NNoottee:: Graphics in this document are for representation
only. Actual model may differ in appearance.
D345855P01
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
IImmppoorrttaanntt:: — This document pack contains a wiring
diagram and service information. This is
customer property and is to remain with
this unit. Please return to service
information pack upon completion of work.
WWAARRNNIINNGG
FFIIRREE OORR EEXXPPLLOOSSIIOONN HHAAZZAARRDD!!
Failure to follow safety warnings exactly
could result in a fire or explosion causing
property damage, personal injury or loss
of life.
The following steps shall be followed for
each appliance connected to the venting
system being placed into operation, while
all other appliances connected to the
venting system are not in operation:
Airflow greater than 1600 CFM requires dual returns
All Furnaces
Document Pack Contents
ItemQty.Description
11Condensate Drain Tube Assembly
21
31
Inlet Vent
Inlet Vent Gasket
41Outlet Vent Assembly
51Outlet Vent Gasket
66Screws
71Condensate Trap Grommet
81Plug — Condensate/Gas
91Plug — Electrical
102Grommet — Condensate/Gas
111Installer’s Guide
121Service Facts
131Owner Guide
141Limited Warranty
1512” to 3” Coupling — CPL00938
(a)
3” inlet vent supplied with S9V2D120UPSBA and S9V2D120DPSBA only. 2” inlet vent supplied with all other models.
(b)
Supplied with S9V2D120U5PSBA and S9V2D120D5PSBA only
(a)
(b)
18-CE01D1-1F-EN
9
Page 10
Furnace Installation Guidelines
The following sections give general guidelines for the
installation of the gas furnaces.
Safety Practices and Precautions
The following safety practices and precautions must be
followed during the installation, servicing, and
operation of this Furnace.
1. Use only with the type gas approved for this
Furnace. Refer to the Furnace rating plate.
2. Install the Furnace only in a location and position as
specified in “Locations and Clearances” of these
instructions.
3. Provide adequate combustion and ventilation air to
the Furnace space as specified in “Air for
Combustion and Ventilation” of these instructions.
4. Combustion products must be discharged
outdoors. Connect this Furnace to an approved vent
system only, as specified in the “Venting” section
of these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made
specifically for the detection of leaks to check all
connections, as specified in the “Gas Piping”
section of these instructions.
6. Always install the Furnace to operate within the
Furnace’s intended temperature-rise range with a
duct system which has an external static pressure
within the allowable range, as specified on the unit
rating plate. Airflow within temperature rise for cfm
versus static is shown in the Service Facts
accompanying this Furnace.
7. When a Furnace is installed so that the supply ducts
carry air circulated by the Furnace to areas outside
the space containing the Furnace, the return air
shall also be handled by a duct(s) sealed to the
Furnace casing and terminating outside the space
containing the Furnace.
8. A gas-fired Furnace for installation in a residential
garage must be installed as specified in "Location
and Clearances" section of these instructions.
9. For non-Canadian applications, the furnace may be
used for temporary heating of buildings or
structures under construction only when the
following conditions have been met:
IImmppoorrttaanntt:: Gas furnaces manufactured on or after May
1, 2017 are not permitted to be used in
Canada for heating buildings or structures
under construction.
a. The Furnace venting system must be complete
and installed per manufacturer’s instructions.
b. The Furnace is controlled only by a room
Comfort Control (no field jumpers).
c. The Furnace return air duct must be complete
and sealed to the Furnace.
d. The Furnace input rate and temperature rise
must be verified to be within the nameplate
marking.
e. All air filters must be in place.
f. 100% of the Furnace combustion air
requirement must come from outside the
structure.
g. The Furnace return air temperature range is
between 55 and 80 Fahrenheit.
h. Clean the Furnace, duct work, and components
upon substantial completion of the construction
process, and verify Furnace operating
conditions including ignition, input rate,
temperature rise, and venting, according to the
manufacturer’s instructions.
This Furnace is certified to leak 2% or less of nominal
air conditioning CFM delivered when pressurized to .5”
water column with all inlets, outlets, and drains sealed.
General Guidelines
The manufacturer assumes no responsibility for
equipment installed in violation of any code or
regulation.
It is recommended that Manual J of the Air
Conditioning Contractors Association (ACCA) or A.R.I.
230 be followed in estimating heating requirements.
When estimating heating requirements for installation
at Altitudes above 2000 ft., remember the gas input
must be reduced. See Combustion and Input Check.
Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing,
and flue connections must be adhered to. In the
absence of local codes, the installation must conform
with latest edition of the National Fuel Gas Code ANSI
Z223.1 / NFPA 54 • National Installation Code, CAN/CGA
B149.1. The latest code may be obtained from the
American Gas Association Laboratories, 400 N. Capitol
St. NW, Washington D.C. 20001.
1-800-699-9277 or www.aga.org.
These Furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI
Z21.47 standards • CSA 2.3. Category IV furnaces
operate with positive vent static pressure and with a
flue loss less than 17 percent. These conditions require
special venting systems, which must be gas tight and
water tight. These Category IV Direct Vent Furnaces are
approved for installation in Manufactured/ Mobile
housing when used with BAYMFGH200A.
A manufactured (mobile) home installation must
conform with the Manufactured Home Constructionand Safety Standard, Title 24 CFR, Part 3280, or when
this Standard is not applicable, the Standard for
Manufactured Home Installations (Manufactured Home
Sites, Communities and Set-Ups), ANSI/NCS A225.1.
and/or MH Series Mobile Homes, CAN/CSA-Z240.
Locations and Clearances
The location of the Furnace is normally selected by the
architect, the builder, or the installer. However, before
the Furnace is moved into place, be sure to consider
the following requirements:
1. Is the location selected as near the chimney or vent
and as centralized for heat distribution as practical?
2. Do all clearances between the Furnace and
enclosure equal or exceed the minimums stated in
Clearance Table below?
Minimum clearance to combustible materials
Closet
Sides0 In.
Back1 In.
Top1 In.
Front0 In.
Bottom0 In.
Flue0 In.
24 In. minimum front clearance recommended for service
Horizontal Closet and Alcove
Right Side0 In.
Left Side0 In.
Back
Top1 In.
Bottom0 In.
Flue0 In.
Horizontal Flue (discharge on left)
Closet
Right Side0 In.
Left Side
Rear1 In.
1 In.
0 In.
Top1 In.
Bottom0 In.
Flue0 In.
3. Is there sufficient space for servicing the Furnace
and other equipment? A minimum of 24 inches
front accessibility to the Furnace must be provided.
Any access door or panel must permit removal of
the largest component.
4. Are there at least 3 inches of clearance between the
Furnace combustion air openings in the front panel
and any closed panel or door provided?
5. Are the ventilation and combustion air openings
large enough and will they remain unobstructed? If
outside air is used, are the openings set 12" above
the highest snow accumulation level?
6. Allow sufficient height in supply plenum above the
Furnace to provide for cooling coil installation, if
the cooling coil is not installed at the time of this
Furnace installation.
7. The Furnace shall be installed so electrical
components are protected from water.
8. If the Furnace is installed in a garage, it must be
installed so that the burners, and the ignition
source are located not less than 18 inches above the
floor and the Furnace must be located or protected
to avoid physical damage from vehicles.
9. The gas furnace must not be located where
excessive exposure to contaminated combustion
air will result in safety and performance related
problems. Avoid the following known
contaminants:
a. Permanent wave solutions
b. Chlorinated waxes and cleaners
c. Chlorine based swimming pool chemicals
d. Water softening chemicals
e. De-icing salts or chemicals
f. Carbon tetrachloride
g. Halogen type refrigerants
h. Cleaning solvents (such as
perchloroethylene)
i.Printing inks, paint removers, varnishes, etc.
j.Hydrochloric acid
k. Cements and glues
l.Antistatic fabric softeners for clothes dryers
m. Masonry acid washing materials
IMPORTANT: The Furnace must be installed level. The
only allowable variation would be slightly to the left
and/ or forward in upflow installations or slightly
toward the front in horizontal installations. This is
necessary for proper condensate drainage.
18-CE01D1-1F-EN
11
Page 12
Outline Drawings
12
18-CE01D1-1F-EN
Page 13
OOuuttlliinnee DDrraawwiinnggss
18-CE01D1-1F-EN
13
Page 14
OOuuttlliinnee DDrraawwiinnggss
14
18-CE01D1-1F-EN
Page 15
OOuuttlliinnee DDrraawwiinnggss
18-CE01D1-1F-EN
15
Page 16
OOuuttlliinnee DDrraawwiinnggss
16
18-CE01D1-1F-EN
Page 17
OOuuttlliinnee DDrraawwiinnggss
18-CE01D1-1F-EN
17
Page 18
Furnace General Installation
Fits 5/16” Allen wrench
The following sections give general instructions for the
installation of the gas furnaces.
Note: Use a 5/16” Allen wrench to remove the front panel.
Important: When converting the gas piping from the factory default,
Upflow furnace with gas piping on left side
Downflow furnace with gas piping on left sideDownflow furnace with gas piping on right side
the plug must be removed from the new gas piping
location and swapped with the grommet from the default
location. The upflow furnace default is left side gas
piping. The downflow furnace default is right side gas
piping.
Important: When converting the gas piping from the factory default,
Horizontal left furnace with gas piping out left side
Horizontal right furnace with gas piping out left sideHorizontal right furnace with gas piping out right side
the plug must be removed from the new gas piping
location and swapped with the grommet from the default
location. The upflow furnace default is left side gas
piping. The downflow furnace default is right side gas
piping.
Horizontal left furnace with gas piping out right side
20
18-CE01D1-1F-EN
Page 21
The upflow/horizontal furnace is shipped standard for left side
installation of gas piping. An opening with plug is provided on the right
side for an alternate gas piping arrangement.
The installation of piping shall be in accordance with piping codes and
the regulations of the local gas company. Pipe joint compound must be
resistant to the chemical reaction with liquefied petroleum gases.
Important: If local codes allow the use of flexible gas appliance
connector, always use a new listed connector. Do not use
a connector which has previously service another gas
appliance.
Refer to the piping table for delivery sizes. Connect gas supply to the
unit, using a ground joint union and a manual shut-off valve. National
codes require a condensation drip leg to be installed ahead of the gas
valve.
The furnace and its individual shut-off valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
The furnace must be isolated from the gas supply piping by closing its
individual manual shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal to or less than 1/2
psig (3.5 kPa).
Note: Maximum pressure to the gas valve for natural gas is 13.8" W.
C. Minimum pressure is 5.0" W.C. Maximum pressure to the
gas valve for propane is 13.8" W.C. Minimum pressure is 10.0"
W.C.
All gas fittings must be checked for leaks using a soapy solution before
lighting the furnace.DO NOT CHECK WITH AN OPEN FLAME!
For LP conversions on all S-Series Furnaces, use BAYLPSS400A
conversion kit with stainless steel burners.
When installing our furnaces in a manufactured house, use.
Manufactured Housing Accessory Kit, BAYMFGH200A.
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (determine the
dial rating of the meter) for one revolution.
3. Match the "Sec" column in the gas flow (in cfh) the table with the
time clocked.
4. Read the "Flow" column opposite the number of seconds clocked.
5. Use the following factors if necessary:
a. For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading ÷ 2
b. For 1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow Reading ÷ 4
c. For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading ÷ 4
6. Multiply the final figure by the heating value of the gas obtained
from the utility company and compare to the nameplate rating.
This must not exceed the nameplate rating.
Gas Flow in Cubic Feet Per Minute
2 Cubic Foot Dial
Sec.FlowSec.FlowSec.FlowSec.Flow
890029248501448288
980030240511418486
1072031232521388684
1165532225531368882
1260033218541339080
1355534212551319278
1451435206561299476
1548036200571269675
1645037195581249873
17424381895912210072
18400391856012010469
19379401806211610867
20360411766411211264
21343421726610911662
22327431676810612060
23313441647010312458
24300451607210012856
2528846157749713254
2627747153769513653
2726748150789214051
2825749147809014450
22
18-CE01D1-1F-EN
Page 23
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure, or changing
orifices (orifice change may not always be required). To adjust the
manifold pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible tubing to the outlet
pressure boss marked "OUT P" on White- Rodgers gas valve
model 36J.
3. Loosen (Do Not remove) the pressure tap test set screw one turn
with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611) contains a 3/32"
hex wrench, a 5/16" hose and a connector and can be
ordered through Global Parts.
4. Turn on system power and energize valve.
5. Adjust 1st stage gas heat by removing the low (LO) adjustment
regulator cover screw.
a. To increase outlet pressure, turn the regulator adjust screw
clockwise.
b. To decrease outlet pressure, turn the regulator adjust screw
counterclockwise.
c. Adjust regulator until pressure shown on manometer
matches the pressure specified in the table.
The input of no more than nameplate rating and no less than
93% of the nameplate rating, unless the unit is derated for
high altitude.
d. Replace and tighten the regulator cover screw securely.
6. Adjust 2nd stage gas heat by removing the high (HI) adjustment
regulator cover screw.
a. To increase outlet pressure, turn the regulator adjust screw
clockwise.
b. To decrease outlet pressure, turn the regulator adjust screw
counterclockwise.
c. Adjust regulator until pressure shown on manometer
matches the pressure specified in the table.
The input of no more than nameplate rating and no less than
93% of the nameplate rating, unless the unit is derated for
high altitude.
d. Replace and tighten the regulator cover screw securely.
7. Cycle the valve several times to verify regulator setting.
a. Repeat steps 5-7 if needed.
8. Turn off all electrical power to the system.
9. Remove the manometer and flexible tubing and tighten the
pressure tap screw.
10. Using a leak detection solution or soap suds, check for leaks at the
pressure outlet boss and pressure tap test screw.
11. Turn on system power and check operation of the unit.
Input ratings (BTUH) of these Furnaces are based on sea level
operation and should not be changed at elevations up to 2,000 ft. (610
m).
If the installation is 2,000 ft. (610 m) or above, the Furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea level.
Installations of this furnace at altitudes above 2,000 ft. (610 m) shall
be made utilizing the Vent Length table and/or Part Numbers for
Replacement Orifices table in these installation instructions.
The Furnace input rate shall be checked by clocking the gas flow rate
(CFH) and multiplying by the heating value obtained from the local
utility supplier for the gas being delivered at the installed altitude.
Input rate changes can be made by adjusting the Manifold Pressure
(min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orifices (orifice
change may not always be required).
If the desired input rate can not be achieved with a change in Manifold
Pressure, then the orifices must be changed. LP installations will
require an orifice change.
Important: Reinstall the replacement orifices to the same depth as
the orifices supplied with the equipment.
See the table for help in selecting orifices if orifice change is required.
Furnace input rate and temperature rise should be checked again after
changing orifices to confirm the proper rate for the altitude.
The vent length table shows the required vent lengths for installations
at various altitudes. Installations above 12,000 feet are not allowed.
Turn the main Gas Valve toggle switch within the unit to the "OFF"
position. Turn the external gas valve to "ON". Purge the air from the
gas lines. After purging, check all gas connections for leaks with a
soapy solution – DO NOT CHECK WITH AN OPEN FLAME. Allow 5
minutes for any gas that might have escaped to dissipate.
LP Gas being heavier than air may require forced ventilation. Turn the
toggle switch on the Gas Valve in the unit to the "ON" position.
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL SIZEPART
NUMBER
44ORF0050154ORF00555
45ORF0064455ORF00693
46ORF0090956ORF00907
47ORF0091057ORF00908
48ORF0109958ORF01338
49ORF0050359ORF01339
50ORF00493
DRILL SIZEPART
NUMBER
The table lists the main burner orifices
used with the furnace. If a change of
orifices is required to correct the furnace
input rating refer to the part number for
replacement orifices table.
Installation of this furnace at altitudes
above 2000 ft (610m) shall be in
accordance with local codes, or in the
absence of local codes, the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 or
National Standard of Canada, Natural
Gas and Propane Installation Code, CSA
B149.1.
Orifice
Twist Drill
Size If
Installed at
Sea Level
42424343434444454647
43444444454546474748
44454545464747484850
45464747474848494950
46474747484849495051
47484849494950505152
54545555555555565656
55555555565656565657
56565657575758595960
57585959606061626363
58596060616262636364
From National Fuel Gas Code — Table F-4
2000300040005000600070008000900010000
Altitude Above Sea Level
and Orifice Required at Other Elevations
24
18-CE01D1-1F-EN
Page 25
General Venting
FIELD SUPPLIED
2” COUPLING
LABEL
SAYS
“TOP”
2" TO 3" COUPLING
CPL00938
BAYREDUCE may be
used in Canadian
applications to meet
ULC-S636
CPL00938 IS FACTORY
SUPPLIED ONLY WITH THE
120,000 BTUH UPFLOW
FURNACE MODELS
FIELD SUPPLIED
2” COUPLING
2" TO 3" COUPLING
CPL00938 IS FACTORY
SUPPLIED ONLY WITH THE
120,000 BTUH UPFLOW
FURNACE MODELS
CPL00938
BAYREDUCE may be
used in Canadian
applications to meet
ULC-S636
FURNACE EXHAUST MUST BE VENTED TO THE OUTDOORS. THESE
FURNACES ARE INDUCED DRAFT VENTED AND MUST NOT BE
CONNECTED TO ANY VENT SERVING ANOTHER APPLIANCE. PLEASE
NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT
SYSTEMS.
Proper venting is essential to obtain maximum efficiency from a
condensing Furnace. Proper installation of the vent system is
necessary to assure drainage of the condensate and prevent
deterioration of the vent system.
ETL has certified the design of condensing Furnaces for a minimum of
0" clearance from combustible materials to single wall plastic vent
pipe.
The recommended system is assembled from 2" or 3" plastic pipe and
fittings found in the Approved Vent Pipe Materials Table. Where the
system is routed to the outdoors through an existing masonry
chimney containing flue products from another gas appliance, or
where required by local codes, then 3" venting of Type 29- 4C
stainless steel must be used in place of PVC material.
These Furnaces have been classified as CATEGORY IV Furnaces in
accordance with ANSI Z21.47 “latest edition” standards. Category IV
Furnaces operate with positive vent pressure and with a vent gas
temperature less than 140°F above the dewpoint. These conditions
require special venting systems, which must be gas tight and water
tight.
3” Venting requirements
Important: To determine if your application requires 3” venting, see
the Maximum Vent Length Table.
Important: Horizontal venting application must use the 2” x 3” offset
reducing coupling. Vertical venting applications to not
require the reducing coupling to be offset.
When the vent pipe is exposed to temperatures below
freezing, e.g., when it passes through unheated spaces, etc.,
the pipe must be insulated with 1/2 inch (22.7 mm) thick
Armaflex-type insulation or equal.
If the space is heated sufficiently to prevent freezing, then the
insulation will not be required. If domestic water pipes are not
protected from freezing then the space meets the condition of
a heated space.
Note: If your furnace comes with a factory supplied 2" X 3" offset
reducing coupling it is used for 3" vent pipe installation. Make
sure the marking "TOP" is located on the top side of the pipe in
horizontal venting applications. The straight side of the
coupling must be on bottom for proper drainage of condensate.
Note: For Canadian applications, BAYREDUCE 2” x 3” offset reducing
coupling meets ULC-S636 requirements. Make sure the
marking "TOP" is located on the top side of the pipe. The
straight side of the coupling must be on bottom for proper
drainage of condensate in horizontal venting.
Note: When an existing Furnace is removed from a venting system
serving other gas appliances, the venting system is likely to be
too large to properly vent the remaining attached appliances.
Important: These Furnaces may be installed as Direct Vent (sealed
combustion) or as Nondirect Vent (single pipe). The
Furnaces are shipped DIRECT VENT with sealed
combustion.
Important: Products installed in Canada must use vent systems that
are certified to the Standard for Type BH Gas Venting
Systems (ULC S636) for Class II-A venting systems (up
to 65°C). Components of the vent system must not be
interchanged with other vent systems or unlisted pipe or
fittings. Plastic components, specified primers, and glues
must be from a single system manufacturer and not
intermixed with other system manufacturer's vent
system parts. In addition, the first three feet of the vent
pipe must be visible for inspection.
Special instructions for direct vent furnace air intake.
In certain applications, particularly when the furnace is located in a
basement, there are certain conditions that can be met where warm
humid air from the outside is drawn into combustion air piping. If the
area where the piping is located is conditioned below 70° F,
condensation could occur inside the piping and ultimately drain into
the furnace compartment, which could lead to premature component
failure.
We recommend following one of the options to prevent this condition
from occurring and possibly damaging components within the
furnace:
Option 1
If possible, slope the inlet combustion air piping away from the
furnace. Condensation that may occur will now drain outside of the
home. The combustion air outlet piping must remain sloped back to
the furnace.
Note: Inlet air piping is not considered to be part of the venting
system. The inlet air piping may be made from PVC.
26
18-CE01D1-1F-EN
Page 27
Option 2 — Top combustion air intake
If sloping the combustion air intake pipe is not possible, install a DWV
Tee as close to the furnace as possible with drain and trap to prevent
condensation from occurring in the furnace cabinet. Do not tee AC
condensate and combustion air condensate trap together.
Option 3 — Side combustion air intake
If sloping the combustion air intake pipe is not possible, install a
sanitary Tee as close to the furnace as possible with drain and trap.
For DIRECT VENT APPLICATION: The Furnaces must be vented to
the exterior of the house and combustion air MUST come through the
inlet air pipe from OUTSIDE AIR.
Note: BAYVENT* accessories can be used for inlet and outlet
terminals when the pipes do not exit the structure together. For
Canadian applications, venting systems must meet ULC-S636
requirements.
For NONDIRECT VENT APPLICATION: The Furnace shall be vented
to the exterior of the house, but combustion air may enter from the
surrounding area as long as combustion air requirements are met.
(See AIR FOR COMBUSTION AND VENTILATION)
FURNACE VENT / INLET PIPE INSTALLATION IN TWO
PRESSURE ZONE CONFIGURATIONS ARE NOT ALLOWED
Note: For single pressure zone applications, see the Horizontal
Venting section.
The following are EXAMPLES ONLY.
EX. 1—
Example 1 shows the vent pipe exhausting through the roof and the
inlet air coming from the interior of the house. The inlet air coming
from the interior of the house must meet combustion requirements for
area, etc., as shown in the section AIR FOR COMBUSTION AND
VENTILATION in this Installer’s Guide.
Vent terminations
•BAYVENT200B
•BAYAIR30AVENTA
Vent terminations — Canadian applications. Meets ULC-S636
requirements.
•BAYVENTCN200B
•BAYAIR30CNVENT
EX. 2—
The inlet air does not have to come from outside the structure.
Example 2 shows the inlet air, may come from the attic if the
requirements for combustion air are met as shown in the section AIR
FOR COMBUSTION AND VENTILATION.
Note: If only the flue gas pipe is to the outside of the structure, a
straight section of pipe (long enough to exit the Furnace
cabinet) must be attached to the inlet air side with an elbow
(which is 5 to 10 equiv. ft.) installed on the end to prevent dust
and debris from falling directly into the Furnace.
Attaching Vent Piping
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for resistance to
corrosive flue condensate, MUST be used throughout.
Listed in the Approved Vent Pipe Materials table are designations for
different types of 2" and 3" size pipe and fittings that meet these
requirements. The materials listed are various grades of PVC, CPVC,
ABS, and DuraVent PolyPro®.
Important: Products installed in Canada must use vent systems that
are certified to the Standard for Type BH Gas Venting
Systems (ULC S636) for Class II-A venting systems (up
to 65°C). Components of the vent system must not be
interchanged with other vent systems or unlisted pipe or
fittings. Plastic components, specified primers, and glues
must be from a single system manufacturer and not
intermixed with other system manufacturer's vent
system parts. In addition, the first three feet of the vent
pipe must be visible for inspection.
PIPE JOINTS: All joints must be fastened and sealed per manufacturer
instructions and local and national codes to prevent escape of
combustion products into the building.
For manufactured modular venting systems that are approved with
this product see PVC vent fitting material table. Do not drill into
polypropelene venting pipes
Note: It is recommended that the first joints from the Furnace be
connected and sealed with high temperature RTV. This will
enable the pipes to be removed later without cutting.
Be sure to properly support these joints.
Commercially available solvent cement for PVC must be used to join
PVC pipe fittings. Follow instructions on container carefully.
Pipe and Fitting – ASTM D1785, D2466, D2661, & D2665
PVC Primer and Solvent Cement – ASTM D2564
Procedure for Cementing Joints – Ref ASTM D2855
1. Cut pipe square, remove ragged edges and burrs. Chamfer end of
pipe, then clean fitting socket and pipe joint area of all dirt,
grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe socket and pipe
with cleaner-primer. Apply a liberal coat of primer to inside
surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a
heavy coat of cement to the pipe end and insert pipe into fitting
with a slight twisting movement until it bottoms out.
4. Hold the pipe in the fitting for 30 seconds to prevent tapered
socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15
minutes before handling. Cure time varies according to fit,
temperature and humidity.
Connection of the pipe and collar of the combustion air inlet should
just be a friction fit. It is recommended that the inlet air joint be sealed
with RTV type sealant to allow the joint to be separated for possible
future service. The inlet and vent pipes must be properly supported
throughout the entire length.
Note: Follow venting instructions carefully when using PVC cement.
Important: All joints must be water tight. Flue condensate is
somewhat acidic, and leaks can cause equipment
damage.
2. FOR DURAVENT MANUFACTURED MODULAR VENTING SYSTEMS THAT ARE IN THE APPROVED VENT PIPE MATERIAL TABLE,
EQUIVALENT VENT LENGTHS MAY BE DIFFERENT FROM WHAT IS SHOWN ABOVE. REFER TO THE VENTING SYSTEM
MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR APPROPRIATE VENTING DIAMETERS AND EQUIVALENT LENGTHS.
3. Minimum vent length for all models: 15' equivalent.
4. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 7
below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
5. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF
EACH (Vent or Inlet air pipes).
6. One SHORT radius 90° elbow is equivalent to 10' of 4" pipe, 10' of 3" pipe, or 8’ of 2" pipe. One LONG radius elbow is equivalent to 6' of 4"
pipe, 7’ of 3" pipe, or 5' of 2" pipe. Two 45° elbows equal one 90° LONG elbow. One MITERED elbow is equivalent to 12’ of 3” pipe or 12’ of
2” pipe.
7. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA or BAYAIR30CNVENT termination kit
is used, the equivalent length of pipe is 5 feet. For BAYVENT200B and BAYVENTCN200B the equivalent length is 0 feet.
8. For Canadian applications, venting systems must meet ULC-S636 requirements.
9. The INLET AIR of one pipe systems require the installation of a minimum of one 90° elbow (to prevent dust and debris from falling straight
into the furnace).
2 Inch or 2.5 Inch Pipe3 Inch or 4 Inch Pipe
Altitude 0–2,000 Feet
Altitude 2,001–5,400 Feet
Altitude 5,401–7,800 Feet
Altitude 7,801–10,100 Feet
Maximum Total Equivalent Length In Feet
for Vent and Inlet Air (See Notes)
200200
100200
50200
Note 1200
200200
80120
50150
Note 1200
100150
5070
Note 1100
Note 1100
9090
Note 150
Note 150
Note 150
18-CE01D1-1F-EN
31
Page 32
FIELD SUPPLIED
2” COUPLING
LABEL
SAYS
“TOP”
2" TO 3" COUPLING
CPL00938
BAYREDUCE may be
used in Canadian
applications to meet
ULC-S636
CPL00938 IS FACTORY
SUPPLIED ONLY WITH THE
120,000 BTUH UPFLOW
FURNACE MODELS
FIELD SUPPLIED
2” COUPLING
2" TO 3" COUPLING
CPL00938 IS FACTORY
SUPPLIED ONLY WITH THE
120,000 BTUH UPFLOW
FURNACE MODELS
CPL00938
BAYREDUCE may be
used in Canadian
applications to meet
ULC-S636
Important: To determine if your application requires 3” venting, see
Important: Horizontal venting application must use the 2” x 3” offset
When the vent pipe is exposed to temperatures below
freezing, e.g., when it passes through unheated spaces, etc.,
the pipe must be insulated with 1/2 inch (22.7 mm) thick
Armaflex-type insulation or equal.
If the space is heated sufficiently to prevent freezing, then the
insulation will not be required. If domestic water pipes are not
protected from freezing then the space meets the condition of
a heated space.
Note: If your furnace comes with a factory supplied 2" X 3" offset
Note: For Canadian applications, BAYREDUCE 2” x 3” offset reducing
the Maximum Vent Length Table.
reducing coupling. Vertical venting applications to not
require the reducing coupling to be offset.
reducing coupling it is used for 3" vent pipe installation. Make
sure the marking "TOP" is located on the top side of the pipe in
horizontal venting applications. The straight side of the
coupling must be on bottom for proper drainage of condensate.
coupling meets ULC-S636 requirements. Make sure the
marking "TOP" is located on the top side of the pipe. The
straight side of the coupling must be on bottom for proper
drainage of condensate in horizontal venting.
32
18-CE01D1-1F-EN
Page 33
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials must be
maintained when using single wall stainless steel venting.
Shield material to be a minimum of 24 gauge stainless or aluminized
sheet metal. Minimum dimensions are 12"x12". Shield must be
fastened to both inside and outside of wall. Use screws or anchor type
fasteners suited to the outside or inside wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to maintain pitch of
vent and properly seal.
Use cement mortar seal on inside and outside of wall.
These Furnaces may be installed as direct vent (as shipped) or
as nondirect vent. Installation must conform to national,
state, and local codes.
The BAYVENT200B, BAYVENTCN200, BAYAIR30AVENTA, and
BAYAIR30CNVENTvent & inlet terminals kits must be located at least
12" minimum above normally expected snow accumulation level.
Avoid areas where staining or condensate drippage may be a problem.
Location of the vent/wind terminal should be chosen to meet the
requirements for either direct or non-direct vent applications.
PITCH — Venting through the wall must maintain 1/4" per foot
pitched upward to insure that condensate drains back to the Furnace.
FLUE GAS DEGRADATION — The moisture content of the flue gas
may have a detrimental effect on some building materials. This can be
avoided by using the roof or chimney venting option. When wall
venting is used on any surface that can be affected by moisture, it is
recommended that a corrosion resistant shield (24 inches square) be
used behind the vent terminal. This shield can be wood, plastic, sheet
metal, etc. Also, silicone caulk all cracks, seams and joints within 3
feet of the vent terminal.
The vent for this appliance shall not terminate
1. Over public walkways; or
2. Near soffit vents or crawl space vents or other areas where
condensate or vapor could create a nuisance or hazard or cause
property damage; or
3. Where condensate vapor could cause damage or could be
detrimental to the operation of regulators, relief valves. or other
equipment.
For Canadian installations, if you used a ULC-S636 approved
manufactured modular venting system, a copy of the manufacturer's
instructions should remain with the system. The installation
instruction can be obtained from the vent termination manufacturer.
BAYVENTCN200B and BAYAIR30CNVENT meet ULC-S636
requirements.
BAYVENT200B / BAYVENTCN200B
Note: For Canadian applications, horizontal vent termination kits
Important: The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through – the
– wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7)
feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be
satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the
installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on
the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a
period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery
operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment.
The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248
CMR 5.08(2) (a)1 through 4.
This appliance requires a special venting system. If BAYAIR30AVENTA or BAYVENT200B are used, a copy of the installation instructions for the
kit shall remain with the appliance or equipment at the completion of installation. The venting system installation instructions can be obtained
from the manufacturer by writing to the following address:
Ingersoll Rand
6200 Troup Highway
Tyler, TX 75707
Attention: Manager of Field Operations Excellence
I=Clearance to service regulator vent outlet3 feet (91 cm)
J=Clearance to nonmechanical air supply
K=Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet
L=Clearance above a paved sidewalk or
M=Clearance under veranda, porch, deck, or
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both
dwellings.
‡. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation
Instructions.
deck, or balcony
opened
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal
Clearance to unventilated soffit**
Clearance to each side of center line
extended above meter/regulator
assembly
inlet to building or the combustion air
inlet to any other appliance
paved driveway located on public
property
balcony
12 inches (30 cm)12 inches (30 cm)
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 12 inches (30 cm)
for appliances > 10,000 Btuh (3 kw) and
=/< 100,000 Btuh (30 kw), 36 inches (91
cm) for appliances > 100,000 Btuh (30
kw)
**
**
3 feet (91 cm) with a height 15 feet (4.5
m) above the meter/regulator assembly
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 12 inches (30 cm)
for appliances > 10,000 Btuh (3 kw) and
=/< 100,000 Btuh (30 kw), 36 inches (91
cm) for appliances > 100,000 Btuh (30
kw)
7 feet (2.13 m)7 feet (2.13 m)
12 inches (30 cm)
4 feet (1.2m) below or to the side of
opening; 1 foot (0.3m) above opening.
4 feet (1.2 m) below or to side of opening;
1 foot (300 m) above opening
I=Clearance to service regulator vent outlet3 feet (91 cm)
J=Clearance to nonmechanical air supply
K=Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet
L=Clearance above a paved sidewalk or
M=Clearance under veranda, porch, deck, or
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both
dwellings.
‡. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation
Instructions.
deck, or balcony
opened
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal
Clearance to unventilated soffit**
Clearance to each side of center line
extended above meter/regulator
assembly
inlet to building or the combustion air
inlet to any other appliance
paved driveway located on public
property
balcony
12 inches (30 cm)12 inches (30 cm)
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 12 inches (30 cm)
for appliances > 10,000 Btuh (3 kw) and
=/< 100,000 Btuh (30 kw), 36 inches (91
cm) for appliances > 100,000 Btuh (30
kw)
**
**
3 feet (91 cm) with a height 15 feet (4.5
m) above the meter/regulator assembly
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 12 inches (30 cm)
for appliances > 10,000 Btuh (3 kw) and
=/< 100,000 Btuh (30 kw), 36 inches (91
cm) for appliances > 100,000 Btuh (30
kw)
7 feet (2.13 m)
12 inches (30 cm)
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 9 inches (23 cm) for
appliances > 10,000 Btuh (3 kw) and =/<
50,000 Btuh (15 kw), 12 inches (30 cm)
for appliances > 50,000 Btuh (15 kw)
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm)
for appliances > 100,000 Btuh (30 kw)
(3m) horizontally
*
*
*
*
38
18-CE01D1-1F-EN
Page 39
Venting Through The Roof
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
VENT
COMBUSTION
AIR
REMOVE RIBS
FROM CAP
COMBUSTION
AIR
ROOF FLASHING BOOT
(FIELD SUPPLIED)
COMBUSTION
AIR
VENT
ELBOW
(FIELD SUPPLIED)
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
SUPPORT
(FIELD SUPPLIED)
VENT
GALVANIZED FIRESTOP SHOULD
BE FABRICATED WITH 3-7/8" DIA.
HOLE FOR SUPPORT FLANGE
(12" x 12" PANEL OR 12" DIA MIN.)
VENTING THROUGH CEILING
CEILING
SUPPORT
FLANGE
FLUE PIPE
COUPLING
SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
Support Horizontal pipe every 3’0” with the first support as close to
the furnace as possible. Induced draft blower, housing, and furnace
must not support the weight of the flue pipe.
When penetrating roof with PVC vent pipe, a flexible flashing may be
used for a weather tight seal. Lubricate flexible seal on flashing before
PVC pipe is pushed through the seal. (Field Supplied)
Note: No vent cap is the preferred method for vertical vent
termination in extremely cold climates.
Note: In extreme climate conditions, insulate the exposed pipe above
the roof line with Armaflex type insulation.
Venting Through an UNUSED Chimney
Venting Routed Through a Masonry Chimney
Important: Refer to Section 12.6.8 of NFPA 54 / ANSI 223.1 2012
Important: The single wall flue pipe joints must be sealed.
Venting Through an UNUSED Chimney
Important: Refer to Section 12.6.8 of NFPA 54 / ANSI 223.1 2012
Important: The single wall flue pipe joints must be sealed.
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed for
resistance to corrosive flue condensate such as Type 29-4C MUST be
used throughout.
These fittings and fitting accessories are to be field supplied.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male end towards the
Furnace.
All horizontal stainless steel sections must be positioned with the
seam on top.
All long horizontal sections must be supported to prevent sagging.
All pipe joints must be fastened and sealed to prevent escape of
combustion products into the building.
when routing vent piping through a chimney.
The 90° elbow connection to vertical pipe must be sealed
to prevent condensate leakage to base of masonry
chimney.
when routing vent piping through a chimney.
The 90° elbow connection to vertical pipe must be sealed
to prevent condensate leakage to base of masonry
chimney.
PVC PLASTIC VENTING
THROUGH UNUSED CHIMNEY
TYPE 29-4C STAINLESS STEEL VENTING
THROUGH UNUSED CHIMNEY
40
18-CE01D1-1F-EN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.