Analogue fire alarm control panel
Extinguishant system control panel
Installation and programming manual
Installation and programming manual
Copyright
The information contained in this document is the sole property of INIM Electronics s.r.l. No part may be
copied without written authorization from INIM Electronics s.r.l.
All rights reserved.
European directive compliance
This Control panel has been designed and developed to the highest standards of quality and performance
implemented by INIM Electronics s.r.l.
This control panel must be installed in accordance with the instructions described in this manual and in
compliance with the laws in force.
All control panels from the SmartLight series are EN54-2, EN54-4 and EN12094-1 compliant.
All control panels from the SmartLight series, and all accessory items and special functions have IMQ
Sistemi di Sicurezza certification, unless otherwise stated.
Note:The control panels described in this manual have been designed and developed to the highest
standards of quality, reliability and performance. All product components are capable to application
requirements and able to operate in compliance with the related technical specifications when the
temperature external to their casing complies with Category 3k5 of EN60721-3-3:1995.
Danger:The GAS control function is not provided for in the aforesaid standard and therefore cannot
be considered EN54-2 compliant.
Danger:In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance with EN54-
2, all the manual alarm buttons and fire detectors employed in the system must be
associated with fire detection and alarm functions.
1.1Application and use
The SmartLight analogue-addressable fire alarm panel manages a single loop that accommodates different
types of fire-security devices (detectors, input modules, outputs, callpoints, fire bells, sirens, etc.). The
maximum loop wire length is 2000 m.
The SmartLight provides supervised outputs which ensure full device functionality. The panel identifies and
signals alarm, pre-alarm, fault, early warning, bypassed zone, test and monitoring conditions.
The system status is indicated on the display and on the system status LEDs. The SmartLight panel
supports up to 4 repeater panels (accessory items) which replicate system data and allow building
occupants with Level 2 authorization to silence and reset the system. The panel also accepts an
extinguishant module (accessory item) that allows it to manage a gas extinguishant system.
The self-addressing feature and reduced-complexity point programming allow fast and easy installation.
D
F
E
C
A
B
Figure 1 - Example of a typical SmartLight installation
Overview5
Installation and programming manual
[A] Loop
All the peripheral devices of the system must be connected in parallel to the loop circuit (2 pole STP). The
loop is a closed electrical circuit in which a wide variety of alarm devices can be accommodated. Opening or
closing the circuit at any point will generate a fault signal. The loop circuit communication path starts on
the Loop-Out terminals and ends on the Loop-In terminals. The panel controls and communicates with the
loop devices via digital protocol. The loop utilizes the same two poles for the power supply to the system
devices and the two-way communication channel. The loop accommodates:
1. Detectors: A smoke detector is an active fire protection device that detects smoke or flames and issues an alarm
thereby alerting building occupants to the danger of fire. Detectors can be:
- Optical smoke detectors which look for the presence of visible by-products of combustion in the detection chamber
(Tyndall effect).
- Optical/Heat detectors which operate as per optical smoke detectors but also sense for increase in the environment
temperature. The combination of both sensing methods (smoke and heat) provides faster detection and reduces
the false alarm rate.
- Heat detectors: sense for an increase in the temperature in the protected environment. There are two types of
heat detector: Fixed temperature — that signal alarm when the temperature exceeds the predefined threshold;
and Rate-of-rise — that as well as monitoring the predefined fixed temperature also respond to rapid increase in
temperature.
- Ionization smoke detectors: feature a harmless radioactive source within a dual detection chamber. They operate
by sensing for a change in electrical conductivity across the detection chamber.
- CO detectors: sense the levels of carbon monoxide given off by all carbon-based materials in the smouldering
stages of a fire (often combined with heat detection sensor).
2. Input Module: a device which monitors the status of another device (callpoint, detector, etc.) and sends the
respective information to the panel. The Input module allows the loop to accommodate any type of device.
3. Output Module: provides a supervised ancillary output. The cause of activation can be defined during the system
configuration phase. Allows you to interface all types of devices to the loop (e.g. bells, signaling devices, fire door
magnets, etc.).
4. Callpoint: a clearly indicated fire button with instructions for use in the event of fire. Usually located near the
entrance/exit of the protected building. These push-button alarm-trigger devices allow building occupants to
activate system alarms.
Note:Sounders and flashers can also be connected directly to the control panel outputs [E].
For the list of the devices the loop accommodates, and for details regarding their wiring and operating
principles, refer to Appendix A - Enea series devices, Appendix B - Argus Devices and Appendix C - Apollodevices.
The loop circuit configuration (as required by the local Fire code in force) is a fault-tolerant circuit which, in
the event of short-circuit or loop interruption, allows the panel to continue to communicate and drive the
elements on either side of the interruption.
Isolator
In order to ensure a fault-tolerant loop circuit that is Fire code compliant, isolators must be installed in
series with the loop circuit. Isolators modules detect short-circuit conditions and consequently interrupt the
loop circuit. If a short-circuit occurs, the two isolators adjacent to the shorted section will open and split the
loop in such way as to allow the panel to drive the elements on either side of the interruption. No more
than 32 detectors/devices should be installed between two isolator modules.
Note:Many detectors/devices have built-in isolators and therefore do not require isolator modules. Refer to
Appendix A - Enea series devices, Appendix B - Argus Devices and Appendix C - Apollo devices for
further details.
This optional system enhancement tool (equipped with keypad, LEDs, fast buttons and display) replicates
all the system data. The panel supports 4 repeaters which can be connected to RS485 BUS (maximum
cable length 1000m from panel). Repeaters are usually located near the entrance/exit of the protected
building, in order to allow users to view the system status without going too far inside the building.
The SmartLevel is the ideal power source for all devices located in the area protected by the detection
system. Its internal board satisfies all EN54 requirements and provides complete supervision of the power
station. The device can be connected to the control panel loop via an input/output module (not included),
installed inside the box, or by means of the RS485 BUS, thus allowing the complete supervision of the
power station and control of the 3 outputs.
[D] Gas extinguishant system (optional system enhancement feature)
The panel can house and manage a gas extinguishant module (SmartLetLooseONE, optional). The Gas
extinguishant module is compliant with EN 12094-1.
[E] Sounderflashers
These audible/visual signaling devices connect to the control panel outputs and activate when specific
conditions occurs The cause of activation (alarm, pre-alarm, early warning, etc.) can be defined during the
system configuration phase.
[F] SmartLink telephone dialer
INIM's SmartLink/G and SmartLink/GP telephone dialers monitor the analogue landline and, in the event of
landline problems (line cutting, etc.) divert incoming and outgoing calls to the GSM network. The
SmartlinkP model operates solely over the PSTN line (landline).
1.2Other parts of the system
Point: synonym and definition of a loop device (detector, etc.).
Zone: a group of points (detectors, etc.). The points can be assigned to the zones during the configuration
phase. Consult your local Fire code for the rules regulating automatic fire detection installations and for full
details regarding zone limitations.
Power Supply (Figure 22 - Connecting the Mains): a module, connected to the mains 230 Vac, that
provides a stabilized voltage @ 24 V (27.6 V) to the system and the charge source to the batteries. The
EN54-4 compliant power-supply module is housed below the motherboard. The mains voltage (230 Vac) is
the primary power source of the system. Refer also to paragraph 6.10.
Batteries: the secondary power source of the system. The panel houses two lead batteries @ 12V 7Ah
(connected in series). The system monitors the battery status (efficiency and charge). In the event of
inefficient or low battery conditions, the system will signal battery fault. If primary (230 Vac) power failure
occurs, the batteries will take over, however, they will shutdown automatically if the blackout persists. The
automatic battery shutdown feature prevents irreparable damage to the batteries. Refer also to paragraph
6.11.
Thermal probe: an accessory tool, to be connected to the panel and attached to the battery pack. This
device monitors the temperature of the external battery pack and regulates the battery charge accordingly.
Refer also to paragraph 6.12.
RS485 BUS: 4 wire BUS for the repeater connections. Four pole twisted-shielded cable must be used for
all connections. Refer also to paragraph 6.5 - Connecting the RS485 BUS.
Timer: a logical entity (the panel provides 8 timers) for automatic time-management of preset intervals (2
intervals per day) on preset days of the week and specific dates. The timers can be used in equations and/
or to manage predefined operations.
Equation: a group of logical conditions defined by the installer. An equation comprises a series of
operators (AND, OR, +, etc.) and a series of operands (Points, Zones, Timers, etc.). An equation can be
associated with an output that will activate when the equation is satisfied.
Holidays: a list of days defined during the system configuration phase that can be associated with a timer.
Early Warning: a signal generated by detectors with the early-warning feature (to be defined during the
system configuration phase). The detector senses for a value (smoke level, heat level,temperature, etc.)
which exceeds its early warning threshold (each detectors can be set separately). This signal indicates that
the person/s responsible for the safety of the building and its occupants should verify the alarm or check
the functionality of the detector concerned.
Overview7
Installation and programming manual
1.3In order to validate the IMQ-SECURITY SYSTEMS certification, and in
compliance with EN54-2 regulations:
All the manual alarm buttons and fire detectors employed in the system must be associated with fire
detection and alarm functions.
1.4The SmartLight fire alarm panel models
The available models are:
• SmartLight/G SmartLight Gold model manages 240 loop devices and 30 zones.
• SmartLight/S Smartlight Silver model manages 64 loop devices and 16 zones.
8Overview
Installation and programming manual
Chapter 2
General information
2.1Documentation supplied
• Installation and programming manual (this manual)
• User's Manual
The Installation manual is inside the device package. For further copies of the Installation manual contact
the offices at INIM Electronics s.r.l. and quote the order number printed in Appendix D - Order Codes.
2.2Manual details
• Title: SmartLight Installation and Programming Manual
• Version: 3.0
• Month and year: 2012
• Code: DCMIINE0SLIGHT
• Addressees: installers, technical assistance
2.3Firmware information
• SmartLight firmware version: 2.0.x
• Extinguishant module firmware version: 1.0.x
2.4Operator qualifications - access levels
The SmartLight is EN-54 compliant. There are four access levels:
Level 1:All building occupants.
All building occupants can view the system status (active events) and events log; silence the
panel beeper and, under pre-alarm conditions, override pre-alarm status and activate an
instant alarm.
Level 2:Authorized operators — person/s responsible for the safety of the building and its occupants.
Authorized operators (keyswitch and PIN users) can silence the outputs; reset the panel;
activate the 'Investigation' delay; disable zones, points and outputs; change the operating
mode (Day/Night) and activate the 'Evacuation' alarm.
Level 3:Authorized technicians appointed by the Installer company.
Such technicians possess the tools required for the removal of the control panel frontplate. And,
are allowed to insert the jumper which enables the control panel programming phase (via
control panel or PC), in order to access the programming and maintenance functions. The
events cannot be accessed during the programming phase.
Level 4:Authorized technicians, appointed by the Manufacturer (INIM Electronics s.r.l.).
The manufacturer company technicians can, by means of special tools, repair or replace the
control panel components.
Note:This manual is for Authorized installer company technicians (Level 3). However, it also provides some
installation information related to level 1 and level 2.
2.5Intellectual property rights
The information contained in this document is private property. All rights reserved.
No part of this document may be copied or reproduced unless expressly authorized in writing by INIM
Electronics, in particular the parts regarding the device specified inparagraph 2.13 - Device identifier INIM
Electronics s.r.l. shall not be responsible for damage arising from improper application or use.
General information9
Installation and programming manual
2.6Disclaimer
INIM Electronics s.r.l. shall not be responsible for damage arising from improper application or use.
This control panel should be handled by qualified personnel only. Installation must be carried out strictly in
accordance with the instructions described in this manual, and in compliance with the local fire code in
force.
2.7Recommendations
INIM Electronics recommends that the entire system be tested on a regular basis (refer to paragraph 2.8).
2.8Testing the system
This system has been designed to the highest standards of quality and performance. The system may fail
to function as intended due to the failure of a component. Most problems that prevent a fire control system
from operating as intended can be found by regular testing and maintenance (refer to Chapter 16 -Maintenance).
Testing should include all detectors, signaling devices and any other operational devices that are part of the
system.
2.9Note to the installer
In order to provide adequate protection and instructions for proper use, you (the installer) must be familiar
with the operating procedure of this device. As the only individual in contact with system users, it is your
responsibility to instruct them on how to use this system properly and to bring to their attention that every
fire is different in the amount of smoke and rate of burning. Therefore, smoke and heat detectors may not
provide timely warning of fires caused by violent explosions, escaping gas or improper storage of
inflammable materials.
Regardless of its capabilities, a fire alarm system is not a substitute for the necessary precautions building
occupants must take to prevent or minimize the harmful effects of fire.
2.10Technical support
Our professional engineers are readily available to assist you. Call our phone number and you will be
connected right away to a person who will answer all your questions and provide you with full technical
support.
2.11Conventions
2.11.1 Glossary and terminology
Panel; device; system: refer to the devices defined in paragraph 2.13.
Left, right, behind, above, below: refer to the directions as seen by the operator in front of the mounted
device.
Communicator (telephone, SMS, digital): synonym of dialer.
STP: Shielded twisted pair cable.
Qualified personnel: those persons whose training, expertise and knowledge of the laws and bylaws
regarding service conditions and the prevention of accidents, are able to identify and avoid all possible
situations of danger.
Select: click on and select a specific item (from drop-down menu, options box, graphic object, etc.).
Press: click on a video button, or press a key on the panel keypad.
10General information
Installation and programming manual
2.11.2 Graphic conventions
Following are the graphic conventions used in the text. For a description of the graphic conventions relating
to the interface, refer to paragraph 5.1 - SmartLight panel frontplate.
ConventionsExampleDescription
Text in ItalicsRefer to paragraph 4.1Text in italics: indicates the title of a chapter, section,
paragraph, table or figure in this manual or other published
reference.
<text> #<CustomerCode>Variable data.
[lowercase letter]
or [number]
BUTTONEsc, RESETComputer or control panel keys.
[A] or [1]Representation of a part of the system or video object.
Note:The detached notes contain important information about the text.
Attention:The attention prompts indicate that total or partial disregard of the procedure could damage
the connected devices.
Danger:The danger warnings indicate that total or partial disregard of the procedure could injure the
operator or persons in the vicinity.
2.12Menu paths
Example:
From panel: <key>, Configuration, Loop, Ok, Loop Parameters
Via software application: Control panel, Loop
Access to specific functions can be achieved by using the panel keys or PC video objects and the respective
path.
Note:This manual describes the recommended programming flow. This manual describes the loop
configuration procedure from the panel, as indicated in the example.
Attention:For most part this manual describes programming from the control panel.
General information11
2.13Device identifier
Installation and programming manual
Figure 2 - Overview
Control and signaling panel with integrated
0051
09
0051 - CPD - 0222
power-source devices.
SmartLIGHT/S
/G
Alimentazione /
Power / Alimentacion
Consumo /
Consumption / Consumo
MADE IN ITALY
0051-CPD-0223
0051
0051 - CPD - 0223
Control and signaling panel with integrated
power-source devices.
SmartLIGHT/G
Isolamento /
Isolation / Aislamiento
Approvato /
Approved / Aprobado
09
02/2012
230V~ -15% + 10%
50/60 Hz
0.5 A
Classe
I
EN54-2, EN54-4
LBDTIN4ASLIGHTG
Isolation: Class I
Available options:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
Isolation: Class I
Available options:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
Figure 3 - CE Approval
2.14Warranty
INIM Electronics s.r.l. warrants the original purchaser that for a period of 24 months from the date of final
acceptance, the product shall be free of defects in materials and workmanship. The warranty applies only
to defects in parts and workmanship relating to normal use. It does not cover:
Improper use or negligence
Damage caused by fire, flood, wind or lightning
Vandalism
Fair wear and tear
INIM Electronics s.r.l. shall, at its option, repair or replace any defective products. Improper use, that is,
use for purposes other than those mentioned
in this manual
system, will void the warranty. For the full details and conditions regarding the warranty, refer to the
purchase order.
which is the cause of fault or damage to the
12General information
Installation and programming manual
2.15Safety laws
The aim of the instructions in this section is to ensure that the device is installed and handled properly. This
chapter contains vital information. The installer should be familiar with this section and bring each item to
the attention of the system users.
2.15.1 Compliancy
The design and manufacture of the SmartLight panel conform with EN 54-2 Fire detection and signaling
systems - Control and signaling panels.
The design and manufacture of the power supply comply with EN 54-2 Fire detection and signaling systems
- Power supply devices.
SmartLight has been developed and designed in compliance with EN 12094-1 Fire-fighting Systems Components of fire-extinguishant systems - Part 1: Requirements and testing methods for automatic
electrical command and fire-extinction or delay management devices.
2.15.2 Managing electronic devices
The normal motions of any person may generate electrostatic potential of thousands of volts. Discharge of
this current through semiconductor devices during handling may cause serious damage which although
may not be immediately evident may reduce the reliability of the circuits.
If located in their housings, the electronic circuits of INIM Electronics products are highly immune to
electrostatic discharge. Do not expose the circuits to damage by removing the modules unnecessarily from
their housings.
• When removing or handling the boards, hold the board edges only.
• Do not touch the electronic components, the printed circuits or the metal parts of the connectors.
• Do not hand the module to another person without first ensuring that you both have the same
electrostatic potential. This can be achieved by simply shaking hands.
• Place the board on an anti-static surface or a conductor surface with the same potential.
Further information regarding procedures relating to safety when working with electronic devices can be
found in Directive IEC 60147-0F.
2.15.3 Setting up the system
In order to provide adequate protection and instructions for proper use, security professionals (Installers and
maintenance technicians) must be familiar with the operating procedure of this device.
Please read the instructions carefully before installing and/or servicing the system.
Before first power-up, be sure that the earth connection has been completed properly on the respective
terminal.
2
The recommended minimum wire cross section for the earth connection is 2.5 mm
otherwise stated in accessory documentation.
, that is, unless
2.15.4 Replacement and disposal of used devices
Replacement-
connections of the new devices in compliance with the instructions printed on the respective leaflets.
Contact your local municipal offices for information regarding the disposal of used electronic devices.
When replacing used devices, disconnect the devices concerned then complete the
Disposal- Do not burn used electronic devices, or allow them to pollute the environment (countryside,
rivers, etc.). Electronic devices must be disposed of in a safe environment-friendly way. In order to avoid
short-circuits, take all the necessary precautions when removing used batteries. Contact your local
municipal offices for information regarding the disposal of batteries.
General information13
Installation and programming manual
Chapter 3
Device management
3.1Product handling and storage
This device is safely packed inside a cardboard box, however, care must be taken to avoid accidental
damage during handling. Cartons/boxes should be placed in such a way as to avoid knocks and falls, and
special care must be taken to protect the devices from extreme heat and/or cold.
3.2Environmental conditions
Temperature limits:
-10° / +55°C for transport and storage
-5° / +40°C operating temperature
3.3Unpacking the device
Take due care when unpacking the product, and dispose of all waste packaging in accordance with the local
method of disposal.
The cardboard box contains the SmartLoop control panel (cabinet in metal).
Note:The two lead batteries @ 12 V - 7 Ah are not included. Be sure you have the batteries on hand before
starting.
When you remove the four screws and metal-frontplate, you will find:
• The SmartLight motherboard mounted on a plastic support that bridges the two sides of the metal box.
• Power supply module located under the plastic support. The power supply module is connected to the
SmartLight motherboard.
• A plastic bag containing:
- Battery connection wires
- Resistors and EOL diodes for supervised circuits
- Key for access level 2
The following accessory items must be ordered separately (see Appendix D - Order Codes):
• [A] SmartLetLoose/ONE - extinguishant module
• [B] SmartLetUSee/LCD-Lite - repeater panel
• [C] ProbeTH - thermal probe battery-charge optimizer which operates in accordance with the battery
temperature.
• [D] SmartLevel - power-supply station
14Device management
Installation and programming manual
A
B
C
Figure 4 - Accessory devices
D
Device management15
Technical description
4.1Internal devices
Installation and programming manual
Chapter 4
S
D
C
R
Figure 5 - SmartLight motherboard
Main components
[A]LOOP-OLoop output terminals
[B]LOOP-ILoop input terminals
[C]Loop status LED (refer to Chapter 5 - User Interface)
[D]RS232 serial port for PC connection
AB
EFGHIJ
Q
P
LM
K
NO
[E]DIALEROutput terminal for dialer connection, supervised
[F]RS485RS485 BUS terminals for repeater connections, max. 0.9 A
[G]FAULTFault output - dry contact
[H]FAULT +/-Fault output - supervised
[I]ALARM NACAlarm output - supervised
[J]AUX24 V 0.8A output for external loads
16Technical description
Installation and programming manual
[K]Connector for the earth wire of the power supply module
[L]Power-supply module connector
[M]Battery connector
[N]Thermal probe connector for batteries - accessory item
[O]Earth-fault-bypass jumper - if this jumper is removed faults will be bypassed
[P]Jumper for programming from panel (keypad and LCD) J8
[Q]Jumper for programming from PC J9
[R]Extinguishant module connector
[S]Buzzer
Note:INIM s.r.l. reserves the right to change, replace, in part or entirely, the components not strictly relating
to the user and therefore, which do not involve the installation process described in Chapter 6 Installation instructions.
4.2Technical specifications
AC power230 Vac (-15% + 10%) 50/60 Hz
Maximum current draw 230V0.5 A
Maximum current draw on terminal +AUX0.8 A
Current ripple on AUX and AUX-R outputs1% MAX
Maximum battery-charge current400mA
Battery specifications2 x 12 V/7 Ah YUASA NP-12 FR or similar with case
flame class UL94-V2 or higher
Maximum battery internal resistance (R
Output current 19V - 27.6V
Fuse (F2) - Switching power supply F 6.3 A 250V
Fuse (F1) - Switching power supply (not resettable)T 3.15 A 250V
Maximum output current ripple1%
Operating temperature-5°C to 40°C
Dimensions325 x 325 x 80 mm
Weight2.8Kg
)23 Ohm
i max
4.3PCB current draw
ModuleStandby current drawMaximum current draw
SmartLight motherboard70 mA120 mA
SmartLetLoose/ONE fire extinguishant board10 mA70 mA
SmartLetUSee/LCD-Lite repeater40 mA80 mA
Technical description17
User Interface
A
C
D
E
F
G
H
I
J
L
K
M
N
O
P
R
Q
T
WS
U
V
Z
Y
X
B
A1
B1
C1
D1
E1
Installation and programming manual
Chapter 5
Figure 6 - Frontplate
5.1SmartLight panel frontplate
5.1.1Commands
CommandAccess level 1Access level 2Note
[A] Navigation
keys
[B] Keyhole for the
access level 2
key
[C] SILENCEPush this button to
Key not inserted or
inserted in vertical
position
silence (turn OFF) the
panel beeper.
Key inserted in horizontal
position
Silences (turns OFF) active
outputs with the silenceable
attribute. The silenceable outputs
will hold silenced status until a
new event occurs that releases
the outputs automatically. The
SILENCE button operates as a
toggle switch, therefore, silenced
outputs can be unsilenced by
pushing the button again.
[D] RESETPush this button to clear any
active events, delete the memory
and restore standby conditions.
18User Interface
To be used to navigate through
the menus on the display. The
effect these keys have during
programming depends on the
specific field. See Chapter 8 - Programming from the panel.
When the key is removed or
placed in the vertical position
and no key is pressed, the
control panel will hold access
level 2 status for 20 seconds.
If the system is operating in
Night mode, SILENCE status will
be held for the preset SILENCE
time only. This is a safety
precaution designed to protect
building occupants and persons
in charge of night-security who,
after silencing the system, may
be overcome by smoke or
fumes during fire investigation
and unable to restart the alarm
signaling devices manually.
Any alarm/fault conditions
which persist after RESET
operations will generate new
alarm/fault signals.
Installation and programming manual
CommandAccess level 1Access level 2Note
[E] EVACUATEIf this button is pressed
during active pre-alarm
conditions, the system
will override the
programmed pre-alarm
time and generate an
instant alarm (i.e.
activate all evacuationwarning devices).
[F]INVESTIGATEIf this button is pressed during
Extinguishant module (accessory item) commands
[G] DISABLE
EXTINGUISH
[H] DISABLE
AUTO
If this button is pressed when
pre-alarm conditions are not
active, the system will generate a
panel alarm.
active pre-alarm conditions, the
system will add the preset
investigation time to the running
pre-alarm time (this operation
can be done once only).
If this button is pressed once, the
system will disable Extinguish
commands. If this button is
pressed again, the system will reenable Extinguish commands.
If this button is pressed once, the
system will disable automatic
extinguish commands generated
by the Extinguishant module. If
this button is pressed again, the
system will re-enable automatic
extinguish commands generated
by the Extinguishant module.
The extended alarm delay will
allow authorized building
occupants and/or security staff
to check and verify the fire
hazard.
This button can be used during
testing and maintenance of the
fire extinguishant devices.
[I]DISABLE
MANUAL
If you push this button once, the
system will disable manual
extinguish commands. If you
push this button again, the
system will re-enable manual
extinguish commands. Refer also
to paragraph 6.8 - Connecting
the extinguishant module
(optional).
5.1.2Signalling
LEDON Solid:Blinking:Note
[J]DisplaySee Chapter 8 - Programming from the
panel.
[K]SILENCED
(yellow)
[L]RESET
INHIBITED
(yellow)
Indicates that the system
has been silenced.
In the event of pre-alarm/
alarm, indicates that reset
commands are not allowed.
Reset will be allowed when
all outputs have been
silenced and this LED goes
Off.
This feature ensures that persons
responsible for the safety of the building
and its occupants do not reset the
system without first silencing the
outputs, and evaluating the alarm. The
silence operation will stop the signaling
devices and restore quiet thus allowing
the operator to consider the best way to
proceed. The operator will then be able
to reset the system and restore standby
status.
User Interface19
Installation and programming manual
LEDON Solid:Blinking:Note
[M]ALARM
(red)
[N]PRE-ALARM
(red)
Indicates an alarm
condition, that is, an input
point (detector, callpoint,
input module, etc.) set to
generate alarms has
detected alarm conditions.
Indicates a pre-alarm
condition, that is, an input
point (detector, callpoint,
input module, etc.) set with
a pre-alarm time has
activated.
Examples: a smoke detector has sensed
a quantity of smoke that exceeds its
alarm threshold; a heat detector has
sensed rise in temperature that exceeds
its alarm threshold; a callpoint has been
activated, etc. Authorized persons only
(level 2) can clear these conditions
(which may occur after an early
warning, pre-alarm, etc.) by means of
silence/reset operations. Signaling will
continue even after the cause of the
alarm has ceased.
Examples: a smoke detector has sensed
a quantity of smoke that exceeds its
alarm threshold; a heat detector has
sensed rise in temperature that exceeds
its alarm threshold; a callpoint has been
activated, etc. Only authorized persons
(level 2) can clear these conditions
(which may occur after an early
warning, pre-alarm, etc.) by means of
silence/reset operations. Signaling will
continue even after the cause of the
alarm has ceased. If the operator does
not intervene in the meantime, the
point in pre-alarm status will generate
an alarm when the programmed prealarm time expires. The pre-alarm time
is a short alarm delay that notifies the
person/s responsible for the safety of
the building and its occupants of the
possibility of fire. An alarm will be
generated when the programmed prealarm time expires, thus causing the
evacuation of all the building. After prealarm notification, the person/s
responsible for the safety of the building
and its occupants will have time to
verify the real risk of fire and, in the
event of a false alarm, will be able to
avoid unnecessary evacuation signaling.
[O]FAULT
(yellow)
[P]CPU FAULT
(yellow)
20User Interface
Indicates an active system
fault condition. The display
will provide the fault
details.
Indicates trouble with the
panel CPU; the panel must
be sent back immediately
to the manufacturer for
repair.
Indicates memory of a
cleared fault event. To
view the restored fault
condition details,
consult the events log
using the Main menu
(level 1).
Indicates that the CPU
re-initialized (due to
control panel
shutdown or fault
condition).
To restore the fault memory (return to
LED Off status), reset the control panel
(level 2).
Danger:If this LED “blinks”,
the efficiency of
entire system must
be checked. To return
to LED Off status,
reset the control
panel (level 2).
Installation and programming manual
LEDON Solid:Blinking:Note
[Q]DISABLED
(yellow)
[R]TEST
(yellow)
[S]ON
(green)
[T]DIALLER ON
(red)
Indicates that one or more
of the system components
(loop point, zone or output)
have been bypassed.
Indicates that one or more
components (points or
zones) are undergoing
tests.
Indicates that the system is
operating (On).
Indicates that the dialer
activation output is active.
The display will provide the respective
details. Bypassed components (/
disabled/out-of-service components)
will be unable to generate faults, alarms
or signals of any sort and cannot be
activated under any circumstances.
Components must be bypassed (put
out-of-service) during maintenance
work.
A bypassed point which is undergoing
tests (separately or as part of a zone)
will not generate alarms or signaling of
any kind. However, the respective LED
will turn On for several seconds and
then reset and turn Off automatically.
This feature allows technicians to carry
out point/zone tests and inspections
alone, as it eliminates the need of
constantly returning to the panel to
verify/reset the events generated by
the points.
This LED will go Off in the event of joint
primary (230 V ac) and secondary
(batteries) power failure.
The dialer will be activated (after the
pre-set delay) in the event of an alarm.
[U]DISABLE/
FAULT
DIALLER
(yellow)
[V]DISABLE/
FAULT BELLS
(yellow)
[W]NIGHT MODE
(yellow)
[X]DISABLE
EXTINGUISH
Indicates that the dialer
activation output is
disabled or faulty—the
display will provide the
respective details.
Indicates that the sounder/
flasher activation output is
disabled or faulty—the
display will provide the
respective details.
Indicates that the panel is
operating in night mode.
Indicates restoral of a
fault event. This
condition can be
cleared by reset only
(level 2).
Indicates restoral of a
fault event. This
condition can be
cleared by reset only
(level 2).
For safety reasons, the pre-alarm time
of all points is cancelled automatically
during night mode (night mode prealarm time = 0 seconds). As a further
safety precaution, the system can be
silenced for the pre-set SILENCE time
only. Night Mode should be applied
when no or few persons are present or
awake in the building, and the building
security is the responsibility of a night
watchman or security patrol guard
notified by the dialer.
Extinguishant module signaling (optional system enhancement tool)
Indicates disablement of all
types of extinguish
commands, via the
appropriate key (paragraph
5.1 - [G]).
[Y]DISABLE
AUTO
Indicates disablement of
automatic extinguish
commands, vvia the
appropriate key (paragraph
5.1 - [H]).
User Interface21
Installation and programming manual
LEDON Solid:Blinking:Note
[Z]DISABLE
MANUAL
[A1] EXTINGUISHIndicates that fire
[B1] PRE-
EXTINGUISH
[C1] FAULTIndicates trouble with the
[D1]STOP
EXTINGUISH
Indicates disablement of
manual extinguish
commands, via the
appropriate key (paragraph
5.1 - [I]).
extinction is running.
Indicates activation of the
pre-extinguish output;
refer to paragraph 6.8 -
Connecting the
extinguishant module
(optional), terminal PRE-
EXT.
fire extinction circuits.
Indicates that the fire
extinguishant system has
been stopped from a
remote hold-off unit; refer
to paragraph 6.8 -
Connecting the
extinguishant module
(optional), terminal STOP-
EXT.
Indicates that only
one zone is in alarm
status, therefore, the
extinguishant system
will not be activated. If
another zone latches
in alarm, the
extinguishant system
will be activated.
Indicates restoral of a
fault event.
Indicates restoral of a
Stop extinguishant
event.
This condition can be cleared by reset
only (level 2).
[E1] CPU FAULTIndicates a CPU fault that
requires immediate repair.
Indicates restoral of a
fault event.
5.2Internal LEDs
ABC
Figure 7 - Internal LEDs
These LEDs indicate communication between the panel and the detectors. They indicate that the panel is
interrogating its devices, the protocol it is using and whether or not the interrogated devices have responded.
• The green LED [A] (nearest to the Loop-I terminals) will blink each time a loop device responds during
the interrogation phase of the devices from address 1 through to the maximum number of devices
allowed (refer to Appendix A, Appendix B and Appendix C regarding the number of devices
accommodated by the loop).
• The red LED [B] will blink each time a command is sent to a loop device using Enea (Appendix A) or
Argus (Appendix B).
• The red LED [C] on the far right will blink each time a command is sent to a loop device using Apollo
(Appendix C) communication protocol.
22User Interface
Installation and programming manual
Under normal operating conditions, the red protocol LED will blink rapidly and the green device-response
LED will flicker. The flickering phase depends on the number of devices connected to the loop. The more
devices the longer the LED will flicker.
5.3Repeater (optional system enhancement panel)
Up to four repeater panels can be connected to the RS485 bus. Connected repeater panels replicate all the
information provided by the control panel and allow access to all level 1 and 2 functions (view active
events, reset, silence, etc. access to the main menu is not possible).
A
K
L
O
P
Q
G
M
N
R
S
T
U
F
V
W
X
J
H
E
Y
Z
Z1
I
C
D
B
Figure 8 - Front view of the repeater panel
The SmartLetUSee/LCD repeater is supported by most control panel models. However, not all the keys/
button will be operational if it is connected to the SmartLight panel. The following keys/buttons are
operational:
[A]Navigation keysScroll keys which will allow navigation through menus, etc.
[B]EVACUATEAs per paragraph 5.1
[C]SILENCEAs per paragraph 5.1
[D] RESETAs per paragraph 5.1
[E]INVESTIGATEAs per paragraph 5.1
[F]BUZZERTurns the panel beeper Off
[G] TESTTurns On al the LEDs to verify functionality.
Repeaters provide the following signals.
5.3.1Display
The display provides same event data as the panel. For further details refer to paragraph 2.5 Signaling on
display in the User Manual.
User Interface23
5.3.2LED
LEDON Solid:ON Blinking:
[H]SILENCEDAs per paragraph 5.1
[I]RESET DISABLEDAs per paragraph 5.1
[J]INVESTIGATEIndicates that investigation time has been
requested.
[K]ALARMAs per paragraph 5.1
[L]PRE-ALARMAs per paragraph 5.1
[M]FAULTAs per paragraph 5.1
[N]CPU FAULTIndicates that the repeater CPU is not operating
properly. If this occurs, the repeater must be
sent back to the manufacturer immediately for
repair.
[O]DISABLEDAs per paragraph 5.1
[P]TESTAs per paragraph 5.1
[Q]NIGHT MODEAs per paragraph 5.1
Installation and programming manual
[R]BATTERYIndicates that the panel batteries are low or
inefficient.
[S]EARTHIndicates voltage dispersion to earth.Indicate restoral of the voltage
[T]FUSEIndicates protection fuse intervention due to
short-circuit on the AUX output.
[U]MAINSIndicates Mains failure.Indicates restoral of the Mains failure
[V]BELLS - ACTIVEIndicates that the ALARM NAC output is active.
[W]BELLS - FAULTIndicates that a fault has been detected on the
ALARM NAC output.
[X]BELLS - DISABLEDIndicates that the ALARM NAC output has been
disabled.
[Y]DIALLER - ACTIVEIndicates that the DIALER output is active.
[Z]DIALLER - FAULTIndicates a DIALER output fault.Indicates restoral of the Dialer
[Z1] DIALLER - DISABLED Indicates that the DIALER output has been
disabled.
Indicates restoral of the low/
inefficient battery event.
dispersion to earth event.
Indicates restoral of the short-circuit
on AUX output event.
event.
Indicates restoral of the ALARM
output fault.
output fault.
24User Interface
Installation and programming manual
5.3.3Repeater board
If you open the repeater enclosure, the rear side of the electronic board (which is attached to the
frontplate) will be on view. Following is a description of the parts which will be used during the installation
phase:
A
C
Figure 9 - The rear side of the repeater board
[A]DIP switchesFor the repeater address setting
[B]RS485 terminals Respectively, from the bottom of the figure to the top “+24V - + GND”, for the
connection to the RS485 BUS
[C]EOL terminals For the setting-jumper position of the repeater position.
B
User Interface25
Installation and programming manual
Chapter 6
Installation instructions
6.1Installing the extinguishant module (accessory item)
The extinguishant module is packed in a separate cardboard box. Together with the extinguishant module
(IN015), you will find a plastic bag containing:
• Pin header for the extinguishant module to SmartLight motherboard connection
• Screws
• EOL resistors and diodes
12
456
Figure 10 - Mounting the extinguishant module
1. Remove the four securing screws and the frontplate.
2. Remove the four securing screws and the plastic support.
3. Position the SmartLight motherboard as shown in the figure.
4. Locate the extinguishant module in its housing.
5. Using the four screws, secure the extinguishant module in position.
6. Connect pins J17 of the SmartLight motherboard (paragraph 4.1 - [R]) to the respective pins J2 on the
extinguishant module.
7. Move the SmartLight motherboard back to its original position.
8. Replace the plastic support.
3
6.2Wall mounting
6.2.1Control panel
1. Pull the wires through the wire entry and ensure they do not get in way of operations.
2. Using the wall plugs, attach the backplate to the wall.
Danger:
6.2.2Repeater (optional system enhancement panel)
1. Remove the four frontplate screws and lift off the frontplate.
2. Pull the wires through the wire entry on the back of the repeater and ensure they do not get in way of
operations.
3. Using the wall plugs, attach the backplate to the wall.
26Installation instructions
Care must be taken not to drill in the vicinity of electrical wiring, heating ducts and plumbing.
Installation and programming manual
6.3Connecting the Loop
The loop accommodates all the peripheral devices of the fire control system (detectors, callpoints,
modules, etc.), and if necessary, also a Gas Extinguishant Module. For a full description of the devices the
loop accommodates, refer to Appendix A, Appendix B and Appendix C.
You can use either a 2 or 4 wire connection. To create a 4 wire connection, start on the LOOP-O terminals,
connect all the system devices and re-enter on the LOOP-I terminals. 4 wire connections tolerate one
wiring fault. If loop interruption occurs, the panel will manage the section entering on the LOOP-I terminals
separately, thus splitting the loop in two separate sections.
Figure 11 - 2 wire connection
Figure 12 - 4 wire connection
Installation instructions27
Installation and programming manual
6.3.1Wiring
1. Use 2 pole shield twisted cable. The cable section must be compatible with the loop load (refer to
Appendix A, Appendix B and Appendix C for further details).
Attention:The maximum wire length is 2000 m.
2. Connect the cable shield to the earth terminal [3] (one end of the loop only).
3. Fire alarm wires must be separate from other power wiring circuits.
6.3.2Loop limitations
Use suitably sectioned shielded twisted cable for the loop wiring. Connect the shield to earth using terminal
3 or 6, connect it to one end of the loop only.
In order to allow the loop to function properly, you must section the device connection cable in such way
that any voltage drop along does not exceed 8 V. The following table shows the minimum dimensions for
the loop wiring with regard the distance between the Loop-O terminals and the most distant device:
up to 500 m
up to 1000 m
up to 1500 m
up to 2000 m
minimum 1 mm
minimum 1.5 mm
minimum 2 mm
minimum 2.5 mm
2
2
2
2
6.3.3Fire code guidelines
Danger:
- 2 wire connection, no more than 32 detectors can be connected to the loop.
- 4 wire connection, T junctions are prohibited, that is unless the maximum number of devices
that risk isolation during any type loop fault does not exceed 32.
- If the system loop devices do not have built-in isolators, you must install an isolator for each
group of 32 detectors.
- All circuits should be wired using the local country Fire Code compliant method.
6.4Connecting the dialer
The panel dialer must have an activation terminal that will generate calls when it connects to GND
(activation -A).
DIALER
POWER-SUPPLY
Figure 13 - Connecting the dialer
6.4.1Wiring
1. Connect the telephone dialer to the DIALER terminals.
2. Connect a 10 k: resistor to the dialer, as shown in the previous figure. This resistor will monitor the
integrity of the connection between the panel and the dialer and will signal any short-circuits or
interruptions.
In the event of an alarm, the panel will trigger the dialer which, after the programmed delay, will send the
respective calls to pre-set telephone numbers.
28Installation instructions
Installation and programming manual
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
Note:If you do not connect a dialer, the control panel +DIALER output should be connected to the +24V
output by a 10 k: resistor.
BLACKORANGE
BROWN
GOLD
Figure 14 - +DIALER output connection without dialer
6.5Connecting the RS485 BUS
The RS485 BUS terminals accept up to 4 SmartLetUSee/LCD-Lite repeaters (remote information points,
generally located in the entrance areas of the protected building) and 2 SmartLevel power stations.
The devices must be connected in parallel. The panel communicates with the repeater panels using a highly
noise-immune digital protocol.
REPEATERS
SmartLetUSee/LCD-Lite
POWER SUPPLY
STATION
SmartLevel
Figure 15 - Connecting the RS485 BUS
6.5.1Wiring
1. Use a 4 pole STP cable.
2. The cable length between the panel and repeater should not exceed 1000 m.
3. Connect the shield to earth (terminal 6 can be used for this connection).
6.5.2Setting the addresses of devices connected to the RS485 BUS
1. Each of the devices connected to the RS485 BUS must have a distinct address. When setting the
addresses of SmartLevel devices, refer to the Power Station programming manual. When setting the
addresses of repeaters, use the DIP switches (paragraph 5.3.3 - [A]).
Address1234
DIP
Switch
position
ON
1 2 3 4
Installation instructions29
Installation and programming manual
FAULT signalling
sign
Attention:All other DIP switch configurations are NOT allowed.
2. Ensure that the EOL jumper (paragraph 5.3.3 - [C]) is set in the EOL position on the last device on the
line ONLY.
EOL jumper position for the
end-of-line repeater
Figure 16 - SmartLetUSee/LCD-Lite board - jumper position
EOL jumper position for the end
power-supply station
Figure 17 - SmartLevel board - jumper position
6.6Connecting the fault signaling outputs
The panel provides 2 fault signaling outputs:
Jumper position for the centrally
positioned repeater
Position the jumper in the
central position
• A normally-open dry contact
• A supervised output protected by a resettable fuse @ 0.3 A
Figure 18 - Normally-open FAULT output connection
30Installation instructions
Installation and programming manual
BLACKORANGE
BROWN
FAULT signalling
sign
GOLD
Figure 19 - supervised FAULT output connection
During standby status the voltage applied to the output will be less than 0.5 V, thus not enough to activate
the connected load, but enough to allow the panel to verify the integrity of the connection cable.
Open or shorted conditions on the wires will generate a fault signal: “
Output”
.
Open” or “Shorted Alarm
In the event of a fault, this output will activate, and the panel will supply 24 V in accordance with the
polarity indicated on the board.
Note:In order to validate the IMQ-SECURITY SYSTEMS certification, these outputs must not be used as Type
J outputs (EN 54-1), therefore, they must not be used to command devices that transmit fault signals.
6.6.1Wiring
1. Use NON-shielded cable.
The wire section should be compatible with the wire length and load connected to the output.
2. Connect the EOL resistor (10 K:) in parallel to the last device on the line.
6.7Connecting the alarm signaling output
VIOLETORANGE
YELLOW
GOLD
Figure 20 - Connecting the Alarm output
The alarm output is a silenceable supervised output protected by a resettable fuse @ 0.9 A.
During standby status the panel will allow a low supervisory current to circulate on the line with reverse
polarity to that indicated on the board. The diodes connected in series to each load on the line will ensure
that the current closes on the EOL resistor. This current allows the panel to verify cable integrity. Open or
shorted conditions on the wires will generate a fault signal: “
Installation instructions31
Open” or “Shorted Alarm Output”.
Installation and programming manual
A
YELLOW
VIOLETORANGE
GOLD
BROWN
GREENORANGE
GOLD
C
YELLOW
VIOLETORANGE
GOLD
D
YELLOW
VIOLETORANGE
GOLD
STOP-
EXTINCTION
signalling LED
SmartLight
control panel
In the event of an alarm, the output will activate and the panel will supply 24 V in accordance with the
polarity indicated on the board.
6.7.1Wiring
1. Use NON-shielded cable.
The wire section should be compatible with the wire length and load connected to the output.
2. Connect the EOL resistor (47 K:) in parallel to the last device on the line.
3. Connect a 1N4007 diode (or equivalent) in series to each load.
6.8Connecting the extinguishant module (optional)
B
POWER SUPPLY 24V
Gas release
electrovalve
Figure 21 - Extinguishant module
32Installation instructions
Installation and programming manual
6.8.1Inputs
Terminal
MAN-EXTExtinction system
STOP-EXTSTOP
PRESSGas extinguishant
Device to be
connected
Start button
extinguishantsystem button
pressure switch.
6.8.2Outputs
Input TypeNoteWiring Diagram
Supervised.Up to 20 devices can be connected to
this input.
Supervised.The STOP extinguishant-system button
should always be located near to the
protected area. This will allow any
persons present during the release of
extinguishant gas to stop the process
and evacuate the area unharmed. Up
to 20 devices can be connected to this
input.
Supervised.The pressure switch has two functions:
- Under normal operating conditions, it
monitors the pressure of the Gas
extinguishant. If the pressure drops
spontaneously below the pre-set value,
it will generate a fault signal.
- After an 'Extinction' command, it
confirms that the command has been
executed.
Figure 21 Extinguishant
module/A
47K = Standby
15K = Active
Terminal
VALVEElectrovalve for
PRE-EXTAudible and Visual
RELEASED“Extinguishant
RRemote LED that
Device/s to
connect
gas release.
signaling devices
Gas release”
signaling devices
signals the
deployment of the
STOP
extinguishantsystem button.
Output TypeNoteWiring Diagram
SupervisedFigure 21 -
Extinguishant
module/B
SupervisedThe signaling devices activate as soon as
the detectors sense fire conditions that
require gas extinguishant intervention.
This will allow building occupants to
evacuate the building before the gas
extinguishant is released. The delay
between the activation of alarm signaling
devices and the release of the gas
extinguishant is customizable.
SupervisedThere are two activation modes:
- activation on confirmation of
Extinguishant Gas release;
- simultaneous activation with the
electrovalve output. This mode requires
gas detectors in the protected
environment.
Open Collector
(nonsupervised)
Activates (closes to GND) in the event of
activation of the STOP EXT input (max
100 mA).
Figure 21 Extinguishant
module/C
47K Balancing
Figure 21 Extinguishant
module/D
6.9The AUX output
The AUX terminals provide the 24 V power supply to the peripheral devices. The output is protected by a
resettable fuse @ 0.9 A.
In the event of short-circuit, the panel will signal a fault.
Installation instructions33
Installation and programming manual
6.10Connecting the Mains
The switching power supply module (housed inside the box under the motherboard) provides the power
source to the entire system and recharges the batteries.
The panel must be connected to a separate line on the electrical switch board. The line must be protected
by a fire code compliant sectioning device.
The protective earthing system must be compliant with the local safety regulations, fire code, laws and
bylaws in force.
6.10.1 Technical specifications
• Primary power source: 230 V ac (-15% + 10%) 50/60 Hz.
• Panel current draw: 0.5 A (max)
6.10.2 Wiring
A
B
Figure 22 - Connecting the Mains
Danger:Switch Off the mains power.
1. Connect the wires to the terminal board [A] of the power supply.
2. Using a plastic cable tie, secure the cable to the hook [B] on the back of the control panel.
Attention:Wiring circuits must not be commingled without proper separation. Adhere to the connection
wiring in the diagram.
6.11Connecting the batteries
The panel box provides housing for two 12 V-7 Ah lead batteries. The two batteries must be connected in
series, in such way as to provide a 24 V current.
Using the battery terminal eyelet wire (included), insert the battery terminal bolt through the washer and
battery terminal eyelet. The actual connection must be completed during initial powerup of the control
panel (refer to paragraph 7.3).
The batteries are the secondary power supply of the system. Once powered up, the panel will charge and
monitor the batteries automatically. The battery monitoring process is as follows:
• Efficiency test
The panel checks the efficiency of the batteries by simulating load current demand at regular 60 second
intervals. If the batteries fail to meet the load current demand, the event will be signaled on the
Battery disconnected fault LED.
• Battery level test
In the event of mains failure, the panel continuously monitors the battery voltage. If it drops below 22.8
V, the panel will signal the event on the
to 24.6 V.
• Deep discharge shutdown
If a mains failure event lasts for a long period, and battery voltage drops below 18 V, the panel will
shutdown the batteries automatically in order to avoid irreparable damage.
34Installation instructions
Low Battery LED. The event will end when the voltage restores
Installation and programming manual
N
6.12Thermal Probe
Attention:In order to validate the IMQ-SECURITY SYSTEMS certification and comply with EN 54-4
requirements, installation of a thermal probe is essential.
The battery has an on-board connector for a Thermal probe (accessory item). This device will regulate the
charging process in accordance with the battery temperature. The thermal probe protects against battery
overheating and consequent permanent damage.
6.12.1 Connecting a thermal probe
Figure 23 - Connecting a thermal probe
1. Disconnect the batteries (if already connected).
2. Connect the thermal probe to the connector (paragraph 4.1 - [N]).
3. Using adhesive-insulating tape, attach the thermal probe to one of the batteries, in order to provide
optimized heat-transfer measurements.
4. Hold a thermometer against the probe, and measure the probe temperature.
5. Using the following graph, find the value the measurement will be based on.
Volt
29
28,5
28
27,5
27
26,5
26
25,5
05101520253035404550
°C
Figure 24 - Voltage charge in relation to the Battery Temperature.
6. Using a tester, measure the voltage on the AUX [A] (paragraph 4.1 - [J]) and turn the trimmer [B] to
the previously measured value.
Installation instructions35
Installation and programming manual
B
A
Figure 25 - Adjusting the voltage charge
36Installation instructions
Installation and programming manual
9
1
1
9
9
1
1
25
Chapter 7
Powering up and configuring the system
7.1Testing wiring integrity
Before powering-up the system, check the wiring integrity and the isolation between the wires and earth.
1. Disconnect the wires from the terminals on the motherboard.
2. Using a tester, ensure there is no electric current flow between the wires and earthing system.
3. Reconnect the wires to their respective terminals on the motherboard.
4. Disconnect the cable shields from the respective terminals on the motherboard.
5. Using a tester, ensure there is no electric current flow between the cable shields and earthing system.
6. Reconnect the cable shields to their respective terminals on the motherboard.
7. Disconnect the wires of the supervised outputs from the respective terminals on the motherboard.
8. Using a tester, measure the cable resistance. Test both polarities. At least one must have the same resistance value as
the EOL resistor.
9. Check that all cables are properly separated, bunched (by means of cable ties) and attached firmly to the cable hooks
on the backbox.
10. Check the proper polarity of the primary power source connections (230 Vac).
11. Ensure that the cable is attached firmly to the cable hook by means of a plastic cable tie.
12. Ensure that the repeater panel address DIP microswitches (
paragraph 6.5.2 - Setting the addresses of devices connected to the RS485 BUS.
13. Ensure that the EOL resistance jumper of the last device connected to the BUS is in the EOL position.
paragraph 5.3.3 - [A]
) have been set properly. See
7.2Connecting the RS232 PC serial link
Connect the RS232 cable to the apparatus by means of an RS232 serial input (paragraph 4.1 - [D]).
Note:The connection between the panel and the PC will be operative only when the PC programming jumper
is inserted.
The cable should be connected to the device as shown:
SmartLight end
DB9F connector
SmartLight-GP end
DB9F connector
23
32
44
55
66
77
88
2
3
4
5
6
7
85
2
3
20
7
6
4
PC end
DB9F connector
PC end
DB25F connector
Powering up and configuring the system37
Installation and programming manual
Note:
THE RS232 link can be ordered separately. The order code is indicated in Appendix D - Order Codes.
If your PC does not have a RS232 port but has a USB, use an RS232-USB adaptor.
7.3Powering up the system
C
BB
A
A
Figure 26 - Connecting the batteries
1. Connect the connection wire [A] to the batteries. Refer also to paragraph 6.11 - Connecting the
batteries.
2. Connect the connection wire [B] to the batteries.
Attention:Be sure that cable polarity is correct.
3. Connect the connector [C] of the battery wire to the control panel (paragraph 4.1 - [M]).
Attention:Ensure that connector polarity is correct.
38Powering up and configuring the system
Installation and programming manual
Control panel
In service
14/05/11 18:23
The panel will take several seconds to stabilize, startup will be indicated by an intermittent audible
signal and the “
Resetting”.
Figure 27 - Reset signaling
Full panel reset will be indicated by:
- The On status of the green LED (paragraph 5.1.2 - [S]) indicates that the panel is operating.
- The CPU LED (paragraph 5.1.2 - [P]) will blink to indicate that the board is initializing.
- If you do not carry out the successive step (connection to the mains power source) within 2 minutes,
the FAULT LED (paragraph 5.1.2 - [O]) will go On and the “
display.
4. Power up the panel from the mains.
In the event of restoral of a Mains fault; the FAULT LED will blink to indicate that the event has been
saved to the memory.
Mains Fault” message will appear on the
5. If the fault persists, check all wiring sections thoroughly. See Chapter 17 - Diagnostics and fault
solutions.
6. Once all faults have been cleared, turn the key in the keyswitch (Access Level 2) and press the RESET
button (paragraph 5.1.1 - [D]).
After Reset operations, all the LEDs should go OFF, with the exception of the green ON LED (paragraph
5.1.2 - [S]).
The display will show “
7. Press any key to access the main menu. Using the cursor key T select the second option on the “
” menu. Press and hold the Ok key and check that all the LEDs go On.
LEDs
Panel working” message.
Test
Powering up and configuring the system39
Installation and programming manual
l
Control panel
IN PROGRAMMING
ver. 2.00
07/07/11 00:00
Control panel
IN MAINTENANCE
ver. 2.00
07/07/11 00:00
The control panel and its points and zones can be programmed and configured via the control panel or by
means of the SmartLeague software programme. For a brief description of the software application and the
programming process, refer to Chapter 15 - SmartLeague software or, for a more complete description,
refer to the SmartLeague user's guide.
Access to programming is allowed only after the programming jumper has been inserted:
1. Remove the frontplate.
Note:To unblock the programming phase, start the SmartLeague application on the PC and type in the code
previously used to block it. This feature protects the system from being accessed by persons other than
qualified technicians authorized by the Installer company.
2. Insert the programming jumper (refer to paragraph 4.1 - [Q]).
3. The display will show the relevant message.
4. The panel switches Off: no faults or alarms will be signaled.
If this message appears, the programming phase has been blocked via
PC. If this occurs, only maintenance functions can be accessed.
Menu options
Press Ok to access the zone screen.
‘
’ indicates that there is further information after the last line.
Press Esc to step back to the previous screen.
Editable alphanumeric field
Use keys SandT to move along the string.
Press and hold Ok to scroll the alphanumeric characters.
Press Esc to confirm the data entry, exit and step back to the previous
screen.
Editable numeric field
Press and hold Ok to scroll the values the two-digit counters (e.g.: 0
to 99 and “--”, which means non-specified).
Use key SorT to move to the next programming field.
Press Esc to confirm the data entry, exit and step back to the previous
screen.
Variable field
Use key SorT to scroll the list.
Press Ok to toggle the parameter in the programming field (e.g.: YES
to NO).
Press Esc to confirm the data entry, exit and step back to the previous
screen.
40Programming from the panel
Installation and programming manual
Chapter 9
Preparing the programming data
Before programming the panel, fire detectors, extinguishant module (if used) and loop points, set the
following values.
9.1Set Time and date
From the panel: <key>, Maintenance, Time and date
Navigate through the programming field and set the new values. The system will select the day of the week
automatically.
9.2Setting delays and times
From the panel: <key>, Programming, Options
Navigate through the programming field and set the new values.
9.2.1Parameters
Delay mains failureA delay (0 to 30 minutes) which much run before the mains failure event is signalled.
This delay avoids unnecessary signaling of brief 'Mains failure' events.
Delay diallerThe period (0 to 10 minutes) which the dialer allows before signaling a zone alarm.
Verify timeThe time (0 to 10 minutes) required to verify the validity of alarms. If the point
(detector) exceeds the pre-set threshold value, it will be reset by the panel. If the
point (detector) exceeds the pre-set threshold value while the 'verify alarm' time is
running, it will trigger an alarm. If it does not, it will restore to standby status. Applies
to points with Verify=YES.
Silence timeThe duration (0 to 10 minutes) of Silence status when the system is operating in Night
mode (starting from the moment the SILENCE key is pressed).
Filter time
Lock resetThe period (0 to 30 minutes), after extinction activation, when reset operations are
The minimum time (expressed in seconds), after reset operations, that an alarm or fault
signal must be present on the line before being processed by the control panel. This filter
avoids accidental activation of fault or alarm signals caused by instant activation (for
example, when an elevator trolley violates the area covered by a linear smoke detector).
not allowed. If a confirm extinction signal is sent to the extinction module during this
period, reset operations will be re-enabled.
9.3Other options
From the panel: <key>, Programming, Options
Navigate through the programming field and set the new values.
9.3.1Parameters
Mon. visibleYESEnables monitor event signaling on the display.
NODisables monitor event signaling on the display Events can be viewed in the events
log only (refer to paragraph 16.1).
Mute buzzer YESDisables the buzzer on the control panel motherboard
Attention:Option to be used only during the programming phase.
NOThe buzzer is operating properly.
Preparing the programming data41
Installation and programming manual
2 Alarm extYESThe control panel uses double alarm signaling instead of zone alarm in order to
activate the extinguishant board.
NOThe control panel uses the zone alarm signal to activate the extinguishant board.
Max led on The maximum number of loop LEDs that can activate at the same time.
9.4Defining zones
From panel: <key>, Programming, Progr. Zone, select zone number, Ok
or create geographical point groups or “logical” point groups (e.g.: outputs). A zone will change status
when one (or more) of its points triggers an alarm, pre-alarm, fault, early warning or monitor signal.
Navigate through the programming field and set the new values.
Attention:Consult the local laws in force for any restrictions regarding the definition of zones
Pre-alarmLength of pre-alarm signal for the zone. The zone will trigger an alarm when the
set time expires..
InvestigateLength of investigation time, the countdown starts when the INVESTIGATE button
is pressed during pre-alarm status. Pressing this button will stop the pre-alarm
timer and start the "Investigate" timer.
9.5Setting holidays
From panel: <key>, Programming, Progr. Holidays, select a holiday, Ok
This option will allow you to set specific periods which determine exceptions with regard timer
programming, for example, holidays, bank holidays, etc. Navigate through the programming field and set
the new values.
9.5.1Parameters
HolidayNumber of holidays (maximum 15), already preset.
day, month, yearDate of the holiday or start date of the holiday period. To indicate any day, month or
year, leave “--” (for example, every 3rd of the: day=3, month = “--”, year = “--”).
Day, month or year should be “--”, if you wish to create the setting using the day of
the week.
Sunday, etc.Day of the week for weekly arrangements. Valid only if Duration = 1
DurationLength of time (expressed in days) of the holiday period (0 at default). If you set 0,
the system will not take the holiday into account.
9.6Setting the Timers
From panel: <key>, Programming, Progr. Timer, select a timer, Ok
This option will allow you define the timer intervals (e.g.: from 13.00 to 14.00), dates (e.g.: 25-12-2006)
or special days (e.g.: Sundays and days of closure). The timer can be included in an equation and can
contribute to the activation of an output. Timer activation may trigger associated actions (e.g. bypass a
zone, toggle to Night Mode). Navigate through the programming field and set the new values.
42Preparing the programming data
Installation and programming manual
9.6.1Parameters
TimerTimer number (maximum 8), preset.
Interval 1, Start/EndHour and minutes of the Start and End of the interval 1. If you do not wish to
Interval 2, Start/EndHour and minutes of the Start and End of the interval 2. If you do not wish to
day, month, yearOperational date of the timer. To indicate any day, month or year, leave “--” (for
Sunday, etc.Day of the week for weekly arrangements. Valid only when the Day, month,
Force nightActivation of the timer will switch the panel to Night mode. The panel cannot be
Set dayActivation of the timer will switch the panel to Day mode. The panel can be
specify an interval, leave “--”.
specify an interval, leave “--”. If both intervals are set as “--”, the timer will
operate on a 24 Hour basis.
example, every 3rd of the: day=3, month = “--”, year = “--”). Day, month or
year should be “--”, if you wish to create the setting using the day of the week.
year are set as “--”. If you select Holiday the timer will operate on the
respective dates (refer to paragraph 9.5 - Setting holidays).
switched back to Day mode until the set timer interval expires. Once the set
timer interval expires, the panel can be switched back to day mode either by
another timer or manually from the panel (refer to paragraph 16.2 - Day/Night Mode).
switched back to Night mode either by another timer or manually from the panel.
Set nightActivation of the timer will switch the panel to Night mode. The panel can be
switched back to Day mode either by another timer or manually from the panel.
ZoneNumber of the zone to be bypassed/unbypassed.
Disable zoneActivation of the timer will bypass the specified zone.
Enable zoneActivation of the timer will unbypass the specified zone.
Preparing the programming data43
Installation and programming manual
Chapter 10
Configuring the loop
When configuring the loop, you must define the typology (refer to Appendix A, Appendix B and Appendix C)
and wiring (two or four wires) and also the connected devices. The connected devices may belong either
to the fire control system (e.g.: detectors, modules, bells, etc.), or to the gas extinguishant system. The
panel considers each device a “point” which must first be enrolled and then programmed.
Note:To install devices other than those specified in the appendix, you must use an input module to interface
between the loop and the devices concerned.
Each point is associated with a device type (e.g. optical smoke detector) and an address.
The following section describes the different ways of configuring loop points:
1. add/remove a point, using the respective address or type
2. assign an address to a device and allow it to acquire data from the panel
3. ask the panel to acquire data from the devices (all or only new devices) and assign their addresses
(only for INIM and Argus loop types).
Once the configuration has been completed, you can go on to program each separate point (refer to paragraph
11.1).
Attention:You must insert the respective programming jumper (J8 or J9) before starting the
addressing procedure (J8 for programming from panel; J9 if for programming from PC).
Note:In the first case, you can configure the loop without panel linkup, for example, at your office. The
configuration can be downloaded to the panel later. In the other two cases, you can configure the loop
from the panel or via a PC connected to the panel.
Once the loop has been configured, any form of tamper to the device (e.g.: disconnection,
dislodgement, etc.) will generate a fault signal.
10.1Defining loop typology
From panel: <key>, Programming, Configuration, Loop, Ok, Loop Parameters
Select the loop type (INIM, Argus, Apollo) and wiring type (2 or 4 wires).
10.2Adding/Removing any type of device manually
From the panel: <key>, Programming, Configuration, Loop, Ok, Add point or Delete point
A new device can be added to the system configuration manually:
1. Select an unassigned address.
2. Associate the respective device type with the selected address.
3. Set the device address.
4. Connect the device to the loop.
Note:
44Configuring the loop
This method is recommended for the addition or removal of a few devices only. The first configuration of a
new installation should be done using the
method, refer to paragraph A.1.1 - Re-addressing and paragraph B.5.2 - Automatic setting of devices) or
Automatic Enrolling
the
separate device.
option (suitable for all devices) after an initial setting done manually on each
Automatic enrolling
option (only for devices that accept this
Installation and programming manual
1. Select the address that corresponds to the physical position of the device (an assigned or unassigned
address), press Ok
2. Press S or T to select the address and device type.
Note:To remove a point, enter ‘0’ in the "Type" programming field.
Once the points have been added, you must complete their programming (refer to paragraph 11.1 Programming fire-detection points).
10.3Configuring the devices
Refer to Appendix A, Appendix B and Appendix C.
10.4Checking enrolled/addressed devices
After initializing the enrolling procedure (for all devices) or the automatic-addressing process (only for
devices that accept this method), you must wait for its completion, then compare the number of enrolled
detectors/devices with the total number of detector/device placements.
If the totals differ:
1. Press Ok to access Programming points (refer to paragraph 11.1).
2. Search the list for the devices that have not been found by the panel.
3. Clear the anomaly and re-initialize the addressing process.
If the totals match:
1. Press Ok to access Programming points.
2. Proceed with the programming process of all the points.
Configuring the loop45
Installation and programming manual
Chapter 11
Programming fire detection points
The panel sees all loop devices as points, therefore, the point must be duly programmed in order for the
panel to determine their operating principles. Each point can be set up as an input and/or output.
If a point is programmed as a 'fire-detection' point, the panel will deal with it as such and manage it
accordingly.
Danger:In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance with EN54-
2 regulations, delays (pre-alarm time) must not be associated with the activation of the
Dialer or “ALARM NAC” if activation is triggered by a manual callpoint.
11.1Programming fire-detection points
From panel: <key>, Programming, Progr. Point, select point, Ok
11.1.1 General parameters
AddressDevice address assigned during configuration.
Device typeDescription of the device type assigned during configuration.
<Point123> Point Description Example: “Downstairs kitchen”.
Led blink
(INIM and Argus
devices only)
Remot. blink
(for INIM devices only)
ExtinguishDetermines whether the point is for fire detection or extinction
ZoneThe zone the point belongs to.
<Zone nn> Zone label (description) assigned during the zone programming phase.
YESThe LED associated with the point will blink each time the control panel
transmits a signal to the point.
NOThe LED associated with the point will not blink
YESThe detector repeater-output will activate briefly each time a signal is
transmitted to the point.
NOThe detector repeater-output will not activate each time a signal is
transmitted to the point.
YESThe point is for extinction purposes
NOThe point is for detection purposes
11.1.2 Detector parameters
LevelFor detectors only. Real-time value The value depends on the type of detector (Heat, Smoke,
etc).
Day
sensitivity
Night
sensitivity
WarningFor detectors only. Early warning threshold (the detector will generate an early-warning signal,
46Programming fire detection points
For detectors only. Alarm threshold (the detector will trigger alarm if the analysis value
exceeds this threshold). If enabled (refer to paragraph 11.1.3 - Signals emitted by the point (Input)), it will generate a signal. The value depends on the type of detector. Two sensitivity
values are applicable, in accordance with the control panel operating mode (day or night).
if the analysis value exceeds this threshold). If enabled (refer to paragraph 11.1.3 - Signals emitted by the point (Input)), it will generate a signal. The value depends on the type of
detector. If a signal is not required, set the level at “---”.
Installation and programming manual
VerifyFor detectors only.
YES
NOIf the device value exceeds the set threshold, the panel will generate an instant alarm.
If the device value exceeds the set threshold, the panel will not generate an instant but will
wait to see if the device values exceed the threshold again within the pre-set time (refer to
paragraph 9.2 - Setting delays and times). If the device value exceeds the set threshold
again, the panel will generate an alarm, otherwise, it will restore to standby.
11.1.3 Signals emitted by the point (Input)
AlarmYES If the analysis value exceeds the alarm threshold (refer to paragraph 11.1.2), it will
generate an alarm signal to the panel, trigger an alarm on the zone it belongs to
(primary zone) and activate the associated outputs. The point cannot be used for
Monitoring purposes.
NOIf the analysis value exceeds the alarm threshold, it will send an alarm signal to the
panel, but will not trigger an alarm on the zone it belongs to (primary zone) or activate
its associated outputs. If alarm events do not require signal transmission to the panel,
select Monitor as the activation signal.
Pre-alarmYESIf the analysis value exceeds the alarm threshold, it will send a pre-alarm signal to the
panel and trigger the pre-alarm time of the zone it belongs to. When the pre-alarm time
expires, it will generate an alarm on the zone it belongs to (primary zone) and activate
its associated outputs. The point cannot be used for Monitoring purposes.
NOIf the analysis value exceeds the alarm threshold, it will send an alarm signal to the
panel, without activating the pre-alarm time.
FaultYES If one of the possible faults occurs on the input (refer to Chapter 17 - Diagnostics and
fault solutions), it will send a fault signal to the panel and generate a fault on the zone it
belongs to (primary zone).
NOFaults that occur on the input will be ignored.
WarningYES If the analysis value exceeds the warning threshold, it will send a warning signal to the
panel and the respective zone.
NOIf the analysis value exceeds the warning threshold, the event will be signaled on the
panel but not on the zone.
MonitorYES If the analysis value exceeds the alarm threshold, it will send a 'Monitor' signal to the
panel and activate all the associated zone outputs.
Attention:Enablement of the Monitor signal inhibits the Alarm and Pre-
alarm signals. If an input is programmed as 'Monitor', it will be
unable to emit Alarm and Pre-alarm signals.
NOThe point will operate as an alarm point.
ActionsEXAMPLE: keyswitch that controls specific zones. Only for detectors with the "ON-OFF" option.
Disable
zone
Test zoneNOOnly for detectors with the "ON-OFF" option. Activation of the point generates test
Night
prealarm
Monitor
restore
YES Only for detectors with the "ON-OFF" option. Activation of the point bypasses the
selected zone or zones.
conditions on the selected zone or zones.
Enable or disable the pre-alarm time during night mode.
For example, buildings closed during the night do not require pre-alarm signaling.
Only for the Monitor input. The outputs will restore to standby when alarm conditions clear.
YES
EXAMPLE: The value exceeds the temperature threshold and thus activates a fan. When the
temperature value returns to normal, the detector should stop signaling.
NO
Only for the Monitor input. If alarm conditions clear, the outputs will remain active.
EXAMPLE: The cooling system continues working until it is switched off manually.
FilteredYES After a re-arm operations, the control panel will ignore the point concerned for the set
Filter time
NOAfter a re-arm operations, the control panel will not ignore the point concerned.
Programming fire detection points47
11.1.4 Signals that activate the output
Installation and programming manual
AlarmYES
NO
Pre-alarmYES
NO
FaultYES
NO
WarningYES
NO
MonitorYES
NO
DisableYES
The output will activate when at least one of its assigned zones goes into alarm status. A zone will
generate an alarm when at least one of its input points goes into alarm status.
The output status will remain unchanged even if one of its assigned zones goes into alarm status.
The output will activate when at least one of its assigned zones goes into pre-alarm status. A zone
will generate a pre-alarm when at least one of its input points goes into pre-alarm status.
The output status will remain unchanged even if one of its assigned zones goes into pre-alarm
status.
The output will activate when at least one of its assigned zones signals fault status. A zone will
generate a fault when at least one of its input points signals fault status.
The output status will remain unchanged even if one of its assigned zones signals fault status.
The output will activate when one at least one of its assigned zones goes into early-warning
status. A zone will generate an early warning when at least one of its input points goes into earlywarning status.
The output status will remain unchanged even if one of its assigned zones goes into early-warning
status.
The output will activate when at least one of its assigned zones goes into Monitor status. A zone
will go into Monitor status if an input point goes into Monitor status.
The output status will remain unchanged even if one of the assigned zones goes into Monitor
status.
The output will activate when at least one of its assigned zones is bypassed.
NO
Double
alarm
Primary
Zone
Secondary
Zone
Zone group YES
Point echoYES
YES
NO
XX
00
XX
--
NO
NO
For example, an external LED outside a hotel room which replicates the status of the detector
located inside.
The output status will remain unchanged even if one of the assigned zones is bypassed.
The output will activate when at least two points assigned to the specified zones go into alarm
status.
The output will activate when at least one of the specified zones goes into alarm status.
Number of a zone that activates the output. Successive zone group option = YES, the number of
the first zone in the group.
The output will activate when at least one of the system zones activates, that is, when the Alarm
NAC output (Panel Alarm) is active.
Number of another zone that activates the output Successive zone group option = YES, the
number of the last zone in the group.
The output can be activated by the primary zone only.
The output activates when one of the zones in the zone group activates (i.e. between the Primary
zone and Secondary zone).
The output will activate when either one of the two zones indicated activates.
The output activates even if the input point is active.
The output will activate only when one of the signals selected under “Output-----” occurs.
Silenceable YES
NO
Reset echoYES
DurationOutput activation time
EquationNumber of the equation that activates the output.
The output can be silenced (switched Off) by the
The output cannot be silenced. Any
The output will activate after Reset.
SILENCE
SILENCE
commands will be ignored.
button on the panel.
Note:Some of the parameters do not apply to certain devices. Accidental programming will not interfere with
the panel functions.
48Programming fire detection points
Installation and programming manual
NO
NO
Automatic
Activation
Automatic
Pre-Extinguish
Time
Automatic Pre-Extinguish
Time NOT Expired
Stand By
ACTIVATION
Stop?
NO
YES
Manual
Activation
Input
STOP-EXT
STOP-EXT
EXTINGUISH
Manual
Pre-Extinguish
Time
Manual Pre-Extinguish
Time NOT Expired
Pre-Extinguish
Time Expired
Wait for
RESET
Activated
until
Reset
NO
Extinguish
Time
YES
PS
activated
?
YES
MAX 3
Discharge attempts
Extinguish
Confirmed
?
Input
Restored
?
YES
NO
Chapter 12
Programming the extinguishant module
The extinguishant module manages a gas extinguishant system activated by automatic or manual
commands:
• automatic commands triggered by the fire-control panel when the programmed zones go into alarm status.
• manual commands from devices connected to the extinguishant module inputs or set up as fire-detection
loop input point.
The extinguishant module uses its own terminals and the loop points to provide its conditions of activation
and command the outputs:
To ensure proper programming of the gas extinguishant system you must:
1. Configure the extinguishant module
2. Program the operating principles
3. Program the input and output extinction points
12.1Configuring the extinguishant module
From panel: <key>, Programming, Configuration, BUS, Extinguish board, Ok
This option allows the panel to determine how many extinguishant modules are connected (this model
accepts one module only).
12.2Programming the module
From panel: <key>, Programming, ExtinguishBoard, Ok
Program the parameters that define the operating principles of the system.
12.2.1 Parameters
Mask zoneZones that will activate the fire extinguishant system if one (or more) of their input points
goes into alarm status.
Mode:At least 1: If you select this mode, only one of the selected zones need be in alarm status in
Confirm
extinguish
Do not confirm
Wait for pressure
switch
Wait for flow
detector
order to activate the fire extinguishant system.
At least 2: If you select this mode, at least 2 of the selected zones must be in alarm status in
order to activate the fire extinguishant system.
ALL: If you select this mode, ALL the selected zones must be in alarm status in order to
activate the fire extinguishant system.
Extinguishant module feature that provides confirmation of extinguishant gas release.
If an “Extinguish” event occurs, the extinguishment module will activate the VALVE output
(for the pre-set time) and the RELEASED output without awaiting confirmation of
extinguishant gas release.
The RELEASED output will be activated when the Extinguish time expires, that is, if the
“pressure switch” signal has been activated (from the pressure switch input or from an point
set up as a “pressure switch” input). The “pressure switch” signal will be considered valid only
when the signal persists after expiry of the Extinguish time.
EXAMPLE: You can connect a pressure-drop signaling device to the PRESS. input or an input
point set up as a “pressure switch” (the device will signal when the cylinders empty thus
confirming that the protected space has been successfully saturated).
The RELEASED output will be activated when the Extinguish time expires, that is, if the
“from flow detector” signal has been activated during this phase (from the pressure switch
input or from a point set up as a “flow detector” input).
EXAMPLE: You can connect a gas-flow signaling device to the PRESS input or a point set up as
a “flow detector” input (the device will signal when gas is being released).
Pressure switchDefines the significance of the signal coming from the PRESS input.
Supervisory: activation of the input signals a drop in gas extinguishant pressure.
From pressure: activation of the input indicates that the gas cylinders are empty, therefore,
the protected space is saturated and activates the “confirm extinction from pressure switch”
signal.
From flow detector: activation of the input indicates that gas has been released and
activates the “confirm extinction from flow detector” signal.
Pre-extinguish
Time
Extinguish TimeLength of time the electrovalve remains active, starting from the end of the pre-extinguish
50Programming the extinguishant module
Duration of the automatic Pre-extinguish Time, activated by a zone in alarm status.
phase. If this value is not defined, the extinction phase will last until a “stop extinction”
command is received (from a STOP-EXT input, or point programmed as “stop ext.” or from a
button on the panel) or until the RESET button is pressed.
Installation and programming manual
Manual Preextinguish Time
Confirm
extinguish time
Pause between
discharges
The duration of the manual pre-extinction phase, activated by a MAN-EXT input or extinction
point set up as a manual extinction input or manual extinguish button.
Delay between activation of the electrovalve output and the pressure switch activation
analysis (if programmed as Confirm extinguish).
EXAMPLE: In this way, the device connected to the pressure switch input can detect the
pressure drop inside the cylinders and intervene.
Length of the pause between one gas discharge and another in the event of non-confirmation
of gas discharge (extinguishant module allows three discharge events).
12.3Programming extinction points
From panel: <key>, Programming, Progr. Point, select point, Ok
The extinguishant module manages three inputs (e.g.: a button to stop the gas extinguishant) and three
outputs (e.g.: a bell that alerts building occupants of the imminent release of gas). Under certain
circumstances, it may be difficult to connect devices directly to the module, in such cases, you may find it
easier to connect the extinction devices to the fire detection loop.
Programming a point as an Extinction point will allow the panel to identify it as an fire extinction device and
manage it accordingly.
12.3.1 General parameters
ADDRESSDevice address assigned during configuration.
<device>Name of the device assigned during configuration
POINT 123Point Description
ExtinguishDetermines whether the point is for fire detection or extinction
YESthe point is for extinction purposes
NOthe point is for detection purposes
Extinguish
boards
Number of extinguishant modules (currently 1 module only)
12.3.2 Actions or operating mode of the input
Input Active:
------------No signal, the point is disabled.
Disable
extinguish
Disable
manual
Disable
auto
Disables extinguish commands, in the same way as the DISABLE EXTINGUISH
button on the panel.
EXAMPLE: During maintenance work on the fire extinguishant system.
Disables manual extinguish commands, in the same way as DISABLE MANUAL
button on the panel.
EXAMPLE: During maintenance work on a manual extinguish button.
Disables automatic extinguish commands, in the same way as DISABLE AUTO
button on the panel.
EXAMPLE: During maintenance work on the panel that may trigger unnecessary
extinguish commands to the extinguishant module.
Pressure
switch
Confirm
extinguish
Programming the extinguishant module51
Same as the PRESS. input, but programmed as “Pressure switch”.
EXAMPLE: This input can manage a pressure detector that measures and signals
pressure drop inside the gas extinguishant cylinders (thus confirming gas release
and the successful saturation of the protected space).
The point provides confirmation of extinguishant gas release.
Installation and programming manual
Monitor
restore
Manual
extinguish
Lock
extinguish
YESThe signal can be reset (e.g.: by releasing the button).
NOThe signal will persist until RESET button on the panel is pressed.
Same as MAN-EXT input.
EXAMPLE: A point connected to a Start-extinction button located inside the
protected environment.
Same as STOP-EXT input
EXAMPLE: A point connected to a Stop-extinction button located inside the
protected environment.
12.3.3 Signals that activate the point
Output-------------The point is not activated by any signal.
ExtinguishPoint activated at the same time as the RELEASED output programmed as
“Extinguish”.
Preextinguish
Confirm
extinguish
Point activated at the same time as the PRE-EXT output.
Point activated by a “Confirm extinguish” input point.
Lock
extinguish
SilenceableYESThe output can be silenced.
NOThe output will remain active until the RESET button on the panel is pressed.
DurationLength of time the outputs will remain active.
Point activated by the activation of “Lock extinguish” input point or by the STOPEXT input.
52Programming the extinguishant module
Installation and programming manual
Extinguish board x
SmartLevel y
Repeater z
OK to Continue
Chapter 13
Configuring the devices connected to the RS485 BUS
From panel: <key>, Programming, Configuration, BUS, Ok
The SmartLetUSee/LCD-Lite repeaters are clone panels. They are equipped with displays and LEDs and
replicate all the information provided by the control panel. The panel supports up to 4 repeaters which,
under normal circumstances, should be located at entrances/exits, in such way as to allow building
occupants or fire officers to view alarm details without going too far inside the building.
The SmartLevel power-supply stations provide load current to remote apparatus located within the area
covered by the system. The control panel supports two power-supply stations, for a maximum of six
devices connected to the RS485 BUS.
After installing and addressing each device, you must include them in the system configuration.
This will allow the panel to determine which devices are connected to
the BUS and indicate those found.
Note:The panel uses the screen above, to indicate the current configuration of repeaters and extinguishant
modules. if you press OK (working from this screen), the panel will search the communication BUS and
include any newly found devices in the configuration.
Configuring the devices connected to the RS485 BUS53
Installation and programming manual
Control panel
In service
17/05/11 18:23
Chapter 14
Closing the programming session
Once you have completed the programming, remove the panel/PC programming jumper. The panel will be
ready to go into service, and the display will be as follows.
Double check the functionality of all the input/output devices.
14.1Restoring factory settings
From panel: <key>, Programming, Factory data, Ok
If you select this option, you will access the 'Confirm' screen. If you press Ok on this screen, all the current
programming data will reset to the default values (factory settings).
Once this operation is confirmed, the control panel will ask you to choose the required language. Using the
arrow keys, select the language and then press Ok to confirm your selection.
54Closing the programming session
Installation and programming manual
Program.
From PC
Chapter 15
SmartLeague software
15.1Overview
The SmartLight system can be programmed from the panel or from a PC. You can access all the
programming process via the SmartLeague programming and management software for INIM Electronics
security products.
The SmartLeague software programme allows you to access all the system parameters which can be
accessed via the control panel. In addition, it provides a clear, complete view of the status of the system
and its parts and thus a more precise programming process. The programming process is further enhanced
by a greater number of parameters for each point and the use of combinatory logic in the zone “equations”.
For further details regarding the SmartLeague software programme, refer to the respective user manual.
15.2The Solutions
Each Solution comprises an installation structure and the respective group of programming parameters.
You can save the system solution to the SmartLeague database and use it for maintenance purposes or as
a “model” for other systems.
Each solution is dedicated to a device type and has its own programming interface. In this way, it is
possible to compare different solutions, or keep two solutions open (one real and the other for test
purposes), in order to verify step by step the effects of the programming process.
A solution can be created and changed without computer to device link up. For example, you can prepare a
system layout and/or set parameters without leaving your office. The data can be downloaded to the
system when you are ready.
15.3Enable programming via PC
All functions can be accessed via PC without the need of connecting to the control panel; this connection
will be necesary only during data upload (transfer of data from the PC to control panel) and download
(transfer of data from the control panel to PC).
The extinguishant module can be programmed only via the SmartLeague software, whereas, the
configuration and programming of the points can be done from the panel. If the programming jumper is
not inserted, access to the programming via PC will be denied.
1. Remove the frontplate.
2. Insert the jumper (paragraph 4.1 - [P]), the respective message will
appear. The panel keys will be disabled.
3. Using the cable (refer to paragraph 7.2 - Connecting the RS232 PC
serial link), connect the PC to the serial port (refer to paragraph 4.1 -
[D]).
SmartLeague software55
Installation and programming manual
Chapter 16
Maintenance
The following operations must be carried out regularly.
1. Using a damp lint-free cloth, remove any dust that may have gathered on the control panel (do not use
any kind of cleaning product or solvent!).
2. From panel: press <key>, Test LED, Ok to test the LEDs.
3. Check the battery efficiency and change them if necessary.
4. Check the integrity of all wires and connections.
5. Ensure that there are no insects inside the control panel.
6. Carry out maintenance on the detectors (clean the detection chamber).
Note:Points 1 and 2 can be carried out by authorized persons, whereas all other points must be carried out
by qualified technicians.
16.1View Events
The system displays information regarding real-time events of major importance and disregards those of
minor importance (e.g.: if the system is dealing with three fault events when a pre-alarm event occurs, the
fault events will be disregarded and cleared from the display and the pre-alarm will take priority). All
events are saved to the log and can be viewed.
16.1.1 Signaling on the display
If several events of the same type occur, only the first will be shown on the display. If several alarms occur,
the first alarm will remain on the first line of the display and the most recent alarm will be shown on the
line below.
To view the events on the display, press button S or T.
16.1.2 Viewing the events log
Press <key>, View log, Ok: all the recorded events (maximum 100) can be viewed in chronological
order.
16.2Day/Night Mode
16.2.1 Day
There are people in the building, therefore, those in charge of the safety of the building and its occupants
should be duly informed before the evacuation command is given.
SilenceSilences (turns Off) the panel beeper and silenceable outputs. The Silence command will be
undone automatically, if a new alarm event occurs (e.g.: another detector signals alarm
conditions).
Pre-alarmSome points can be programmed to signal pre-alarm status. If no-one intervenes during the
pre-alarm phase, the system will generate an alarm when the programmed pre-alarm time
expires. Refer to paragraph 11.1 - Programming fire-detection points to enable/disable the
pre-alarm time of points.
Alarmdetectors can be programmed with a Day mode alarm threshold and a Night mode alarm
threshold, refer to paragraph 11.1 - Programming fire-detection points.
56Maintenance
Installation and programming manual
POINT 123
j
<point123>
In test
l
16.2.2 Night
There are no people in the building, therefore, there is only one person in charge of building safety (e.g.:
night watchman, guard).
SilenceThe Silence command holds off signaling. The Silence phase will run for the pre-set time. If
no-one intervenes during this phase, the system will undo the silence command and the
alarm will continue. To change the night-mode silence time, refer to paragraph 9.2 - Setting delays and times.
Pre-alarmThe pre-alarm signal can be disabled on certain points. Alarm events will generate instant
alarms. Refer to paragraph 11.1 - Programming fire-detection points to enable/disable the
pre-alarm time on points during Night mode.
AlarmDetectors can be programmed with a Day mode alarm threshold and a Night mode alarm
threshold, refer to paragraph 11.1 - Programming fire-detection points
16.2.3 Changing Day/Night mode manually
From the panel:<key>, Settings
16.2.4 Changing Day/Night mode automatically
Setting up a timer (refer to paragraph 9.6 - Setting the Timers) to toggle the panel status.
16.3Bypassing a zone or point
From the panel:<key>, Disablement, Point or Zone - select the point or zone, press Ok
Under certain circumstances (e.g. maintenance or fault), it may be necessary to bypass a zone or a point.
Bypassed zones or points cannot generate fault or alarm signals and cannot be activated.
16.4Bypass Dialer output and supervised fault
From the panel:<key>, Disablement, Outputs, Ok
Under certain circumstances (e.g. maintenance or fault), it may be necessary to bypass the dialer outputs
(paragraph 4.1 - [E]) and Fault NAC (paragraph 4.1 - [I]). The bypassed object cannot be activated.
Bypass may be necessary in the event of fault signaling triggered by the Dialer or Supervised output (refer
to Chapter 17 - Diagnostics and fault solutions).
16.5Testing points and zones
From the panel:<key>, Maintenance, Test point, select the point, press Ok
From the panel:<key>, Maintenance, Test zone, select the zone,press Ok
Maintenance work often entails point or zone tests. Points or zones in test status cannot generate faults or
alarms signals, and cannot respond to activation signals. For example, if a zone is in test status, you can
inspect all the zone detectors (points) without generating false alarms.
Note:When a detector (point) is put in test status, its LED will go On for several seconds.
1. Press Ok to put the detector (point) or zone in test/operating
status.
2. Press SorT to go to the adjacent point or zone.
16.6Force the LEDs and point outputs
From the panel:<key>, Maintenance, Test outputs, select the point, press Ok
From the panel:<key>, Maintenance, Test LED, select the point, press Ok
Maintenance57
Installation and programming manual
Point 123
j
<point123>
Output
ON
l
Maint. Fault
dd/mm/yy hh:mm
Monday
Dust
Average xxx%
Maximum xxx%
Point nnn
After maintenance or on first startup, it may be necessary to force a point output or detector LED. For
example, the On status of a detector LED allows fast identification of the detector location on the protected
premises.
1. Press Ok to activate/deactivate the LED or output
2. Press SorT to go to the adjacent point or zone.
16.7Set the date for the next maintenance session
From the panel:<key>, Maintenance, Maintenance, Ok
If you have set the date of the next maintenance session, the system will signal a fault event on the
specified date. Only a new date, selected via this menu, will clear this fault signal.
16.8Loop Diagnostics
From panel:<key>, Maintenance, Diagnostic
This menu will allow you to carry out diagnostics on all the smoke detectors connected to the loop. After
the diagnostics phase, the panel will show the maximum level of dust detected, the detector concerned and
the average dust level of all the detectors.
The loop diagnostics and that of each of its point can be done via FireGenius software supplied with the
EITK1000 driver (refer to Appendix A - Enea series devices). This software, in addition to allowing use of
the driver via PC, offers a graphic interface which provides a detailed view of the entire loop.
For a detailed description, refer to the respective user manual.
58Maintenance
Installation and programming manual
Chapter 17
Diagnostics and fault solutions
Danger:Only authorized operators (Level 2 or 3) may search for, and correct faults.
17.1“Open I/O” fault
The panel is unable to find the EOL resistor on the supervised input/output terminals. The next line
indicates the specific terminals (NAC, on a module connected to the loop etc.).
Check the EOL resistor connection on the last device. Using a tester check that the resistor has not burnt
out.
17.2“Shorted I/O” fault
A short-circuit has been detected on the input/output terminals. The next line indicates the specific terminals
(NAC, on a module connected to the loop etc.). Check the device connections and cable sections.
17.3Loop fault
Message on displayCauseRemedy
Short-circuit
on A
Short-circuit
on R
(for 4-wire loops
only).
Loop Open
(for 4-wire loops
only).
No loop continuity
between the “Loop-O”
and “Loop-I”
terminals.
A short-circuit has been detected
on the wiring section between
the “Loop - O” terminals and the
first isolator on the loop.
A short-circuit has been detected
on the wiring section between
the “Loop - I” terminals and their
nearest isolator on the loop.
One or more open isolators on
the line.
Interrupted cableDisconnect the "Loop-I" terminals of the panel; search the loop until
The number of devices found by
the panel is less than expected.
Duplicated address: means the
same address has been assigned
to two devices.
Check the connections and integrity of the wiring on the section
concerned.
Check the connections and integrity of the wiring on the section
concerned.
Check all the isolators on the loop: the LED of at least one of the
isolators will indicate “isolated” status. Once you have found the open
isolator, check the connections and integrity of the wiring on the cable
section between the open isolator and the successive one.
you find the last device on the line in working order. To check whether
a device is working or not, access the Main menu from the panel and
select “
turn the various device LEDs On and Off (refer also to Chapter 16 - Maintenance). Once you have found the last device on the line in
working order, check the connections and integrity of the wiring in the
adjacent cable section.
Using the “
devices that are not recognized (refer also to Chapter 16 - Maintenance). Check the wiring of the devices concerned and their
respective addresses.
Using the “
of the device with the duplicated address; find the loop devices with
the duplicated address and assign them new addresses. Refer also to
Chapter 16 - Maintenance.
Maintenance, Test zone”. This menu will allow you to
Maintenance, Test zone” menu, identify the
Maintenance, Test zone” menu: turn On the LED
17.4Testing the Loop
For the distinction of the internal LEDs ([A], [B] or [C]) refer to paragraph 5.2.
17.4.1 Testing the Loop status LEDs
Verify that the loop transmission LED [B] or [C] that blinks matches the loop type setting. In the event of
mismatch, check the loop parameter settings.
Diagnostics and fault solutions59
Installation and programming manual
17.4.2 Testing the Loop response LED
The green loop LED [A] should flicker each time an interrogated device responds.
If the green LED goes On solid, it means that there is a conductive path between the two poles of the loop
that allows current to circulate and thus blind the device response.
Check that there is nothing other than the devices connected to the loop.
17.5Repeater faults
If the number of repeaters recognized by the control panel is less than expected (refer also to Chapter 13 Configuring the devices connected to the RS485 BUS):
1. Check that the address of each repeater has been set properly (by means of the DIP switches.
2. Check that the cabling is intact.
3. Check the connection polarity.
4. Check that the EOL jumper is in the EOL position only on the last repeater connected the BUS.
5. Using a tester, measure the voltage across the +24 V and GND terminals of the RS485 BUS.
If the voltage is less than 20 V, it means that the resettable protection fuse is open and the current
draw of the devices connected to the BUS is excessive.
Disconnect the BUS devices and reconnect them one by one until you find the problem.
17.6Battery Fault
17.6.1 Battery Disconnected
The battery is not connected or has failed the batter efficiency test.
1. Allow the batteries to charge for several hours.
2. If the fault signal persists, disconnect the batteries from the panel and test them separately.
3. If only one of the batteries has a voltage below 12.5 - 13 V:
• Replace the faulty battery only.
• Allow the batteries to charge for several hours.
• Check that the fault has cleared.
4. If both batteries have a voltage of 12.5 - 13 V, it means they are both inefficient (even though the
voltage without load is correct).
• Replace both batteries.
• Allow them to charge for several hours.
• Check that the fault has cleared.
• Disconnect the batteries, then check that the voltage on the control-panel battery connector is 27.6 V, or
follow the procedure described in paragraph 6.12.1 - Connecting a thermal probe.
17.6.2 Low Battery
The batteries are running low.
This signal should be present only during primary power source failure (Main 230 Vac). Mains power must
be restored in order to charge the batteries.
17.7Other faults
The panel shows the message:Meaning
Dialer Fault
24V output
Mains fail
Ground fault
Lost
Duplicated Add.
Maintenance
60Diagnostics and fault solutions
Trouble on the dialer communication line (dialer output).
Short-circuit on the AUX terminals protected by the resettable fuse.
Primary power failure (230 Vac).
Voltage dispersion detected
A loop device (included in the configuration) cannot be found.
There are two loop devices with the same address.
The pre-set date for Maintenance has expired.
Installation and programming manual
Appendix A
Enea series devices
All devices in INIM ELECTRONIC's new Enea series of addressableanalogue detection devices are LPCB certified and carry the CE mark
according to CPD.
Each device is equipped with a short-circuit isolator which, in the event of short-circuit between two
control-panel (loop) connection wires, is capable of interrupting the negative wire and isolating the wire
section concerned. The loop supports up to 240 devices. Each device is identified by a factory-assigned
serial number which allows automatic addressing.
The Enea series of INIM Electronics provides three analogue detector model:
• Optical chamber with sealed upper-part and 500 micron hole-diameter mesh insect screen
• Tricolour LED - Red for alarm, Green flash for standby and for identification from the control panel;
Yellow for fault status
• Supervised remote output configurable from the control panel
• Automatic recognition of remote signaller connection
• Drift compensation for sensor drift caused by dust in the chamber
• Sensitivity selection for smoke and heat thresholds
• Operating mode selection (for ED300 version) - Only smoke; Only heat
• AND mode, OR mode, PLUS mode
• Complete diagnostics - provides contamination level and real-time values
• Memory of the smoke and temperature levels measured in the five-minute period prior to the last alarm
detected
• Bypass plate on base guatantees continuity in the event of removal of the detector from the line
For further details regarding the precise features and technical specification of each device, refer to the
respective instructions booklet.
TypeModelDescription
DetectorsED100 Optic smoke detector
ED200Heat detector
ED300Smoke and heat detector
BasesEB0010Mounting base
EB0020Relay base
ESB010Sounder base (to be installed under EB0010 mounting base)
ESB020Sounder base and beacon (to be installed under EB0010
mounting base)
ModulesEM312SRInput and Output module
EM110Input module
EM311Micromodule
EM344S4 input + 4 output conventional zone interface
EC0010EManual callpoint for outdoor installation (IP67)
Enea series devices61
Installation and programming manual
SoundersES0010REAddressable loop-powered sounder unit in red enclosure
ES0020REAddressable loop-powered sounder&beacon unit in red enclosure
ES0010BEAddressable loop-powered sounder unit in white enclosure
ES0020BEAddressable loop-powered sounder&beacon unit in white
enclosure
ES0020Loop-powered addressable warning sign
DriverEITK1000Kit for the configuration, maintenance and diagnostics of systems
EITK-DRVDriver for zones with IRIS series devices or loops with ENEA
EITK-BASEBase for IRIS and ENEA series detectors
EITK-PWSPPower supply for the EITK-DRV driver
using IRIS and ENEA series devices
series devices
A.1Configuring Enea devices
The distinct serial number of each detector is shown on the device information label. Manual addressing is
unnecessary as the addressing phase is automatic. To address devices, connect them to the loop and work
through the following steps.
A
BB
Figure 29 - The reverse side of Enea detectors
The serial number is shown on the information label [A] and on two smaller removable labels [B]. When
installing the devices, it is strongly advises to remove the small labels and place one on the system layout
and the other on the mounting base. This will facilitate device tracing and re-location operations.
Note:Each loop supports up to 240 devices.
A.1.1Re-addressing
After connecting the devices to the loop, you must then configure the loop.
The addressing phase allows the system to determine the serial number of each device connected to the
loop and assign a logic address (a number between 1 and 240). The system will use this number to
indentify the point during all the system programming operations.
From the panel: insert the jumper in programming-mode position, <key>, Programming,
Configuration, Loop, Ok, Loop parameters, then select INIM as the type of protocol
and 4 Wires as the wiring method by pressing Ok, Esc, Auto configure, Readdress
Once this operation is complete (which may take several minutes), a summary screen - indicating the total
number of devices found - will be shown. Ensure that the number of devices found corresponds to the
number of devices actually installed.
62Enea series devices
Installation and programming manual
Via PC: select the loop -> Parameter Tab to select the type of protocol and wiring, select the icon and
select Re-address loop.
Once this operation is complete (which may take several minutes), the software programme will design a
layout of the loop wiring ishowing all the connected devices.
A.2Reading the loop
This operation allows the system to learn the serial numbers of all the devices connected to the loop and
enroll the logic addresses (number between 1 and 240) assigned to them during the addressing phase.
Note:The loop reading phase can be carried out only on previously addressed loops, either via the control
panel or by means of an EITK-DRV loop driver.
From the panel: insert the jumper in programming-mode position, <key>, Programming,
Configuration, Loop, Ok, Loop parameters, then select INIM as the type of protocol
and 4 Wires as the wiring method by pressing Ok, Esc, Auto configure, Acquire
Once this operation is complete, a summary screen - indicating the total number of devices found - will be
shown. Ensure that the number of devices found corresponds to the number of devices actually installed.
Via PC: select the loop -> Parameter Tab to select the type of protocol and wiring, select the icon and
select Read loop.
Once this operation is complete (which may take several minutes), the software programme will design a
layout of the loop wiring ishowing all the connected devices.
A.3Updating the loop
This operation must be carried out each time a device is replaced or added to the loop. After replacing or
adding devices to the loop, work through the following operations.
From the panel
Adding/Replacing a device: insert the jumper in the programming position, <key>, Programming,
Configuration, Loop, Ok, Add point, select the point and enter the serial number of the
new or replacement device.
Removing a device: insert the jumper in the programming position, <key>, Programming,
Configuration, Loop, Ok, Delete point, select the point, press Ok to confirm the
operation.
Via PC: select the loop from the tree structure, then select the icon followes by Update Loop.
Once this operation is complete (which may take several minutes), the software programme will show a
double layout which will allow you to compare the previously-saved loop configuration with the new one.
The part with changes will be highlighted.
In order to continue, you must accept all the highlighted changes and double-click on any icons which are
not green, or press the Accept All button) and press CONTINUE. A new addressing phase (which may
take several minutes) will transfer the new configuration to the control panel.
Enea series devices63
Installation and programming manual
Appendix B
Argus Devices
Note:The ARGUS devices accepted by this control panel do not have IMQ-SECURITY SYSTEMS certification;
refer to the instructions leaflet provided with each device.
All Argus Vega devices have built-in loop isolators. Therefore, isolators are not required. A short-circuit on
the loop will not provoke loss of any device.
Each detector is equipped with a 3-colour LED: green (periodic blinking) indicates the detector is working
properly (if enabled). Yellow indicates fault or open isolator status; red indicates alarm status (if enabled by
the operator).
Detectors are equipped with test LEDs: if you hold a magnet near the detector base (near to the two
notches) the detector should generate an alarm signal.
VPU100ProgrammerAllows fast addressing of Argus series devices
a. Configured as “Rate-of-rise detector” at default (alarm is triggered by rapid rise in temperature or when the temperature
exceeds the 54°C alarm threshold). To configure as “High temperature detector” ( Rate-of-rise feature bypassed and
fixed temperature set at 70°C) use the VPU100 programmer. The panel will recognize the configuration criteria automatically.
Weatherproof Intelligent Wall SounderflasherLoop-powered sounderflasher for outdoor installation
B.2Device Bases
ModelNameDescription
VB100BaseStandard base for VEGA detectors
VDBS100Deep Standard BaseAllows connection to wall-mount cable runs
BLR100Relay BaseRelay activated by the detector R output attached to the base
VBS100Base with SounderActivated by the detector R output attached to the base
VBLS100Base with addressable sounderOccupies a loop address
B.3Wireless devices
ModelNameDescription
VW2WWireless translatorConnected to Loop, 32-device interface (Sagittarius series -
SGWEWireless expansion
SG100Wireless analogue smoke detector
SG200Wireless analogue smoke and heat detector
SG350Wireless heat detector
SGRBS100Wireless sounder base
SGRBS100-AVWireless sounder base with beacon
SGMI100Wireless input module
SGMC100Wireless output module
SGMCB100Wireless module with 2 outputs
SGCP100Wireless callpoint
SGRS100Wireless sounder
SGVA100Wireless voice announcer
SG) wireless to panel
The panel sees the 32 devices as if they were connected to
the Loop (with different addresses)
a
)
(
SGFI100Wireless addressable remote alarm repeater
a. Configured as “Rate-of-rise detector” at default (alarm is triggered by rapid rise in temperature or when the temperature
exceeds the 54°C alarm threshold). To configure as “High temperature detector” ( Rate-of-rise feature bypassed and fixed
temperature set at 70°C) use the VPU100 programmer. The panel will recognize the configuration criteria automatically.
Argus Devices65
Installation and programming manual
B.4Device Consumption
Devicein standbyin alarm
Detectors90 PA 6 mA
Modules120 PA 6 mA
B.5Configuring Argus devices
You can either use an Argus VPU100 programmer to set the Argus device addresses and then let
SmartLight enroll them or, launch the automatic addressing procedure provided by the SmartLight.
Note:Each loop supports up to 240 devices.
For detailed installation and addressing instructions, contact www.argussecurity.it.
B.5.1Manual device addressing via VPU100
Addressing devices via VPU100
Work carefully through the Argus VPU100 addressing procedure and address all the devices.
Enrolling addresses
Once the Argus VPU100 addressing procedure has been completed, initialize the enrolling process.
From panel: <key>, Programming, Configuration, Loop, Ok, Auto configure, Acquire
B.5.2Automatic setting of devices
The SmartLight can assign an address (1 to 240) automatically to each loop device, starting from the
device on the LOOP-0 (J18) terminal.
Note:The automatic addressing process will automatically delete the previous address.
Once all the loop device connections have been properly completed and double checked, initialize the
process.
From panel: <key>, Programming, Configuration, Loop, Ok, Auto configure, Readdress
66Argus Devices
Installation and programming manual
Appendix C
Apollo devices
Note:The APOLLO devices accepted by this control panel do not have IMQ-SECURITY SYSTEMS certification;
refer to the instructions leaflet provided with each device.
Apollo devices are not equipped with built-in loop isolators (that is, unless otherwise specified). Therefore,
you must install loop isolators in such way as to avoid the loss of devices in the event of short-circuit.
C.1Devices
C.1.1Detectors: XP95 series
Note:XP95 series detectors are especially designed to operate with a sensibility of 55 (sensibility at default).
Sensibility adjustment should be made only when absolutely essential, as any change may lead to
delays in loop response time.
55000-803 XP95 DIN RAIL Input Output UnitDIN RAIL Module with 1Input + 1 Output
55000-804 XP95 DIN Rail Output UnitDIN Rail Module with 1 Output
55000-821 XP95 DIN RAIL Switch Monitor PlusDIN RAIL Module with 1 Delayed Input and Reset Output for
55000-822 XP95 DIN RAIL Switch Monitor DIN RAIL Module with 1 Input
55000-812 XP95 DIN RAIL Zone Monitor (with Isolator)DIN RAIL Interface Module for Conventional Zones (with
waterflow detectors (waterflow alarm)
isolator)
55000-826 XP95 DIN RAIL Sounder control UnitDIN RAIL Module with 1 sounder control output externally-
powered
55000-802 XP95 DIN RAIL Dual IsolatorDIN RAIL Dual Isolator
C.8Modules with Isolators
ModelNameDescription
55000-841XP95 Switch Monitor Plus with IsolatorDIN RAIL module with 1 delayed input and reset output for waterflow
detectors (waterflow alarm)
55000-843XP95 Switch Monitor with IsolatorSingle Input Module with Isolator
55000-845XP95 Zone Monitor with IsolatorInterface Module for Conventional Zones with Isolator
55000-847XP95 Input/Output module with IsolatorModule with 1relay output + 1 Supervised Input + 1 Non-supervised Input
(optoisolated)
55000-849XP95 Output unit with isolatorModule with 2 relay outputs with isolator
55000-852XP95 Sounder control unit with isolatorModule with 1output for self-powered siren (optoisolated)
C.9Configuring APOLLO devices
You must address all Apollo devices manually, and then allow the Smart Light panel to learn the assigned
addresses.
Note:Each loop supports up to 126 devices.
Apollo devices69
Installation and programming manual
For information regarding Apollo device installation and address assignment, contact www.apollo-
fire.co.uk.
C.9.1Addressing detectors manually using the XPERT card
Setting detector addresses manually
1. Detach the detector from its base and remove the XPERT card.
1. Remove the breakoffs in such way as to achieve the address you wish to assign (sum up the value of
each breakoff). Example: for address 43 remove breakoffs 1, 2, 8 and 32.
2. Insert the XPERT card an re-attach the detector to its base.
Addressing modules manually
Remove the cover and set the DIP microswitches. Refer to the Instructions leaflet for the various
combinations available.
Allow the Smart Light panel to learn the manually assigned addresses.
Once all the Apollo devices have been properly addressed, initialize the enrolling process.
From panel: <key>, Programming, Configuration, Loop, Ok, Auto configure, Acquire
70Apollo devices
Installation and programming manual
Order Codes
Quote the following order codes when ordering INIM Electronics s.r.l. products:
CodeDescription
DCMIINE0SLIGHTInstallation manual
DCMUINE0SLIGHTUser's manual
Link232F9F9RS232 link
LINKUSB232CONVRS232-USB adapter cable
ProbeTHThermal probe for battery charge optimization
SmartLeagueProgramming software, runs under Windows
SmartLetLoose/ONEExtinguishant module
Appendix D
SmartLetUSee/LCD-LiteRepeater
SmartLight/GAddressable analogue control panel with 1 loop Supports up to 240 loop devices and
30 zones
SmartLight/SAddressable analogue control panel with 1 loop Supports up to 64 loop devices and
16 zones
SPS24040SmartLevel power-supply station @ 24V, 1.4A