Inkbird ITC-1000F User Manual

ITC-1000F Temperature Controller
Manual
Thank you very much for selecting INKBIRD products. Read the instruction manual carefully before use, for right application and maintenance.
Safety Precautions
occasionally result in injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic shaving or filings from
installation to enter the product. Doing so may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive gas. Otherwise,
injury from explosion may occasionally occur.
Never disassemble, modify or repair the product or touch any of the internal parts.
Electric Shock, fire, or malfunction may occasionally occur.
If the output relays are used past their life expectancy, contact fusing or burning may
occasionally occur. Always consider the application conditions and use the output relays within their rated load and electrical life expectancy. The life expectancy of output relays varies considerably with the output load and switch conditions.
Main Function:
Fahrenheit and Celsius Display Can Be Choose  More User-friendly Operating  Switch Between Cooling and Heating Modes  Control the Temperature by Setting the Temperature Set Value and the Difference
Value
Temperature Calibrating  Refrigerating control output delay protection  Alarm When Temperature Exceeds the Limit or When Sensor Error
Mounting dimension:
Front Panel Size: 75(L)*34.5(W)mm Mounting Size: 71(L)*29(W)mm Product Size75(L)*34.5(W)*85(D)mm Sensor Length: 2m (include the probe)
http://waterheatertimer.org/Add-another-thermostat-to-gas-or-electric-water-heater.html#PID
Technical Parameter:
Temperature Measuring Range: -50210 oF / -50 oC-99 oC Resolution: 0.1 oF / 0.1 oC Accuracy: ±1 oF-50 oF -160 oF/ ±1 oC-50 oC -70 oC Power Supply: 110VAC 50Hz/60Hz Power Consumption: <3W Sensor: NTC Sensor Relay Contact Capacity: Cooling (10A/250VAC)/ Heating (10A/250VAC); Ambient Temperature: 0 oC-60 oC Storage Temperature: -30 oC-75 oC Relative Humidity: 20-85% (No Condensate)
Panel Instruction:
Key Operating instruction:
1. Check Parameter: In normal working status, press “ key once, it will display the setting temperature
value; press “ ” key once, it will display the difference value;
2. Parameter Setting: In normal working status, keep pressing for more than 3s to enter set mode, set
indicator lamp is on, screen displays the first menu code “TS”. Press “ ” key or “ ” key to move up or down the menu item and display the menu
code. Press “ key to enter the parameter setting of current menu, the parameter value
starts to flash.
Press “ ” key or “ ” key to adjust the parameter value of current menu.
After the set, press “ ” key to exit the parameter setting of current menu,
the parameter value stops to flash. User can set the other functions as above steps.
In any status, press “ ” key to save the parameter modified value, and return to the
normal temperature value. If no operating within 10s, it will exit the menu automatically and return to normal temperature display status, and does not save the parameter of this modification.
Operating instruction:
In normal working status, press and hold “ key for more than 3s to turn off the
controller; in Power-off Status, press and hold “ ” key for more than 1s to turn on the controller.
In normal working status, screen displays the current measuring value, the controller switch modes between heating and cooling automatically. If the measuring temperature ≥ temperature set value + difference set value, the controller starts refrigerating, the cool indicator lamp lights on, and the refrigerating relay is connected. When cool indicator lamp flashes, indicating that the refrigerating device is under compressor delay protecting status. If the measuring temperature ≤ temperature set value, the cool indicator lamp turns off, and the refrigerating relay is disconnected. If the measuring temperature ≤ temperature set value - difference set value, the controller starts heating, the heat indicator lamp lights on, and the heating relay is connected.
If the measuring temperature ≥ temperature set value, the heat indicator lamp turns off,
and the heating relay is disconnected.
Menu Instruction:
1. When the set temperature is degrees Celsius (FCC)
Code
Function
Set range
Default
Note
TS
Temperature Set Value
-5099.9 oC
10.0 oC
DS
Difference Set Value
0.315 oC
1.0 oC
PT
Compressor Delay
010 minutes
3munites
CA
Temperature Calibration Value
-15 oC15 oC
0 oC
CF
Fahrenheit or Celsius Setting
C
2. When the set temperature is degrees Fahrenheit (FCF)
Code
Function
Set range
Default
Note
TS
Temperature Set Value
-50210 oF
50 oF
Min. Unit 1 oF
DS
Difference Set Value
130 oF
3 oF PT
Compressor Delay
010 minutes
3 minutes
CA
Temperature Calibration Value
-1515 oF
0 oF CF
Fahrenheit or Celsius Setting
F
Note:
When CF value change, all the set values restore to default value.
Error Description
Sensor Error Alarm: When the temperature sensor circuit is short circuit or open circuit, the controller starts sensor error mode and closes all running status, the buzzer alarm sounds, screen displays ER. Press any keys can cancel buzzer alarm, the system returns to the normal working status after error is cleared. Over-temperature Alarm: When the measuring temperature exceeds the temperature measuring range, the controller starts over-temperature error alarm mode and closes all running status, the buzzer alarm sounds, screen displays HL. Press any keys can cancel buzzer alarm, the system returns to the normal working status after the temperature returns to measuring range.
Wiring Diagram
INKBIRD TECH. CO. LTD.
www.ink-bird.com
Email: cs@ink-bird.com