Packaged Rooftop Air Conditioners
Precedent™ — Heat Pump
3 – 10 Tons – 60 Hz
Model Numbers
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or alter ed equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
August 2012RT-SVX23F-EN
WSC036E - WSC120E
SAFETY WARNING
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provide to alert
installing contractors to potential hazards that could result
in death or personal injury . Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servicing
this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read
these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may af fect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment. T rane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, y ou MUST f ollow r equir ements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servi cin g th is un it, technicians
MUST put on all P ersonal Protective Equipmen t (PPE)
recommended for the work being undertaken.
AL W A YS r efer to appr opriate MSDS sheets and OSHA
guidelines for proper PPE.
•When working with or ar ound hazar dous chemi cals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
•If there is a risk of arc or flash, te chnicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
Failure to f ollow recommendations could result in death
or serious injury.
B Supply Air Smoke Detector
C Supply and Return Air Smoke
Detectors
9
D Plenum Smoke Detector
Digit 25 - System Monitoring
Controls
0No Monitoring Control
1Clogged Filter Switch
2Fan Failure Switch
3Discharge Air Sensing Tube
4Clogged Filter Switch and Fan
Fail Switch
5Clogged Filter Switch and Discharge
Air Sensing Tube
6Fan Fail Switch and Discharge Air
Sensing Tube
7Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube
A Condensate Drain Pan Overflow
Switch
B Clogged Filter Switch and
Condensate Drain Pan Overflow
Switch
6
C Fan Failure Switch and Condensate
Drain Pan Overflow Switch
D Discharge Air Sensing and
Condensate Drain Pan Overflow
Switch
E Clogged Filter Switch, Fan Failure
Switch and Condensate Drain Pan
6
Overflow Switch
FClogged Filter Switch, Discharge
Air Sensing Tube and Condensate
Drain Pan Overflow Switch
G Fan Failure Switch, Discharge Air
Sensing Tube and Condensate
Drain Pan Overflow Switch
H Clogged Filter Switch, Fan Failure
Switch, Discharge Air Sensing
and Condensate Drain Pan Overflow
Switch
Digit 26 - System Monitoring
Controls
0No Monitoring Controls
A Demand Control Ventilation (CO
8
Digit 27 - Unit Hardware
Enhancements
0No Enhancements
1Stainless Steel Drain Pan
2
15
)
RT-SVX23F-EN5
Model Number Descriptions
Model Number Notes
1. Available on 3-5 ton models.
2. Manual outside air damper will
ship factory supplied within the
unit, but must be field installed.
3. High pressure control is standard
on all units.
4. Multispeed direct drive standard
on single-phase products. Belt
drive standard on three-phase 37½ ton. Variable speed direct
drive standard on 10 ton.
5. Economizer with Barometric
Relief is for downflow configured
units only. Order Economizer
without Barometric Relief for
horizontal configuration.
Barometric Relief for horizontal
configured units must be ordered
as field installed accessory .
6. Through the base electric
required when ordering
disconnect/circuit breaker
options.
7. Requires use of Disconnect or
Circuit Breaker.
8. Standard metering devices are
TXVs.
9. The return air smoke dete ctor
may not fit up or work properly on
the Precedent units when used in
conjunction with 3rd party
accessories such as bolt on heat
wheels, economizers and power
exhaust. Do not order the return
air smoke detectors when using
this type of accessory.
10. Requires hinged access panels.
11. Crankcase heaters are only
available as option on WSC036E,
WSC048E1, & WSC060E1. CCH
are standard on all other units.
12. Motorized outside air damper is
not available on Multi-Speed or
SZVAV (Single Zone Variable Air
Volume)
13. Frostat standard on Multi-speed
and SZVA V (Single Zone V ariable
Air Volume)
14. Multi-speed indoor fan only
available on 10 ton products.
15. Demand Control Ventilation
Option includes wiring only. The
products.
products.
sensor is a field-installed only
C0
2
option.
6 RT-SVX23F-EN
General Information
Unit Nameplate
A Mylar unit nameplate is located on the unit’s corner
support next to the filter access panel. It includ es the unit
model number, serial number, electrical characteristics,
refrigerant charge, as well as other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the side
of the compressor.
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and compressor oil, and run
tested for proper control operation.
The condenser coils are aluminum fin, mechanically
bonded to copper tubing.
Direct-drive, vertical discharge condenser fans are
provided with built-in thermal overload protection.
The ReliaT el™ Control Module is a microelectronic control
system that is referred to as “Refrigeration Module”
(RTRM). The acronym RTRM is used extensively
throughout this document when referring to the control
system network.
These modules through Proportional/Integral control
algorithms perform specific unit functions that governs
unit operation in response to; zone temperature, supply air
temperature, and/or humidity conditions depending on
the application. The stages of capacity control for these
units is achieved by starting and stopping the
compressors.
The RTRM is mounted in the control panel and is factory
wired to the respective internal components. The RTRM
receives and interpret information from other unit
modules, sensors, remote panels, and customer binary
contacts to satisfy the applicable request for cooling.
Economizer Control Actuator (Optional)
The ECA monitors the mixed air temperature, return air
temperature, minimum position setpoint (local or
remote), power exhaust setpoint, CO2 setpoint, CO2, and
ambient dry bulb/enthalpy sensor or comparative
humidity (return air humidity against ambient humidity)
sensors, if selected, to control dampers to an accuracy of
+/- 5% of stroke. The actuator is spring returned to the
closed position any time that power is lost to the unit. It is
capable of delivering up to 25 inch pounds of torque and
is powered by 24 VAC.
RTCI - ReliaTel™ Trane Communication
Interface (Optional)
This module is used when the application calls for an
ICSTM building management type control system. It
allows the control and monitoring of the system through
an ICS panel. The module can be ordered from the factory
or ordered as a kit to be field installed. Follow the
installation instruction that ships with each kit when field
installation is necessary.
RLCI - ReliaTel™ LonTalk Communication
Interface (Optional)
This module is used when the application calls for an
ICSTM building management type control system that is
LonT alk. It allows the control and monitoring of the system
through an ICS panel. The module can be ordered from the
factory or ordered as a kit to be field installed. Follow the
installation instruction that ships with each kit when field
installation is necessary.
This module is used when the application calls for an open
BACnet protocol. It allows the control and monitoring of
the system through an ICS panel. The module can be
ordered from the factory or as a kit to be field installed.
Follow the installation instructions that ships with each kit
when field installation is necessary.
RTOM – ReliaTel™ Options Module
The RT OM monitors the supply fan proving, clogged filter ,
supply air temperature, exhaust fan setpoint, supply air
tempering, Frostat™ and smoke detector. R efer to system
input devices and functions for operation.
This module is standard on 10 ton products.
System Input Devices &
Functions
The RTRM must have a zone sensor or thermostat input in
order to operate the rooftop unit. The flexibility of havi ng
several mode capabilities depends upon the type of zone
sensor thermostat selected to interface with the RTRM.
The descriptions of the following basic Input Devices used
within the RTRM network are to acquaint the operator with
their function as they interface with the various modules.
Refer to the unit’s electrical schematic for the specific
module connections.
The following controls are available from the factory for
field installation.
RT-SVX23F-EN7
General Information
Supply Fan Failure Input (Optional)
The Fan Failure S witch can be connected to sense indoor
fan operation:
FFS (Fan Failure Switch) If air flow through the unit is not
proven by the differential pressure switch connected to the
RTRM (factory set point 0.07 “w.c.) within 40 seconds
nominally, the RTRM will shut off all mechanical
operations, lock the system out, send a diagnostic to ICS,
and the SERVICE output will flash. The system will remain
locked out until a reset is initiated either manually or
through ICS.
Clogged Filter Switch (Optional)
The unit mounted clogged filter switch monitors the
pressure differential across the return air filters. It is
mounted in the filter section and is connected to the
RTO M. A diagnostic SER V ICE signal is sent to the remote
panel if the pressure differential across the filters is at least
0.5" w.c. The contacts will automatically open when the
pressure differential across the filters decreases to
approximately 0.4" w.c. The clogged filter output is
energized when the supply fan is operating and the
clogged filter switc h has been closed for at least 2 minutes.
The system will continue to operate regardless of the
status of the filter switch.
Note: On units equipped with factory instal led MERV 13
filters, a clogged filter switch with different
pressure settings will be installed . This switch will
close when the differential pressure is
approximately 0.8' w.c. and open when the
differential falls to 0.7" w.c.
Condensate Drain Pan Overflow Switch
(Optional)
compressor operation, the compressor for that circuit is
immediately turned “Off”. The compressor will not be
allowed to restart for a minimum of 3 minutes should the
contacts close.
If four consecutive open conditions occur during the first
three minutes of operation, the compressor for that circuit
will be locked out, a diagnostic communicated to the
remote panel (if installed), and a manual reset will be
required to restart the compressor .
Low Pressure Control
When the LPC is opened for 1 continuous second, the
compressor for that circuit is turned off immediately. The
compressor will not be allowed to restart for a minimum
of 3 minutes.
If four consecutive open conditions occur during an active
call for cooling, the compressor will be locked out, a
diagnostic communicated to ICS™, if applicable, and a
manual reset required to restart the compressor. On dual
compressor units only the affected compressor circuit is
locked out.
High Pressure Control
The high pressure controls are wired in series between the
compressor outputs on the RTRM and the compressor
contactor coils. If the high pressure control switch opens,
the RTRM senses a lac k of current while calling for cool ing
and locks the compressor out.
If four consecutive open conditions occur during an active
call for cooling, the compressor will be locked out, a
diagnostic communicated to ICS™, if applicable, and a
manual reset required to restart the compressor. On dual
compressor units only the affected compressor circuit is
locked out.
ReliaTel Option
This input incorporates the Condensate Overflow Switch
(COF) mounted on the drain pan and the ReliaT el Options
Module (RTOM). When the condensate level reaches the
trip point for 6 continuous seconds, the RTOM will shut
down all unit functions until the overflow condition has
cleared. The unit will return to normal operation after 6
continuous seconds with the COF in a non-tripped
condition. If the condensate level causes unit shutdown
more than 2 times in a 3 days period, the unit will be
locked-out of operation requiring manual reset of
diagnostic system through Zone Sensor or Building
Automation System (BAS). Cycling unit pow er will also
clear the fault.
Compressor Disable (CPR1/2)
This input incorporates the low pressure control (LPC) of
each refrigeration circuit and can be activated by opening
a field supplied contact installed on the LTB.
If this circuit is open before the compressor is started, the
compressor will not be allowed to operate. Anytime this
circuit is opened for 1 continuous second during
8 RT-SVX23F-EN
Power Exhaust Control (Optional)
The power exhaust fan is started whenever the position of
the economizer dampers meets or exceed the power
exhaust setpoint when the indoor fan is on.
The setpoint panel is located in the return air section and
is factory set at 25%.
Lead/Lag Control (Dual Circuit Only)
Lead/Lag is a selectable input located on the RTRM. The
RTRM is configured from the factory with the Lead/Lag
control disabled. T o activate the Lead/Lag function, simply
cut the wire connected to J3-8 at the RTRM. When it is
activated, each time the designated lead compressor is
shut off due to the load being satisfied, the lead
compressor or refrigeration circuit switches. When the
RTRM is powered up, i.e. af ter a power failure, the control
will default to the number one circuit compressor.
Zone Sensor Module (ZSM) (BAYSENS107*)
This electronic sensor features three system switch
settings (Heat, Cool, and Off) and two fan settings (On and
General Information
Auto). It is a manual changeover control with single
setpoint. (Cooling Setpoint Only)
Zone Sensor Module (ZSM) (BAYSENS109*)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto). It is a manual or auto changeover control with dual
setpoint capability. It can be used with a remote zone
temperature sensor BAYSENS077*.
Programmable Zone Sensor - (BAYSENS119*)
This 7 day programmable sensor features 2, 3 or 4 periods
for Occupied or Unoccupied programming per d ay. If the
power is interrupted, the program is retained in
permanent memory. If power is off for an extended period
of time, only the clock and day may have to be reset.
The zone sensor allows selection of 2, 3 or 4 system modes
(Heat, Cool, Auto, and Off), two fan modes (On and Auto).
It has dual temperature selection with programmable start
time capability.
The occupied cooling set point ranges between 45 and 98
degrees Fahrenheit. The heating set point ranges between
43 and 96 degrees Fahrenheit.
A liquid crystal display (LCD) displays zone temperature,
temperature set points, day of the week, time, and
operational mode symbols.
The Option Menu is used to enable or disable applicable
functions, i.e.; Morning Warm-up, Economizer minimum
position override during unoccupied status, Fahrenheit or
Centigrade, Supply air tempering, Remote zone
temperature sensor, 12/24 hour time display, Smart fan,
and Computed recovery.
During an occupied period, an auxiliary relay rated for 1.25
amps @ 30 volts AC with one set of single pole double
throw contacts is activated.
Status Inputs (4 Wires Optional). The ZSM can be wired to
receive four (4) operating status signals from the RTRM
(HEAT, COOL, SYSTEM “ON”, SERVICE). Four (4) wires
from the RTRM should be connected to the appropriate
terminals (7, 8, 9 & 10) on the ZSM.
Remote Zone Sensor (BAYSENS073*)
This electronic sensor features remote zone sensing and
timed override with over ride cancellation. It is used with a
Trane Integrated Comfort™ building management
system.
Remote Zone Sensor (BAYSENS074*)
This electronic sensor features single setpoint capability
and timed override with override cancellation. It is used
with a Trane Integrated Comfort™ building management
system.
Remote Zone Sensor (BAYSENS016*)
This bullet type temperature sensor can be used for;
outside air (ambient) sensing, return air temperature
sensing, supply air temperature sensing, remote
temperature sensing (uncovered). Wiring procedures vary
according to the particular application and equipment
involved. Refer to the unit’s wiring diagrams for proper
connections.
Remote Zone Sensor (BAYSENS077*)
This electronic sensor can be used with BAYSENS106*,
108*, 110*, 119* Remote P anels. When this sensor is wired
to a BAYSENS11 9* remote panel, wiring must be 18 AWG
shielded twisted pair (Belden 8760 or equivalent). Refer to
the specific remote panel for wiring details.
Wireless Zone Sensor (BAYSENS050*)
This electronic sensor features five system settings (Auto,
Off, Cool, Heat, and Emerg ency Heat) and with On and
Auto fan settings. It is a manual or auto c hangeover control
with dual setpoint capability. Other features include a
timed override function, lockable system settings, and
Fahrenheit or Celsius temperature display. Included with
the wireless zone sensor will be a receiver that is to be
mounted inside the unit, a mounting bracket, and a wire
harness.
High Temperature Sensor (BAYFRST001*)
This sensor connects to the RTRM Emergency Stop Input
located on the LT B and provides high limit “shutdown” of
the unit and requires a manual reset. The sensor is used to
detect high temperatures due to fire in the air conditioning
or ventilation ducts. The sensor is desig ned to mount
directly to the sheet metal duct. Each kit contains two
sensors. The return air duct sensor (X1310004001) is set to
open at 135°F. The supply air duct sensor (X131 0004002) is
set to open at 240°F. The control can be reset after the
temperature has been lowered approximately 25°F below
the cutout setpoint.
Evaporator Frost Control
This input incorporates the Frostat™ control (FOS) located
on the indoor coil and can be activated by closing a field
supplied contact installed in parallel with the FOS.
If this circuit is open before the compressor is started, the
compressor will not be allowed to operate. Anytime this
circuit is opened for 1 continuous second during
compressor operation, the compressor for that circuit is
immediately turned “Off”. The compressor will not be
allowed to restart for a minimum of 3 minutes should the
FOS close.
Frostat is standard on multi-speed indoor motors and
single zone VAV products (SZVAV).
Smoke Detector Sensor (Optional)
This sensor is only applicable on units equipped with a
RTOM. It provides high limit “shutdown” of the unit and
requires a manual reset. The sensor is used to detect
smoke due to fire in the air conditioning or ventilation
ducts.
RT-SVX23F-EN9
General Information
Important:
•The supply air smoke detector samples supply air. The
return and plenum air smoke detectors sample return
air. The smoke detectors are designed to shut off the
unit if smoke is sensed in the supply air stream or
return air stream. This function is performed by
sampling the airflow enteri ng the unit at the return air
opening. Follow the instructions provided below to
assure that the airflow through the unit is sufficient for
adequate sampling. Failure to follow t hese instructions
will prevent the smoke detectors from performing it's
design function.
•Airflow through the unit is affected by the amount of
dirt and debris accumulated on the indoor coil and
filters. To insure that airflow through the unit is
adequate for proper sampling by the return air smoke
detector, complete adherence to the maintenance
procedures, including recommended intervals
between filter changes, and coil cleaning is required.
•Periodic c hec ks and maintenance procedures must be
performed on the smoke detector to insure that it will
function properly . For detailed instructions concerning
these checks and procedures, refer to the appropriate
section(s) of the smoke detector Installation and
Maintenance Instructions provided with the literature
package for this unit.
In order for the supply air smoke detector or return air
smoke detector to properly sense smoke in the supply air
stream or return air stream, the air velocity entering the
smoke detector unit must be between 500 and 4000 feet
per minute. Equipment covered in this manual will
develop an airflow velocity that falls within these limits
over the entire airflow range specified in the evaporator
fan performance tables.
Phase Monitoring protection
Precedent units with 3-phase power are equipped with
phase monitoring protection as standard. These devices
protect motors and compressors against problems caused
by phase loss, phase imbalance, and phase reversal
indication.
This sensor monitors voltage between the 3 conductors of
the 3 phase power supply. Two LED lights are provided.
The green light indicates that a balanced 3 phase supply
circuit is properly connected. The red light indicates that
unit operation has been prevented. There are two
conditions that will prevent unit operation. The power
supply circuit is not balanced with the proper phase
sequence of L1, L2, L3 for the 3 conductors of a 3 phase
circuit. The line to line voltage is not between 180 v olts and
633 volts.
10 RT-SVX23F-EN
Unit Clearances
WSC036-048E Units
WSC060-120E Units
Figure 1.Typical installation clearances for single & multiple unit applications
RT-SVX23F-EN11
Unit Clearances
CLEARANCE 36” (914 MM)
Figure 2.Heat pump - 3-4 ton standard efficiency
Note: All dimensions are in inches/millimeters.
Figure 3.Heat pump - 3-4 ton standard efficiency - unit clearance and roof opening
Note: All dimensions are in inches/millimeters.
12 RT-SVX23F-EN
Figure 4.Heat pump - 3-4 ton standard efficiency - roof curb
7
4444 MMMM
4444 MMMM
10381038 MMMM
10531053 MMMM
Note: All dimensions are in inches/millimeters.
Unit Clearances
Figure 5.Hea t pumps - 5-6 ton standard efficiency
Note: All dimensions are in inches/millimeters.
RT-SVX23F-EN13
Unit Clearances
Figure 6.Heat pump - 7½ ton standard efficiency
Note: All dimensions are in inches/millimeters.
Figure 7.Heat pump - 5-7½ ton - unit clearance and roof opening
2” ELECTRICAL CONNECTION
(SINGLE POINT POWER WHEN
HEAT INSTALLED)
COMPRESSOR ACCESS PANEL
CONDENSER COIL
CONTROL BOX SECTION
ACCESS PANEL
UNIT CONTROL WIRE
7
/8”(
22MM
)
DIA HOLE
SERVICE GAUGE PORT ACCESS 1
3/8” (35MM) DIA. HOLE
Note: All dimensions are in inches/millimeters.
Unit Clearances
Figure 9.Heat pump - 10 ton standard efficiency
Notes:
1. All dimensions are in inches/millimeters.
2. 2" Electrical Connection: Single Point Power When Heat Installed (WSC Models only.)
RT-SVX23F-EN15
Unit Clearances
99 11/16”
(2532 MM)
63 3/16”
(1605 MM)
13/4”
(
44 MM
)
2”
(
51 MM
)
84 1/2”
(2146 MM)
83 7/8”
(2130 MM)
60 3/8”
(1534 MM)
59 7/8”
(
1521 MM
)
14”
(
356 MM
)
2”
(
51 MM
)
56 3/8”
(1432 MM)
34 3/8”
(873 MM)
34 3/8”
(873 MM)
18 1/2”
(470 MM)
18 1/2”
(470 MM)
1”
(
25 MM
)1”(
25 MM
)
1”
(
25 MM
)
65/8”
(
168 MM
)
80 1/2”
(2045 MM)
CL
EARANCE 18” (4
57 MM
)
FO
R
H
O
RIZO
NTAL
CLE
ARAN
C
E36”(914 MM)
FO
R
DO
WNFLOW
Figure 10. Heat pump - 10 ton standard efficiency - unit clearance and roof opening
Notes:
1. All dimensions are in inches/millimeters.
Figure 11. Heat pump - 10 ton standard efficiency - roof curb
Notes:
1. All dimensions are in inches/millimeters.
16 RT-SVX23F-EN
Pre-Installation
Unit Inspection
As soon as the unit arrives at the job site
•V erify that the nameplate data matches the data on the
sales order and bill of lading (includin g electrical data).
•Verify that the power supply complies with the unit
nameplate specifications.
•Visually inspect the exterior of the unit, including the
roof, for signs of shipping damage.
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or rep air will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. You MUST wear all necessary Personal
Protective Equipment (PPE) including gloves, eye
protection, mask, long sleeves and pants when
working with products containing fiberglass wool.
Exposition to glass wool fibers without all necessary
PPE equipment could result in cancer, respiratory, skin
or eye irritation, which could result in death or serious
injury.
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or rep air will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers could also cause
respiratory, skin or eye irritation.
Precautionary Measures:
• Avoid breathing fiberglass dust.
• Use a NIOSH approved dust/mist respirator.
• Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye
protection. Wash clothes separately from other
clothing: rinse washer thoroughly.
• Operations such as sawing, blo wing, t ear-out, and
spraying may generate fiber concentrations
requiring additional respir atory protection. Use the
appropriate NIOSH appro ved respiration in th ese
situations.
First Aid Measures:
• Eye Contact - Flush eyes with wa ter to remove du st.
If symptoms persist, seek medical attention.
• Skin Contact - Wash aff ected areas gently with soap
and warm water after handling.
If the job site inspection of the unit reveals damage or
material shortages, file a claim with the carrier
immediately. Specify the type and extent of the damage on
the “bill of lading” before signing.
•Visually inspect the internal components for shipping
damage as soon as possible after delivery and before
it is stored. Do not walk on the sheet metal base pans.
•If concealed damage is discovered, notify the carrier’s
terminal of damage immediately by phone and by
mail. Concealed damage must be reported within 15
days.
•Request an immediate joint inspection of the damage
by the carrier and the consignee. Do not remove
damaged material from the receiving location. Take
photos of the damage, if possible. The owner must
provide reasonable evidence that the damage did not
occur after delivery.
•Notify the appropriate sales representative before
installing or repairing a damaged unit.
Storage
Take precautions to prevent condensate from forming
inside the unit’s electrical compartments and motors if:
•the unit is stored before it is installed; or,
•the unit is set on the roof curb, and temporary heat is
provided in the building. Isolat e al l side p anel servi ce
entrances and base pan openings (e.g., conduit holes,
S/A and R/A openings, and flue openings) from the
ambient air until the unit is ready for start-up.
Note: Do not use the unit’s heater for temporary hea t
without first completing the start-up procedure
detailed under “Starting the Unit”.
The manufacturer will not assume any responsibility for
equipment damage resulting from condensate
accumulation on the unit’s electrical and/or mechanical
components.
Unit Clearances
p. 11 illustrates the minimum operating and service
clearances for either a single or multiple unit installation.
These clearances are the minimum distances necessary to
assure adequate serviceability, cataloged unit capacity,
and peak operating efficiency.
Important: Providing less than the recommended
clearances may result in condenser coil
starvation, “short-circuiting” of exhaust
and economizer airflows, or recirculation of
hot condenser air.
RT-SVX23F-EN17