8
Iris
and open the chamber then, using a small, soft-bristle brush or hand-held vacuum cleaner remove all dust particles from
inside and around the smoke detection chamber and free the protection mesh from all contaminants.
•
Heat detector test
; using a suitable device (e.g. hairdryer), create heat in the vicinity of the detector, then work through
the steps described in the device instruction sheet. During each periodic maintenance inspection, ensure that the heat
element is intact and that is not obstructed by dust or paint. If it is, using a small, soft-bristle brush or hand-held vacuum
cleaner remove all contaminants.
Operating mode
The bicolour LED (360° viewing) indicates the detector status.
• Green blinking at 30-second intervals: detector in standby status (i.e. operating properly).
• Green blinking at 5-second intervals: detector in fault status. Further details regarding the cause of the fault (high
contamination level in the smoke chamber, detector component fault, etc.) can be obtained through the EITK-DRV driver.
• Red LED On solid: detector in alarm status.
The detectors have an output (terminal “R”), for the connection of an alarm repeater LED. This LED will activate
when the detector it refers to triggers an alarm.
Using the EITK-DRV driver
The EITK-DRV driver allows you to change the operating parameters of the detectors, check the contamination
level of the smoke chambers and also obtain accurate diagnostic data. It can operate through the USB port of a
computer furnished with the relative software programme, or can function autonomously by way of the battery
housed inside.
Each detector is capable of retaining memory (smoke and/or temperature depending on the model) of the 5
minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain information regarding the
onset of the fire by simply connecting the EITK-DRV driver to the detection line.
For further information and details regarding use of the EITK-DRV driver, refer to the respective handbook.
Warnings and limitations
Iris series detectors must be used exclusively with fully compliant, compatible control panels. Detectors may not
provide timely warning of fire if coverage is limited by large obstructions (pillars, large machinery, etc.). When
installing or working on a fire detection system, always refer to and comply with the established standard
regulations and codes. Appropriate fire-risk assessment should be undertaken to determine the type of detectors
required and their placements.
CE marking and certifications
DoP, EC DoC and certificates related to these products can be downloaded from the following link:
www.inim.biz/certifications
0832
INIM Electronics s.r.l.
Via Fosso Antico snc - Fraz. Centobuchi
63076 Monteprandone (AP) - Italy
15
0832-CPR-F1152
EN 54-7:2000 + A1:2002 + A2:2006
ID100
Conventional optical smoke detector for fire detection and fire
alarm systems installed in buildings
Essential characteristics
Performance
Nominal activation condition /sensitivity,
response delay (response time) and
performance under fire cond itions
PASS
Operational reliability
PASS
Tolerance to supply voltag e
PASS
Durability of
operational
reliability
Temperature resistance
PASS
Vibration resistance
PASS
Humidity resistance
PASS
Corrosion resistance
PASS
Electrical stability
PASS
0832
INIM Electronics s.r.l.
Via Fosso Antico snc - Fraz. Centobuchi
63076 Monteprandone (AP) - Italy
15
0832-CPR-F1243
EN 54-5:2000 + A1:2002
ID200
Conventional class P heat detector for fire detection and fire
alarm systems installed in buildings
Essential characteristics
Performance
Nominal activation conditi on/sensitivity,
response delay (response t ime) and
performance under fire cond itions
PASS
Operational reliability
PASS
Tolerance to supply voltage
PASS
Durability of
operational
reliability
Temperature resistance
PASS
Vibration resistance
PASS
Humidity resistance
PASS
Corrosion resistance
PASS
Electrical stability
PASS
Detector class (EN54-5): A1 R or B
0832
INIM Electronics s.r.l.
Via Fosso Antico snc - Fraz. Centobuchi
63076 Monteprandone (AP) - Italy
15
0832-CPR-F1153
EN 54-5:2000 + A1:2002
EN 54-7:2000 + A1:2002 + A2:2006
ID300
Conventional multicriteria optical smoke and class P heat
detector for fire detection and fire alarm systems installed in
buildings
Essential characteristics
Performance
Nominal activation condition/ sensitivity,
response delay (response tim e) and
performance under fire cond itions
PASS
Operational reliability
PASS
Tolerance to supply voltage
PASS
Durability of
operational
reliability
Temperature resistance
PASS
Vibration resistance
PASS
Humidity resistance
PASS
Corrosion resistance
PASS
Electrical stability
PASS
Detector class (EN54-5): A1R or B