve-configured analogue output channel. See Figure 3-5.
For more than four Heat Valve outputs, it is recommended that Models IHV4002 or IHV4004 Heat Valves for Solid State Relays be used. These heat valves are driven by the Digital Controller’s Analogue Output channel in the Variable Mode.
For more information on these devices, refer to:
• Datasheet DS3.31 for Type IHV Heat Valves
• Datasheet DS3.32 for Type IHV42 Heat Valves
L3
HEATERS
12
3+ve
4
TO
ANALOGUE
OUTPUT
TERMINALS
-
+
L1 L2
TO
HEATERS
12
3+ve
4
HEATERS
12
3+ve
4
TO

Figure 3-5:  MPCII Mid Points Controller Driving Multiple Solid State Relays

There are four analogue active signal terminals (AO1 through AO4), one for each channel and two return (Common) terminals. The fewer number of Common terminals is intended to reduce the overall number of terminals.
Cable screening may be terminated into the provided Analogue Output Screens, space permitting. Alternatively, all cable screens can be combined by soldering within the slotted cable-routing ducts with a common 1mm2 earth lead connected to the Analogue Output Screens.
Page 48 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
Refer to Table 3 -12 for Analogue Output terminal number assignments:
NOTE
Screen Terminals, located between the Analogue Output terminals AO 2 and AO 3 on the MPCII Mid Points Controller, are provided for terminating Analogue Output Cable Screens.

Table 3-12:  MPCII Mid Points Controller Analogue Outputs

Ter minal Signal Ter minal Signal
AO 1 AO 1+ 38 AO 1-
AO 2 AO 2+ 39 AO 2-
Screen Common 40 Common
Screen Common 41 Common
AO 3 AO 3+ 42 AO 3-
AO 4 AO 4+ 43 AO 4-
3-3.2.6 REM Connector
The MPCII Mid Points Controller has the facility for I/O expansion using Remote Expansion Modules (REMs). Each REM provides an array of points which can be connected to a sub network up to 600 metres in length.
The fieen REMs can be made up of any mix of the available types with one exception - the MP REM. The MP REM can only be addressed between 1 and 8 and only 8 MP REMS can be used.
The REM connector is a 4 way terminal connection that provides access between the MPCII Mid Points Controller and the expansion modules.
The individual REMs are connected to the device by means of an RS485 Comms cabling arrangement, as explained below in 3-4 Wiring of Remote Expansion Modules.
Page 49
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions

3-4 Wiring of Remote Expansion Modules

The following paragraphs contain wiring information for the following types of Remote Expansion Modules (REMs) used in the Genesis II System:
• GENII AI REM Analogue Input Module (3-4.3)
• GENII AO REM Analogue Output Module (3-4.4)
• GENII DI REM Dry Contact Digital Input Module (3-4.5)
• GENII DO REM Digital Output Module (3-4.6)
• GENII IDI REM Opto Isolated Digital Input Module (3-4.7)
• GENII PI REM Pulse Input Module (3-4.8)
• GENII MZS REM Multi Zone Station Module (3-4.9)
• GENII MZSAH REM Zone Control Station A/H (3-4.10)
• GENII CS REM Control Station Module (3-4.11)
• GENII CSAH REM Control Station Aer Hours Module (3-4.12)
• GENII CSFCAH REM Control Station Fan Control, Aer Hours Module (3-4.13)
• GENII MP405 Multipoint Module (3-4.14)
• GENII MP414 Multipoint Module (3-4.15)
• GENII MP423 Multipoint Module (3-4.16)
• GENII MP432 Multipoint Module (3-4.17)
• GENII Wireless Module Interface (3-4.18)
• SENRx Wireless Temperature Sensors (3-4.19)
Communication between the Genesis II Direct Digital Controller or MPCII Mid Points Controller and REMs is by way of a RS485 cable connected between the dedicated REM network socket on the digital controller and the REM network.
The method for connecting the modules to electrical power and to the RS485 Comms cable system is similar for most of the dierent types of modules, except where otherwise noted. The following two paragraphs provide detailed instructions for connecting electrical power and the RS485 system, respectively.

3-4.1 REM Power Connections

Power requirements are 24VAC, ±10% at 50/60 Hz. Refer to the appropriate paragraph below for the physical location of the power connection block within each type of REM. At the power connection block, the 24VAC power terminals are:
• Terminal 1 = 24VAC Supply
• Terminal 2 = 0VAC Supply
• Terminal 3 = Earth
Terminal 3 is for the protection of the RS485 Comms circuitry and must be connected to a good, electrically bonded earth. This may be the earth bus bar of the switchboard or the point that connects the chassis of the equipment the module is located in. This connection is independent of and in addition to the earthed AC Neutral at Terminal 2.
CAUTION
Do not connect Terminal 3 to Terminal 2.
Page 50 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
CABLE #1 CABLE #2
_

3-4.2 REM Comms Connections

The RS485 Comms link between the Genesis II Direct Digital Controller and REMs, or the MPCII Mid Points Controller and REMs, is designed to allow reliable communications over long distances in electrically adverse signal conditions.
The following guidelines, which are common to all REMs, should be followed when installing the RS485 Comms network:
• Cables used for RS485 Comms must be shielded, single twisted pair, 120 Ohms characteristic impedance with 36 to 45 picoFarads per metre capacitance between conductors.
• The RS485 Comms cable must be organised as a bus topology. See 5-3.3 for a description of bus topology. To connect a module to the RS485 cable, the cable is cut at the point the module is to be connected. Then, the two new cable ends are wired into the module. The two shields are then terminated at terminals marked SHLD1 and SHLD2 respectively. “Stub” connections are not allowed in the bus topology configuration.
• The cable run between the digital controller and any other REM must not exceed 600 metres in length.
On most units, the RS485 Comms connection block contains four terminals. The four terminals on the standard RS485 connection block are:
• S1 Screen of Cable Number 1
+ Positive Comms Line
• - Negative Comms Line
• S2 Screen of Cable Number 2
The four-terminal arrangement accommodates the use of one or two RS485 Comms cables. A single cable connection is used when the module is located at the end of the network and two cable connections are used when the REM is connected to a point in the cable network other than the end.
An End of Cable Jumper plug near the RS485 connection block provides the proper termination impedance for the Comms line. If only single RS485 Comms cable is connected to the module, the End of Cable Jumper must be installed. If two cables are fitted, the End of Cable Jumper must be removed.
IMPORTANT
The RS485 Comms System will not function properly if the connection polarities are incorrect. Ensure correct polarity of the connections throughout the length of the Comms Cable.
Figure 3-6 shows how to connect a two-cable Comms network to a module. If the module has only one RS485 Comms cable connected to it, the cable screen must be connected to S1. If two Comms cables are fitted, the screen of the second cable must be connected to the S2 terminal. Screens must not be connected to each other.

Figure 3-6:  RS485 Comms Cable Connections

S1 S2
+
Page 51
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions

3-4.3 GENII AI REM Analogue Input Module

The GENII AI REM Analogue Input Module (Figure 3-7) is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 4 VA maximum.
The GENII AI REM provides for six analogue inputs from field equipment. Each Analogue Input circuit has a socket for fitting an Analogue Input Signal Conditioner (AISC), which defines the input type and range selection. Installing the AISCs is part of the commissioning process and is explained in the
Commissioning chapter.

Figure 3-7:  GenII AI REM Analog Input Module

The RS485 Comms connection block is in the upper right section of the module and the End of Cable Jumper is next to it.
Analogue Input terminals for the GENII AI REM are listed in Ta ble 3-1 3 . Analogue Input cables should be run using twisted pair, shielded cable. The screens are to be connected to either of the two terminals marked SCREEN.

Table 3-13:  GenII AI REM Analog Input Signal Conditions

Active Reference
Ter minal Signal Terminal Signal
A AI 1+ B AI 1-
C AI 2+ D AI 2-
E AI 3+ F AI 3-
G AI 4+ H AI 4-
I AI 5+ J AI 5-
K AI 6+ L AI 6-
Screen
Common
Screens
Commons
Screens
Commons
Screens
Page 52 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions

3-4.4 GENII AO REM Analogue Output Module

The GENII AO REM Analogue Output Module (Figure 3-8) is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 4VA maximum.
The GENII AO REM provides up to five Analogue Outputs to be connected to field equipment. Jumpers on the board allow for either Linear 0-10V (maximum load 2mA) or PWM 10Vpp (maximum load 2mA) output settings for each channel.

Figure 3-8:  GENII AO REM Analogue Output Module

Page 53
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
The RS485 Comms connection block is in the upper right section of the module and the End of Cable Jumper is next to it.
Analogue Output terminals are located at the bottom of the module; output signal connections are listed below in Table 3-14. Analogue Output cables should be run using twisted pair shielded cable. The screens should be connected to the signal’s negative output terminal (B, D, F, H or J) in each case.

Table 3-14:  GENII AO REM Analogue Output Signal Conditions

Ter minal Signal Terminal Signal
A AO 1+ B AO 1-
C AO 2+ D AO 2-
E AO 3+ F AO 3-
F AO 4+ H AO 4-
I AO 5+ J AO 5-

3-4.5 GENII DI REM Digital Input Module

The GENII DI REM Digital Input Module (Figure 3-9) is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 4VA maximum.
The GENII DI REM provides 8 dry contact closure switches (inputs provide 5VDC that is shorted to common when the input is closed) to sense contact closures from field equipment.

Figure 3-9:  GENII DI REM Digital Input Module

Page 54 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
The RS485 Comms connection block is in the upper right section of the module and the End of Cable Jumper is next to it.
Digital Input terminals are located at the bottom of the module; input signal connections are listed in Table 3 -15.

Table 3-15:  GENII DI REM Digital Input Signal Conditions

Ter minal Signal
A DI 1+
B DI 2+
C DI 3+
D DI 4+
E DI 5+
F DI 6+
G DI 7+
H DI 8+
I Common
J Common
Page 55
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
CONNECTIONS
END OF
CONNECTIONS

3-4.6 GENII DO REM Relay Output Module

The GENII DO REM Relay Output Module (Figure 3-10) is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 4VA maximum.
The GENII DO REM provides 5 Relay Outputs (2A @ 24VAC – Normally open contacts) to control or switch field equipment.
POWER
12
3
CABLE
JUMPER
RS485 COMMS
R
GENESI S DIGI TA L OUTPUT Remote Expansion Modul e
DIGITAL
DI2
DI1
DI4
DI3
+
+
+
+
ABCDE FGHI J
DI8
DI7
DI5
DI6
+
+
COM
COM
+
+
-
-
OUTPUT

Figure 3-10:  GENII DO REM Relay Output Module

The RS485 Comms connection block is in the upper right section of the module and the End of Cable Jumper is next to it.
Digital Output terminals are located at the bottom of the module; input signal connections are listed in Table 3-16.

Table 3-16:  GENII DO REM Relay Output Signal Conditions

Normally Open (NO) Common (COM)
Ter minal Signal Terminal Signal
A NO Relay 1 B COM Relay 1
C NO Relay 2 D COM Relay 2
E NO Relay 3 F COM Relay 3
G NO Relay 4 H COM Relay 4
I NO Relay 5 J COM Relay 5
Page 56 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
CONNECTIONS
END OF
CONNECTIONS

3-4.7 GENII IDI REM Opto Isolated Digital Input Module

The GENII IDI REM Opto Isolated Digital Input Module (Figure 3-11) is powered by 24VAC ±10% @ 50/60Hz. Power Consumption is 4VA maximum.
The GENII IDI REM provides 5 opto isolated digital inputs to sense signals from field equipment. The voltage detection range is 12 to 24 volts AC or DC.
POWER
12
3
CABLE
JUMPER
RS485 COMMS
R
GENESI S ISOLA TED DIGI TA LINPUT Remote Expansion Modul e
DIGITAL
+DI2-
+DI1-
ABCDE FGHI J
+DI3-
+DI4-
+DI5-
INPUT

Figure 3-11:  GENII IDI REM Opto Isolated Digital Input Module

Table 3-17:  GEN II IDI REM Opto Isolation Digital Input Signal Conditions

Active Reference
Ter minal Signal Terminal Signal
A DI 1 + B DI 1 -
C DI 2 + D DI 2 -
E DI 3 + F DI 3 -
G DI 4 + H DI 4 -
I DI 5 + J DI 5 -
Page 57
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
CONNECTIONS
END OF
CONNECTIONS

3-4.8 GENII PI REM Pulse Input Module

The GENII PI REM Pulse Input Module (Figure 3-12) is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 4 VA maximum.
The GENII PI REM provides 5 opto isolated digital inputs to sense pulsed signals from field equipment. The voltage detection range is 12 to 24VDC. The GENII PI REM detects pulses with a minimum on time of 20ms, with a minimum o time of 20ms, which gives a maximum of 25 pulses per second.
POWER
12
3
CABLE
JUMPER
RS485 COMMS
R
GENESI S PULSE INPUT Remote Expansion Modul e
DIGITAL
+DI2-
+DI1-
ABCDE FGHI J
+DI3-
+DI4-
+DI5-
INPUT

Figure 3-12:  GENII PI REM Pulse Input Module

The RS485 Comms connection block is in the upper right section of the module and the End of Cable Jumper is next to it.
Digital Input terminals are located at the bottom of the module; input signal connections are listed in Table 3 -18 .

Table 3-18:  GENII PI REM Pulse Input Signal Conditions

Active Reference
Ter minal Signal Terminal Signal
A DI 1 + B DI 1 -
C DI 2 + D DI 2 -
E DI 3 + F DI 3 -
G DI 4 + H DI 4 -
I DI 5 + J DI 5 -
Page 58 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
CONNECTIONS

3-4.9 GENII MZS REM Multi Zone Station Module

The GENII MZS REM Multi Zone Station Module (Figure 3-13) is powered by 24VAC ±10% @ 50/60Hz. Power Consumption is 3VA maximum.
The GENII MZS REM mounts into a standard electrical wall plate. The only connections to the GENII MSZ REM are 24VDC power and the RS485 Comms link. Locations of electrical terminals are shown in Figure 3-13, which is a rear view of the module.
When all connections have been made, protect the module from dirt and moisture by covering it with plastic but do not mount the module in the wall plate until commissioning is completed. This is to allow addresses to be set as part of the commissioning process.
POWER
RS485
COMMS

Figure 3-13:  GENII MZS REM Multizone Station Module

END OF
CABLE
JUMPER
Page 59
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
CONNECTIONS

3-4.10 GENII MZSAH REM Multi Zone Station A/H Module

The GENII MZSAH REM Multi Zone Station A/H Module is powered by 24VAC ±10% @ 50/60Hz. Power Consumption is 3VA maximum.
The GENII MZSAH REM mounts into a standard electrical wall plate. The only connections to the GENII MZSAH REM are 24VAC power and the RS485 Comms link. Locations of electrical terminals are shown in Figure 3-14, which is a rear view of the module.
When all connections have been made, protect the module from dirt and moisture by covering it with plastic but do not mount the module in the wall plate until commissioning is completed. This is to allow addresses to be set as part of the commissioning process.
POWER
RS485
COMMS

Figure 3-14:  GENII MZSAH REM Multizone Station A/H Module

END OF
CABLE
JUMPER
Page 60 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions

3-4.11 GENII CS REM Control Station Module

The GENII CS REM Control Station Module is powered by 24VAC ±10% @ 50/60Hz. Power Consumption is 3 VA maximum.
The GENII CS REM mounts into a standard electrical wall plate. The only connections to the GENII CS REM are 24VAC power and the RS485 Comms link. Locations of electrical terminals are shown in Figure 3-15, which is a rear view of the module.
When all connections have been made, protect the module from dirt and moisture by covering it with plastic but do not mount the module in the wall plate until commissioning is completed. This is to allow addresses to be set as part of the commissioning process.
POWER
RS485
COMMS
CONNECTIONS

Figure 3-15:  GENII CS REM Control Station Module

END OF
CABLE
JUMPER
Page 61
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions

3-4.12 GENII CSAH REM Control Station A/H Module

The GENII CSAH REM is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 3VA maximum.
The GENII CSAH REM mounts into a standard electrical wall plate. The only connections to the GENII CSAH REM are 24VAC power and the RS485 Comms link. Locations of electrical terminals are shown in Figure 3-16, which is a rear view of the module.
When all connections have been made, protect the module from dirt and moisture by covering it with plastic but do not mount the module in the wall plate until commissioning is completed. This is to allow addresses to be set as part of the commissioning process.
POWER
RS485
COMMS
CONNECTIONS

Figure 3-16:  GENII CSAH REM Control Station A/H Module

END OF
CABLE
JUMPER
Page 62 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions

3-4.13 GENII CSFCAH REM Control Station Fan Control A/H Module

The GENII CSFCAH REM Control Station Fan Control, A/H Module is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 3VA maximum.
The GENII CSFCAH REM mounts into a standard electrical wall plate. The only connections to the GENII CSFCAH REM are 24VAC power and the RS485 Comms link. Locations of electrical terminals are shown in Figure 3-17, which is a rear view of the module.
When all connections have been made, protect the module from dirt and moisture by covering it with plastic but do not mount the module in the wall plate until commissioning is completed. This is to allow addresses to be set as part of the commissioning process.
POWER
RS485
COMMS
CONNECTIONS
END OF
CABLE
JUMPER

Figure 3-17:  GENII CSFCAH REM Control Station Fan Control, A/H Module

Page 63
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
NOTE:
ALL OUTPUT RELAYS:­Rated at :
16Amp R esistive 6Amp Inductive Com = Common Contact NO = Normally Open Contact
24V AC /DC
24V AC or DC Supply
CONTR OL SYS TEMS
A
USTRALIA
®
0V AC or DC Supply
MP405
(Voltage Free Contacts by other)
DIGI TA LINPUT S
+24V
0V
DI#+
DI#-
NOTE:
ALL DIGITAL INPUTS:­Ra ted at : 24V (AC or DC)
(Voltage Free Contacts by other)
TYPICAL DIGI TA LINPUTS
SENSOR
C+
C­S2
S1
Comms
+24V
0V
EARTH
DI
4
DI
1
DI
2
DI
3
+
-
Comms
Jumpers
A2
A1
A0
TERM
SHLD2
SHLD1
TH2
TH1
+
-
+
-
+
-
+
-
ComNO
DO 1
DO 2
DO 3 DO 4
0 V
24V
ComNO
ComNO
ComNO
DO 5
ComNO
E
DI
4
DI
1
DI
2
DI
3
+
-
Comms
Jumpers
A2
A1
A0
EOL
SHLD2
SHLD1
TH2
TH1
+
-
+
-
+
-
+
-

3-4.14 GENII MP405 REM Multipoint Module

The Innotech GENII MP405 REM Multipoint Module is a remote expansion device that has both input and output expansion capabilities. The GENII MP405 REM provides relay outputs for distributed control, digital inputs for status detection and Thermistor inputs for temperature measurement.
The GENII MP405 REM (Figure 3-18) is powered by 24VAC ±10% @ 50/60 Hz, or powered by 24VDC ±15%. Power Consumption is 4VA maximum.
Inputs:
• 10 kΩ thermistor temperature sensor.
• 4 x 24VAC or DC Isolated switched contact digital inputs.
Outputs:
• 5 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp Inductive.

Figure 3-18:  GENII MP405 REM Multipoint Module

The RS485 Comms connection block is in the lower-le section of the module (as illustrated above) and the End of Cable Jumper is next to it.
IMPORTANT
The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing addresses or adding or removing cabling from the terminals.
Page 64 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
I/O Terminal Connections for the GENII MP405 REM Multipoint Module are listed in Table 3-19 and Table 3 -20.

Table 3-19:  GENII MP405 REM Input Signal Conditions

Signal
Positive
Ter minal
Negative Ter minal
Thermistor TH1 TH2
Digital Input 1 DI 1+ DI 1-
Digital Input 2 DI 2+ DI 2-
Digital Input 3 DI 3+ DI 3-
Digital Input 4 DI 4+ DI 4-

Table 3-20:  GENII MP405 REM Output Signal Conditions

Normally Open (NO) Common (COM)
Ter minal Signal Terminal Signal
DO 1 NO Relay 1 DO 1 COM Relay 1
DO 2 NO Relay 2 DO 2 COM Relay 2
DO 3 NO Relay 3 DO 3 COM Relay 3
DO 4 NO Relay 4 DO 4 COM Relay 4
DO 5 NO Relay 5 DO 5 COM Relay 5
Page 65
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions

3-4.15 GENII MP414 REM Multipoint Module

The Innotech GENII MP414 REM Multipoint Module is a remote expansion device that has both input and output expansion capabilities. The GENII MP414 REM provides relay outputs for distributed control, digital inputs for status detection and Thermistor inputs for temperature measurement.
The GENII MP414 REM (Figure 3-19) is powered by 24VAC ±10% @ 50/60Hz, or powered by 24VDC ±15%. Power Consumption is 4 VA maximum.
Inputs:
• 10 kΩ thermistor temperature sensor.
• 4 x 24VAC or DC Isolated switched contact digital inputs.
Outputs:
• 4 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp Inductive.
• 1 x Analogue Output, 0-10VDC ±0.05V into > 2 kΩ load.
DIGI TA LINPUT S
(Voltage Free Contacts by other)
+24V
0V
NOTE:
ALL DIGITAL INPUTS:­Ra ted at : 24V (AC or DC)
DI#+
DI#-
Comms
TYPICAL DIGI TA LINPUTS
(Voltage Free Contacts by other)
+24V
0V
SENSOR
S1
C+
C­S2
-
-
+
+
-
-
+
+
-
-
+
+
-
-
+
+
TH2
TH2
TH1
TH1
SHLD1
SHLD1
SHLD2
SHLD2
A0
A0
A1
A1
A2
A2
EOL
TERM
+
+
-
-
DI
DI
DI
DI
DI
DI
DI
DI
4
4
3
3
2
2
1
1
Comms
Comms
Jumpers
Jumpers
MP414
®
USTRALIA A
CONTR OL SYS TEMS
-
1
AO
+
ComNO
DO 4
ComNO
DO 3
ComNO
DO 2
ComNO
DO 1
E
0 V
24V
NOTE:
ALL OUTPUT RELAYS:­Rated at :
24V AC /DC
16Amp R esistive 6Amp Inductive Com = Common Contact NO = Normally Open Contact ANALOGUE OUTPUT:­Rated at : 0-10VDC into >2 kLoa d
EARTH
0V AC or DC Supply 24V AC or DC Supply

Figure 3-19:  GENII MP414 REM Multipoint Module

The RS485 Comms connection block is in the lower-le section of the module (as illustrated above) and the End of Cable Jumper is next to it.
IMPORTANT
The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing addresses or adding or removing cabling from the terminals.
Page 66 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
I/O Terminal Connections for the GENII MP414 REM Multipoint Module are listed in Table 3-21 and Table 3 -22.

Table 3-21:  GENII MP414 REM Input Signal Conditions

Signal
Positive
Ter minal
Negative Ter minal
Thermistor TH1 TH2
Digital Input 1 DI 1+ DI 1-
Digital Input 2 DI 2+ DI 2-
Digital Input 3 DI 3+ DI 3-
Digital Input 4 DI 4+ DI 4-

Table 3-22:  GENII MP414 REM Output Signal Conditions

Normally Open (NO) Common (COM)
Ter minal Signal Terminal Signal
DO 1 NO Relay 1 DO 1 COM Relay 1
DO 2 NO Relay 2 DO 2 COM Relay 2
DO 3 NO Relay 3 DO 3 COM Relay 3
DO 4 NO Relay 4 DO 4 COM Relay 4
AO 1 AO 1+ AO 1 AO 1- & Screen
Page 67
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions

3-4.16 GENII MP423 REM Multipoint Module

The Innotech GENII MP423 REM Multipoint Module is a remote expansion device that has both input and output expansion capabilities. The GENII MP423 REM provides relay outputs for distributed control, digital inputs for status detection and Thermistor inputs for temperature measurement.
The GENII MP423 REM (Figure 3-20) is powered by 24VAC ±10% @ 50/60 Hz, or powered by 24VDC ±15%. Power Consumption is 4 VA maximum.
Inputs:
• 10 kΩ thermistor temperature sensor.
• 4 x 24VAC or DC Isolated switched contact digital inputs.
Outputs:
• 3 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp Inductive.
• 2 x Analogue Output, 0-10V DC ±0.05V into > 2 kΩ load.

Figure 3-20:  GENII MP423 REM Multipoint Module

The RS485 Comms connection block is in the lower-le section of the module (as illustrated above) and the End of Cable Jumper is next to it.
IMPORTANT
The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing addresses or adding or removing cabling from the terminals.
Page 68 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
I/O Terminal Connections for the GENII M423 REM Multipoint Module are listed in Table 3-2 3 and Table 3 -24 .

Table 3-23:  GENII MP423 REM Input Signal Conditions

Signal
Positive
Ter minal
Negative Ter minal
Thermistor TH1 TH2
Digital Input 1 DI 1+ DI 1-
Digital Input 2 DI 2+ DI 2-
Digital Input 3 DI 3+ DI 3-
Digital Input 4 DI 4+ DI 4-

Table 3-24:  GENII MP423 REM Output Signal Conditions

Normally Open (NO) Common (COM)
Ter minal Signal Terminal Signal
DO 1 NO Relay 1 DO 1 COM Relay 1
DO 2 NO Relay 2 DO 2 COM Relay 2
DO 3 NO Relay 3 DO 3 COM Relay 3
AO 1 AO 1+ AO 1 AO 1- & Screen
AO 2 AO 2+ AO 2 AO 2- & Screen
Page 69
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions

3-4.17 GENII MP432 REM Multipoint Module

The Innotech GENII MP432 REM Multipoint Module is a remote expansion device that has both input and output expansion capabilities. The GENII MP432 REM provides relay outputs for distributed control, digital inputs for status detection and Thermistor inputs for temperature measurement.
The GENII MP432 REM (Figure 3-21) is powered by 24VAC ±10% @ 50/60Hz, or powered by 24VDC ±15%. Power Consumption is 4 VA maximum.
Inputs:
• 10kΩ thermistor temperature sensor.
• 4 x 24VAC or DC Isolated switched contact digital inputs.
Outputs:
• 2 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp Inductive.
• 3 x Analogue Output, 0-10VDC ±0.05V into > 2 kΩ load.

Figure 3-21:  GENII MP432 REM Multipoint Module

The RS485 Comms connection block is in the lower-le section of the module (as illustrated above) and the End of Cable Jumper is next to it.
IMPORTANT
The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing addresses or adding or removing cabling from the terminals.
Page 70 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
I/O Terminal Connections for the GENII M432 REM Multipoint Module are listed in Table 3-2 5 and Table 3 -26 .

Table 3-25:  GENII MP432 REM Input Signal Conditions

Signal
Positive
Ter minal
Negative Ter minal
Thermistor TH1 TH2
Digital Input 1 DI 1+ DI 1-
Digital Input 2 DI 2+ DI 2-
Digital Input 3 DI 3+ DI 3-
Digital Input 4 DI 4+ DI 4-

Table 3-26:  GENII MP432 REM Output Signal Conditions

Normally Open (NO) Common (COM)
Ter minal Signal Terminal Signal
DO 1 NO Relay 1 DO 1 COM Relay 1
DO 2 NO Relay 2 DO 2 COM Relay 2
AO 1 AO 1+ AO 1 AO 1- & Screen
AO 2 AO 2+ AO 2 AO 2- & Screen
AO 3 AO 3+ AO 3 AO 3- & Screen
Page 71
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions

3-4.18 GENII WMI Wireless Module Interface

The Innotech GENII WMI Wireless Module Interface is a remote expansion for the Genesis II Direct Digital Controller or MPCII Mid Points Controller. The GENII WMI provides an interface to the SENRx series of wireless temperature sensors.
The GENII WMI (Figure 3-22) is powered by 24VAC ±10% @ 50/60Hz. Power Consumption is 4 VA maximum.
There are no inputs or outputs on a GENII WMI. It is designed to receive the input data from any SENRx modules located up to 20 metres away (depending on obstructions).

Figure 3-22:  GENII WMI Wireless Module Interface

The RS485 Comms connection block is in the upper right section of the module and the End of Cable Jumper is next to it (Figure 3-22).
The Cable run between the Genesis II Direct Digital Controller and GENII WMI, or MPCII Mid Points Controller and GENII WMI, should not exceed 600 metres. The Comms wiring requires cable especially suited for RS485. Other shielded cable is not suitable and may cause spasmodic Comms failures.
The GENII WMI should be mounted within a 20 metre radius (depending on obstructions) of all SENRx modules from which it will be receiving data (Figure 3-23). The location should be dry, clean and free of excess vibration.
GENII WMI modules operate within the 2.4-2.5 GHz worldwide unlicensed Industrial-Scientific-Medical (ISM) frequency band.
There are four jumpers located in a row on the GENII WMI, labelled F0, F1, F2 and F3. These select the frequency channel to use within the 2.4-2.5 GHz range. Typically, these jumpers need only be changed if multiple GENII WMIs are used, or in areas with poor reception or strong interference.
IMPORTANT
• The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing addresses or adding or removing cabling from the terminals.
• The frequency jumpers on the GENII WMI must exactly match the frequency jumpers on any SENRx modules to be communicated with.
Page 72 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions

3-4.19 SENRx Series Wireless Temperature Sensors

The Innotech SENRx Series Wireless Temperature Sensors are remote expansion devices for the Genesis II range of digital controllers. There are four unique models in the SENRx series:
• SENR1: Temperature Sensor, Low Battery Indicator.
• SENR2: Temperature Sensor, Low Battery Indicator, Set Point Adjustment.
• SENR5: Temperature Sensor, Low Battery Indicator, Aer Hours Button.
• SENR5: Temperature Sensor, Low Battery Indicator, Set Point Adjustment, Aer Hours Button.
The SENRx Series Wireless Temperature Sensors (Figure 3-23) are powered by 3.6VDC ½AA Lithium Battery. Battery life is 12 months minimum.
There are no inputs or outputs on a SENRx Series Wireless Temperature Sensor. They are designed to send the output data to a GENII WMI Wireless Module Interface located up to 20 m away (depending on obstructions).

Figure 3-23:  SENRx Wireless Temperature Sensor (Back View)

Page 73
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
Genesis II Installation Instructions
SENRx modules should be mounted within a 20 m radius (depending on obstructions) of the GENII WMI Wireless Module Interface in a dry and clean location free of excess vibration.
To remove the battery from a SENRx module, simply insert a flat screwdriver underneath the battery between the two clips and lever the battery out (Figure 3-23). When re-inserting the battery, press and hold the “RESET” button. Release the “RESET” button aer the battery is located back in the clips.
There are two sets of four jumpers located on the back of the SENRx module (Figure 3-23). The set of jumpers closest to the battery are labelled A0, A1, A2 and A3. These set the network address of the SENRx module in the same manner as GENII REM products.
Directions for setting the address are shown in the wiring diagram generated by the GEN2Config soware. The jumpers located on the far right of the SENRx module are labelled F0, F1, F2 and F3. These select the frequency channel to use within the 2.4-2.5 GHz range. Typically, these jumpers need only be changed if multiple Wireless Module Interfaces are used or in areas with poor reception or strong interference. The frequency jumpers on the SENRx module must exactly match the frequency jumpers on the GENII WMI module to be communicated with.
IMPORTANT
If any jumpers on a module need to be changed, the unit must be powered down before the jumpers are altered. This can be achieved by removing the battery as described above. Antistatic precautions should be taken when changing jumpers or removing the battery.
Page 74 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Direct Digital Controller
INSTALLATION INSTRUCTIONS
Chapter 4 ­Commissioning
Genesis II Installation Instructions

4-1 Introduction

The commissioning phase begins upon completion of the mechanical and electrical installation of the system and is the phase in which the user makes the system ready for operation. The commissioning process consists of performing the following procedures, which are explained elsewhere in this section:
• Inspect the Installation
• Check Input and Output Wiring
• Install Analogue Input Signal Conditioners (AISCs)
• Set Jumpers (such as address jumpers and end-of-cable termination jumpers)
• Apply Partial Power
• Load Soware and Configure the Controller(s)
• Initial Tests
• Final System Checkout
CAUTION
To prevent injury to personnel and damage to equipment, all electrical power must be o before starting the commissioning process this includes power to the Genesis units and power to input and output circuits and equipment. When working with live power ensure that all electrical safety standards for work on live electrical systems meet local regulatory requirements. Do not apply power to any unit or circuit until instructed to do so by procedures in this section.

4-1.1 Inspect the Installation

Referring to Chapters 2, 3 and 5, inspect the entire system for correct mechanical, electrical and network installation. Correct any discrepancies noted. Inspection should include the factors listed in the following paragraphs, as a minimum.
4-1.1.1 Mechanical Inspection
Ensure that all units and enclosures are free of debris such as dust, metal chips, moisture, etc. That may have been deposited during installation. Clean as necessary.
• Ensure all covers are properly installed. Exceptions are the CS REM Control Station Module and MZS REM Multi Zone Station Module, which should be covered by plastic at this time (see 3-4.9 to
3-4.13).
• Ensure all units and DIN-rails are solidly mounted.
• Check cable ducts. Ensure they are placed so that cables entering and leaving the ducts do not make overly tight bends.
• Make sure all units are located to provide safe access for operation and maintenance.
• Make sure all units are located where they are not subject to temperature extremes beyond the 0 ­40°C range.
• Make sure all units are located as far as practical from high current or high voltage cables or sources of RF emissions.
• Ensure if wireless sensors are used that a GEN II WMI wireless module interface (WMI) is connected to and no further than 500 metres from the Genesis II Direct Digital Controller or MPCII Mid Points Controller and that each wireless sensor is no further than 20 metres from the WMI.
• Do not install the WMI inside a fully enclosed metal switch board.
Page 76 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
4-1.1.2 Electrical Inspection
• Make sure all sources of electrical power, including power to ancillary items are o.
• Check all input and output connections against the computer-generated wiring diagram supplied for your installation.
• Ensure all connections are in accordance with the wiring diagram and that connections are solidly made.
• Ensure all enclosures are solidly earthed.
• Check all input and output cabling; ensure cabling requirements of Section 3 - Electrical Installation are met.
• Make sure all cables, especially analogue input cables, are routed clear of high current, high voltage or high speed switching current cables and other sources of interference.
• If using Remote Expansion Modules (REMs) make sure the cable run between does not exceed 600 metres in length.
• Inspect all cables running external to the enclosure. Ensure they are free from potential mechanical damage, such as impacts and chafing.
Cabling plays an important role in the installation of Genesis II Systems. The following general cabling guidelines should be observed:
• In all cases, use electromagnetic-shielded cable for sensor wiring.
• When necessary to protect cabling from physical damage, both shielding and physical protection may be provided by running the cable in a metal conduit. Alternatively, use steel wire armoured (SWA) cable, which also contains an electromagnetic shield.
• Avoid running cables in the vicinity of high voltage power cables or cables carrying switching voltages/currents. This especially applies to sensor signal cables.
• Interconnecting cables must have multi-strand conductors with a cross-sectional area of 1mm2 for each conductor.
• The earth cable to Genesis II enclosures must be 2.5mm2.
• For analogue inputs to the controller, a 16 conductor (0.5mm2) shielded cable is required.
Table 3 -1 provides assistance in determining the cabling requirements for various installation
configurations. It shows the dimensions, wire gauge designations and resistance values per unit length for common wire sizes. Use Table 3-1 to determine specific cabling requirements for your installation.

4-1.2 Check Input and Output Wiring

The purpose of checking the input and output wiring is two-fold. Firstly, the wiring is checked to verify that it is connected properly, thus ensuring proper operation of the system. Secondly, the wiring is also checked to ensure the absence of any external voltages that could damage a Genesis unit. The following paragraphs contain instructions for checking inputs and outputs.
4-1.2.1 Checking Power Inputs
Power inputs must be checked to ensure that the applied voltage is of the proper level and, in the case of DC power inputs, of the correct polarity. Table 4-1 shows the input voltage specifications for the various types of units. Most units operate on 24VAC 10%, 50/60 Hz.
Controllers can be provided with an optional 24VDC ±10% power capability. Procedures for checking the 24VAC and 24VDC units are similar, except that: for 24VAC units, AC Neutral must be at earth potential and connected to Terminal 2. For 24VDC units, Terminal 1 must be positive and Terminal 2 negative.
Page 77
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions

Table 4-1:  Genesis II System Power Inputs

Unit
24VAC ±10% 24VDC ±10 %
Operating Voltage
GENII DDC Digital Controller Yes Yes MPCII Mid Points Controller Yes Yes GENII AI REM Analogue Input Module Yes No GENII AO REM Analogue Output Module Yes No GENII DI REM Dry Contact Digital Input Module Yes No GENII DO REM Relay Output Module Yes No GENII IDI REM Opto-Isolated Digital Input Module Yes No GENII PI REM Pulse Input Module Yes No GENII MZS REM Multi Zone Station Module Yes No GENII MZSAH REM Zone Control Station Module
A/H
Yes No
GENII CS REM Control Station Module Yes No GENII CSAH REM Control Station A/H Module Yes No GENII CSFAH REM Control Station with 3 Speed
Fan, A/H Module
Yes No
GENII MP4xxx REM Multipoint Module Yes See Note GENII WMI Wireless Module Interface Yes No SENRx Wireless Temperature Sensor REM Yes No
NOTE
Optional 24VDC supply is available but tolerance is ±15%.
Page 78 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
Check 24VAC and 24VDC inputs as follows:
1. Ensure power to the unit is turned o.
2. For 24VAC units, ensure the AC Neutral is connected to Terminal 2 and the resistance between
Terminal 2 and the enclosure’s main earth link is 3.0 Ohms, or less.
3. Disconnect the power lead from Terminal 1 (Figure 4-1).
4. Connect a digital volt-ohm-meter red (+) test lead to the disconnected power lead and the black
(-) test lead to Terminal 2.
5. Set the voltmeter to the proper range to measure 24 Volts.
6. Turn on the power.
7. The voltmeter should read 24 Volts ±10%. For 24VDC units, make sure the power lead going to
Terminal 1 is positive and Terminal 2 is negative.
8. Ensure measurement is in DC and not AC voltage.
9. Turn o the power.
10. Disconnect the digital voltmeter and reconnect the wire to Terminal 1.
11. Repeat Steps 1 through 9 for the other 24-Volt units. For units not included in this manual, refer
to the appropriate product datasheet.
240VAC POWER
POINT

Figure 4-1:  Checking Power Input

24VAC
TRANSFORMER
EARTH
DIGITAL
VOLT-OHM
METER
24V
V
V DC
1
2
DIGITAL CONTROLLER
AC
Page 79
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
4-1.2.2 Checking Digital Input Wiring
Digital input wiring to controllers and digital input expansion modules should be checked to ensure the following conditions:
• The digital signal source voltage is within the correct range. Refer to Table 4-2 for digital input signal source specifications for the various digital input units.
• The signal polarity is correct for digital input signals with DC sources
• Wiring to the signal actuator (switch, relay contacts, contact points, etc.) is correct
4-1.2.3 - External-Source Digital Inputs contains procedures for checking most Genesis REMs except for the GENII DI REM Dry Contact Digital Input Module. Whereas most Genesis units use external source digital input signals, the DI REM signals are dry contact (voltage free) inputs. Procedures for checking voltage-free digital inputs are contained in 4-1.2.4 - Internal-Source Digital Inputs.

Table 4-2:  Digital Input Signal Voltages

Unit Signal Voltage
GENII DDC Digital Controller 24VAC/24VDC ±15% MPCII Mid Point Controller 24VAC/12VDC ±15% GENII PI REM Pulse Input Module 12 - 24VDC GENII IDI REM Opto-Isolated Digital Input Module 12 – 24VAC/VDC GENII DI REM Dry Contact Digital Input Module Not Applicable GENII MP REM Multipoint Module 24VAC/24VDC ±15%
4-1.2.3 External-Source Digital Inputs
The following procedures for checking digital input wiring are specifically for the Genesis II Digital Controller. However, they also apply to the other units listed in Table 4 -2 except for the GENII DI REM.
Refer to the Electrical Installation chapter for digital input terminal numbers for the various Genesis units.
Figure 4-2 is a schematic representation of a typical Digital Controller installation containing AC- and
DC-powered digital inputs and how the wiring can be checked using a digital voltmeter. Use Figure
4-2 for reference when performing the following procedures:
1. Ensure power to the Digital Controller is turned o.
2. Set the digital voltmeter range to read at least 25 Volts.
3. Connect the voltmeter to the first digital input channel (Terminals 4 and 5 for the Genesis II Digital Controller). Observe polarity, ensuring the red (+) test lead is connected to the positive terminal (4) and the black (-) test lead is connected to the negative terminal (5).
4. Ensure the voltmeter reads Zero Volts. If the reading is other than Zero Volts it indicates the input is driven by Normally Closed contacts or the input is not wired correctly.
Page 80 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
CAUTION
Avoid risk of electrical shock observe all local electrical safety requirements when performing the nest step.
5. With the voltmeter still connected, manually close the input contacts. If it is not possible to close the circuit manually, connect a jumper wire across the contacts at the switching device, as shown in Figure 4-2.
6. Ensure the voltmeter indicates the proper signal voltage as listed in Table 4-2.
7. Ensure that the voltmeter indicates the correct polarity. The unit will not operate properly if the signal polarity is incorrect.
8. Release the manually closed contacts or remove the temporary jumper from the switch contacts.
9. Repeat Steps 3 through 7 for the remaining digital input channels.
1
2
JUMPER WIRE
3
24V
V
V DC
DC
SOURCE
89
4
56
7
10
DIGITAL CONTROLLER
AC
11 121314
SOURCE
15 16
17
AC
18
24V
AC
V
V DC
+
CHECKING DC SOURCE CHECKING AC SOURCE

Figure 4-2:  Checking Digital Input Wiring

-
Page 81
+
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
-
Genesis II Installation Instructions
4-1.2.4 Internal-Source Digital Inputs
The GENII DI REM provides eight dry contact (voltage-free) inputs to sense contact closure from field equipment. The eight digital inputs are connected to terminals A through H (see Figure 4-3). Contacts I and J are signal common terminals. The REM provides 5VDC between each input and common. This voltage is shorted to common when the switch is closed. Check the digital input wiring as follows:
1. Tag and disconnect the RS485 Comms cable(s) from the RS485 Comms Connector at the upper­right corner of the REM. The cable shields may be le connected if desired.
2. Apply 24VAC operating power to the GENII DI REM. Power o other units.
3. Set the digital voltmeter range to read at least 5.0VDC.
4. Connect the voltmeter between the first digital input channel (Terminal A) and the associated switch common (Terminal I or J). Observe polarity, ensuring the red (+) test lead is connected to Terminal A and the black (-) test lead is connected to the switch common terminal.
5. Observe the voltmeter. It should indicate 5VDC with the input switch open.
CAUTION
Avoid risk of electrical shock observe all local electrical safety requirements when performing the nest step.
6. Manually close the input switch. If that is not practical, connect a short jumper wire across the contacts.
7. Observe the voltmeter. It should indicate 0VDC with the input switch closed.
8. Release the manually-closed contacts. If a jumper wire was used in Step 6, remove the jumper wire.
9. Repeat Steps 4 through 8 for the remaining digital input channels.
10. Remove operating power from the REM.
11. Reconnect the RS485 cable that was disconnected in Step 1.
CAUTION
• Digital outputs are controlled by relays within the associated Genesis unit. These relays are connected to the external circuits that can contain up to 24VAC.
• Procedures in this manual require checking these circuits with power applied. To avoid death or serious injury by electrical shock, use extreme caution when working with energised circuits and follow precautions in this manual.
• Checks are to be performed only by qualified, licensed electricians who are familiar with local safety procedures. Under no circumstances should anyone other than a qualified electrician perform these checks.
Page 82 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
GENII DI REM
C
A B
D E FGH I J
5V
V
V
AC
DC
SWITCH OPEN
+
-
GENII DI REM
C
A B
D E FGH I J
0V
AC
V
V DC
SWITCH CLOSED
+

Figure 4-3:  Checking Dry Contact Inputs

4-1.2.5 Checking Digital Output Wiring
Digital outputs of the various units are interfaced through relays, each having single-pole changeover contacts.
-
The following units contain only Normally Open (NO) digital output contacts in each digital output channel:
• GENII DDC Digital Controller
• MPCII Mid Points Controller
• GENII DO REM Relay Output Module
• GENII MP REM Multipoint Module
Relay contacts in all units with digital outputs are rated at 24VAC, 2 A with the exception of the MP REM Multipoint Modules which are rated at 240 AC, 16 A. For this reason, the presence of lethal voltages at the relay contacts should be anticipated. Even though good wiring practice is to use lower voltage pilot relays when controlling higher voltage equipment, this practice can not be guaranteed and it is possible that the relay contacts will carry dangerous voltages. For this reason, it is important that only a qualified electrician, familiar with safety practices, check the digital output wiring.
Page 83
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
Before checking the digital output circuits, it is important to ensure that there are no short circuits in the external wiring which could cause the contact current to exceed the rated amount. Current in excess of this through the relay contacts will result in permanent damage to the unit.
Following is a general description of the process for safely checking digital output circuits. Specific procedures for checking the wiring are provided toward the end of this paragraph (see Figure 4-4).
With power applied to the digital output circuits, but not to the Genesis unit, the output circuits are checked for operation. Devices connected between the NO and C terminals should be de-energised. If the operational status cannot be determined by observation (indicator lamp on/o, fan running/ not running, etc.) a voltmeter is placed across the device to determine whether or not it is energised.
The output circuits are then checked for the opposite condition. For circuits using the NO contacts, a jumper wire is temporarily connected between the NO and C terminals; the associated device is checked to make sure it is energised.
IMPORTANT
Before performing the following procedures ensure there are no short circuits in the digital output wiring which could cause the relay contact current to exceed the maximum amperes, excess relay contact current will cause permanent and irreparable damage to the unit.
The following are procedures for checking digital output wiring; refer to the Electrical Installation chapter for output terminal numbers for the applicable Genesis units:
1. Ensure there is no operating power applied to the Genesis unit to be checked nor is power applied to any of the digital output circuits.
2. Start at the first device connected to the NO contacts. If the device cannot be checked for operation by simple observation, connect a digital voltmeter across it. Set the voltmeter range for the expected voltage.
3. Apply operating power to the output device.
4. Determine that the device is de-energised, either by direct observation of the device itself or by checking that the volt-ohm-meter indicates an open circuit.
5. Remove operating power from the output device.
6. Temporarily connect a jumper wire between to NO and C contacts. Ensure that the jumper wire is of adequate size to temporarily carry the load.
7. Apply operating power to the output device.
8. Determine that the device is energised, either by direct observation of the device itself or by checking that the voltmeter indicates full operating voltage.
9. Remove operating power from the output device.
10. Remove the jumper wire connected in Step 6.
11. Repeat Step 2 through Step 10 for the remaining output devices connected to the NO contacts.
Page 84 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
240V
+
RELAY
ON
43
NO NOC
44 45
NO CNOC
RELAY
OFF
47 48
46
GENESIS II
442
DIGITAL
CONTROLLER
TERMINALS
0V
AC
AC
V
DC
V
EXTERNAL
DEVICE
-
V
DC
V
+
-
0V

Figure 4-4:  Checking Digital Output Wiring

4-1.2.6 Checking Analogue Input Wiring
The analogue input wiring for the following Genesis units should be checked as part of the commissioning process:
24V
AC/DC
0V 24V
AC/DC
• GENII DDC Digital Controller
• MPCII Mid Points Controller
• GENII AI REM
Checking analogue input wiring requires special consideration due to the wide variety of analogue input devices that may be used in the system. Some input devices function as signal voltage sources; some devices function in the loop current mode and others provide resistive inputs to the Genesis unit. For this reason there is no single procedure that can be used on all analogue inputs.
Procedures presented in this manual are based on identifying the type of Analogue Input Signal Conditioner (AISC) assigned to each analogue input channel. Since each analogue input device requires a specific AISC type to match the signal to the Genesis unit, the type of AISC assigned to an analogue input channel indicates the type of input signal and the range. The various types of AISCs are listed in Table 4 -3 along with the type of analogue signal and the range. Reference to the paragraph containing the instructions for checking the input wiring is also provided in Table 4 -3.
Page 85
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
NOTE
Current value is determined by measuring voltage across a resistor in series.

Table 4-3:  Analogue Input Checks

AISC Model Input Type
Parameter Measured
Expected Value
Reference Paragraph
DO5 Digital Voltage 0 or 5VDC 4-1.2.7
D33 Digital Voltage 0 or 10VDC 4-1.2.7
IO5 0 - 5mA Passive Current (see Note) 0 - 5mA 4-1.2.8
I20 4 - 20mA Passive Current (see Note) 4 - 20mA 4-1.2.8
P20 Loop Powered Inspect Wiring N/A 4-1.2.8
TD1 Current Loop Current (see Note) 0- 250µA 4-1.2.8
TD2 0 - 500µA Current (see Note) 0 - 500µA 4-1.2.8
TH1 Thermistor Resistance 0 - 1kΩ 4-1.2.9
TH2 Thermistor Resistance 0 - 2kΩ 4-1.2.9
TH3 Thermistor Resistance 0 - 3.8kΩ 4-1.2.9
TH4 Thermistor Resistance 0 - 8.2kΩ 4-1.2.9
TH5 Thermistor Resistance 0 - 16.2kΩ 4-1.2.9
TH6 Thermistor Resistance 0 - 33.3kΩ 4-1.2.9
TH7 Thermistor Resistance 0 - 68.1kΩ 4-1.2.9
TH8 Thermistor Resistance 0 - 121kΩ 4-1.2.9
TH9 Thermistor Resistance 0 - 221kΩ 4-1.2.9
V05 Voltage Voltage 0 - 5VDC 4-1.2.7
V10 Voltage Voltage 0 - 10VDC 4-1.2.7
Page 86 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
For example, an analogue input channel that has Model TH2 AISC assigned receives its input from a thermistor device; the input circuit is checked by measuring its resistance, which should be between 0 and 2k. Procedures for checking the resistance are contained in section 4-1.2.9. The type of AISC for each analogue input channel is determined when the system configuration is established by the Genesis Configuration Soware prior to delivery. The configuration soware automatically generates a Materials List and a Wiring Diagram, which are delivered with the system. The Materials List shows the number of AISCs by type but does not show which analogue input channels they are assigned to. The Wiring Diagram (Figure 4-5) identifies the AISC type for each analogue input channel.
When an Analogue Input Module REM is used, the output of the REM is connected to one of the controller’s analogue input channels. When checking the analogue connection between the GEN II AI REM and a controller, ensure the cable is wired in accordance with the Electrical Installation chapter and is free of potential physical damage. Ensure also that the cable is routed outside of the cable ducts.
01 02
SCR
2120
SS
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
+
-------
+
+
+
+
3231302928272625242322
+
33
+
363534
+
37
-
38 39 40 41
12V PC
+
+
- -
REM COMMS
Sensor #1 Innotech Temperture
Sensor #2 Innotech Temperture
Sensor #3 Innotech Temperture
Sensor #4 Innotech Temperture
Sensor #5 Innotech Temperture
Sensor #6 Innotech Temperture
Switchboard Temp Thermistor, Philips 10k
AI LEM #1, Terminal 3 NC
ANALOGUE
INPUT
SIGNAL
VAV #3
SSR #3
VAV #4
SSR #4
Siren
66
03 04 05 06 07 08 09 10
1 32 4 9 121110
78
5 76 8
6867
8079
69
81
8382
727170
84
7473
13 161514
8685
75
87
76
88
77
89
RS-232
VAV #1 SSR #1 VAV #2 SSR #2
11 12
VAV #5 SSR #5
13
14
15 16
ANALOGUE OUTPUTS
Global Ne t
+
91 92 93 9490
RS-485
-
C
+
-
(Wiring diagram - bottom board)
ANALOGUE INPUTS
GENESIS II DDCINNOTECH
SCREEN MUS T GO HERE !
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TH7: Thermistor
AIM: <external>
CONDITIONERS
+A1-
Sensor #7
Innotech T emperatur e
Sensor #8
Innotech T emperatur e
Sensor #9
Innotech T emperatur e
Sensor #10
Innotech T emperatur e
Sensor #1 1
Innotech T emperatur e
Sensor #1 1
Innotech T emperatur e
A B C D F E
G H I J
LK
SCREEN
+A2- +A3- +A4- +A5- +A6-
SCREEN
AI1
AI2
AI4AI3 AI5 AI6
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
Address jumpers
A0 A1 A2 A3
Remote Expansion Module #1 (AI)

Figure 4-5:  Analogue Input Signal Conditioner (AISC) Locations

Page 87
24 V AC SUPPL Y
21
0 V AC SUPPL Y
3
COMM EARTH
RX
TX
SHLD1
+
-
SHLD2
CIRCUIT FROM DDC OR REM
SHLD1
+
-
SHLD2
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
COMMS CONNECTIONS
CIRCUIT FROM DDC OR REM
RS485(+ ) RS485(-) RS485(+ ) RS485(-)
CIRCUIT TO OTHER REMS
RS485(+ ) RS485(-)
Genesis II Installation Instructions
4-1.2.7 Voltage Checks
IMPORTANT
The wiring checks in the following paragraphs are performed with AISCs removed. The units are delivered with their AISCs removed. Do not install the AISCs until all wiring checks are completed.
This paragraph contains procedures for checking analogue inputs associated with AISC Models D05, D33, V05 and V10. Note from Table 4-3 that inputs associated with Digital AISC D05 will be either Zero Volts OR 5VDC but not between the two extremes. The same is true for AISC D33 except that the voltage range is Zero OR 10VDC.
Note also that inputs associated with AISC Models V05 (0 – 5VDC) and V10 (0 – 10VDC) may be at any value within the ranges noted.
IMPORTANT
Ensure that no AC voltage is present on either terminal. AC voltage at the input terminals can cause damage to the unit also the unit will not operate properly if the analogue input signal polarity is incorrect.
Procedures for performing voltage checks are:
1. Ensure all AISCs have been removed and no power is applied to the Genesis II Digital Controller.
2. Connect a digital voltmeter to the input terminals; set the voltmeter to indicate VAC. Ensure there is no AC voltage present on either terminal. If AC voltage is measured, check the analogue input wiring for faults/errors.
3. Set the digital voltmeter to indicate VDC. Set the range for the expected voltage value shown in
Table 4 -3.
4. Connect the voltmeter across the analogue input terminals observing polarity. If necessary, reduce the voltmeter range to obtain an accurate reading.
5. Ensure the measured voltage is within the expected range and of the correct polarity. If not, check the analogue input wiring for faults/errors
6. Repeat Steps 2 through 5 for the remaining inputs associated with the AISC models noted above.
4-1.2.8 Current Checks
This paragraph contains procedures for checking analogue inputs associated with AISC Models I05, I20, P20, TD1 and TD2.
CAUTION
Procedures in this paragraph require connecting a 500 Ohm resistor across the analogue input terminals and measuring the resultant voltage. Although 500 Ohms is suitable in most cases, some applications may require a higher value of resistance to avoid damage to circuits. Always ensure that a suitable resistor is used.
Analogue inputs associated with the I05, I20, TD1 and TD2 AISCs are checked by measuring voltage across a resistance connected in series with the current source. A 500 Ohm resistance is normally suitable for this procedure.
Page 88 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
The matrix below lists the expected voltages to be measured across a 500 Ohm resistance for the various values of input current. For other resistor values use Ohm’s Law (V=IR) to determine the voltage.
INPUT VOLTAGE AISC CURRENT ACROSS 500 ohms I05 0 – 5 mA 0 – 2.5VDC I20 4 – 20 mA 2 – 10VDC TD1 0 – 250 A 0 – 0.125VDC TD2 0 – 500 A 0 – 0.25VDC
Inputs associated with the P20 AISC are 4 – 20 mA loop-powered inputs. These inputs cannot be conveniently checked in the same manner as the other current inputs without applying power to the Genesis II Digital Controller before it is safe to do so. Loop powered input wiring is checked by using a voltmeter to ascertain that there is no stray voltage present at the input terminals. The input wiring is then visually inspected for proper connection.
The following are procedures for performing current checks:
1. Ensure all AISCs have been removed and no power is applied to the Genesis II Digital Controller.
2. For analogue inputs associated with P20 AISCs go to Step 9.
3. Temporarily connect a 500-Ohm (or suitable value) resistor across the terminals of the first current input channel to be checked.
4. Set a digital voltmeter to indicate VDC. Set the range for the expected voltage value shown in the matrix above.
5. Connect the voltmeter across the analogue input terminals observing polarity. If necessary, reduce the voltmeter range to obtain an accurate reading.
6. Ensure the measured voltage is within the expected range and of the correct polarity. If not, check the analogue input wiring for faults/errors.
7. Remove the temporary resistor connected in Step 3. above. Repeat Steps 2 through 7 for the remaining inputs associated with the AISC models noted above.
8. To check inputs for the P20 type AISC, connect a digital voltmeter across the input terminals. Do not connect a resistor across the terminals. Reduce the voltmeter range to the lowest setting practical. If voltage is present at the input terminals, it indicates a fault or improper wiring of the input circuit.
9. Visually inspect the wiring of the P20 type analogue input. Ensure that all wiring conforms to the associated wiring diagram. Ensure correct polarity is maintained throughout.
4-1.2.9 Resistance Checks
This paragraph contains procedures for checking analogue inputs associated with AISC Models TH1 through TH9. Checking these inputs consists of performing a simple continuity/resistance check.
Procedures for performing voltage checks are:
1. Ensure all AISCs have been removed and no power is applied to the Genesis II Digital Controller.
2. Set a digital volt-ohm-meter to indicate Ohms. Set the ohmmeter range to the resistance value shown in Table 4-3.
3. Connect the volt-ohm-meter across the analogue input terminals.
4. Ensure the measured resistance is within the expected range. If it is not, check the analogue input wiring for faults/errors
5. Repeat Steps 2 through 4 for the remaining inputs associated with AISC Models TH1 through TH9.
Page 89
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
4-1.2.10 Checking Analogue Output Wiring
Analogue output wiring is checked for the following reasons:
• To ensure the analogue output terminals are free of any external voltage
• To check continuity through the external analogue circuit
• To ensure the resistance of the external analogue circuit is suicient to avoid overloading the
analogue output circuit.
The following procedures apply to analogue outputs of the GENII DDC Digital Controller, MPCII Mid Points Controller, GENII AO REM Analogue Output Module and the GENII MP REM Multipoint Module. Refer to the Electrical Installation chapter for analogue output terminal numbers for the applicable Genesis units.
Procedures for performing Analogue Output wiring checks are:
1. Ensure the operating power to the unit is o.
2. Turn on the excitation and operating power for the digital inputs, digital outputs and, as applicable, the analogue inputs. The reason for this step is to detect the presence of voltages at the analogue output terminals that may be caused by “sneak” circuits or wiring errors.
3. At the analogue output terminal, disconnect the active signal wire for the first analogue output.
4. Connect a digital voltmeter between the disconnected signal wire and the common terminal.
5. The voltmeter should indicate Zero Volts. Set the voltmeter range as low as possible to ensure there is no voltage present.
6. Set the volt-ohm-meter to the Ohms range. The volt-ohm-meter should indicate a minimum resistance of 2,000 or 5,000 Ohms (See note below). A reading of Infinite Ohms indicates an open circuit condition that should be corrected.
7. Disconnect the meter and reconnect the signal wire disconnected in Step 3.
8. Repeat Step 3 through Step 7 for the remaining analogue outputs.
9. Turn o any power applied in Step 2.
NOTE
The analogue output circuit resistance for the Genesis II Digital Controller and the MPCII Mid Points Controller should be at least 2,000 Ohms. The circuit resistance for the GENII AO REM should be at least 5,000 Ohms.

4-1.3 Install AISCs

Analogue Input Signal Conditioners (also referred to as Input Straps in some other Innotech documents) are insert plugs used to configure the Genesis II unit’s input to match the analogue input device. All units having analogue inputs require an AISC for each input channel; these units are:
• Genesis II Digital Controller
• MPCII Mid Points Controller
• GENII AI REM Analogue Input Module
With all power o, and using the computer-generated wiring diagram (Figure 4-5) as a guide, insert each AISC module into its assigned slot. The modules are keyed to prevent them from being plugged­in backwards. When all AISCs are installed, double-check the installation. The system will not operate correctly with an AISC plugged into the wrong slot.
Page 90 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions

4-1.4 Set Jumper Plugs

Various jumper plugs throughout the system must be set properly before power can be applied to the system.
There are 4 categories of jumper plug: Address Plugs set the address of each Remote Expansion Module
• Analogue Output plugs are used to select either Variable or Heat Valve Mode of operation for
analogue outputs. Refer to section 3-3.1.5 for a definition of Variable and Heat Valve Modes.
• End-of-Cable jumpers provide the proper termination impedance for the RS485 Comms Cable. It is
installed in the last unit of the cable run
• Frequency Plugs set the frequency of each wireless Remote Expansion Module or Interface
The computer-generated wiring diagram (Figure 4-5) shows the locations and required settings for each address jumper and analogue output jumper.
Table 4 -4 is provided as an aid for properly setting the various jumper plugs. The table lists the required jumper setting, the types of jumper plugs and the reference paragraph containing instructions for setting them for each Genesis II unit.

Table 4-4:  Units Requiring Jumper Settings

Ter minal Address End of Cable Analogue Output Frequency
See Paragraph: 4-1.4.1 4-1.4.2 4-1.4.3 4-1.4.4 GENII DDC Digital
Controller MPCII Mid Points
Controller GENII AI REM Yes Yes
GENII AO REM Yes Yes Yes
GENII DI REM Yes Yes
GENII DO REM Yes Yes
GENII IDI REM Yes Yes
GENII PI REM Yes Yes
GENII MZS REM Yes Yes
GENII MZSAH REM Yes Yes
GENII CS REM Yes Yes
GENII CSAH REM Yes Yes
GENII CSFCAH REM Yes Yes
GENII MP REM Yes
GENII MP405 REM Yes
Yes
Yes
GENII MP414 REM Yes
GENII MP423 REM Yes
GENII MP432 REM Yes
GENII WMI Yes
SENRx Yes Yes
Page 91
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
PORTION OF COMPUTER-GENERATED WIRING
4-1.4.1 Address Jumpers
Locations and settings of address jumpers are shown on the computer-generated wiring diagram provided with the system hardware. Figure 4-6 shows a portion of a typical computer-generated wiring diagram. Address jumper connectors are A0, A1, A2 and A3. Open jumper connectors are shown in grey on the wiring diagram. Connectors shown in black require a jumper to be installed. Address jumpers must be properly set on all REMs except for those which are wireless in order for the
system to operate correctly.
DIAGRAM SHOWING ANALOGUE INPUT MODULE
<not used>
A1
Sensor #7
Sensor #8
AI 5 AI6 AI7 AI8 AI9
+
-----
+
DCBA
TD1: 0-250 µAmps
TD1: 0-250 µAmps
Address jumpers
A0
A2
A1
1 2 3
Sensor #9
Sensor #10
Sensor #1 1
+
+
+
JIHGFE
TD1: 0-250 µAmps
TD1: 0-250 µA mps
TD1: 0-250 µAmps
TD1: 0-250 µAmps
JUMPER
OPEN

Figure 4-6:  Address Jumpers, Typical Settings

Page 92 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
4-1.4.2 End of Cable Jumpers
Although the locations of End-of-Cable jumpers are not shown on the computer-generated wiring diagram, they are easily located close to the unit’s RS485 Comms connector. Figure 4-7 shows the location of the End-of-Cable jumper for a GENII AI REM unit. Jumpers for other units are similarly placed. The rule for installing an End-of-Cable jumper is:
• If only one cable is connected into an RS485 Comms connector, a jumper must be installed in that
unit.
• If two cables are connected to the same RS485 Comms connector, the jumper plug must be le
open.
All units along the RS485 Comms network should be carefully checked to ensure that jumpers are installed only in the last unit in the network.
END-OF-CABLE
JUMPER
3
12
GEN II AI REM

Figure 4-7:  End of Jumper, Typical Location

RS485 COMMS
CONNECTIONS
R
Page 93
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
4-1.4.3 Analogue Output Jumpers
An analogue output jumper plug arrangement is provided for each analogue output channel. The three-pin jumper sockets will accept a shorting plug between the centre pin and either of the outside pins. Depending upon which pair of pins the jumper is connected to, the analogue output is configured for either the Variable Mode or the Heat Valve Mode. For inactive analogue output channels, the jumper is not installed in either position. In such cases the jumper plug can be conveniently stored in the unit by inserting only one end of the plug into the socket.
The computer-generated wiring diagram shows the location and jumper position for each analogue output in the system. Figure 4-8 shows a portion of a typical wiring diagram centred on a Genesis II Digital Controller’s analogue output jumpers. The figure shows how the jumpers are configured for the Variable and Heat Valve Modes of operation.
JUMPER
VARIABLE
MODE
VAV #3
SSR #3
VAV #4
SSR #4
Siren
01 02 03 04 05 06 07
65
5 76 8 13 161514
+
-
C
+
-
66
6867 69
7170 72
7473 75 76
Global Net
RS-485
1 32 4
9 121110
VAV #1 SSR #1 VAV #2 SSR #2
08 09
10
11 12
VAV #5 SSR #5
13
14
15 16
ANALOGUE OUTPUTS
90 9189
+
93 9492
-
G
G
N
JUMPER
HEAT
VALVE
MODE
Alternative
Plug Style
RS-485
+
-
G
77 78
8079 81
8382 84
8685 87 88
90 91 92 9389
RS-232
GEINNOTECH
(Wiring diagram -
PORTION OF COMPUTER-GENERATED
WIRING DIAGRAM SHOWING GENESIS II
DIGITAL CONTROLLER

Figure 4-8:  Setting Analogue Output Jumpers

Page 94 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
4-1.4.4 Frequency Jumpers
The GENII WMI Wireless Module Interface provides an interface to the SENRx series of wireless temperature sensors. There are four user selectable frequency jumpers for configuration. To enable correct communication over a wireless frequency, the settings of these jumpers must be matched.
Locations and settings of frequency jumpers a fare shown on the datasheets for each of these products. Figure 4-9 shows a portion of a the GENII WMI datasheet, and Figure 4-10 shows an image of the SENRx series of wireless temperature sensors.
Frequency jumper connectors are F0, F1, F2 and F3. Frequency jumpers must be set properly on all wireless REMs.

Figure 4-9:  Setting Frequency Jumpers on the GENII WMI

Figure 4-10:  Setting Frequency Jumpers on the SENRx Module

Page 95
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
4-1.5 Load Soware and Configure the Controller(s)
The Innotech configuration soware program was prepared for your Genesis System at the factory before delivery of the system. The soware contains all the data for internally configuring the controller(s) to perform the specific functions for which it was intended. Until the controller is configured, it can not accept input signals or produce outputs.
To configure the controller(s), a Windows-based PC and the applicable version of the Innotech Gen2Config program are required. A soware disk is provided with the Genesis hardware at delivery. The disk contains a program called Gen2Works, which is a collection of several Innotech programs, including Gen2Config. The other soware programs supplied in Gen2Works are for the purpose of enhancing operation and de-bugging of the system. But it is the Gen2Config soware that is required for commissioning the system.
4-1.5.1 - Loading Gen2Works contains instructions for loading the Gen2Works soware into your PC.
4-1.5.2 - Configuring a Controller explains how to configure the controller using the Gen2Config
program.
NOTE
• The instructions in the next two paragraphs are generalised procedures based on the assumption the operator is familiar with operation of a PC in a Windows environment.
• Loading the Gen2Works soware requires entry of an Activation Key. The Activation Key is a password provided by Innotech to permit access to the Gen2Works soware. If an Activation Key has not been provided, contact Innotech Control Systems at the contact details shown on the last page of this manual. Note that the Activation Key is only eective for one session. If Setup is to be run at a later date, a new Activation Key is required.
4-1.5.1 Loading Gen2Works
To load Gen2Works into the PC:
1. Insert the Gen2Works CD 1 into the appropriate CD or DVD drive.
2. Windows auto run should start the installation process or open the Windows explorer dialog in the location of the CD, from here select setup. If however the auto run does not open the CD go to step 3 otherwise skip it.
3. Click on Run and type “<CD Drive Letter>:\setup” (where the drive letter is which ever letter corresponds to your PC’s CD drive e.g. “D”) in the Run dialogue box, then click on OK.
4. Gen2Works will display a Product Activation dialogue box with a block requesting entry of the Activation Key.
5. Enter the Activation Key, then click OK.
6. The Gen2Works soware will begin to load. Follow instructions on the screen to complete the installation process.
Page 96 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
4-1.5.2 Configuring a Controller
The following is the procedure for configuring a controller:
1. Turn o the electrical power to the controller.
2. Connect to the controller via an RS232 cable, RJ45 or over a connected Innotech network.
3. Turn on the computer and allow it to boot-up. Turn on the controller’s operating power.
4. Using standard Windows procedures, open the Gen2Config folder.
5. Click on the Gen2Config icon to open the Gen2Config program. The Gen2Config screen is displayed.
6. At the upper-le corner of the Gen2Config window, select File and then Open. The Open File dialog box is displayed showing the configuration files that can be selected. Configuration files are indicated by the file extension: “.g4c”.
7. Select the configuration file for the controller to be configured then click OK. The window for the selected configuration is displayed. The window will show the block diagram representing the controller’s configuration.
8. At the top of the window select Communicate and then Transfer to DDC. The Gen2Config soware begins to automatically transfer the configuration data to the controller by way of iComm (Communications server used by Innotech soware to communicate with Innotech digital controllers)
9. Follow instructions given on the screen.
10. It is safe to exit the Gen2Config program at this point.
11. If the next commissioning step: Initial Tests is to be performed soon, leave the controller and the PC turned on. Otherwise, remove operating power from the controller and PC if an appreciable delay is expected before performing initial tests.
NOTE
The following procedures are limited to the steps necessary to configure the controller. For more detailed information on the operation of the Gen2Con soware refer to the Innotech Genesis II Digital Controller User Manual.

4-1.6 Initial Tests

Initial tests of the system involve the use of the Gen2Mon soware to perform a thorough check of the system. The basic approach to performing these tests is to use the soware to apply simulated inputs to the controller and to check the eect on the output circuits. The following paragraphs describe the Gen2Mon soware and the checks to be performed as part of initial tests.
4-1.6.1 Gen2Mon Soware
Initial tests of the system are simplified by use of the Gen2Mon monitoring and debugging utility soware. This soware allows the operator to trace the flow of control and to view the various values within a configuration residing in a controller. With Gen2Mon, each controller can be monitored one at a time in real time. Therefore, what appears on the screen is what is actually happening inside the controller. Gen2Mon must have a constant connection to the controller to be able to operate. This connection is either through a controller network, the RS232 serial port or the RJ45 ethernet port.
The Gen2Mon allows the operator to monitor any output value from any block in the configuration. Also, Gen2Mon has a Simulation Mode that allows the operator to control the values of any, or all, of the controller’s input blocks. In this manner, the action of a sensor or switch can be simulated to determine how the rest of the configuration reacts to the input.
Detailed procedures for operation of the Gen2Mon Soware is beyond the scope of this technical manual. Refer to the Innotech Genesis II Digital Controller User Manual.
Page 97
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
4-1.6.2 Performing Initial Tests
Because of the Genesis II System’s flexibility, the various configurations can be vastly dierent from each other. For this reason, it is not practical to provide detailed procedural instructions for performing initial tests that apply to all configurations. However, this paragraph describes the general methodology for performing the initial tests.
Initial tests using the Gen2Mon Soware are divided into three separate phases; these tests should be performed on each controller in turn:
• In the first phase of testing, power is removed from all output circuits and the Gen2Mon soware
is used to monitor the states and input/output values of the various configuration blocks using variable input stimuli. This phase serves two purposes: It checks the configuration of the controller and it helps to familiarise the operator with the operation of the system.
• In the second phase of testing, the controller’s primary output circuits, such as motor controllers
and relay circuits are energised but the output machinery (fans, pumps, compressors, etc.) are de-energised. In this phase, the controller inputs are stimulated just enough to cause the output circuits to operate or change state. This phase checks the operation of the output control circuits without operating the plant machinery.
• In the third phase, the primary output control circuits as well as the plant machinery are
energised. In this phase the controller inputs are carefully stimulated just enough to briefly test the operation of the plant machinery. This phase should involve the minimum of controller input stimulation required to operate the machinery.
4-1.6.3 First Phase Testing
Perform the first phase of initial tests of the system as follows:
1. Turn o all electrical power to the Genesis II System.
2. Connect the controller to the PC by finding it on a connected network, connecting an RS232 cable between the controller’s RS232 connector and the computer’s serial port or by connecting an RJ45 cable between the controller's RJ45 connector and the computer's.
3. Turn on the computer and allow it to boot-up. Turn on the controller’s operating power. All output circuits should be de-energised at this time.
4. Using standard Windows procedures, open the Gen2Mon folder.
5. Click on the Gen2Mon icon to open the Gen2Mon program. The Gen2Mon screen is displayed.
6. In the Simulation Mode, carefully adjust the controller’s input parameters, such as temperature, pressure, switch position, etc. Adjust the values within normal and practical operating limits and just enough to verify that a realistic change in output is produced.
7. When all inputs and outputs have been checked, return the input parameters to their original settings. The first phase is completed.
CAUTION
Operation of the GEN2MON soware in the simulation mode presents a serious risk to the system. In the simulation mode, the operator is actually forcing values into the controller, therefore, it is possible to overcome any of the natural safeguards which may be in place to protect the plant. When in simulation mode, exercise great care in adjusting values. The soware is a powerful facility and should not be used carelessly.
Page 98 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Genesis II Installation Instructions
4-1.6.4 Second Phase Testing
Perform the second phase of initial tests of the system as follows:
1. Turn on operating power to the primary output circuits such as pilot relays, motor controllers and heat valves.
2. Ensure that operating power to plant machinery (compressors, fans, etc.) is turned o.
3. In the Simulation Mode, observing the CAUTION noted above, carefully adjust the controller’s input parameters. Adjust the values within normal and practical operating limits and just enough to verify operation of the primary output circuits.
4. When all outputs have been checked for proper operation, return the input parameters to their original settings. The second phase is completed.
4-1.6.5 Third Phase Testing
Perform the third phase of initial tests of the system as follows:
1. Turn on operating power to the plant machinery in accordance with the manufacturers’ instruction manuals.
2. In the Simulation Mode, observing the CAUTION noted previously, carefully adjust the controller’s input parameters. Adjust the values within normal and practical operating limits and just enough to verify control and operation of the plant machinery.
3. When items of plant machinery have been checked for proper operation, return the input parameters to their original settings. The third phase is completed.
4. Exit the Gen2Mon program.
5. Turn o operating power to the entire Genesis System and the PC.
6. Disconnect the RS232 cable between the PC and the controller, if RS232 was not used to connect to the device skip this step.
7. Repeat procedures in Paragraphs 4-1.6.3 through 4-1.6.5 for the other controllers.

4-1.7 Final System Check

Final check of the system involves checking the operation of the system, performing any necessary adjustments and verifying that the system functions properly under normal operating conditions. The following are the procedures for performing final system checkout:
1. Apply normal operating power to the entire system in accordance with the applicable manufacturers instruction manuals.
2. Allow adequate time for the various units to stabilise. Unless specified otherwise in the applicable instruction manuals, allow approximately one hour for the circuits to stabilise.
3. Carefully check each unit of the system for proper operation. If necessary, the Gen2Mon soware may be used in the Monitor Mode (NOT in the Simulation Mode) to check proper operation within the controller.
4. Check manufacturers’ recommended adjustments and settings to ensure all units are set-up for optimum function.
5. At the controller enter final operational preferences such as schedules, passwords, flash watches, etc.
6. The system is ready for operation.
Page 99
© Mass Electronics Pty Ltd 2010Chapter 4 – Commissioning
Genesis II Installation Instructions
This page has been le intentionally blank.
Page 100 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
Loading...