Ingersoll Rand DA5IM, DA15IM, DA25IM, DA40IM, DA55IM Owners Manual

...
Page 1
A
PPROVED 11/Jun/2020 11:47:53 GM
T
DA Heatless Purge
DA5IM, DA15IM, DA25IM DA40IM, DA55IM, DA70IM, DA100IM, DA150IM DA200IM, DA250IM, DA300IM
17933550
Revision D
June 2020
Save These Instructions
Page 2
EN
A
T
PPROVED 11/Jun/2020 11:47:53 GM
CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 ABBREVIATED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . 3
3.0 RECEIVING AND INSPECTION . . . . . . . . . . . . . . . . . . . . . . 4
3.1 INSPECTION ..............................................4
3.2 UNPACKING AND HANDLING .............................4
4.0 SAFETY AND OPERATION PRECAUTIONS . . . . . . . . . . . 5
4.1 SAFETY PRECAUTIONS LIST ...............................5
5.0 PRINCIPLES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . 6
5.1 INTRODUCTION ..........................................6
5.2 DRYING CYCLE ...........................................6
5.3 REGENERATION CYCLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.4 REGENERATION AIR FLOW ................................6
5.5 TOWER REPRESSURIZATION ..............................6
5.6 VALVES ...................................................6
5.7 TIMING SEQUENCE .......................................6
5.8 COMPRESSOR INTERLOCK FUNCTION DA40IM  DA300IM
ONLY ....................................................7
5.9 ENERGY MANAGEMENT SYSTEM .........................7
5.10 DRYER CONTROLS .......................................7
6.0 INSTALLATION AND STARTUP . . . . . . . . . . . . . . . . . . . 11
6.1 APPLICATION AND CHECK ANALYSIS ................... 11
6.2 LOCATING AND MOUNTING ............................ 11
6.3 PIPING .................................................11
6.4 FILTRATION ............................................. 12
6.5 ELECTRICAL CONNECTION ............................. 14
6.6 DEW POINT MONITOR EMS OPTION ................... 14
6.7 STARTUP PROCEDURE ................................. 14
6.8 DRYER SHUTDOWN SEQUENCE ........................ 16
7.0 MAINTENANCE AND SYSTEM CHECK . . . . . . . . . . . . . 17
7.1 SCHEDULED MAINTENANCE ............................ 17
7.2 PREFILTERS AND AFTERFILTERS ......................... 17
7.3 PILOT AIR CONTROL SOLENOID VALVES AND ......FILTER/
REGULATOR ............................................ 17
7.4 MUFFLER CHANGEOUT PROCEDURE .................... 17
7.5 ANGLE SEATED PURGE AND SWITCHING
VALVES ................................................. 18
7.6 DESICCANT CHANGEOUT PROCEDURE ................. 18
8.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9.0 WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.1 DA5IMDA25IM, ELECTRICAL SCHEMATIC ...............20
9.2 DA40IMDA300IM, ELECTRICAL SCHEMATIC ............21
10.0 FLOW DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.1 DA5IM  DA25IM ...................................... 22
10.2 DA40IMDA150IM ..................................... 23
10.3 DA200IMDA300IM .................................... 24
11.0 ANGLE VALVE REBUILD PARTS . . . . . . . . . . . . . . . . . . 25
12.0 ENGINEERING SPECIFICATIONS . . . . . . . . . . . . . . . . . 26
12.1 ENGINEERING DATA 40°C ............................ 26
12.2 ENGINEERING DATA 70°C ............................ 27
Page 3
A
PPROVED 11/Jun/2020 11:47:53 GM
T
1.0 INTRODUCTION
EN
Ingersoll Rand DA Heatless Desiccant Dryers are designed
to adsorb moisture from compressed air. The DA dryers are constructed with two towers that alternate between online (drying) and oine (regenerating modes) in order to yield a continuous stream of dry air at the dryer’s outlet. Each tower contains desiccant beads.
During normal operation, wet air passes through the online tower and water vapor from the air is adsorbed (collected) on the desiccant beads. While air is being adsorbed in the online tower, the moisture on the desiccant in the oine tower is removed by a process called desorption (regeneration). After an initial rapid depressurization, a portion of dried air from
2.0 ABBREVIATED WARRANTY
Ingersoll Rand heatless desiccant dryer products
are warranted to be free from defects in material and workmanship for a period of 12 months from the original date of shipment from the factory. To allow the warranty to be in eect for 12 months from the date of equipment start-up, the Warranty Registration Card must be completed and returned to Ingersoll Rand. Alternately, the Warranty Registration Card may be completed online at www.Ingersollrand.com. The total warranty period cannot exceed 18 months from the original date of shipment from the factory.
Equipment must be installed and operated in accordance with Ingersoll Rand’s recommendations. Ingersoll Rand liability is limited to repair of, refund of purchase price paid for, or replacement in kind at Ingersoll Rand’s sole option
the online tower passes over the desiccant bed and carries the moisture o the bed and out the dryer’s exhaust.
The continuous, alternating process of adsorption and desorption is controlled using a timer that switches the towers in a specic timed sequence. Very dry compressed air dew points are achieved through the continuous switching and operation of this dryer. Ingersoll Rand oers dryers to provide either -40°F (-40°C) or -100°F (-70°C) pressure dew point outlet air.
during the warranty time period stated above. IN NO EVENT SHALL Ingersoll Rand BE LIABLE OR RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, even if the possibility of such incidental or consequential damages has been made known to Ingersoll Rand. In addition, the usual maintenance and replacement type products are not covered by this warranty. See SECTION 7.
The warranties expressed above are in lieu of and exclusive of all other warranties. There are no other warranties, expressed or implied, except as stated herein. There are no implied warranties of merchantability or tness for a particular purpose, which are specically disclaimed.
Page 4
EN
A
T
PPROVED 11/Jun/2020 11:47:53 GM
3.0 RECEIVING AND INSPECTION
 3.1 INSPECTION
Upon receiving your Ingersoll Rand desiccant dryer, inspect the unit closely. Evidence of rough handling should be noted on the delivery receipt, especially in the case where the dryer is not going to be uncrated immediately. Obtaining the delivery person’s signed agreement to noted damages will facilitate submission of insurance claims.
Contact your local sales oce to obtain an RMA claim to initiate the return process (if required).
 3.2 UNPACKING AND HANDLING
WARNING
Under no circumstances should any person attempt to lift heavy objects without proper lifting equipment (i.e. crane, hoist, slings or fork truck). Lifting any unit without proper lifting equipment can cause serious injury.
Refer to labels on the dryer for the appropriate means for lifting or moving the dryer. When lifting the dryer, ensure that no stress is applied to the piping or the valves. Refer to SECTION 6.2 for locating and mounting of the dryer.
The dryer can be rigged using the forklift rails (See Figure1) that are located on the bottom of the feet assembly. Use care when inserting fork lift tongs beneath these rails to avoid damage to piping at the rear of the dryer.
Figure: 1
Page 5
A
PPROVED 11/Jun/2020 11:47:53 GM
T
4.0 SAFETY AND OPERATION PRECAUTIONS
EN
 4.1 SAFETY PRECAUTIONS LIST
Because an air dryer is pressurized and contains mechanical parts, the same precautions should be observed as with any piece of machinery of this type where carelessness in operation or maintenance is hazardous to personnel. In addition to the many obvious safety rules that should be followed with this type of machinery, the safety precautions as listed below must be observed:
1. Only qualied personnel shall be permitted to adjust, perform maintenance or repair this air dryer.
2. Read all instructions completely before operating unit.
3. Pull main electrical disconnect switch and disconnect any separate control lines, if used, before attempting to work or perform maintenance on the unit. Use proper lockout/tag out procedures.
4. Do not attempt to service any part while dryer is in an operational mode.
5. When servicing this dryers, do not attempt to remove any parts without rst relieving the entire air system of pressure.
6. Do not operate the dryer at pressures in excess of its rating.
7. Inspect unit daily to observe and correct any unsafe operating conditions.
8. Dryer must be de-pressurized before servicing.
WARNING
“WARNING” is used to indicate a hazardous situation which has some probability of death or severe injury. Warning should not be considered for property damage accidents unless personal injury risk is present.
CAUTION
“CAUTION” is used to indicate a hazardous situation which may result in minor or moderate injury.
NOTICE
“NOTICE” is used to indicate a statement of company policy as the message relates directly or indirectly to the safety of personnel or protection of property. Notice should not be associated directly with a hazard or hazardous situation and must not be used in place of “DANGER,” “WARNING,” or “CAUTION.”
NOTICE
The user of any air dryer manufactured by Ingersoll Rand, is hereby warned that failure to follow the included Safety and Operation Precautions can result in personal injuries or equipment damage. However, Ingersoll Rand does not state as fact, nor does it mean to imply, that the preceding list of Safety and Operation Precautions is all inclusive, and further, that the observance of this list will prevent all personal injuries or equipment damage.
Page 6
EN
A
T
PPROVED 11/Jun/2020 11:47:53 GM
5.0 PRINCIPLES OF OPERATION
 5.1 INTRODUCTION
As described in SECTION 1, the DA series dryer is used to remove water vapor from compressed air by diverting air ow alternately between two towers that are lled with desiccant material. While one tower processes the compressed air stream by adsorbing water vapor, the opposite tower is regenerated by desorbing the water vapor accumulated in the previous cycle and venting it to atmosphere. Refer to SECTION 10, FLOW DIAGRAM for a visual representation of the drying and regenerating cycles.
Inlet ow to the dryer is directed to the bottom manifold and the outlet ow exits through the upper manifold. The manifolds are comprised of both pneumatically actuated valves and check valves that direct compressed air ow through the dryer.
 5.2 DRYING CYCLE
Saturated compressed air enters the dryer and is directed to the appropriate drying tower by the corresponding inlet ow valves. The inlet ow valves are normally-open and one of the valves will be actuated closed to direct the ow of compressed air to the designated drying tower. It is important to note that only one inlet valve is closed during this process. The FLOW DIAGRAM in SECTION 10 depicts the scenario where the left tower is being regenerated and the drying process is occurring with the right tower. In this example, wet compressed air enters the dryer and is directed to the right tower for drying when the left tower valve is actuated to a closed position. The normally-closed right tower purge valve is closed while the left tower purge valve is actuated to an open position during this period. As the compressed air ows through the desiccant material on the right tower, removal of water vapor from the air stream begins to occur through adsorption.
 5.3 REGENERATION CYCLE
Previously adsorbed moisture, removed from the process stream, gets stripped or desorbed from the desiccant material in the regeneration process. The rst stage of regeneration is tower depressurization. After the inlet Flow Valves are switched to divert air ow away from the regenerating tower, the appropriate normally-closed purge valve will be opened and the tower will be depressurized. Through rapid depressurization, a signicant portion of the previously adsorbed water vapor is stripped o the desiccant material and exhausted to the atmosphere.
DA Heatless Dryers are equipped with a downstream purge feature as standard. The downstream purge utilizes air from a downstream source to purge the regenerating tower. This feature is useful for applications with downstream (dry) storage tanks, as pulling air from a downstream source can minimize cycling of the air compressor.
 5.4 REGENERATION AIR FLOW
To enable the desiccant media within the towers to be thoroughly regenerated and to get proper dryer performance, purge air ow is factory preset. Setting the purge ow too high wastes compressed air and setting it too low results in the dryer not achieving proper dew point performance.
NOTICE
Do not restrict purge exhaust ow in any way. Keep purge muers clean. If exhaust air must be piped away from dryer, consult factory for correct pipe sizing and conguration.
 5.5 TOWER REPRESSURIZATION
Upon completion of tower regeneration, and prior to the inlet ow valves changing position to switch towers, the regenerated tower must be repressurized.
Repressurization is accomplished when the appropriate purge valve closes. Closing the purge valve allows the regeneration air to begin to pressurize the tower.
 5.6 VALVES
Control air solenoid valves (See Figure 2) are used to actuate the main ow valves and purge valves. The inlet ow valves are normally-open valves, while the purge valves are normally-closed valves. This arrangement permits air to ow through the dryer in the event of power failure. The control air solenoid valves are located on the bottom manifold assembly.
Figure: 2
The second stage of regeneration uses a portion of the dry, compressed air expanded to atmospheric pressure to complete the desorption process. As depicted in the FLOW DIAGRAM, the compressed air exits the drying tower and a portion of the air ows through the purge orice. Once the air has passed through the purge orice, it expands to atmospheric pressure and continues the regeneration process. Desorption occurs as the desiccant releases water vapor into the regeneration air that is then exhausted through the purge muer.
 5.7 TIMING SEQUENCE
A Digital Controller controls all dryer timing functions. The timing of Ingersoll Rand -40°F (-40°C) and -100°F (-70°C) dryers is outlined as follows:
Page 7
A
PPROVED 11/Jun/2020 11:47:53 GM
T
EN
5.7.1 TIMING CYCLE FOR -40°F (-40°C) DEW POINT DRYERS
The standard timing cycle for -40°F (-40°C) operation switches the inlet ow valve position every ve minutes which alternates the drying tower. At the same time as a tower inlet valve opens, the appropriate tower purge valve opens to depressurize the regenerating tower. Tower regeneration occurs for 4 minutes and 10 seconds, at which time the purge valve closes to initiate repressurization.
5.7.2 TIMING CYCLE FOR -100°F (-70°C) DEW POINT DRYERS
The standard timing cycle for -100°F (-70°C) operation alternates the drying tower by switching the inlet ow valve position every two minutes. At the same time a tower inlet valve opens, the appropriate tower purge valve opens to depressurize the regenerating tower. Tower regeneration occurs for 1 minute and 50 seconds, at which time the purge valve closes to initiate repressurization.
NOTICE
Do not restrict purge exhaust ow in any way. Keep purge muers clean. If exhaust air must be piped away from dryer, consult factory for correct pipe sizing and conguration.
 5.9 ENERGY MANAGEMENT SYSTEM
The Energy Management System (EMS) feature is designed to minimize the use of purge air during low ow or low water loading conditions. On -40°F (-40°C) units, a dew point sensor samples the moisture content from the online tower and provides a signal to the controller. This function utilizes a dew point transmitter that monitors the dew point of the air exiting the dryer. Please note that the dew point transmitter should not be installed on a newly started machine until the dryer has operated continuously for a minimum of 24 hours.
 5.10 DRYER CONTROLS
The dryer is controlled by a digital controller that includes an illuminated display and keypad, accessible on the dryer main panel.
DA5IM – DA25IM Models
ON/OFF Button
UP/DOWN Arrow key
LT RT
D D
250
R R
 5.8 COMPRESSOR INTERLOCK FUNCTION
DA40IM  DA300IM ONLY
The compressor interlock function enables the dryer to reduce the timing of the purge cycle based on compressed air demand. When the function is activated through the TECHNICIAN MODE within the digital controller, the controller monitors the cycle rate of the air compressor load/unload relay. The dryer will need to be eld wired to the normally­open contact of the air compressor to allow the controller to monitor the cycle rate. The compressor interlock connections are depicted on the dryer wiring diagram (SECTION 9, Wiring Diagram).
It is important to note that the compressor interlock function is designed to be operated independent from the Energy Management System (EMS) option. For dryers equipped with the EMS option, the compressor interlock must be set to “OFF” in order to activate the EMS function. Setting the compressor interlock to “ON” in TECHNICIAN MODE will disable the EMS function.
For dryers equipped with the EMS option, the compressor interlock function can be used as a backup method to reduce purge air consumption when the dew point monitor is removed for calibration or for service. It is important to note that the performance of the dryer is based on the inlet temperature and pressure conditions along with ow. If the inlet temperature of the compressed air being supplied to the dryer is above 100oF (38°C), the user must exercise caution in order to prevent the desiccant beds from becoming overloaded, possibly requiring the compressor interlock function to be de-activated. Consult the factory for higher inlet temperatures (101°F/38°C - 120°F /49°C). Dryer sizing is aected by increased inlet temperatures.
CONTROLLER BUTTONS AND KEYS
ON/OFF Button Press 2 seconds
Set up Menu Button To enter cycle time setting
UP/DOWN Arrow key To change cycle time
When the dryer is actively cycling LT or RT and R or D will illuminate to indicate working phase of each tower. The numeric countdown timer indicates seconds remaining in the operating sycle step.
If cycle times need to be adjusted to meet site conditions, a trained service technician must be the one to make the changes.
Set up Menu
Page 8
EN
A
T
DA40IM – DA300IM Models
PPROVED 11/Jun/2020 11:47:53 GM
BACK NAVIGATION
KEY
FORWARD NAVIGATION
KEY
ON/RESUME
BUTTON
RESET BUTTON
OFF BUTTON NUMERAL KEYS
CONTROLLER BUTTONS AND KEYS
INFORMATION
BUTTON
ON/RESUME
BUTTON
OFF BUTTON
NUMERAL KEYS
RESET BUTTON Exit current screen.
+ / - BUTTON
ENTER BUTTON
NAVIGATION
KEYS (ARROWS)
Restricted Level access - for factory use only.
Initiates Dryer Operating Cycle. Begins system monitoring and valve switching functions.
Stops Dryer Operating Cycle. Stops valve switching functions. Initiates Shutdown Sequence. Dryer remains pressurized.
Allow the operator to enter values for selectable settings and assignments.
Use to toggle or change multistate variables. Also allows entering negative numbers in numeric input variables.
Use to change and accept set point values.
Enables navigation between screens and lines.
On models DA40IM – DA300IM Multiple screens can be viewed. Use the BACK (left) and FORWARD (right) navigation keys to navigate within dierent screens.
INFORMATION
BUTTON
ENTER
BUTTON
+ / - BUTTON
5.10.1 DRYER ALARMS
DA5IM – DA25IM do not oer any alarms.
DA40IM – DA300IM oer predened elapsed time alarms,
that can be reset by pressing the "Reset" button.
1. Filter element change – 6 months
2. Muers – 12 months
3. Dew point sensor – 12 months
4. Valves – 36 months
5. Desiccant change – 48 months
5.10.2 DRYER COMMUNICATION RS485 (DA40IM - DA300IM)
1. RS485 port
2. RS485 connector signals
• D+ Tx/Rx+ (B)
• D- Tx/Rx– (A)
• T+ Positive Termination
• T- Negative Termination
• SG Signal Ground
NOTICE
In order to ensure proper tower pressurization, every dryer ON (restart) has 30 seconds delay incorporated into software. Countdown is visible on PLC main screen.
On models DA40IM – DA300IM Multiple screens can be viewed. Use the BACK (left) and FORWARD (right) navigation
Page 9
A
PPROVED 11/Jun/2020 11:47:53 GM
T
EN
5.10.3 CONTROLLER DISPLAY SCREENS
Visual display of dryer status, Operating Cycle information, conguration, and Alarm status.
INITIALIZATION (Screen appears briey when electrical power is initially supplied to the dryer.)
LINE 1: Intentionally left blank.
LINE 2: Dryer Operating Program Version
ANTI-SHORT-CYCLE (30-second delay that occurs any time the dryer is turned o.)
LINE 1: Dryer operating status (ON or OFF)
LINE 2: Anti-Short-Cycle countdown (seconds remaining)
HOME (Screen appears after ON button (green) has been pressed. Screen indicates Operating Cycle Step information and dryer conguration. Use forward NAVIGATION KEY to advance to Operating screens.)
LINE 1: Dryer operating status (ON or OFF).
LINE 2: Dryer Operating Cycle Step number (1-10). Seconds Remaining in Step.
UP Arrow indicates Drying Flow (Left Tower). Down Arrow indicates Regeneration Flow (Right Tower). (Arrows will switch at time of tower changeover.)
IF EQUIPPED WITH DEW POINT TRANSMITTER (when Energy Management System (EMS) option is installed):
LINE 1: Dryer operating status (ON or OFF). Outlet compressed air Pressure Dew Point (PDP)
during operation.
LINE 2: EMS is activated (blinking) - dryer operating in standby mode.
Interrupted Step number remains visible. Countdown timer pauses. UP Arrow indicates Drying Flow (Left Tower). Down Arrow indicates Regeneration Flow
(Right Tower). (Arrows will switch at time of tower changeover.)
OPERATING STATUS (Screens indicate normal Operating Cycle information and Alarm states. Press forward NAVIGATION KEY to advance through screens. Press back NAVIGATION KEY to return to HOME screen.)
LINE 1: Dryer Alarm Status: 0 = No Alarm; 1 = Dryer in Alarm state
LINE 2: Appears blank if no Alarm condition exists. Press ENTER to view Alarm menu.
If in Alarm state, the condition will be indicated: 1 - 3 = Alarms; 4 - 8 = Service Reminders.
See ALARM STATUS AND SERVICE REMINDERS on next page.
LINE 1: Total Operating Time: Days/Hours
LINE 2: Intentionally left blank.
LINE 1: Temperature Scale: Use +/- button to select degrees Celsius or degrees Fahrenheit
LINE 2: Intentionally left blank.
LINE 1: Protected Settings: Enter Password to access: Technician Mode (TM) = 2010; Service
Reminders = 4040
LINE 2: Intentionally left blank.
LINE 1: Intentionally left blank.
LINE 2: Operating Mode: Use +/- button to select: t = Timed;
ࣅ = Energy Management System (EMS); CI = Compressor Interlock
Page 10
EN
LINE 1: Intentionally left blank.
LINE 2: Optional Energy Management System (EMS) temperature setpoint
ALARM STATUS AND SERVICE REMINDERS (Annunciation of Dryer Operating Fault Conditions.)
ALARMS
LINE 1: Dryer Alarm Status: 0 = No Alarm; 1 = Dryer in Alarm state
LINE 2: Current Alarm condition: 1 = High Pressure Dew Point (PDP); 2 = Energy Management
System (EMS) o;
3 = Pressure Dew Point (PDP) out of range; 4 = Replace lter element; 5 = Replace exhaust muers; 6 = Replace pressure dew point sensor; 7 = Replace valves; 8 = Replace desiccant media)
ALARM HISTORY FORMAT
LINE 1: Alarm identier number
LINE 2: Time and Date format
EXAMPLE - RECORDED ALARM
LINE 1: 3 = Pressure Dew Point (PDP) out of range
LINE 2: Time and date of the occurrance
Press ENTER to view the next recorded alarm.
SERVICE REMINDERS (Accessible through Protected Settings screen.)
LINE 1: Dryer service requirement: 0 = No service needed; 1 = Service required
LINE 2: Service descriptions:
4 = Replace lter element (SERVICE-1), 6 months 5 = Replace exhaust muers (SERVICE-2), 12 months 6 = Replace pressure dew point sensor (SERVICE-3), 12 months 7 = Replace valves (SERVICE-4), 36 months 8 = Replace desiccant media (SERVICE-5), 48 months
TECHNICIAN MODE (Accessible through Protected Settings screen.)
LINE 1: Dryer Restart following power outage. Use +/- button to select:
0 = MANUAL - Press ON button (green). Dryer will start at the beginning of the Operating Cycle. 1 = AUTOMATIC - Dryer will automatically restart and operation will resume at the Step in the Operating Cycle that was active before the power outage occurred.
LINE 2: Intentionally left blank.
LINE 1: Pressure Dew Point high temperature alarm setpoint. Use numeral keys to change
temperature value. Press ENTER button to input the new setpoint.
LINE 2: Use +/- button to select: 0 = O; 1 = On
LINE 1: Energy Management System (EMS) operating time limit (preset 10-hour limit).
LINE 2: Use +/- button to select: 0 = O; 1 = On
Page 11
A
PPROVED 11/Jun/2020 11:47:53 GM
T
6.0 INSTALLATION AND STARTUP
 6.1 APPLICATION AND CHECK ANALYSIS
To achieve the best dryer performance, you should carefully check that the design and installation requirements outlined below are satised.
NOTICE
The standard dryer is not rated for any gas other than air.
The dryer is designed to be operated with a compressed air inlet temperature ranging from 68°F (20°C) to up to 120°F (49°C) and at an operating pressure ranging from 60psig (4barg) to 200psig (14barg). The volume of air will be dependent on the system operating pressure. The air compressor delivering air to the dryer must be sized properly to handle both the demand and the purge air requirements necessary for regeneration.
EN
 6.2 LOCATING AND MOUNTING
Use a forklift to lift the dryer only at the lift points identied with labeling. Use care to avoid damage to the manifold assembly. Bolt the dryer to the foundation using the bolt holes provided in the base frame. Anchor bolts should protrude a minimum of 1 inch (25 mm) above the foundation. Models DA5IM-DA25IM can be wall mounted (See Figure 3). Use appropriate size bolts to hold entire dryer weight.
Figure: 3
The factory should be consulted if the dryer is to be operated at pressures below 60psig (4barg) to verify sizing and proper conguration.
The standard dryer is rated to operate at an inlet temperature and pressure of 100°F (30°C) @ 100psig (7barg). The operating conditions should be veried prior to installing and operating the dryer to ensure it is properly sized. A dryer with greater capacity may be required to achieve expected dew point performance in installations with elevated inlet air temperatures. Lower inlet temperature conditions may also reduce dryer performance.
It is important to note that delivering lower compressed air inlet temperature levels will reduce drying performance. A minimum compressed air inlet temperature of 68°F (20°C) is required to be supplied to the dryer for proper operation.
The dryer should generally be installed in an enclosed area where the ambient temperature does not drop below 50°F (10°C) and is not above 115°F (46°C). Please consult the factory for outdoor installation applications where additional provisions may be required for lower ambient conditions.
NOTICE
Ingersoll Rand recommends the muers be cleaned after initial start-up to remove any desiccant dust generated during dryer shipment. After running the dryer for the initial 30 minute period, de-energize/ depressurize the dryer and remove the muers. Disassemble and clean the removable insert inside the muer core. Reinstall the muers prior to operating dryer. Periodic inspection of the muers is required to ensure proper dryer operation.
 6.3 PIPING
Pipe the compressed air lines to the inlet and outlet connections. When installing the prelters, which are shipped loose in the package, the prelters should be located as close to the dryer as possible. In addition, they should be positioned to allow for ease of service.
Note that the wet air inlet is at the dryer’s lower manifold, while the dry air outlet is at the dryer’s upper manifold. In situations where air supply is required 24 hours a day (where it is undesirable to interrupt the compressed air ow), an optional three valve by-pass system is recommended to bypass the dryer. To keep pressure drop at a minimum, the fewest elbows possible should be used. In order to prevent ooding of the desiccant bed when the dryer is o, the bypass should be used when troubleshooting the air compressor operation or when servicing the dryer.
Once all piping has been connected, all joints, including those on the dryer, should be soap bubble tested at line pressure to ensure no joints have been damaged in transit and during site placement. All installed piping must be self-supported. The dryer manifold piping cannot be used to support the interconnecting piping.
A minimum inlet temperature of 68°F (20°C) is required for proper dryer operation.
Page 12
EN
A
T
PPROVED 11/Jun/2020 11:47:53 GM
 6.4 FILTRATION
NOTE: A prelter and an afterlter are provided with your dryer. Afterlters can be directly mounted on the dryers outlet while prelters need additional piping to allow the height to be sucient for maintenance purposes (See Figure 4 & 5).
Figure: 4
Figure: 5
Located before the dryer, coalescing prelters protect the desiccant beds from contamination from oil, entrained water, pipe scale and other contaminants. This extends the dryer’s desiccant life.
Prelters should be located as close to the dryer as possible and must be provided with drains to prevent liquid water from entering the desiccant beds. Drain maintenance is not covered by the standard warranty.
It is recommended that a mechanical separator with a properly functioning drain be installed immediately preceding the prelter to remove bulk liquid and entrained water.
The particulate/coalescing afterlter, located after the dryer, helps eliminate the possibility of desiccant dust carryover into the air system. To ensure proper dryer operation, the prelter drain(s) must be inspected periodically.
The outlet lter on models DA5IM – DA25IM can be mounted on left or right outlet connection (See Figure 6) while the opposite connection must be plugged.
Figure: 6
NOTICE
All DA model dryers must have proper ltration. Liquid water and oil must be removed before compressed air enters the dryer. Ensure Prelters and drains are in good working order. Failure to do so will void warranty.
Page 13
A
PPROVED 11/Jun/2020 11:47:53 GM
T
EN
6.4.1 FILTER DRAIN VALVE
DA dryer models are furnished from the factory with lters that include an automatic condensate drain valve. The drains require periodic inspection and maintenance to ensure proper dryer operation. Drain maintenance is not covered by the standard warranty.
Filters include an automatic drain valve. The drain valve must be checked for correct conguration prior to pressurization of the dryer as follows:
• Filters must be oriented vertically for proper operation.
• The drain stem must be properly adjusted as follows:
- Twist the drain stem (No. 18 in Figure 8) to set for AUTOMATIC (Normal) or MANUAL (Test) operation (See Figure 7 below).
- Twist the stem fully clockwise (when viewed from the bottom of the lter bowl) for AUTOMATIC draining of condensate. This is the Normal position.
- Twist the stem fully counter-clockwise (when viewed from the bottom of the lter bowl) for MANUAL draining of condensate (Test/Bleed) or if connected to an external drain.
Figure 8
Figure 7
MANUAL
AUTOMATIC
Minimum operating pressure of 22psig (1.5barg) is required for the oat that is within the drain assembly to seat properly. Pressures below 22psig (1.5barg) allow air to escape from the drain when the compressed air system is being pressurized.
WARNING
Proper safety precautions must be followed when servicing lters and drains. Filter bowl must be de-pressurized before servicing drain.
Service should only be performed by qualied personnel.
Before rst-time use, and after maintenance, the drain stem (See 18 in Figure 8) should be twisted fully clockwise to provide AUTOMATIC operation (See Figure 7).
Method of Operation (See Figure 8)
• When the lter pressure is below 22psig (1.5barg), the
piston (9) is held in an open position by the spring (3).
• When the lter is pressurized above 22psig (1.5bar), the
piston closes the drain aperture at the O-ring (13).
• As the condensate collects in the lter bowl, the oat (1)
is pushed upward, opening the nozzle (7) and allowing air to reach the top of the piston (9). This causes the piston to move downward, opening the aperture at the O-ring (13) for drainage of the condensate.
Maintenance and Initial Operation
• After initial startup, inspect drain(s) for system debris.
Clean as required. Float drain assembly is screwed into the bottom of the bowl from the inside.
• Drains require periodic inspection and maintenance to
ensure proper operation. Clogging of drains due to system debris or fouling is not considered warranty. Faulty drains must be returned to the factory for analysis in order to receive warranty credit.
Clogged drain screens can be cleaned by immersing the drain in a detergent and rinsing thoroughly in water.
Page 14
EN
A
T
PPROVED 11/Jun/2020 11:47:53 GM
 6.5 ELECTRICAL CONNECTION
Make all electrical connections to the dryer as shown on the wiring diagram (SECTION 9). Care must be taken to connect the proper voltages.
NOTICE
Dryer must be grounded with the full size ground wire connected to an earth ground.
NOTICE
Dryer must be fused according to NEC with the size fuse listed on the dryer serial nameplate, or on specication sheet in Technical Manual.
Size eld connection knock-out for the conduit tting required by the NEC. Installer must use UL Type 4 rated tting.
The compressor interlock wiring should be veried if this function is to be activated at start-up.
 6.6 DEW POINT MONITOR EMS OPTION
The dew point transmitter assembly (See Figure 9) that is supplied with the dryer as a separate component (when the dryer is ordered with the EMS option) must not be installed until the dryer has been in operation for 24 hours.
Figure 9
 6.7 STARTUP PROCEDURE
A Startup Form (included with the manual) must be completed and submitted with the Warranty Card as part of the commissioning process. This is included with the dryer at shipment.
Prior to pressurizing the compressed air system, conduct a visual inspection of the dryer to verify that the unit was not damaged during the installation process. This includes:
• Inlet and outlet compressed air piping connections are
properly supported.
• Extruded pressure vessels are not damaged.
• Gauges are in good condition.
• Pneumatic control air hoses, inlet and outlet compressed
air piping connections are properly supported and tightened.
• Prelter and afterlter bowl are properly tightened.
• Drain lines are installed to the lters. Refer to SECTION
6.4.1.
• Fasteners securing the dierential pressure indicator to
lter head are secured.
• Drain stem on each lter bowl is placed in the proper
direction such that it operates in the manual mode for initial startup. Refer to SECTION 6.4.1. The drains will allow air to escape until the system reaches 22psig (1.5barg) at which point the internal oat will seat properly and the drain will seal closed.
The dryer warranty will be voided if the dew point transmitter is damaged as a result of ooding condition.
NOTICE
The Dew Point Transmitter that is supplied with the dryer as a separate component must not be installed until the dryer has been in operation for 24 hours.
After the visual inspection is complete, slowly pressurize the dryer and perform a verication check on the following items:
1. Verify that the air outlet shut-o valve is closed (if this is provided for the dryer). This can be provided as part of a three-valve bypass option for the dryer or eld provided as part of the installation.
2. Check for air leakage prior to initiating ow through the dryer. Repair all leaks prior to starting the dryer. In order to maintain the drying performance of the dryer, any leaks must be xed; most important are leaks identied on the outlet side of the dryer.
NOTICE
DO NOT FLOW COMPRESSED AIR THROUGH THE DRYER WHEN THE DRYER IS OFF. The desiccant beds will become ooded with moisture and the Warranty will be voided.
Page 15
A
PPROVED 11/Jun/2020 11:47:53 GM
T
EN
3. Verify that the prelter drain is blowing freely to drain residual water in the system. If no moisture is observed exiting the drain, turn drain stem to the automatic position. Verify drains ahead of dryer are functioning properly.
4. Turn the eld disconnect switch to the ON position to apply power to the dryer. This will energize the controller. Use proper PPE to verify that the voltage to the control panel matches the voltage/phase listed on the serial plate of the dryer. Do not apply power to the dryer until items 1-4 listed above have been veried. Do not apply power to the dryer or activate the dryer for operation until the air system checks are completed.
• For dryers equipped with the EMS option, do
not install the dew point transmitter until the dryer has operated for a minimum of 24 hours to reach steady state conditions. See the Warning note regarding installation of the dew point transmitter. Failure to follow this procedure will damage the dew point sensor and will void the sensor warranty.
5. The control air regulator located inside the top cover is preset to not exceed 100psig (7barg). The main ow inlet and purge valves are regulated to operate with a control air pressure level not to exceed 145psig (10barg).
after the dryer is placed into operation. Drain maintenance or cleaning of system debris is not covered under warranty. Improper drain maintenance will result in damage to the desiccant beds and will void the warranty.
• Once the system has operated for approximately
two hours, the muers will need to be inspected. Follow proper safety procedures prior to replacing the muers. Muers are consumable items and are not warranted other than for manufacturing defects.
• Monitor the operation of the dryer and contact
Ingersoll Rand if any problems arise during the startup process. The oat drains on the dryer's should be inspected daily to ensure proper operation.
• For dryers equipped with the EMS option, install
the dew point transmitter once the dryer has operated for a minimum of 24 hours and the BMI is fully blue in color. After the sensor has been installed, re-activate the EMS function through the settings screen.
• Verify (if wired) compressor interlock Function.
See SECTION 5.8.
9. Complete the warranty startup card after the dryer is fully commissioned.
6. Press the ON button on the dryer controller to initiate dryer operation.
• Observe the operation of the dryer and verify
that the dryer sequence is operating properly. The dryer controller will automatically sequence the valves. Do not allow the dryer to operate if problems are observed.
• Slowly open the outlet air shut-o valve (if
equipped) and allow the system to slowly pressurize.
7. Verify that the compressed air system remains pressurized.
NOTICE
At initial start-up, check the dryer operation for one or two cycles, especially at the time of the tower shift. Verify that all systems are operating in their proper order and sequence. If the dryer is not functioning properly, contact distributor or Ingersoll Rand Technical Service.
8. Verify the Technician and Maintenance settings of the dryer. Refer to SECTION 5.10 for further instructions.
• Verify that the oat drain(s) on the inlet lters
are operating properly. It is important to note that debris from the system piping may interfere with the operation of the oat drain and it is the responsibility of the installer to verify this
Long-Term Storage
If a dryer has been in storage for an extended period of time, follow the instructions above to start the dryer. Depending on the amount of time the unit was in storage, it may take between 8 and 12 hours before dryer would be regenerated.
NOTICE
When opening the outlet valve, ensure drying tower gauge maintains line pressure. Allowing the pressure in the dryer to drop will result in an overow condition and potentially cause valves to stop functioning.
NOTICE
-100°F (-70°C) dryers require ow through the dryer to lower the pressure dew point to design levels. Failure to permit air ow through dryer (deadheading) will result in elevated outlet dew points. Once air is permitted to ow through the dryer, the pressure dew point will gradually reduce to design levels.
Page 16
EN
A
T
PPROVED 11/Jun/2020 11:47:53 GM
 6.8 DRYER SHUTDOWN SEQUENCE
The following procedures must be followed to correctly terminate dryer operation:
NOTE: The DA dryer must remain pressurized during the shut-down sequence.
- Press the red “OFF” button to deactivate the dryer operating sequence and de-energize the control valves. The main ow valves will be positioned to the default position:
a.The purge valve will close b.The regenerating tower will re-pressurize c.The main inlet ow valves will open
The system must remain pressurized in order for the main ow valves on the dryer to revert to the default position.
- The status line in the home screen will display “OFF”.
- The system will remain pressurized at all times. The dryer does not contain any provisions to permit a system bleed down.
- The red “OFF” button only de-activates the dryer operating sequence - electric power will remain live within the dryer main panel.
WARNING
Failure to follow this procedure may result in the system retaining pressure within the dryer and potentially result in an unsafe condition for service personnel.
NOTICE
DO NOT FLOW COMPRESSED AIR THROUGH THE DRYER WHEN THE DRYER IS OFF. The desiccant beds will become ooded with moisture. The dryer Warranty will be void.
Page 17
p
7.0 MAINTENANCE AND SYSTEM CHECK
EN
 7.1 SCHEDULED MAINTENANCE
DAILY MAINTENANCE FUNCTIONS:
• Check and record inlet pressure, temperature and ow.
Verify that it is within specications.
• Check tower pressure gauge readings are within operating
tolerance (DA40IM - DA300IM only).
• Check dryer operation for proper cycling, depressurization
and re-pressurization.
• Check that the prelter drain is operating properly and that
there is no condensate discharged from purge muers.
• Verify that pressure in purging tower is 3psig (0.2barg) or
less. If higher, muer replacement is recommended. See SECTION 8.
• Check the dryer digital controller for alarms (DA40IM –
DA300IM only).
• Verify that prelter and afterlter dierential pressure
is within operating limits. Replace elements and/or cartridges as required.
MONTHLY MAINTENANCE FUNCTIONS:
• Check condition of muers by reading tower pressure
gauge when the tower is in the re-generation cycle. If pressure is above 3psig (0.2barg), muer replacement may be required.
 7.2 PREFILTERS AND AFTERFILTERS
PREFILTERS - The cartridges of the prelter must be changed as often as required to prevent contamination of the regenerative dryer’s desiccant bed.
The prelter and automatic drain must be checked daily. To prolong lter cartridge life, it is recommended that a mechanical air/moisture separator be placed immediately before the prelter.
AFTERFILTERS - The purpose of the afterlter is to remove residual desiccant dust. Depending upon equipment application and usage, frequency of lter element change will vary. It is recommended that, at the minimum, the lter element be changed every six months.
 7.3 PILOT AIR CONTROL SOLENOID VALVES AND
FILTER/REGULATOR
The length of time the pilot air valves can reliably operate without replacement is dependent upon the dryer operating cycle. On Ingersoll Rand -40°F (-40°C) dew point dryers, replacing the valves every 36 months is recommended. For
-100°F (-70°C) units, it is recommended that the pilot valves be replaced every 24 months. The control air regulator (See Figure 10) should be set for 100psig (7barg).
Figure: 10
NOTE: Ingersoll Rand recommends the muers be cleaned
after initial start-up to remove any desiccant dust generated during dryer shipment. After running the dryer for the initial 30 minute period, de-energize/depressurize the dryer and remove the muers. Disassemble and clean the removable insert inside the muer core. Reinstall the muers prior to operating dryer. This procedure should be repeated within the rst seven days of dryer operation.
SEMI-ANNUAL MAINTENANCE FUNCTIONS:
• Check outlet dew point (EMS option only).
• Replace prelter and afterlter elements and/or cartridges.
ANNUAL MAINTENANCE FUNCTIONS:
• Check desiccant and replace if necessary.
• Inspect and clean pilot air control solenoid valves, check
valves and ow valves. Rebuild and / or replace as required.
• Replace drains on prelter and afterlter.
• Test electrical components, replace as necessary.
• Check for loose electrical wiring connections and tighten
as required.
• Check and replace muers
EVERY THREE YEARS:
• Inspect pneumatic valves and replace angle valve bonnets
if not functioning properly (Preventive). Check and replace shuttle valve assembly
• Replace control air solenoid valve (Preventive).
• Re
lace desiccant.
 7.4 MUFFLER CHANGEOUT PROCEDURE
WARNING
To avoid injury, depressurize dryer before performing any service.
• Stop dryer cyclic function.
• Depressurize the dryer. Disconnect dryer from electric
power source.
• Replace muers.
• Follow Start-up Procedure described in SECTION 6.7.
• Turn control power back on.
Page 18
EN
 7.5 ANGLE SEATED PURGE AND SWITCHING
VALVES
• Purge Valves – Normally-Closed (N.C.) for purge air ow.
Control air is supplied through tubing that is connected to the side port. When control air is supplied to the valve, a position indicator will extend from the top of the bonnet, indicating that the valve is open (See Figure 11).
Figure 11
 7.6 DESICCANT CHANGEOUT PROCEDURE
When it becomes necessary to replace the desiccant in the towers, observe the following procedure:
Units (DA40IM - DA300IM) are furnished with ll and drain ports (See Figure 12) on each extruded tower. Remove the caps on both ports. Units (DA5IM - DA25IM) are not equipped with drain ports, upper block cover needs to be taken o to change desiccant media
Figure 12
• To assist in getting the desiccant to ow from the tower,
insert a small rod into the drain port as necessary. This may be required as the desiccant is packed into the towers which may interfere with the desiccant ow from the towers.
• With the ll port plug removed, ll the dryer tower with the
appropriate grade and size desiccant.
• When the towers have been lled to the correct level,
replace the ll port plug on each tower.
• Any connections and joints disturbed in the desiccant
change out procedure should be leak tested prior to re-commissioning the dryer.
CAUTION
Desiccant will produce dust during the change out procedure. Be sure to wear respiratory protection during the draining and lling process to minimize inhalation of desiccant dust.
Page 19
A
PPROVED 11/Jun/2020 11:47:53 GM
T
8.0 TROUBLESHOOTING
For troubleshooting procedures, refer to maintenance descriptions in SECTION 7 as required.
PROBLEM PROBABLE CAUSE CORRECTIVE ACTION
EN
Elevated Dew-point Insucient purge ow
Improper valve operation • Verify operation of main ow and purge valves.
Inlet air pressure below design condition
Flow rate is higher than design condition
Inlet temperature to the dryer exceeds the rated capacity of the dryer
Desiccant bed is ooded with moisture. The BMI will turn gray when this occurs
Excessive Pressure in
Purge Muer is clogged Inspect purge muers for clogging and replace as required. Tower Designated For Regeneration (Above 3psig (0.2 barg))
Inability to Maintain Line
Air leak across purge muer Determine if inlet valves and outlet check valves are functioning
Leaking check valve Utilize valve function to determine if inlet and outlet valves are Pressure On Drying Tower
• Inspect purge valve & control air solenoid valves for proper
operation.
• Inspect muers for clogging.
• Inspect control air solenoid valves for proper operation.
• Check pressure source and inspect piping system for
leakages.
• Verify that the dryer was sized appropriately for the operating
conditions.
• Verify that compressor sizing is properly matched to dryer
capacity.
• For specialty systems where the outlet of the dryer is piped
to a booster compressor, verify that the ow of the booster compressor is below the rated capacity of the dryer. Excessive ow will uidize the desiccant bed and result in dusting and signicantly reduce performance.
• Inspect the air compressor after-cooler and drain to ensure
proper operation. After-cooler may require cleaning in to operate properly.
• Verify the inlet temperature does not exceed 120
o
F (50oC) under normal operating conditions. For applications that approach 120oF (50oC) on a continuous basis, dryer sizing should be reviewed prior to operation of the dryer. The standard design is rated based on an inlet condition of
o
100
F (38oC) @ 100psig (7barg) and will not deliver proper
performance if it is undersized.
• Verify that the air compressor after-cooler drain is
functioning properly.
• The desiccant will become saturated if compressed air is
permitted to ow through the dryer before it is operating.
• If this occurs, the performance of the dryer will not easily
recover and this will void the warranty on the desiccant material.
Follow proper safety pre-cautions during this process.
properly.
functioning properly.
Page 20
A
PPROVED 11/Jun/2020 11:47:53 GM
T
EN
9.0 WIRING DIAGRAM
 9.1 DA5IMDA25IM, ELECTRICAL SCHEMATIC
POWER CORD
MODEL
DA5IM 2.0 DA15I DA25IM
LENGTH
)
(m
M
2.0
2.0
LEFT
1
3
45
67
9
10
11
POWER CORD 3 X 1.5 FLEX-JZ SEE TABLE ON
1 CONTROLLER EW 902 1
2
3 TERMINAL BLOCK, 5x2,5mm² BM 9200 1
4 FUSE HOLDER 866-3454 1
Pos. DESCRIPTION CODE QTY.
BLUE
BLACK
LPEN
1.5mm²
1.5mm²
1.5mm²
GN/YE
PE
4
PE
TOWER 1
N
N
PE
L
VALVE TOWER 1
5
1 SUPP
3 0V32 PE
2
5 SOLENOID VALVE 1
6A
POWER
230 VAC
Page 21
A
PPROVED 11/Jun/2020 11:47:53 GM
T
 9.2 DA40IMDA300IM, ELECTRICAL SCHEMATIC
EN
MODEL
POWER CORD
LENGTH
(m)
DA40IM 3.5 DA55IM 3.7 DA70IM
3.8
DA100M 4.2 DA150IM 4.4 DA200IM 4.2 DA250IM 4.4 DA300IM 4.4
VALVE EMS 2 = DA200IM-DA300IM
VALVE EMS 1 = DA40IM-DA150IM
SIGNAL
EMS 2(OPTION)
EMS 1(OPTION)
PURGE VALVE 2
PURGE VALVE 1
COMPRESSOR
INTERLOCK
3 POWER
1 4..20mA
DEW POINT (OPTION)
TRANSMITTER
DEW POINT
JZ20-J-ZK2
COMR1R2R3
+V0VI1I0 AN0
2
1 SUPP
3 0V
VALVE EMS 2
1 SUPP
3 0V
VALVE EMS 1
1 SUPP
3 0V
VALVE TOWER 2
1 SUPP
3 0V
VALVE TOWER 1
6
DEW POINT
EMS
TOWER 2
TOWER 1
INTERLOCK
DEW POINT
0VDC
0VDC
24VDC
24VDC
3
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
L
PE
N
0.75mm²
1.5mm²
1.5mm²
BLACK
4
1.5mm²
PE
L
DARK BLUE
BLUE/WHITE
WHITE
GN/YE
24VDC
PE
0V
N
+VADJ.
54321
1 POWER SUPPLY 230VAC, 24VDC 15W RS-15-24 1
2 PLC+HMI JZ20-J-ZK2 1
3 POWER CORD 3 X 1.5 FLEX-JZ 28039 SEE TABLE ON LEFT
4 TERMINAL BLOCK, 10x2,5mm² BM 9200 1
5 FUSE HOLDER 866-3454 1
6 SOLENOID VALVE 3
Pos. DESCRIPTION CODE QTY.
7 DEW POINT EA2-TX-100-HD 1
5
1
7
230 VAC
POWER
6A
RS-15-24
Page 22
EN
A
T
 10.1 DA5IM  DA25IM
PPROVED 11/Jun/2020 11:47:53 GM
10.0 FLOW DIAGRAM
AIR OUTLET
LEGEND:
1) PV-1: LEFT PRESSURE VESSEL
2) PV-2: RIGHT PRESSURE VESSEL
3) DPG-1: INLET DIFFERENTIAL PRESSURE INDICATOR
4) DPG-2: OUTLET DIFFERENTIAL PRESSURE INDICATOR
5) FLT-1: HIGH EFFICIENCY INLET PREFILTER
6) FLT-2: GENERAL PURPOSE AFTERFILTER
7) EXH-1: LEFT VESSEL PURGE MUFFLER
8) EXH-2: RIGHT VESSEL PURGE MUFFLER
9) FV-3B: LEFT & RIGHT VESSEL PURGE SOLENOID CONTROL VALVES 10
) FO-1: PURGE ORIFICE
11) CV-1 NON RETURN CHECK VALVE
: DRYING AIR FLOW : REGENERATING AIR FLOW : DRYER FLOW LINE
DPG
2
FO
PV
1
FLT
2
FO
1
CV
1
CV
1
1
PV
2
FV
AIR OUTLET
3B
EXH
1
DPG
1
S
EXH
2
FLT
1
Page 23
 10.2 DA40IMDA150IM
A
T
HCV
.
AIR OUTLET
DPT 1
1
DPG 2
PPROVED 11/Jun/2020 11:47:53 GM
FLT 2
FV 2A
: DRYING AIR FLOW : REGENERATING AIR FLOW : DRYER FLOW LINE : CONTROL FLOW / AIR LINE : OPTIONAL LINE
EN
AIR INLET
EXH 1
HCV 2
FV 4B
.
P
PV 1
GP 1
FV 1B
DPG 1
FO 1
PR 1
PV 2
FV 3B
GP 2
FV 1A
LEGEND:
1) PV-1: LEFT PRESSURE VESSEL
2) PV-2: RIGHT PRESSURE VESSEL
3) DPG-1: INLET DIFFERENTIAL PRESSURE INDICATOR
4) DPG-2: OUTLET DIFFERENTIAL PRESSURE INDICATOR
5) FLT-1: HIGH EFFICIENCY INLET PREFILTER
6) FLT-2: GENERAL PURPOSE AFTERFILTER
7) FV-1A: LEFT / RIGHT VESSEL INLET BALL VALVE
8) FV-2A: LEFT / RIGHT VESSEL OUTLET BALL VALVE
9) FV-1B: LEFT VESSEL PURGE NC PNEUMATIC VALVE
10) FV-2B: RIGHT VESSEL PURGE NC PNEUMATIC VALVE
11) EXH-1: LEFT VESSEL PURGE MUFFLER
12) EXH-2: RIGHT VESSEL PURGE MUFFLER
13) FV-3B: LEFT & RIGHT VESSEL PURGE SOLENOID CONTROL VALVES
14) FV-4B: EMS CONTROLING VALVE (OPTIONAL)
15) FO-1: PURGE ORIFICE
16) PR-1: PRESSURE REGULATOR
17) GP-1: LEFT VESSEL PRESSURE GAUGE
18) GP-2: RIGHT VESSEL PRESSURE GAUGE
19) HCV-1: EMS TRANSMITTER SHUT-OFF VALVE (OPTIONAL)
20) HCV-2: EMS BLEED VALVE (OPTIONAL)
21) DPT-1: DEW POINT TRANSMITTER (OPTIONAL)
FV 2B
EXH 2
FLT 1
Page 24
EN
A
T
 10.3 DA200IMDA300IM
PPROVED 11/Jun/2020 11:47:53 GM
DPG 2
FLT 2
.
.
.
PV 1
GP 1
P
AIR OUTLET
FV 2A
LEGEND:
1) PV-1: LEFT PRESSURE VESSEL FV 4B
FO 1
PR 1
PV 2
FV 3B
GP 2
FV 1A
2) PV-2: RIGHT PRESSURE VESSEL
3) DPG-1: INLET DIFFERENTIAL PRESSURE INDICATOR
4) DPG-2: OUTLET DIFFERENTIAL PRESSURE INDICATOR
5) FLT-1: HIGH EFFICIENCY INLET PREFILTER
6) FLT-2: GENERAL PURPOSE AFTERFILTER
7) FV-1A: LEFT / RIGHT VESSEL INLET BALL VALVE
8) FV-2A: LEFT / RIGHT VESSEL OUTLET BALL VALVE
9) FV-1B: LEFT VESSEL PURGE NC PNEUMATIC VALVE
10) FV-2B: RIGHT VESSEL PURGE NC PNEUMATIC VALVE
11) EXH-1: LEFT VESSEL PURGE MUFFLER
12) EXH-2: RIGHT VESSEL PURGE MUFFLER
13) FV-3B: LEFT & RIGHT VESSEL PURGE SOLENOID
CONTROL VALVES
14) FV-4B: EMS CONTROLING VALVE (OPTIONAL)
15) FO-1: PURGE ORIFICE
16) PR-1: PRESSURE REGULATOR
17) GP-1: LEFT VESSEL PRESSURE GAUGE
18) GP-2: RIGHT VESSEL PRESSURE GAUGE
19) HCV-1: EMS TRANSMITTER SHUT-OFF
VALVE (OPTIONAL)
20) HCV-2: EMS BLEED VALVE (OPTIONAL)
21) DPT-1: DEW POINT TRANSMITTER (OPTIONAL)
: DRYING AIR FLOW : REGENERATING AIR FLOW : DRYER FLOW LINE : CONTROL FLOW / AIR LINE : OPTIONAL LINE
FV 2B
HCV 1
DPT 1
HCV 2
FV 1B
EXH 1
AIR INLET
DPG 1
FLT 1
EXH 2
Page 25
A
PPROVED 11/Jun/2020 11:47:53 GM
T
11.0 ANGLE VALVE REBUILD PARTS
EN
VALVE PART
NUMBER
17933374
47681287001
*Seal Rebuild Kit includes: Seat Seal, Head Section Seal, Exterior Lip Seal
Mounting tool is required for normally-closed valves (P.O.N.C.) only. Tool is required to decompress springs and is required for safe dismantling of the valve.
Tool is needed to install Replacement Actuator, as well as to install Seal Rebuild kit.
Normally Closed Valve
VALVE DESCRIPTION
VALVE, ANGLE,
3/4” P.O.N.C.
VALVE, ANGLE,
1/2” P.O.N.C.
REPLACEMENT
ACTUATOR PART NUMBER
(CALLOUT 1)
17933402 17933394 17933411
47682457001 47682458001 17933411
SEAL REBUILD KIT*
PART NUMBER
(CALLOUT 2 )
MOUNTING TOOLS
Page 26
A
PPROVED 11/Jun/2020 11:47:53 GM
T
EN
12.0 ENGINEERING SPECIFICATIONS
 12.1 ENGINEERING DATA 40°C
DA5IM DA15IM DA25IM DA40IM DA55IM DA70IM
(-40°C) Inlet Capacity (m3/h) 5 1525405570
Purge (m3/h) 0,9 2,7 4,5 7,2 9,9 12,6 Desiccant per Tower (kg) 0,7 2,15 3 6,5 8,3 11 Electrical 230/1/50-60 230/1/50-60 230/1/50-60 230/1/50-60 230/1/50-60 230/1/50-60
Air In/Out Connections BSPP (Dryer)
Air In/Out Connections BSPT (Filter)
C -Width (mm) 238 238 238 475 475 475 B -Depth (mm) 212 212 212 365 365 365 A -Height (mm) 423 823 1073 968 1118 1318 Weight (kg) (Without Filters) 9 1621465562
3/8" 3/8" 3/8" 3/4" 3/4" 3/4"
3/8" 3/8" 3/8" 1/2" 3/4" 3/4"
DA100IM DA150IM DA200IM DA250IM DA300IM
(-40°C) Inlet Capacity (m3/h) 100 150 200 250 300
Purge (m Desiccant per Tower (kg) 15,5 18 30,8 36 36 Electrical 230/1/50-60 230/1/50-60 230/1/50-60 230/1/50-60 230/1/50-60
Air In/Out Connections BSPP (Dryer)
Air In/Out Connections BSPT (Filter)
C -Width (mm) 475 475 536 536 536 B -Depth (mm) 365 365 495 495 495 A -Height (mm) 1673 1873 1705 1905 1905 Weight (kg) (Without Filters) 82 86 160 180 180
3
/h) 18 27 36 45 54
1" 1" 1.5" 1.5" 1.5"
1" 1" 1.5" 1.5" 1.5"
NOTICE
Specication information above accurate at time of publication. Refer to equipment serial label for actual
Page 27
A
PPROVED 11/Jun/2020 11:47:53 GM
T
EN
 12.2 ENGINEERING DATA 70°C
DA40IM DA55IM DA70IM DA100IM DA150IM
(-70°C) Inlet Capacity (m
Purge (m
3
/h) 7,2 9,9 12,6 18 27 Desiccant per Tower (kg) 6,5 8,3 11 15,5 18 Electrical 230/1/50-60 230/1/50-60 230/1/50-60 230/1/50-60 230/1/50-60
Air In/Out Connections BSPP (Dryer)
Air In/Out Connections BSPT (Filter)
C -Width (mm) 475 475 475 475 475 B -Depth (mm) 365 365 365 365 365 A -Height (mm) 968 1118 1318 1673 1873 Weight (kg) (Without Filters) 46 55 62 82 86
(-70°C) Inlet Capacity (m
Purge (m3/h) 36 45 54 Desiccant per Tower (kg) 30,8 36 36 Electrical 230/1/50-60 230/1/50-60 230/1/50-60
Air In/Out Connections BSPP (Dryer)
Air In/Out Connections BSPT (Filter)
C -Width (mm) 536 536 536 B -Depth (mm) 495 495 495 A -Height (mm) 1705 1905 1905 Weight (kg) (Without Filters) 160 180 180
3
/h) 32 44 56 80 120
3/4" 3/4" 3/4" 1" 1"
1/2" 3/4" 3/4" 1" 1"
DA200IM DA250IM DA300IM
3
/h) 160 200 240
1.5" 1.5" 1.5"
1" 1.5" 1.5"
NOTICE
Specication information above accurate at time of publication. Refer to equipment serial label for actual specications for units.
Page 28
A
PPROVED 11/Jun/2020 11:47:53 GM
T
ingersollrandproducts.com
© 2020 Ingersoll Rand
Loading...