Infosec ICUE2LCD1500, ICUE2LCD2000, ICUE2LCD600 Datasheet

Page 1
From 600 to 2000 VA
High-performance protection
The On Line Performance technology controlled by microprocessor makes the E2 LCD an ideal protection solution thanks to its perfect sinusoidal current and fully protected outlput. It also provides effective protection for particularly sensitive loads such as servers or even video surveillance, telephone switchboards, VOIP etc.
Smart features
The built-in charger takes only 4 hours to reach maximum backup capacity. When the UPS is not powered up, the cold startup function enables emergency starting of connected hardware. When power is restored the UPS automatically starts up again and does not require any operator input.
Company networks; Service industries
The range of E2 LCD was designed to offer your networks and professional IT applications reliable and high-performance protection against power supply problems and dangerous electrical disturbances.
E2 LCD 600 & 800
Online Performance
Technology
4 to 6 protected
UPS outlets
Energy saving features
The battery automatically recharges when there is mains power and the UPS is OFF. This feature, available for the whole range, ensures that when connected devices are not in use and the UPS is OFF, the battery continues recharging. Real energy savings are achieved thanks to its advanced battery charger which enables the batteries to charge twice as fast as normal.
Designed for ease of use
A single On/Off switch
LCD screen and audible alarms indicating UPS status
E2 LCD 1000
E2 LCD 1500 & 2000
USB
communication port
(USB cable included)
Up to 60 min. backup time*
*Depending on the model and the
connected load
Page 2
CONNECTION
5 6
1. Integrated power cable
2. Power input
3. IEC protected outlets
4. Input fuse
5. RJ11/45 connectors
6. USB port
7. Circuit breaker
8. RS232 port
3
E2 LCD 600 & 800 VA E2 LCD 1000 VA E2 LCD 1500 & 2000 VA
TECHNICAL CHARACTERISTICS
E2 LCD 600 E2 LCD 800 E2 LCD 1000 E2 LCD 1500 E2 LCD 2000
GENERAL SPECIFICATIONS
Technology
Power
Power factor
IEC outputs with backup time
Tel./ADSL line protection
600 VA 800 VA 1000 VA 1500 VA 2000 VA
0.6 0.6 0.7 0.7 0.7
PROTECTION & FILTERING
Output form
Protection
Input protection
Overvoltage protection
Circuit breaker Fuse
Phase-Neutral protection: 1 kV; Phase-Ground & Neutral-Ground protection: 2 kV
PHYSICAL CHARACTERISTICS
Dimensions - LxWxH (mm)
Net weight (kg)
145 x 100 x 330 160 x 146 x 350 205 x 146 x 397
5.2 6 9 11,6 12,25
INPUT TECHNICAL CHARACTERISTICS
Voltage
Voltage range
Frequency
OUTPUT TECHNICAL CHARACTERISTICS
Voltage
Automatic voltage regulation
Frequency
BATTERY
Battery charger
Cold startup (no mains)
Battery type & number
Recharging time
Backup time
12 V/7 Ah x 1 12 V/9 Ah x 1 12 V/7 Ah x 2 12 V/9 Ah x 2 12 V/10 Ah x 2
4-6 hours at 90% after total discharge 10 hours at 90% after total discharge
DISPLAY
LCD screen
Mains power supply mode, battery mode, output charge level, battery level, input voltage,
AUDIBLE ALARM
Battery mode
Low battery mode
Overload
Battery replacement
Fault
COMMUNICATION
USB communication port
RS232 communication port
Communicationsoftware
InfoPower (supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, 8, Linux, Unix et MAC)
ENVIRONMENT
Ideal environment
Noise level
< 40 dB < 45 dB < 55 dB
NORMS
Standard
Electromagnetic compatibility
Low voltage safety
EN 62040-2 / IEC 61000-4-2 / IEC 61000-4-3 / IEC 61000-4-4 / IEC 61000-4-5 / IEC 61000-2-2
SALES INFO
Warranty
Gencods
* Low voltage (110V) and High voltage (230V) are dierent products
3700085 65348 7 3700085 65349 4 3700085 65350 0 3700085 65351 7 3700085 65352 4
On Line Performance controlled by microprocessor
4 6
Discharge / overload / overvoltage + Tel./ADSL line
Automatic battery charging upon connection to the mains
From 12 to 60 min. depending on the connected load
output voltage, overload, fault and battery low
- Yes
0-40°C, 0-90% relative humidity (without condensation)
6
5
1
7
3
3
RJ11/45 (1-IN/1-OUT)
Pure sinusoidal
[110-120 VAC] or [220/230/240 VAC]*
[81-145 VAC] or [162-290 VAC]*
50/60 Hz (auto-detection)
[110-120 VAC] or [220/230/240 VAC]*
± 10%
50 or 60 Hz ± 1Hz
yes
Sounding every 10 seconds
Sounding every second
Sounding every half second
Sounding every 2 seconds
Continuous sounding
Yes
CE RoHS
EN 62040-1-1 / IEC 60950-1
2 years
8
5
2
4
2 4
6
From 600 to 2000 VA
3
Communications solutions and remote management
USB & RS232 communication ports
Software :
• Simple user interface
• UPS startup and shutdown programming
• Data and events record enabling daily maintenance
• E-mail messaging to manage UPS status at all times via the local network
• Free download from the website
Packaging content
E2 LCD 600 & 800:
• 1 integrated input cable
• 2 IEC output cables
• 1 RJ11 cable
• 1 USB cable
• 1 user manual
E2 LCD 1000:
• 2 IEC output cables
• 1 RJ11 cable
• 1 USB cable
• 1 user manual
E2 LCD 1500 & 2000:
• 3 IEC output cables
• 1 RJ11 cable
• 1 USB cable
• 1 user manual
Warranty
2-year warranty against manufacturing defects under normal conditions and compliance with precautionary measures.
Warranty to be taken out on our website within 10 days of purchase.
Infosec Communication
4, rue de la Rigotière
44700 ORVAULT - FRANCE
Sales contact
Tél: 02 40 76 11 77
sales@infosec.fr
©2016 Infosec Communication, all rights reserved. Infosec UPS System is a trademarks or registered trademark of Infosec Communication. All other trademarks or registered trademarks belong to their respective owners. Photos are not binding. Specifications are subject to change without prior notice. Backup time is only a guide: actual duration may vary depending on the temperature, battery condition and peripherals added. UPS are part of electronic and electric equipments category. At the end of their lives, they have to be collected separately. 02 16 AA XX 111 08
Loading...