Inhep Digital Security IDS 800 Installer Manual

2 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
Summary of Operation
mrasid/mrA
]#[ + ]EDOCRESU[
mrAyawAkciuQ
]1[
dnoces1rof
mrAyatSkciuQ
]5[
dnoces1rof
oG&mrAyatSkciuQ
]6[
dnoces1rof
lenaPybrewsnAdecroF
]8[
demrasidebtsummetsyS-
cinaP
]P[
dnoces1rof
eriF
]F[
dnoces1rof
ycnegremElacideM
]M[
dnoces1rof
yromeMmralA
]0[
dnoces1rof
eliforPyatSegnahC
]EDOM[ + ]9[ + ]REBMUNELIFORP[ + [(((((]
enozassapyB
[(((((] + ]REBMUNENOZ[
enozemihcmargorP
]2[
[+dnoces1rof
]
REBMUNENOZ
+ [(((((]
enozyatsmargorP
]3[
[+dnoces1rof
]
REBMUNENOZ
+ [(((((]
enozzzubmargorP
]4[
[+dnoces1rof
]
REBMUNENOZ
+ [(((((]
sutatSelbuorTweiV
]7[
sseruD
]#[ + ]EDOCSSERUD[
41egapeeS-ediuGgnimmargorProF
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 3
IDS800 INST ALLER MANUAL
Contents
1. Introduction to the IDS800............................................5
1.1 Features...........................................................................5
2. Installation and Wiring ..................................................6
3. End-of-Line Resistors/Tamper per Zone .................... 7
4. Connecting the Telephone Communicator ................8
5. Programmable Outputs.................................................8
6. Expansion Board ...........................................................9
7. The Key-Switch or Remote Control Unit ..................10
8. Additional Technical Data ...........................................10
9. Hardware Reset Switch ..............................................12
10. Event Log..................................................................... 12
11. Dialler Progress Mode ................................................ 13
12. Download Code ...........................................................13
13. Programming Instructions ..........................................14
13.1 Introduction ....................................................................14
13.2 Location V alues..............................................................14
13.3 Programming the Panel .................................................15
13.4 Program Location Summary ..........................................16
14. Trouble Conditions Summary.....................................52
4 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
Figures
Figure 1: Connection Diagram..............................................6
Figure 2: Tamper per Zone Connection ..............................7
Figure 3: Resistors user for Tamper per Zone ...................8
Figure 4: Programmable Output Configuration ..................9
Figure 5: Expansion Board Connection ..............................9
Figure 6: Strobe Output Sequence ...................................29
Figure 7: Fire Detect Output Sequence............................30
Tables
Table 1: Dialler Progress as shown by zone LED’s..........13
Table 2: Value represented by each zone indicator .........14
Table 3: Binary Representation..........................................15
Table 4: Location/ Zone Defaults........................................17
Table 5: Programmable Zone Types...................................18
Table 6: Output Options......................................................28
Table 7: Location default values ........................................28
Table 8: Standard Contact ID reporting codes.................35
Table 9: Alarm reporting codes...........................................36
Table 10: Trouble Conditions .............................................52
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 5
IDS800 INST ALLER MANUAL
1. Introduction to the IDS800
The IDS800 is a versatile, state of the art, microprocessor based, eight zone alarm panel. Most features are optional and may be programmed either directly through the keypad or via the telephone system, using the IDS download software and appropriate modem. There are eight programmable burglary zones, appropriate siren, auxiliary power outputs and 5 outputs which may be programmed to perform various trigger/switching functions. For correct operation the IDS800 must be used in conjunction with the specified transformer/battery combination and appropriate peripheral sensors and signalling devices.
1.1 Features
Four wire keypad operation - up to a maximum of 4 keypads. Eight, fully programmable, end-of-line (3K3) supervised zones,
and 1 dedicated panic zone per keypad which is not end-of-line supervised.
Optional tamper reporting per zone using double end-of-line
resistors (12K and 4K7).
Fully programmable digital telephone communicator which
supports most industry standard formats.
Five programmable trigger outputs. Non volatile EEPROM memory retains all program and event log
data in the event of a total power failure.
Programmable loop response time for all zones (global). Up and downloadable using IDS windows based software. Excellent protection against lightning (provided by specialised
“zap tracking” and transient suppressors).
Auto-arm - panel can be programmed to arm daily at a pre-
determined time.
Event log (200 events) date and time stamped. Fax defeat allows download access to the panel with other
devices connected to the phone line.
Dual reporting provides for duplicated reporting to two independent
central base stations.
Programmable silent or audible panic. Unique dialler progress bar allowing for monitoring of dialler
status.
6 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
2. Installation and Wiring
Please refer to Figure 1: Connection Diagram and familiarise yourself with the following sections.
Figure 1: Connection Diagram - without tamper per zone
3 2
1
ZONE 8
ZONE 7 ZONE 6
ZONE 5 ZONE 4
ZONE 3 ZONE 2
ZONE 1
C D
-
+
+
+
-
+
+TX
18V AC
AUXILLIARY OUTPUTS
KEYPAD
12V
SIREN
CONNECT TO MA INS TRANSFORMER
RADIO TRANSMITTER / COMMUNICATOR POWER
PANIC BUTTON N/O
PANIC BUTTON N/O
NCNCC
C
+
+
-
-
P.I.R.
P.I. R.
MAG SW N/C
CONNECT A S REQUIRED WITH A RESISTOR IN UNUSED ZONES
B
L
A
C
K
W
IR
E
R
E
D
W
I
R
E
-
+
12V BATTERY
1
2
3
456
789
0*#
P
M O D E
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8
CK
DAT
GND
+12V
PAN
LED
P A N
I C
3K3
3K3
3K3
3K3
P A N I C
NOTE: NO END OF LINE RESISTOR
DOOR LED
EARTH
EARTH
LINE
LINE
PHONE
SW1 HARDWARE RESET SWITCH
FU2 AUXILIARY
POWER FUSE
1 AMP
FU1 BATTERY FUSE 4 AMP
Dialler Board
Position of Dialler Board
RADIO
TRANSMITTER
OR
COMMUNICATOR
TELKOM
M
F
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 7
IDS800 INST ALLER MANUAL
3. End-of-Line Resistors/Tamper per Zone
All zones are end-of-line supervised. Any unused zones must also
be terminated with the appropriate resistor .
The end of line resistor should be placed inside or as close to the
sensor as possible.
If the zones are not programmed to report tamper by zone i.e. a
[0] is programmed into location 1 1 then use the 3K3 end-of-line resistor .
If the zones are programmed to report tamper by zone, the 4K7
and 12K end-of-line resistors should be connected as per Figure 2 below. The 4K7 and 12K resistors are not included with the panel but may be obtained from your local distributor of IDS products.
Figure 2: Tamper per Zone Connection
The operation of the tamper is as follows:
If the panel is not armed and a tamper condition occurs, the
siren will not sound but a tamper condition will be reported.
If the panel is armed and tamper condition occurs the alarm
will register a zone violation and a tamper condition will be reported.
Regardless of whether the panel is armed or not, if a zone is
programmed as a priority/panic zone, a tamper will register a panic condition as well a tamper condition.
If the tamper per zone is enabled, it affects all zones and therefore
both end-of-line resistors must be connected in all zones. If the tamper facility is not used on a zone then the 12K resistor must be connected directly across the zone (i.e. between the zone
8 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
input and ground) and the 4K7 resistor is used as the normal end­of-line resistor .
The colour codes for the 12K and 4K7 resistors are as seen in
Figure 3 below .
Figure 3: Resistors used for T amper per Zone
Purple
Brown
Orange
Red
1
2K
4K7
Yellow
Red
4. Connecting the Telephone Communicator
Refer to Figure 1. The integral communicator has built in lightning protection to
protect it from lightning induced transients. For optimum protection connect a low impedance earth to the communicator . A poor earth will be ineffective and may result in damage to the communicator and alarm panel.
Always connect the telephone communicator in the line seizure
mode. Never in parallel with the telephone i.e. connect the telephone receiver to the communicator terminals marked “phone” and the incoming line to the terminals marked “line”.
5. Programmable Outputs
A relay board must be used when any device requiring a high current is connected to a programmable output. The current sink and source capability is the same for outputs 1, 2 and 3. The output circuitry consists of a 12 volt source with a 56 series resistor . Current sink is via a 1000 resistor to negative. The output circuitry is provided in Figure 4 overleaf.
There is also an expansion board attached to the keypad bus which provides for an additional two programmable outputs which function as per outputs 1 - 3. See the connection diagram in Section 2 for further details. See also Section 6: Expansion Board.
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 9
IDS800 INST ALLER MANUAL
Figure 4: Programmable Output Configuration
6. Expansion Board
Attached to the keypad bus, in parallel with the keypad, is an optional expansion board which allows for the following: Programmable outputs 4 and 5 which function as per the values
programmed into locations 22 - 40 and locations 159 - 166.
Designated keypad buzzer which will function as per the
description in the user manual.
ARM, READY and POWER LED’s which will function as per the
description in the user manual for keypad LEDs.
Figure 5: Expansion Board Connection
Keypad
123 4
56
789
0
*
#
P
M O D E
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8
GND CK DAT +12V
+
C D
_
Keypad connection on main board
+
GD
DT
CK
BZ
PR RD AM
P4
P5
GD
Keypad Buzzer
Power LED Ready LED
Arm LED
Auxilliary
Outputs
Expansion
Board
FM
12V
56R
1000R
GND
Output 2
56R
1000R
GND
Output 1
56R
1000R
GND
Output
3
10 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
7. The Key-Switch or Remote Control Unit
A momentary key-switch or non-latching remote control receiver may be connected to any zone to allow remote arm/disarm capability and/ or remote panic.
If a key-switch or remote control unit is used, a 3K3 resistor must
be connected between the zone input and ground. (Use the 4K7 and 12K resistors if tamper per zone is enabled).
Use a normally open, spring-loaded momentary key-switch or a
non-latching remote control unit. The remote receiver must provide
a pulsed output.
If using a key-switch, program the zone as an Arm/Disarm zone
i.e. a value of [5] entered into the relevant location.
If using a remote control, program the zone as either a Paniczone
or an Arm/Disarm zone, as required.
The panel will arm instantly (no entry/exit delay) when arming by
means of a key-switch or remote control unit.
The panel has an exit delay which can be enabled or disabled
with the key-switch or remote control (See location 12).
8. Additional Technical Data
Use a suitable transformer with an output voltage of 15 volt s AC
±10% with a 16V A minimum rating. A 32 VA transformer is preferable for larger installations.
Use a 12v sealed lead acid battery , min. 3ah. The back up period
after mains failure will depend on the number of keypads, sensors and peripheral devices attached to the system. The current drawn by the panel and keypad (no indicators illuminated) excluding sensors is 240mA.
The panic zone provided on the keypad is not an end-of-line
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 11
IDS800 INST ALLER MANUAL
supervised zone and requires a normally open panic switch. If using this panic zone connect a normally open panic switch between the P AN terminal and the GND terminal. If this zone is not used leave the terminal open circuit.
A door LED may be connected to the keypad. This LED will
mimic the ARM LED on the keypad i.e. When the system is not armed the LED will be extinguished. If the system is armed the LED will be illuminated and will flash if an alarm condition was registered while the system was armed. Note that the anode of the LED connects to the LED terminal on the keypad and the cathode of the LED is connected to the GND terminal. No series resistor is required.
Do not connect more than 8 PIR’s and two keypads, (or 6 PIR’s
and 3 keypads) to the auxiliary 12 volt outputs.
The siren output requires a self driven 12 volt siren. The siren
minus terminal is connected to ground. The positive terminal of the siren is connected to 12 volts via a relay during the siren period.
A full description of each programmable function of the panel is
contained in the section headed Program Location Summary .
All information regarding the programming of user codes, home
zones delayed interior zones and chime zones is contained in the User Manual.
If a radio transmitter or voice message communicator is being
used for monitoring purposes the power for these devices should be taken from the “+TX” terminal.
NOTE:
The TX+ terminal is protected by means of the battery fuse. If excessive current (2 amps max) is drawn from this terminal, battery power to the alarm may be lost.
12 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
9. Hardware Reset Switch
In the event that the installer code is lost, it is possible to reset the panel to its factory default values using the hardware reset switch labelled SW1 on the main PC board. Provided that the reset switch has not been disabled (see location 21) the panel may be defaulted by removing both battery and AC power from the panel, and then reapplying the power (AC/battery) while depressing the switch. Factory default values will be restored to all locations.
NOTE:
Once the reset switch has been disabled it is not possible to default the panel using the reset switch. The panel may only be defaulted if a valid installer code is used and a value of [0] is entered into location 0.
10. Event Log
The IDS800 automatically keeps an internal log of all events which may be communicated through the onboard communicator. 200 of the most recent events will be retained. Once the event log is “full” the oldest event will be overwritten by the most recent event. An event is logged regardless of whether or not the panel is programmed to communicate the event.
The event log can only be retrieved by means of the Windows based download/upload software and appropriate modem.
The time of each event is not logged in absolute terms i.e. time of day and date but relative to the previous event. The date and time indicated on an uploaded event log is calculated by the PC using the PC clock time. Since the time at which the upload event was initiated is known, all other times can be calculated relative to this event.
The IDS800 does not contain an onboard battery to maintain the clock time in the event of a total power failure (AC mains failure and discharged battery) therefore in the event of a total power failure it will not be possible to calculate the absolute time at which an event took place. The relative time of each event will still be indicated.
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 13
IDS800 INST ALLER MANUAL
11. Dialler Progress Mode
When the panel sends data to a central station, the keypad zone
LED’s may be used to display the “progress” of such communication.
To view the communication status proceed as follows:
1. Hold down the [0] key until the keypad buzzer sounds twice.
2. Press the [9] key. The ARMED, READY and AW AY LED’s will flash simultaneously indicating that the Dialler Progress Mode has been selected. Using the zone indicators the following table will provide the communication status.
3. To exit this mode press the [#] key.
Table 1: Dialler Progress as shown by zone LED’s
eno
Z
DE
L
ybdnatS gnizeiS
eniL
gnillaiD
esaB
noitatS
rofgnitiaW
nO-ssiK
gnidneS
ataD
rofgnitiaW
ffO-ssiK
r
ofgnitiaW
l
aidtxen
tpmetta
1enoZ
)))))))
2enoZ
)))))
3enoZ

))))
4enoZ

)))
5enoZ

))
6enoZ

)
7enoZ

)
dehsiugnitxE
)
detanimullI
12. Download Code
A download code is used for download access. The default download code is 9999. Via the downloading it is possible to set a location to either allow or disallow defaulting of the download code. The location is only accessible using the download software. If selected to allow defaulting of the download code, the download code will be defaulted to 9999 if the panel is defaulted. A value of [10] programmed into this location prevents the download code from being defaulted.
This function may only be used with download software version 1.4.0 or later.
14 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
13. Programming Instructions
13.1 Introduction
The panel may be programmed either using the keypad or using the up/download software. Programming the panel by means of the keypad is explained in the following sections of this manual. For information on programming the panel using the up/download software refer to the manual pertaining to the software.
NOTE:
Before commencing the programming it is advisable to read the Installer Manual thoroughly
13.2 Location Values
All values within a program location are displayed by the zone indicators in binary format. The table below indicates how these values may be read.
Table 2: Value represented by each zone indicator
1enoZ
1
2enoZ
2
3enoZ
4
4enoZ
8
T o read a binary value on the keypad add the values represented by each illuminated LED. The total value is the number being represented e.g. Assume the following zone indicators are illuminated: Zone 1, Zone 3 and Zone 4. The value would be as shown in the table below .
1enoZ
1
3enoZ
4
4enoZ
8
latoT31
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 15
IDS800 INST ALLER MANUAL
Table 3: Binary Representation
eulaV
0 1 2 3 4 5 6 7 8 9 01 11 21 31 4151
2(1enoZ
0
)1=
)
)
)
)
)
)
)
)
2(2enoZ
1
)2+

))

))

))

))
2(3enoZ
2
)4=

))))

))))
2(4enoZ
3
)8=

))))))))
dehsiugnitxE
)
detanimullI
13.3 Programming the Panel
For all programming procedures, the [(] (star) key functions as
the enter key and the [#] (hash) key functions as a clear key to clear incorrect or unintended entries, as a back space and to exit the programming mode.
If an error has been made i.e. an attempt is made to enter an
illegal value or an incorrect series of keystrokes, the keypad will beep three times to indicate the error . The panel will automatically discard the invalid entry allowing the correct entry to be made without manually clearing the incorrect entry .
Procedure
1. Ensure that the panel is not armed.
2. Press the [#] key (this will clear any previous or accidental entries) followed by the 4 digit [INST ALLER CODE] (the default code is 9999).
3. If the correct code has been entered the green READY indicator will begin flashing.
4. Press the [(] key.
5. Enter the [LOCATION NUMBER] of the program location that you wish to change.
6. Press the [(] key. The READY indicator will continue flashing and the AWAY indicator will illuminate.
7. The zone LED’s will now display the content of the selected program location in binary format (ref. Table 3).
8. If you wish to change the content of the location, enter the [NEW
VALUE
] followed by the [(] key . If you do not wish to change the
16 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
location value, press the [#] key . The READY indicator will continue flashing and the AWAY indicator will extinguish.
9. If the data value has been changed, the buzzer will give a long beep indicating that a valid entry has been stored.
10. Repeat steps 5-8 until all necessary locations have been programmed.
1 1 . To exit from the programming mode press the [#] key .
The READY indicator will stop flashing to indicate that the program mode has been exited.
13.4 Program Location Summary
Following is a detailed description of the functioning of each location and its options.
0NOITACO
L
edocresuretsamrolenapehtfognitluafeD
eulaV noitcA
0
tluafeD
ehtninwohssaseulavtluafedyrotcafehtotsnoitacolllasteseR
oslalliwsedocresullA.tsilgnimmargorpehtninmulocTLUAFED
.4321emoceblliwedocresuretsamehtdnadetluafedeb
1ehtgnitluafedtuohtiw4321otedocresuretsamehttluafedlliW
-nuniamerlliwnoitamrofnirehtollA.sedocresuehtforedniamer
.deretla
2rehtotamrofrotacinummocafI.0otsedocgnitroperllateserlliW
-erebotdeensedocgnitropereht,desusiDItcatnoCnaht
r
oirp0otsedocgnitroperllatluafedotelbasivdasitI.demmargorp
.sedocehtgnimmargorperot
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 17
IDS800 INST ALLER MANUAL
8-1SNOITACO
L
)8-1senoZ(scitsiretcarahCenoZ
Program locations 1 to 8 define the zone characteristics of each of the eight zones. Each zone can be programmed to function in one of eleven modes. T able 4 provides a location/zone cross-reference together with the default zone characteristics.
Table 4: Location/Zone Defaults
coL enoZ tluafeD epyTenoZ
111 tixE/yrtnE 222 rewolloF 334 tnatsnIelbiduA 444 tnatsnIelbiduA 554 tnatsnIelbiduA 664 tnatsnIelbiduA 774 tnatsnIelbiduA 883 ytiroirPelbiduA
T able 5 overleaf provides a description of the different zone types that may be programmed into these locations i.e. a value of 3 programmed into location 5 would cause zone 5 to be an audible priority zone.
18 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
Table 5: Programmable Zone Types
eulaV epyTenoZ
0 DELBASID
derongisienozdelbasidafonoitaloiV.delbasideblliwenoZehT
.dapyekehtnodetacidnitonsidna
1 TIXE/YRTNE
yaledtixeehtgnirudderongisienoztixE/yrtnEnafonoitaloiV
nehwenoztixE/yrtnEnagnitaloiV.erudecorpgnimraehtfodoirep
otnidemmargorpyaledyrtneehT.yaledyrtneehtsetaitinidemra
eblliw81noitacolotnidemmargorpyaledtixeehtdna02noitacol
lliwgnimraretfaenoztixE/yrtnEnahguorhttixeoteruliaF.desu
e
hterofebderetnetonsiedocresUdilavafI.edomyatsehtelbane
.deretsigereblliwnoitidnocmralana,seripxedoirepyaledyrtne
sidoirepyaledtixeehtgnirudepytenozsihtforuoivahebehT
.9noitacolotnidemmargorpeulavehtybdetceffa
2 REWOLLOF
eehtgnirudderongieblliwenozrewolloFafonoitaloivA tixe/yrtn
doirepyaled rewollofehtaivtixe/retneotresuehtswollasiht(
si
lenapehtfienoztnatsninasaevaheblliwenozrewolloFA.)enoz
foruoivahebehT.tsrifdetaloivtonsienoztixE/yrtnEnadnademra
.9noitacolotnidemmargorpeulavehtybdetceffasiepytenozsiht
3 CINAP/YTIROIRPELBIDUA
nafonoitaloiva,tonrodemrasilenapehtrehtehwfosseldrageR
naretsigerotlenaplortnocehtesuaclliwenozytiroirPelbiduA
.nerisehtdnuosdnanoitidnocmrala
4 TNATSNIELBIDUA
ehtesuaclliwenoztnatsninafonoitaloiveht,demrasilenapehtfI
ehT.noitidnocmralanaretsigeryletaidemmiotlenaplortnoc
otnidemmargorpeulavehtnopudnepedlliwnerisehtforuoivaheb
tnatsnInafonoitaloiva,demranusilenapehtelihW.51noitacol
.derongisienoz
5 MRASID/MRA
romraotlenapehtesuaclliwenozmrasiD/mrAnafonoitaloivA
-nonrohctiws-yekyratnemomatcennocytilicafsihtesuoT.mrasid
ll
iwrotsiserenil-fo-dneehT.enozsihtottinulortnocetomergnihctal
.deriuqerebllits
6 YTIROIRPTNELIS
afonoitaloiv,tonrodemrasilenapehtrehtehwfosseldrageR
troperlliwtubdnuosotnerisehtesuactonlliwenozytiroirPtneliS
margorptnavelerehtotnidemmargorpedocetairporppaeht
.noitatslartnecehtotsnoitacol
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 19
IDS800 INST ALLER MANUAL
eulaV epyTenoZ
7 TNATSNITNELIS
esuaclliwenoztnatsnItneliSafonoitaloivehtdemrasilenapehtfI
ehT.noitidnocmralanaretsigeryletaidemmiotlenaplortnoceht
afonoitaloivehtdemranusilenapehtelihW.dnuostonlliwneris
sienozsihT.derongisienoztnatsnItneliStonehtybdetceffa
.51noitacolotnidemmargorpeulav
8 TIXE/YRTNEYRADNOCES
sihtnehwdesueblliw)01noitacolees(yaledyrtneyradnocesehT
ehtgniretnenehW.demrasilenapehtelihwdetaloivsienoz
aretfadetaloivsienoztixE/yrtnEyradnoceSafidna,sesimerp
o
teunitnoclliwlenapehtdetaloivneebsahenoztixE/yrtnEyramirP
.yaledyrtneyramirpehtnwod-tnuoc
01 ENOZERIF
fosseldragerdnuosotnerisehtesuaclliwenozeriFafonoitaloiV
yl
tnettimretnidnuoslliwnerisehT.tonrodemrasilenapehtrehtehw
tuptuoelbammargorpA.)ffodnoceseno,nodnoceseno(
oslalliw)73noitacol(tuptuorewoprotcetederifasademmargorp
detavitcaeb
21 MRAOTHSUP
sahyaledtixeehtecno;51si81noitacolnieulavehtfI
yletaidemmilliwenozmraothsupehtfonoitaloiva,decnemmoc
lenapehtmra
20 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
9NOITACO
L
snoitpOtixE/yrtnE
eulaV
senoztixe/yrtnE
raelcebtsum
senozrewolloF
raelcebtsum
yaledtixe/yrtnE
delbane
0
mrAtnatsnI
raelcebtsumsenozllA
1 2 3 4 5 6 7 8

>
9
tluafeD
>
>
01
>>
11
>>>
21

>
31
>
>
41
>>
51
>>
>
>
delbanE
delbasiD
If the Entry/ exit delay is enabled, the panel can be programmed to allow arming with violated Follower and/ or Entry/ exit zones.
NOTE:
For all values programmed into location 9 the panel will only arm if the
READY indicator is illuminated.
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 21
IDS800 INST ALLER MANUAL
01NOITACO
L
yaleDyrtnEyradnoceS
eulaV yaleD eulaV yaleD
0
.ces52.0
8
.nim4
1
.ces01
9
.nim5
2
.ces02
01
.nim01
3
.ces03
11
.nim51
4
.ces54
21
.nim81
5
)tluafeD(.nim1
31
.nim12
6
.nim2
41
.nim42
7
.nim3
51
.nim72
The secondary entry delay applies to the secondary entry/exit zone. If a primary entry zone is violated, the primary entry delay is activated. If a subsequent violation of a secondary entry/exit zone occurs, the panel will continue to count down the primary delay . If a valid user code is not entered during this period an alarm condition will occur.
11NOITACO
L
elbanEenoZreprepmaT
eulaV noitcA
0
tluafeD
delbasiD
1delbanE
See Section 3: End-of-Line Resistors/ Tamper per Zone for the correct use of tamper per zone.
22 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
21NOITACO
L
snoitpOgnimrA
eulaV mrAkciuQ
yaledtixe/yrtnE
enozmrahtiw
gnimradecroF
t
eserreenignE
0
 
1
tluafeD
>
2
>

3
>>

4

>
5
>
>
6
>
>
7
>
>
>
8

>
9
>

>
01
>
>
11
>
>
>
21

>>
31
>
>>
41
>
>>
51
>>
>>
>
delbanE
delbasiD
The quick arm option allows the user to arm the panel by holding down the [1] key until the keypad beeps. Using the quick arm key initiates an arming cycle as if a valid user code has been entered. User code 1 will be reported if the quick arm key is used.
The key-switch exit delay option enables or disables entry/ exit delays with key-switch arming. See Section 5 in the User Manual for information pertaining to key-switch arming.
Forced arming allows the panel to arm with violated zones e.g. an open window. Once the panel arms, a violated zone will byp ass automatically . If a zone which has been automatically byp assed clears while the panel is armed, the zone will become active i.e. the window is pushed closed. Opening the window again will cause an alarm
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 23
IDS800 INST ALLER MANUAL
condition to be registered. The Engineer reset function determines whether the panel can be
armed after an alarm condition has been registered. This can be used to force the customer to have the system inspected in the event of an alarm condition. If the function is enabled:
If an alarm condition occurs and a valid user code is entered,
thereby disarming the system, a trouble condition will be
indicated. Upon entering the Trouble mode (hold down [7]), the
indicator for zone 8 is illuminated indicating that the installers
code must be entered to clear this condition before re-arming. To
clear the engineer reset simply enter the program mode by
entering a valid[INSTALLER CODE] followed by [(] followed by [#]
to exit the program mode. The panel can now be armed.
If the function is disabled:
The panel can be rearmed normally after an alarm condition has
been registered. No trouble condition will be indicated.
31NOITACO
L
snoitpOmrAyatS
eulaV noitcA
0
tluafeD
resuehtfiedomyatsehtnimrayllacitamotualliwlenapmralaehT
nafonoitaloiv.e.i(enoztixe/yrtneehtesutonseoddnasmra
.)enoztixe/yrtne
1fonoitaloivonfineveedomyawaehtnimralliwlenapmralaehT
gnidloh(yekmrakciuqedomyatsehT.sruccoenoztixe/yrtnena
ehtnwod ]5[ .)delbasidoslasi
2fonoitaloivonfineveedomyawaehtnimralliwlenapmralaehT
yekmrakciuqedomyatsehtrevewohsruccoenoztixe/yrtnena
.evitcasniamer
The stay mode allows the user access to certain pre-programmed “stay” zones while the panel is armed. Zones that are programmed as stay zones (See Section 12 in the User Manual) will automatically be bypassed when the panel is armed into the stay mode. The [5] key will arm the panel in stay mode with no exit delay.
24 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
41NOITACO
L
snoitpOcinaPdapyeKtneliS
eulaV noitcA
0
tluafeD
)cinapelbidua(delbasiD
1)cinaptnelis(delbanE
The value programmed into this location only affects the keypad panic.
51NOITACO
L
snoitpOmralAtneliS
eulaV noitcA
0
tluafeD
)mralaelbidua(delbasiD
1)mralatnelis(delbanE
If a zone is programmed as a silent instant zone, an alarm condition as a result of a violation of this zone would be silent regardless of the value programmed into this location.
61NOITACO
L
mrasiD&mrAnotooTneriS
eulaV mranotootneriS mrasidnotootneriS
0
tluafeD
1
>
2
>
3
>>
>
delbanE
delbasiD
This option allows the user to confirm that arming has occurred. The siren will give a short beep after successful arming, and two short beeps after disarming. This is recommended if a remote control or external key-switch is used.
NOTE:
The siren will not beep if the panel is stay armed into or disarmed from the stay mode.
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 25
IDS800 INST ALLER MANUAL
71NOITACO
L
doirePtuOemiTneriS
eulaV yaleDtuo-emiT eulaV yaleDtuo-emiT
0
.ces52.0
8
.nim4
1
.ces01
9
.nim5
2
.ces02
01
.nim01
3
.ces03
11
.nim51
4
.ces54
21
.nim81
5
.nim1
31
.nim12
6
)tluafeD(.nim2
41
.nim42
7
.nim3
51
.nim72
The siren time out period is the period of time for which the siren will sound after an alarm condition is registered. Select the appropriate time-out period from the table above.
81NOITACO
L
doirePyaleDtixE
eulaV yaleD eulaV yaleD
0
.ces52.0
8
.nim4
1
.ces01
9
.nim5
2
.ces02
01
.nim01
3
)tluafeD(.ces03
11
.nim51
4
.ces54
21
.nim81
5
.nim1
31
.nim12
6
.nim2
41
.nim42
7
.nim3
51
.nim72
This is the period of time allowed for exiting before the panel arms. The exit delay begins after entry of a valid user code. During this period it is possible to violate entry/exit and follower zones without causing an alarm condition. Select the appropriate exit delay period from the table above.
26 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
91NOITACO
L
emiTerotseRdnaliaFCA
eulaV yaleD eulaV yaleD
0
.nim1
8
.nim9
1
)tluafeD(.nim2
9
.nim01
2
.nim3
01
.nim11
3
.nim4
11
.nim21
4
.nim5
21
.nim31
5
.nim6
31
.nim41
6
.nim7
41
.nim51
7
.nim8
51
.nim61
If the AC power should fail, the panel will wait for this period of time before reporting the mains failure to the base station or logging the event to the event log. If the AC power is restored after the time out period has ended the same time out period will apply before the restoral event is reported and logged.
If the AC power is restored during the delay period neither the power failure nor the power restoral will be reported or logged to the event log. This delay eliminates unnecessary reporting if the AC power to the panel is accidentally removed for a short period (provided the back up battery is in good condition, short AC power failures will not affect the functioning of the alarm system).
Select the appropriate value from the table above.
02NOITACO
L
yaleDyrtnEyramirP
eulaV yaleD eulaV yaleD
0
.ces52.0
8
.nim4
1
.ces01
9
.nim5
2
.ces02
01
.nim01
3
)tluafeD(.ces03
11
.nim51
4
.ces54
21
.nim81
5
.nim1
31
.nim12
6
.nim2
41
.nim42
7
.nim3
51
.nim72
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 27
IDS800 INST ALLER MANUAL
This is the period of time allowed to enter and disarm the panel before an alarm condition is registered. The entry delay begins after the violation of a primary entry/exit zone. During this period it is permissible to violate follower zones without causing an alarm condition provided that an entry/exit zone was violated first. If a follower zone is violated without a prior entry/exit zone violation, it will be treated as an instant zone. If an instant zone is violated during this period the alarm condition will immediately be registered. Select the appropriate value for the primary entry delay from the table on the previous page.
12NOITACO
L
elbasiD/elbanEhctiwSteseRerawdraH
WARNING:
Make certain that the new installer code has been correctly entered before disabling the reset switch.
eulaV noitcA
01elbasiD 51
tluafeD
elbanE
For the correct operation of this switch refer to Section 9: Hardware Reset Switch.
04-22SNOITACO
L
slortnoCtuptuOelbammargorP
SEE: LOCA TIONS 159 - 166 for Zone Programmable Outputs
These locations control the functioning of the 3 onboard programmable outputs as well as the 2 outputs provided if the Output Expansion Board is used. If a smoke detector, strobe light (or any other device requiring power) is connected to a programmable output, a relay board must be used to provide the high current. Please refer to the Section
5. Programmable Outputs. Multiple events may be programmed to a single output. The output
may be programmed to function as follows:
Output pulsed for two seconds. Output may be latched high. Output may be latched low .
28 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
T able 6: Output Options
tuptuOelbammargorP eulaVmargorP
desluP hgiHtroPteS woLtroPteS
1tuptuO1611 2tuptuO2721 3tuptuO3831
)draobnodda(4tuptuO4941 )draobnodda(5tuptuO50151
The strobe and fire-detect outputs may only be programmed with
[0] to [5] i.e. a pulsed output.
The second phone number dialled output can only be
programmed with values [1] - [5] ([0] will disable the output).
.
Table 7: Location default values
.coL tnevE eulaV noitcAtluafeD
22
mralA
2
2POgorPesluP
32
ytiroirPelbiduA
1
1POgorPesluP
42
yrettaBwoL
0
delbasiD
52
tset-otuA
0
delbasiD
62
sseruD
1
1POgorPesluP
72
liaFCA
0
delbasiD
82
esolC
8
hgiH3POgorPteS
92
nepO
31
woL3POgorPteS
03
erotseRCA
0
delbasiD
13
lecnaC
0
delbasiD
23
eriF
0
delbasiD
33
lacideM
0
delbasiD
43
ebortS
0
delbasiD
53
repmaT
0
delbasiD
63
ytiroirPtneliS
1
1POgorPesluP
73
rewoProtceteD-eriF
0
delbasiD
83
emihC
0
delbasiD
93
liaFnoitacinummoC
0
delbasiD
04
dellaid2.oNenohP
0
delbasiD
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 29
IDS800 INST ALLER MANUAL
Programming Example
Program output No. 2 to report open and close, with close HIGH and open LOW:
It will be noted from Table 7 that output No. 2 is already assigned as the alarm output. This condition first needs to be disabled from output 2 before a new condition may be assigned otherwise CLOSE, OPEN and
ALARM will all be programmed to Programmable Output 2. To do this a
[0] should be programmed into location 22.
The location for a close instruction is location 28. From Table 6 it will be noted that a value of [7] programmed into this location will cause output 2 to go high. This output will remain high until the appropriately programmed value gives the instruction for this output to be set low. It will be noted that location 29 corresponds to an open condition. From Table 6 it will be noted that a value of [12] will drive output 2 low. Therefore if a value of [12] is programmed into location 29 output 2 will be set low on an open condition.
If an output is programmed as a strobe output, the output will follow the sequence illustrated below.
Figure 6: Strobe Output Sequence
Similarly , a fire detect output follows the sequence illustrated overleaf.
30 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
Figure 7: Fire Detect Output Sequence
NOTE:
Since multiple conditions may be programmed to a single output It is essential to ensure that no unwanted conditions are assigned to the same output.
14NOITACO
L
devreseR
24NOITACO
L
snoitpOgnillaiD/snoitpOrebmuNenohP
Provision is made for the panel to dial different phone numbers (locations 48-63 for primary number and 64-79 for the secondary number). The panel can be programmed to report to these phone numbers as follows: Reporting codes can be programmed to report to a single central
station (single reporting).
Report independently to 2 central stations (dual reporting). The primary and secondary numbers may be joined to provide for
a single number up to 32 digits.
The numbers can be dialled using either tone or pulse dialling. Enter the appropriate value from the following to setup the required
phone number options.
eulaV nioJ edoMlaiD
0oNgnitropeRelgniS-esluP
gnitrope
R
:
litnusrebmunenohpeletyradnocesdnayramirplaidesluP
stpmettaforebmunehtrofrolufsseccussinoitacinummoc
.521noitacolotnidemmargorp
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 31
IDS800 INST ALLER MANUAL
eulaV nioJ edoMlaiD
1
tluafeD
oN gnitropeRelgniS-enoT
:gnitropeR
gnillaidenothtiwtub0eulavrofsA
eulaV nioJ edoMlaiD
2oNgnitropeRlauD-esluP
gnitrope
R
litnusrebmunenohpeletyradnocesdnayramirplaidesluP
s
rebmunhtobotnoitacinummoclufsseccusaneebsahereht
.
521noitacolotnidemmargorpstpmettaforebmunehtrofro
eulaV nioJ edoMlaiD
3oNgnitropeRlauD-enoT
:gnitropeR
.gnillaidesupfodaetsnignillaidenothtiwtub2eulavrofsA
eulaV nioJ edoMlaiD
4seYesluP
:gnitropeR
elgnisasadellaidebdluowsrebmunenohpelethtoB
nahtregnolrebmunafonoitaercehtrofswollasiht,rebmun
.stigid61
rebmunelgnissihtotdetacinummoceblliwatadllA
eulaV nioJ edoMlaiD
5seYenoT
:gnitropeR
.gnillaideslupfodaetsnignillaidenothtiwtub4eulavrofsA
32 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
If single base reporting is selected, program the following
locations:
Locations 43 - 46 : Primary Account Code
Location 47 : Primary Communicator Code
Locations 48 - 63 : Primary Phone Number
Locations 64 - 79 : Secondary Phone Number
If dual reporting is selected, program the following locations:
Locations 43 - 46 : Primary Account Number
Location 47 : Primary Communicator Format
Locations 48 - 63 : Primary Phone Number
Locations 64 - 79 : Secondary Phone Number
Locations 144 - 147 : Secondary Account Code
Location 148 : Secondary Communicator Format
If both phone numbers are to use the same communicator format
and account codes then locations 43 - 47 must be programmed
with the same values as locations 144 - 148.
64-34SNOITACO
L
edoCtnuoccArotacinummoCyramirP
The four digit account code for the telephone communicator is programmed into these locations. The panel is identified at the receiver by this account number. The account code must be four digits long. Any account number
shorter than four digits must be preceded with “10”s.
When programming locations 43-46 a [0] must be entered as
a [10]
Sescoa Superfast format does not support account codes higher
than 3374.
The account code is not converted to hexadecimal by the panel
when Sescoa Superfast is used.
The following table provides the conversion between the hexadecimal value and the value programmed into a particular location.
eulaVlaciremu
N
123456789 011121314151
eulaVlamicedaxe
H
123456789ABCDEF
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 33
IDS800 INST ALLER MANUAL
Example: The desired account code is 14 (i.e. 0014)
1. Enter [10] into location 43.
2. Enter [10] into location 44.
3. Enter [1] into location 45.
4. Enter [4] into location 46.
74NOITACO
L
tamroFrotacinummoCyramirP
eulaV noitcA noitpircseD
0
tluafeD
tsafrepuSaoceS SHzHk3.2,XTzHk8.1
1sserpxEocmedAFMTD,SHenoTlauD
2)ytiraPoN(2x4IBFSPP02,SHzHk3.2,XTzHk8.1
3)ytiraP(2x4IBFSPP04,SHzHk3.2,XTzHk8.1 4tsaFnilknarF/aocseSSPP02,SHzHk3.2,XTzHk8.1 6DI-tcatnoCFMTD,SHenoTlauD 7gnitropeRcitsemoDSPP02,dnilB,XTzHk8.1 8tamroFregaPFMTD,dnilB
21tsaF2x4thginKtneliSSPP02,zHk4.1,XTzHk9.1
TX = Transmit HS = Handshake PPS = Pulses per Second
The value entered into location 47 selects the format to be used for communication to the base station receiver or o ther device. Select from the table above the value appropriate to the required format. During communication the green LED on the communicator PCB will illuminate. If programmed accordingly (see location 131), the keypad will beep once the panel has received a handshake from the base station. This indicates a successful transmission of data.
NOTE ON DUAL REPORTING
If dual reporting is enabled both base stations will receive the codes programmed into locations 80 - 1 16. Codes that are disabled are disabled to both communicator formats.
34 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
NOTES ON CONTACT ID.
If the panel has been programmed to use the Contact ID reporting format (i.e. location 47=6) it is not necessary to program the reporting codes. All codes will be reported by default. Table 8 contains a list of standard (default) Contact ID reporting codes. Under certain conditions it may be necessary to change or disable certain codes. If a particular reporting code is not required, program a [0] (not “10”) into the relevant locations.
Any event that relates to a specific zone, or to a specific user, will have the relevant zone/user number attached to the end of the Contact ID reporting code.
If dual reporting is enabled and the Contact ID reporting format is required, both the primary and secondary communicator formats need to be programmed as Contact ID. It is not possible to use Contact ID in conjunction with a second format eg. Pager Format, as the second format will transmit all codes as FF or F.
It is common not to report stay arming, away arming and disarming for domestic alarms. To disable the reporting of these functions, program the following locations:
Arming or Closing code Location 108 = 0 Disarming or Open code Location 109 = 0 Home or Stay arming Location 110 = 0
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 35
IDS800 INST ALLER MANUAL
Table 8: Standard Contact ID reporting codes
noitpircseD sedoC noitircseD sedoC
resuybesolC1043ssapyBenoZ0751
mraotuaybesolC3043nwodtuhSenoZ3751
daolnwodybesolC7043larotserenoZ0313
hctiws-yekhtiwesolC9043enozybrepmaT7311
resuybnepO1041repmaTdapyeK7311
daolnwodybnepO7041tuokcoldapyeK7311
hctiws-yekhtiwnepO9041enozcinaP0211
lecnaC6041cinaP0211
noitaloivyralgruB0311cinapdapyeK0211
noitaloivretemireP1311liafCA1031
noitaloivroiretnI2311larotserCA1033
noitaloiv)efaS(ruoH423311yrettabwoL2031
noitaloivtixe/yrtnE4311tropertseT2061
noitaloivthgin/yaD5311erifdapyeK0111
noitaloivroodtuO6311eriF0111
noitaloivrepmaT7311sseruD1211
noitaloivmralaraeN8311lacidemdapyeK0011
The generic Contact ID reporting code for an alarm caused by a zone violation is 1 130, corresponding to a BURGLAR Ydescription. If you wish particular zone violations to be reported with a description other than BURGLARY an option may be chosen from Table 9 overleaf. The first digit of the reporting code relevant to that zone must be changed to the value as indicated in the table.
36 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
Table 9: Alarm reporting codes
eulaV noitpircseD sAdetropeR
01yralgruB0311
1retemireP1311 2roiretnI2311
3)efaS(ruoH423311
4tixE/yrtnE4311
5thgin/yaD5311 6roodtuO6311 7repmaT7311 8mralaraeN8311
EXAMPLE
Assuming for a given installation it is required to differentiate between entry/exit, interior and general burglary zones, and assuming that zone 1 is a front door (entry/exit zone), zone 2 is an interior PIR (interior zone) and zone 3 is a general burglary zone.
Program the following locations
1. Location 86 (Zone 1) = 4 (Code 1 134 = ENTRY/EXIT)
2. Location 88 (Zone 2) = 2 (Code 1 132 = INTERIOR)
3. Location 90 (Zone 3) = 10 (Code 1 130 = BURGLARY)
NOTES:
Although zone reporting codes for all other formats require that
both digits are programmed, the panel will only use the first digit
of the reporting code for this application. It is therefore only
necessary to program the required value into digit 1 of the relevant
zone reporting code.
NOTES ON PAGER FORMAT
The pager format transmits to an automatic digital pager . All communication takes place with the pager network in DTMF format. It will be necessary to check with the paging company to ensure that this format is supported in the area as not all pager systems support this format. To use this format the panel must be programmed as follows:
1. Program the phone numbers into locations 48-63 and locations
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 37
IDS800 INST ALLER MANUAL
64-79.
2. Follow the phone number with an 8 second delay by programming a [15] into the 2 locations immediately following the phone number (see locations 48-63).
3. Program a [6] in the location immediately after the 8 second delay . This digit serves to inform the paging network that 6 digit s of data will follow .
4. A [0] must be programmed into the location immediately following the 6. This [0] serves to terminate the phone number.
5. The account code and reporting codes must be programmed as normal.
NOTE:
Only the decimal numbers 1-10 may be used for the reporting codes, the hexadecimal numbers B-F (i.e. 1 1-15) are not permissible.
Some pager systems may require a termination digit/s to be communicated. These termination digits inform the pager network that the message is complete. Any required termination digits must be programmed into locations 142 and 143. Enter [11] for a “(” and [12] for a “#”. A [0] in these locations will be ignored.
To achieve the above it may be necessary to join the 2 phone numbers to create a single number i.e. [5] must be programmed into location
42. If both phone numbers are programmed, the data will be
transmitted alternately to each phone number. If the same number is programmed into each phone number the data will be sent multiple times (as programmed to location 125).
EXAMPLE
Assume the following:
1. The paging network number is 705 1373
2. The panel account code is 0123
3. The reporting code for a zone 1 violation is A1
4. The reporting code for a zone 2 violation is A2.
38 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
The panel would be programmed as follows:
noitacoL eulaV noitpircseD
847 rebmunenohpfotigidts1­9401rebmunenohpfotigiddn2-
055 rebmunenohpfotigiddr3­151 rebmunenohpfotigidht4­253 rebmunenohpfotigidht5­357 rebmunenohpfotigidht6­453 rebmunenohpfotigidht7­5551yaleddnoces4­6551yaleddnoces4­756 stigidgnitroperforebmun-
850 rebmunenohpetanimret­3401edoctnuoccafotigidts1­441 edoctnuoccafotigiddn2­542 edoctnuoccafotigiddr3­643 edoctnuoccafotigidht4-
6801edocgnitroper1enozfotigidts1-
781 edocgnitroper1enozfotigiddn2-
8801edocgnitroper2enozfotigidts1-
982 edocgnitroper2enozfotigiddn2-
After a successful communication attempt caused by a zone 1 violation the pager will display 012301
NOTES ON DOMESTIC REPORTING:
Domestic reporting will dial both phone numbers as programmed into locations 48-63 and 64-79. The data to be reported will be transmitted 3 times immediately after the phone number is dialled. This format provides for a simple form of easily identifiable remote alarm which may be reported to an office, mobile phone etc.
When using either of the blind formats (i.e. Domestic Reporting or Pager Format) the number will be dialled and the data will be transmitted the number of times as programmed into the number of dial attempts (location 125).
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 39
IDS800 INST ALLER MANUAL
NOTES ON PROGRAMMING TELEPHONE NUMBERS:
To dial a “0” program a [10] into the location. To dial a “(” program an [11] into the location. To dial a “#” program a [12] into the location. To create a 12 second pause in the number program a [14] into
the location.
To create a 4 second pause in the number program a [15] into the
location.
To terminate a telephone number, program a [0] (not 10) into the
location immediately following the last digit of the telephone number .
36-84NOITACO
L
rebmuNenohpeleTyramirP
.oN.coL84940515253545556575859506162636
These locations contain the primary telephone number, which may be up to sixteen digits long. A four second delay can be programmed at any point by entering a value of [15] in the respective location.
EXAMPLE
Assuming a phone number consisting of an area code 031, a 4 second pause and a phone number of 705 1373
noitacoL demmargorPeulaV
8401edocaerafotigidts1­943 edocaerafotigiddn2-
051 edocaerafotigiddr3-
1551yaleddnoces4-
257 rebmunenohpfotigidts1-
3501rebmunenohpfotigiddn2-
455 rebmunenohpfotigiddr3-
551 rebmunenohpfotigidht4-
653 rebmunenohpfotigidht5-
757 rebmunenohpfotigidht6-
853 rebmunenohpfotigidht7-
950 rebmunetanimret-
40 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
97-46SNOITACO
L
rebmuNenohpeleTyradnoceS
.oN.coL46566676869607172737475767778797
These locations contain the secondary telephone number that may be up to sixteen digits long. The same procedures apply as for the Primary T elephone Number .
Communicator Reporting Codes (Locations 80-116)
With the exception of Contact ID and Sescoa Superfast, all other communications formats are 4 x 2 reporting formats i.e. a 4 digit account code will be reported with a 2 digit reporting code. It will be noted that some reporting functions require that both digits of the reporting code be programmed while others only require a single digit to be programmed. Reporting codes with only one digit will have the second digit added automatically by the panel. An explanation is provided under each reporting code. It is however important to note that wherever space is provided for the programming of 2 reporting digits i.e. Locations 86 and 87 for zone 1 reporting code BOTH DIGITS
MUST BE PROGRAMMED
.
NOTE:
To disable any of the reporting codes program a [0] into the
locations for both digit 1 and digit 2.
All reporting codes that require a “0” to be reported must be
programmed as a [10] i.e. An “A” will be reported in the place of the “0” as per the hexadecimal values below .
eulaVlaciremu
N
123456789 011121314151
eulaVlamicedaxe
H
123456789ABCDEF
18-08SNOITACO
L
edocgnitropersseruD
This code will be reported if the panel is disarmed using the duress code (User 15 is the duress code - see the User Manual).
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 41
IDS800 INST ALLER MANUAL
38-28SNOITACO
L
edocgnitropercinaPdapyeK
This code will be reported if the panic button [P] on the keypad is pressed.
58-48SNOITACO
L
edocgnitroperrepmaTdapyeK
The keypad tamper code will be reported if multiple attempts are made to disarm the panel using the wrong user code. The code will be reported after 16 incorrect keystrokes i.e. four incorrect user codes.
101-68SNOITACO
L
sedocgnitroperenoZ
snoitacoL edoCgnitropeR
78-681enoZ 98-882enoZ 19-093enoZ 39-294enoZ 59-495enoZ 79-696enoZ 99-897enoZ
101-0018enoZ
Zone reporting codes will be reported if a violation of a zone causes an alarm condition. Various conditions will apply as to when an alarm condition will be registered. These conditions are determined by the zone characteristics as programmed into locations 1 to 8.
301-201SNOITACO
L
edocgnitroperliaFCA
The AC fail will only be reported if the AC power is lost for a period longer than the delay programmed into location 19.
501-401SNOITACO
L
edocgnitroperlarotseRCA
The AC restoral code will be reported if the AC power was lost for a period longer than the delay programmed into location 19 and only after the AC power has been restored for the same period of time.
42 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
701-601SNOITACO
L
edocgnitroperyrettaBwoL
The low battery condition will be reported if the battery voltage drops below 10 volts. If the battery fuse blows then the battery will discharge and a low battery condition will be reported, even if the AC power is present.
801NOITACO
L
edocgnitroperyawA&esolC
The close code will be reported when the system is armed in the AWAY mode indicated by illuminated ARMED and AWAY LED’s on the keypad.
NOTE:
The close code will not be reported if the system is armed in the ST AY mode. The digit programmed into this location is the first digit of the reporting code. The second digit will automatically be added and will be the number which corresponds to the user code used to arm the system (See Users Manual).
EXAMPLE:
If a close code of C (12) is programmed and the master user code is used to arm the system the 2 digit reporting code would be C1 indicating a close by user 1.
NOTE:
If the system is armed using the quick arm “AWA Y” key the system will report a close by user 1. If the system is armed by means of a key or remote using an arm/ disarm zone the system will report a close by user 13.
901NOITACO
L
edocgnitropernepO
The open code will be reported when the system is disarmed.
NOTE:
The open code will not be reported if the system was armed in the stay mode and the stay arming reporting code (location 110) is 0 i.e. Disabled.
The digit programmed into this location is the first digit of the reporting code. The second digit will automatically be added and will be the number which corresponds to the user code used to disarm the
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 43
IDS800 INST ALLER MANUAL
system (See Users Manual).
EXAMPLE:
If an open code of B (1 1) is programmed and the master user code is used to disarm the system, the 2 digit reporting code would be B1 indicating an open by user 1.
NOTE:
If the system is disarmed by means of a key or remote using an arm/ disarm zone the system will report open by user 13.
011NOITACO
L
edocgnitroperyatS&esolC
The stay code will be reported when the system is armed in the stay mode indicated by an illuminated ARMED but extinguished AWAY
LED
on the keypad. The digit programmed into this location is the first digit of the reporting code. The second digit will automatically be added and will be the number which corresponds to the user code used to arm the system (See Users Manual). See the EXAMPLE and NOTE for location 108.
211-111SNOITACO
L
edocgnitropertset-otuA
This code is the test reporting code and will be reported at regular intervals as programmed into location 138. Reporting of this code is recommended as it provides verification that the system is functioning correctly.
411-311SNOITACO
L
edocgnitropereriFdapyeK
This code will be reported if the fire button [F] on the keypad is pressed until the keypad beeps (approximately 2 seconds).
611-511SNOITACO
L
edocgnitroperlacideMdapyeK
This code will be reported if the medical button [M] on the keypad is pressed until the keypad beeps (approximately 2 seconds).
711NOITACO
L
edocgnitroperenoZdessapyB
A zone bypass code will be reported if the panel is armed with a
44 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
bypassed zone. The zone number will be appended to this reporting code to provide the 2 digit reporting code.
811NOITACO
L
edocgnitroperrepmaTenoZ
The zone tamper code will only be reported if the zone tamper function has been enabled, see location 1 1. The zone number will be appended to this reporting code to provide the 2 digit reporting code.
911NOITACO
L
edocgnitropernwod-tuhSenoZ
The zone shut down code will be reported if the system is armed and a zone is automatically bypassed as a result of multiple violations of that zone while the panel is armed. The number of permissible violations is dependent on the value programmed into location 132. The zone number will be appended to this reporting code to provide the 2nd digit of the reporting code.
021NOITACO
L
edocgnitroperlecnaC
If the siren is sounding and the siren is cancelled by either a valid user code or key/remote, a cancel code will be reported. A silent alarm or silent panic will not cause the cancel code to be reported.
121NOITACO
L
edocgnitroperlarotseRenoZ
If the panel is armed and a violation of a zone occurs followed by the zone returning to the normal (non alarm) state, a zone violation followed by a zone restoral will be reported. The zone restoral code indicates that the zone has returned to the ready condition.
321-221SNOITACO
L
edocgnitroperetelpmoCdaolnwoD
This code will be sent once a successful download to a panel has been completed.
421NOITACO
L
devreseR
521NOITACO
L
)4=tluafeD(stpmettAlaiD
Determines the maximum number of dial attempts the panel will make to contact the base station.
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 45
IDS800 INST ALLER MANUAL
NOTE:
Entering [0] into this location will disable the dialler.
921-621SNOITACO
L
)9999:tluafeD(edocDIsrellatsnI
The installer’s ID code is used by the installer to enter the program mode. This may be changed by entering a new 4 digit code into these 4 locations. Although not possible from the keypad it is possible using the IDS PC download software to enter an installers ID code containing the hexadecimal digits A-F. If these digits are used as part of the installers ID it will prevent access to programming mode from the keypad. In this case program access can only be achieved by using the IDS PC download software.
031NOITACO
L )
4=tluafeD(tuokcolpkerofebsedoctcerrocni.oN
Determines the number of incorrect codes that can be entered before a keypad lockout event occurs. This number can be any number between 1 and 15. The default value is 4 i.e. 16 incorrect keystrokes, and a [0] entered into this location disables keypad lockout. When keypad lockout has occurred the keypad will beep 10 times and will remain unresponsive to any keystroke for 30 seconds.
131NOITACO
L
snoitpOrezzuBdapyeK
eulaV noitcA
0peeBoN
1elbuortnopeeB
)tluafeD(2 noitacinummocnopeeB
3noitacinummocnopeeb,elbuortnopeeB
The keypad can be programmed to beep once to indicate successful communication of data to the base station, and intermittently (on/off) to provide and audible indication of a trouble condition. The beeping can be cancelled by pressing [#]. For a list of trouble conditions and how to view them refer to the section headed “Trouble Conditions” in the Users Manual. Enter the appropriate value from the above table.
231NOITACO
L
)0=tluafeD(eulaVtnuoCnwodtuhSregniwS
Determines the number of times a zone may be violated during an arm
46 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
cycle before it is automatically bypassed. The count will be twice the value entered. The maximum value of 15 may be entered, corresponding to 30 violations required to force the zone to bypass. Disable swinger shutdown by entering [0] in this location.
331NOITACO
L
esnopseRpooLenoZ
eulaV
noitcA
0
tluafeD
emitesnopseR sm001-
1emitesnopseRsm21­2emitesnopseRsm42­3emitesnopseRsm63-
4emitesnopseRsm84-
5emitesnopseRsm06­6emitesnopseRsm27­7emitesnopseRsm48­8emitesnopseRsm69­9emitesnopseRsm801-
01emitesnopseRsm021­11emitesnopseRsm231­21emitesnopseRsm441­31emitesnopseRsm651­41emitesnopseRsm861­51emitesnopseRsm081-
The zone loop response is the period of time for which the zone must be violated before a violation is registered. A value of [0] provides a loop response time of 100ms.
431NOITACO
L
)0=tluafeD(tnuoCpirTenoZ
This feature is to prevent false alarms while the panel is armed. If the panel is armed and a zone is violated the number of times programmed into this location within the time period programmed into location 135, then an alarm condition will be registered. Program a value from [0] to [15]. A [0] will disable the location.
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 47
IDS800 INST ALLER MANUAL
531NOITACO
L
)0=tluafeD(yaleDemiTtnuoCpirTenoZ
This time delay period applies to location 134. If the panel is armed and the number of violations programmed into location 134 occurs within this time delay , an alarm condition will register . Program a value from [0] to [15]. Multiply the value of the entry by 10 seconds to calculate the delay time.
631NOITACO
L
yaleDpeelSdapyeK
eulaV yaleD eulaV yaleD
0
delbasiD
)tluafeD(8
sdnoces821
1
sdnoces61
9
sdnoces441
2
sdnoces23
01
sdnoces061
3
sdnoces84
11
sdnoces671
4
sdnoces46
21
sdnoces291
5
sdnoces08
31
sdnoces802
6
sdnoces69
41
sdnoces422
7
sdnoces211
51
sdnoces042
This location programs the period of time that the keypad’s back­lighting will remain illuminated without activity . [0] disables this function resulting in constantly illuminated keys. The location can have a value from [0] to [15].
48 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
731NOITACO
L
yalpsiDelbuorTelbammargorP
eulaV
foyalpsiD
liaF.smmoC
foyalpsiD
repmaTdapyeK
.
gnEfoyalpsiD
teseR
0

1
>

2
>
3
>>
4

>
5
>
>
6
>
>
7
tluafeD
> > >
>
delbanE
delbasiD
This location determines whether Communication failure, keypad tamper or engineers reset are displayed as trouble conditions. Should the display be disabled no trouble condition will be shown i.e. the power LED will not flash and no trouble condition shown when entering trouble viewing mode. However , reporting codes, if programmed, will be reported to the base station.
NOTE:
Low battery and AC fail trouble condition displays cannot be
disabled.
If Engineer reset is enabled (see location 12), but the trouble
condition display is disabled, the panel will not show a trouble condition if an alarm condition has been registered but the system will not arm until an Installer code has been entered.
831NOITACO
L
yaleDtset-otuA
eulaV noitcA
0
tluafeD
sruoh42yrevestropeR
1sruoh84yrevestropeR
6keewaecno.e.isyad7yrevestropeR
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 49
IDS800 INST ALLER MANUAL
The time period between auto-test reports is programmed using this location. The time period is incremented in 24 hour increments with the shortest time period being 24 hours. The maximum value which may be programmed into this location is
15.
931NOITACO
L
devreseR
041NOITACO
L
)51=tluafeD(rewsnaerofebsgnirforebmuN
This location programs the number of rings before the panel picks up the telephone line and attempts to up/download. In the event that the panel picks up the phone and no valid download log on sequence is received by the panel, the call will be terminated by the panel after 40 seconds.
Note that the default value of 15 (maximum permissible value) enables the fax defeat mode. If fax defeat is enabled and the phone rings 15 times the panel will answer the call, if however the phone rings and the call is terminated within 3 rings the panel will within a 60 second window answer a second call on the first ring.
Fax defeat is a useful feature for downloading when a fax or answering machine is connected to the same phone line as the alarm panel. If enabled: dial the panel and hang up before 3 rings. Dial the panel again within 1 minute. The panel will pick up the call on the first ring thereby preventing the fax/ answering machine from answering the call before the alarm panel.
A number lower than 15 programmed into this location disables the fax defeat mode.
141NOITACO
L
devreseR
341-241SNOITACO
L
)0:tluafeD(stigiDdnEregaP
If the pager format is selected (a value of 8 in location 47) these digits are communicated after the panel has sent all data to the paging network. They are used to indicate to the automated pager service that the message is complete. These are typically either a ( (11) or a # (12), if only a single digit is required, program location 142 only .
50 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
741-441SNOITACO
L
edoCtnuoccArotacinummoCyradnoceS
This account code is used if the panel is communicating to two base stations and will be transmitted to the secondary phone number . See Locations 43 - 46 for information regarding the programming of these locations.
841NOITACO
L
)0=tluafeD(tamroFrotacinummoCyradnoceS
This communicator format is used if the panel is communicating to two base stations and will be transmitted to the secondary phone number . See Location 47 and the subsequent notes for information regarding the programming of this location.
651-941SNOITACO
L
devreseR
751NOITACO
L
)0=tluafeD(yaleDnoitacinummoC
If an event occurs that will be reported, the panel will wait for this period of time before transmitting the relevant reporting codes either by phone or radio outputs. If a valid user code is entered during the delay period, the reporting codes will not be transmitted. The event will still be recorded in the event log. The value of this location ranges from 0 to 75 seconds in 5 second increments. Program a value from [0] to [15]. Multiply the value of the entry by 5 seconds to calculate the delay time. The communication of the following events will not be delayed under any circumstances:
Duress Audible/ Silent Priority Zones Keypad Panic Keypad Medical Keypad Fire Zone Programmable Outputs (see Loc. 159 - 166)
851NOITACO
L
)0=tluafeD(ekahsdnaHretfAyaleDXT
Sets the delay time that the control panel waits before sending data after it receives the initial handshake tone from the base station. This feature allows the panel to be customized to communicate with a wide range of base station receivers. The value entered into this location is in increments of 100ms.
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 51
IDS800 INST ALLER MANUAL
661-951SNOITACO
L
senoZ-slortnoCtuptuOelbammargorP
SEE LOCA TIONS 22 - 44 and T ABLE 6
.coL tnevE eulaV noitcAtluafeD
951
tuptuo1enoZ
0
delbasiD
061
tuptuo2enoZ
0
delbasiD
161
tuptuo3enoZ
0
delbasiD
261
tuptuo4enoZ
0
delbasiD
361
tuptuo5enoZ
0
delbasiD
461
tuptuo6enoZ
0
delbasiD
561
tuptuo7enoZ
0
delbasiD
661
tuptuo8enoZ
0
delbasiD
A programmable output will be activated when a zone is violated.
Set System Time, Auto-Test Time, Automatic Arm Time
All time values must be entered as a 4 digit value in hours and minutes in a 24 hour format i.e. 1.00pm is entered as 1300.
T o view and change values in these locations:
1. Enter programming mode by entering a valid [INST ALLER
CODE]
followed by [)].
2. Enter [LOCA TION NUMBER] e.g. 800 followed by [)]
3. The value displayed by the LEDs will be the hour value.
4. Press [)] and the LEDs will display the minutes value. It is necessary to display the hours and minutes separately as it is not possible to display 4 digits on the keypad simultaneously.
008NOITACO
L
)0000:tluafeD(emiTmetsyS
This location is used for setting the system clock time.
108NOITACO
L
)0010:tluafeD(emiTtset-otuA
This location is used for setting the time of day at which the auto-test will be reported.
EXAMPLE:
If a value of 6 was programmed into location 138 and 1400 was
52 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
programmed into location 801, the auto test would be sent every seven days at 2:00pm.
208NOITACO
L
)9999:tluafeD(emiTmrAotuA
This location sets the time at which the panel will automatically arm every day (if enabled). The auto arm feature is disabled by entering an invalid time greater than 2400 e.g. 9999.
14. Trouble Condition Summary
The table below indicates the trouble conditions.
rotacidnI noitidnoCelbuorT
2ynapmocgnirotinomotetacinummocoteruliaF 3eruliafrewopsniaM
4yrettabwoL
7repmatadecneirepxesahdapyeK 8noitidnocmralanaraelcotderetneebtsumedocsrellatsnI
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 53
IDS800 INST ALLER MANUAL
Index
A
AC Fail ............................................................... 12, 26, 28, 35, 41, 48
AC Power ............................................................................. 12, 26, 41
AC Restore ..................................................................... 26, 28, 35, 41
Alarm Memory ....................................................................................2
Arm/ Disarm Zone - see “Zone” Audible Instant Zone - see “Zone” Audible Priority Zone - see “Zone”
Auto-arm.......................................................................................5, 35
Time ................................................................................... 51, 52
Auto-test..................................................................................... 28, 43
Delay ........................................................................................ 49
Time .........................................................................................51
Auxiliary Power Outputs .....................................................................5
Away Mode.......................................................................................42
B
Base St ation...................................................5, 26, 30, 33, 45, 48, 50
Battery.......................................... 5, 10, 11, 12, 26, 28, 35, 42, 48, 49
Fuse ................................................................................... 1 1, 42
Binary ......................................................................................... 14, 15
Buzz ...................................................................................................2
Bypass ...........................................................2, 22, 23, 35, 43, 44, 46
C
Ch ime ..................................................................................... 2, 1 1, 28
Communicator .............................................................. 5, 8, 11, 12, 40
Format..............................................................16, 32, 33, 34, 50
Primary Account Code .............................................................32
Secondary Account Code...................................................32, 50
Contact ID ................................................................16, 33, 34, 35, 40
D
Dial Attempts....................................................................................44
Dialler Progress ............................................................................5, 13
54 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
Dialling
Pulse .................................................................................. 30, 31
Ton e....................................................................................30, 31
Dialling Options ................................................................................ 30
Domestic Reporting ....................................................................33, 38
Download ..............................................................5, 13, 14, 35, 45, 48
Download Code................................................................................. 13
DTMF.......................................................................................... 33, 36
Dual Reporting ............................................................5, 30, 31, 33, 34
Duress ..............................................................................2, 28, 35, 40
E
End-of-Line Resistors .....................................................5, 7, 8, 18, 21
Engineer Reset ............................................................... 22, 23, 47, 48
Entry
Delay ................................................................10, 18, 20, 22, 26
Primary Delay...............................................................19, 21, 26
Secondary Delay ................................................................ 19, 21
Entry/ Exit Zone - see “Zone”
Event Log..........................................................................5, 12, 26, 50
Exit Delay.....................................................10, 18, 19, 20, 22, 23, 23
Expansion Module ....................................................................8, 9, 27
F
Factory Default V alues ............................................................... 12, 16
Fax Defeat Mode ....................................................................5, 48, 49
Fire .....................................................................2, 28, 29, 30, 35, 43
Fire Zone - see “Zone” Follower Zone - see “Zone”
Forced Answer by Panel.....................................................................2
Forced Arming ..................................................................................22
H
Hardware Reset Switch ..............................................................12, 27
Hexadecimal................................................................... 32, 37, 40, 45
I
Installer Code................................................12, 15, 23, 27, 45, 48, 51
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 55
IDS800 INST ALLER MANUAL
K
Keypad Sleep Delay .........................................................................47
Keyswitch.....................................................10, 18, 22, 24, 35, 43, 44
L
Lightning.........................................................................................5, 8
Line Seizure Mode.............................................................................. 8
Loop Response Time ....................................................................5, 46
M
Master User Code ................................................................16, 42, 43
Medical Alarm...................................................................2, 28, 35, 43
P
Pager ..................................................................33, 34, 36, 37, 38, 49
Panic ....................................................................2, 24, 28, 35, 41, 44
Phone Numbers - see “T elephone Numbers”
Power ............................................................................................... 11
Power Failure................................................................................5, 26
Primary Communicator Format - see “Communicator” Primary Entry Delay - see “Entry”
Programmable Outputs.............................................5, 8, 9, 27, 29, 50
Programming Mode .......................................................................... 16
Push to Arm Zone - see “Zone”
Q
Quick Arm ..................................................................................22, 23
R
Relay Board..................................................................................8, 27
Reporting Code ..................... 34, 35, 36, 37, 38, 40, 41, 42, 43, 44, 50
S
Secondary Communicator Format - see “Communicator”
56 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
Secondary Entry/ Exit - see Entry
Sescoa Superfast .................................................................32, 33, 40
Shutdown.......................................................................................... 44
Siren ........................................................... 5, 7, 11, 18, 19, 24, 25, 44
Time-out Period ........................................................................ 25
St ay Arm.....................................................................................23, 34
St ay Mode ................................................................18, 23, 24, 42, 43
St ay Profile .........................................................................................2
Strobe ................................................................................... 27, 28, 29
System Time .................................................................................... 51
Swinger Shutdown ......................................................................45, 46
T
Tamper..................................................................5, 28, 35, 36, 41, 47
T amper per Zone ..................................................................... 7, 10, 21
T elephone Numbers ......................................30, 31, 36, 37, 38, 39, 48
Primary................................................................... 31, 32, 39, 40
Secondary ..............................................................27, 31, 32, 49
T ermination Digits............................................................................. 37
Trouble Condition ..............................................................2, 23, 47, 48
Trouble Condition Display .....................................................47, 48, 52
Trouble Mode ....................................................................................23
Z
Zone Arm/ Disarm .................................................................10, 18, 42
Audible Instant ...................................................................17, 18
Audible Priority ...............................................................5, 17, 18
Disable .....................................................................................18
Entry/ Exit .................................................. 17, 18, 20, 23, 25, 36
Fire ...........................................................................................19
Follower............................................................ 17, 18, 20, 25, 27
Instant ......................................................................................27
Panic .................................................................... 5, 7, 10, 1 1, 35
Primary Entry/ Exit.......................................................19, 21, 27
Push to Ar m .............................................................................19
Secondary Entry/ Exit ........................................................19, 21
Silent Instant ...................................................................... 19, 24
Silent Priority..................................................................5, 18, 28
Stay......................................................................................2, 23
Trip Count................................................................................. 46
Trip Count Time Delay ..............................................................46
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 57
IDS800 INST ALLER MANUAL
COL noitpircseD eulaVweN tluafeD ataD.feD
0tluafeDyrotcaFotteseR teseRot0
1epyT1enoZtixe/yrtnE1 2epyT2enoZrewolloF2 3epyT3enoZtnatsnIelbiduA4 4epyT4enoZtnatsnIelbiduA4 5epyT5enoZtnatsnIelbiduA4 6epyT6enoZtnatsnIelbiduA4 7epyT7enoZtnatsnIelbiduA4 8epyT8enoZytiroirPelbiduA3
snoitpOmetsyS
9snoitpOtixe/yrtnEnoitacoleeS9
01yaleDyrtnEyradnoceSetuniM15 11elbasid/elbanEenoZreprepmaTdelbasiD0 21snoitpOgnimrAnoitacoleeS1 31snoitpOmrAyatS delbanEedoMyatS0 41snoitpOcinaPdapyeKtneliS delbasiDcinaPtneliS0 51snoitpOmralAtneliS delbasiDmralAtneliS0 61mrasid/mrAnotooTneriStooToN0 71doirePtuOemiTneriSsetuniM26 81doirePyaleDtixEsdnoceS033 91emiTerotserdnaliaFCAsetuniM21 02yaleDyrtnEyramirPsdnoceS033 12elbasid/elbanEhctiwSteseRerawdraHdelbanE51
snoitpOtuP-tuO
22P/O.gorPmralA2P/O.gorPesluP2 32P/O.gorPytiroirPelbiduA1P/O.gorPesluP1 42P/O.gorPyrettaBwoLdelbasiD0 52P/O.gorPtset-otuAdelbasiD0 62P/O.gorPsseruD1P/O.gorPesluP1 72P/O.gorPliaFCAdelbasiD0 82P/O.gorPyawA&esolC hgiH3P/O.gorPteS8 92P/O.gorPnepO woL3P/O.gorPteS31 03P/O.gorPerotseRCAdelbasiD0 13P/OgorPlecnaCdelbasiD0
58 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
COL noitpircseD eulaVweN tluafeD ataD.feD
23P/O.gorPeriFdelbasiD0 33P/O.gorPlacideMdelbasiD0 43P/O.gorPebortSdelbasiD0 53P/O.gorPrepmaTdelbasiD0 63P/O.gorPytiroirPtneliS1POgorPesluP1 73P/O.gorPrewoPtceteDeriFdelbasiD0 83P/O.gorPemihC.xuAdelbasiD0 93P/O.gorPliaFsmmoCdelbasiD0 04P/O.gorP2rebmuNenohPdelbasiD0
14 devreseR
snoitpOnoitacinummoCyramirP
24snoitpOgnillaiDenoT1 341tigiDedoCtnuoccAyramirPdelbasiD0 442tigiDedoCtnuoccAyramirPdelbasiD0 543tigiDedoCtnuoccAyramirPdelbasiD0 644tigiDedoCtnuoccAyramirPdelbasiD0 74tamroFrotacinummoCyramirPtsafrepuSaocseS0
rebmuNenohPyramirP
841tigiD1.oNenohPdelbasiD0 942tigiD1.oNenohPdelbasiD0 053tigiD1.oNenohPdelbasiD0
154tigiD1.oNenohPdelbasiD0 255tigiD1.oNenohPdelbasiD0 356tigiD1.oNenohPdelbasiD0 457tigiD1.oNenohPdelbasiD0 558tigiD1.oNenohPdelbasiD0 659tigiD1.oNenohPdelbasiD0 7501tigiD1.oNenohPdelbasiD0 8511tigiD1.oNenohPdelbasiD0 9521tigiD1.oNenohPdelbasiD0 0631tigiD1.oNenohPdelbasiD0
1641tigiD1.oNenohPdelbasiD0 2651tigiD1.oNenohPdelbasiD0 3661tigiD1.oNenohPdelbasiD0
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 59
IDS800 INST ALLER MANUAL
COL noitpircseD eulaVweN tluafeD ataD.feD
rebmuNenohPyradnoceS
461tigiD2.oNenohPdelbasiD0 562tigiD2.oNenohPdelbasiD0 663tigiD2.oNenohPdelbasiD0 764tigiD2.oNenohPdelbasiD0 865tigiD2.oNenohPdelbasiD0 966tigiD2.oNenohPdelbasiD0 077tigiD2.oNenohPdelbasiD0 178tigiD2.oNenohPdelbasiD0 279tigiD2.oNenohPdelbasiD0 3701tigiD2.oNenohPdelbasiD0 4711tigiD2.oNenohPdelbasiD0 5721tigiD2.oNenohPdelbasiD0 6731tigiD2.oNenohPdelbasiD0 7741tigiD2.oNenohPdelbasiD0 8751tigiD2.oNenohPdelbasiD0 9761tigiD2.oNenohPdelbasiD0
sedoCgnitropeR
081tigiDedoCgnitropeRsseruDdelbasiD0 182tigiDedoCgnitropeRsseruDdelbasiD0 281tigiDedoCgnitropeRcinaPdapyeKdelbasiD0 382tigiDedoCgnitropeRcinaPdapyeKdelbasiD0 481tigiDedoCgnitropeRrepmaTdapyeKdelbasiD0 582tigiDedoCgnitropeRrepmaTdapyeKdelbasiD0 681tigiDedoCgnitropeRmralA1enoZdelbasiD0 782tigiDedoCgnitropeRmralA1enoZdelbasiD0 881tigiDedoCgnitropeRmralA2enoZdelbasiD0 982tigiDedoCgnitropeRmralA2enoZdelbasiD0 091tigiDedoCgnitropeRmralA3enoZdelbasiD0 192tigiDedoCgnitropeRmralA3enoZdelbasiD0 291tigiDedoCgnitropeRmralA4enoZdelbasiD0 392tigiDedoCgnitropeRmralA4enoZdelbasiD0 491tigiDedoCgnitropeRmralA5enoZdelbasiD0 592tigiDedoCgnitropeRmralA5enoZdelbasiD0
60 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
COL noitpircseD eulaVweN tluafeD ataD.feD
691tigiDedoCgnitropeRmralA6enoZdelbasiD0 792tigiDedoCgnitropeRmralA6enoZdelbasiD0 891tigiDedoCgnitropeRmralA7enoZdelbasiD0 992tigiDedoCgnitropeRmralA7enoZdelbasiD0
0011tigiDedoCgnitropeRmralA8enoZdelbasiD0
1012tigiDedoCgnitropeRmralA8enoZdelbasiD0 2011tigiDedoCgnitropeRliaFCAdelbasiD0 3012tigiDedoCgnitropeRliaFCAdelbasiD0 4011tigiDedoCgnitropeRerotseRCAdelbasiD0 5012tigiDedoCgnitropeRerotseRCAdelbasiD0 6011tigiDedoCgnitropeRyrettaBwoLdelbasiD0 7012tigiDedoCgnitropeRyrettaBwoLdelbasiD0 801edoCgnitropeRyawA&esolCdelbasiD0 901edoCgnitropeRnepOdelbasiD0 011edoCgnitropeRyatS&esolCdelbasiD0 1111tigiDedoCgnitropeRtset-otuAdelbasiD0 2112tigiDedoCgnitropeRtset-otuAdelbasiD0 3111tigiDedoCgnitropeReriFdapyeKdelbasiD0 4112tigiDedoCgnitropeReriFdapyeKdelbasiD0 5111tigiDedoCgnitropeRlacideMdapyeKdelbasiD0 6112tigiDedoCgnitropeRlacideMdapyeKdelbasiD0 711edoCgnitropeRenoZdessapyBdelbasiD0 811edoCgnitropeRrepmaTenoZdelbasiD0 911edoCgnitropeRnwodtuhSenoZdelbasiD0 021edoCgnitropeRlecnaCdelbasiD0
121edoCgnitropeRlarotseRenoZdelbasiD0 2211tigiDedoCgnitropeRetelpmoCdaolnwoDdelbasiD0 3212tigiDedoCgnitropeRetelpmoCdaolnwoDdelbasiD0 421 devreseR 521stpmettAlaiDruoF4 6211tigiDedoCsrellatsnI 9 7212tigiDedoCsrellatsnI 9 8213tigiDedoCsrellatsnI 9 9214tigiDedoCsrellatsnI 9
IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45 61
IDS800 INST ALLER MANUAL
COL noitpircseD eulaVweN tluafeD ataD.feD
031tuokcolpkerofebsedoctcerrocnifo.oNsedoctcerrocnI44
131snoitpOrezzuBdapyeK noitacinummoCnopeeB2 231tnuoCnwodtuhSregniwSdelbasiD0 331esnopserpooLenoZsm0010 431tnuoCpirTenoZdelbasiD0 531yaleDemiTtnuoCpirTenoZdelbasiD0 631yaleDpeelSdapyeKsdnoceS8218 731yalpsiDelbuorTelbammargorPnoitacoleeS7 831yaleDtset-otuAsruoH42yrevE0 931 devreseR 041rewsnAerofeBsgniRfo.oNsgniR5151
141 devreseR 2411tigiDdnEregaPdelbasiD0 3412tigiDdnEregaPdelbasiD0
snoitpOrotacinummoCyradnoceS
4411tigiDedoCtnuoccAyradnoceSdelbasiD0 5412tigiDedoCtnuoccAyradnoceSdelbasiD0 6413tigiDedoCtnuoccAyradnoceSdelbasiD0 7414tigiDedoCtnuoccAyradnoceSdelbasiD0 841tamroFrotacinummoCyradnoceS tsafrepuSaocseS0 941 devreseR 051 devreseR
151 devreseR 251 devreseR 351 devreseR 451 devreseR 551 devreseR 651 devreseR 751yaleDnoitacinummoCyaledoN0 851ekahsdnaHretfAyaleDXTdelbasiD0
stup-tuOelbammargorPenoZ
951P/O.gorP1enoZdelbasiD0 061P/O.gorP2enoZdelbasiD0
161P/O.gorP3enoZdelbasiD0
62 IDS800 INSTALLER MANUAL NO. 700-175-02N ISSUED JUL 2003 VER 1.45
IDS800 INST ALLER MANUAL
COL noitpircseD eulaVweN tluafeD ataD.feD
261P/O.gorP4enoZdelbasiD0 361P/O.gorP5enoZdelbasiD0 461P/O.gorP6enoZdelbasiD0 561P/O.gorP7enoZdelbasiD0 661P/O.gorP8enoZdelbasiD0 008emiTmetsySdelbasiD0 108emiTtseT-otuA.m.a10010 208emiTmrAcitamotuAdelbasiD9999
Loading...