rated 100, 200, & 230 amps , single phase, 240 V ac
Manual
DANGER is used in this manual
to warn of risk of electrical shock
from high voltages capable of
causing shock, burns, or death.
!
WARNING is used in this
manual to warn of possible
personal injury.
!
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
Series 165 Automatic Transfer Switches
for automatic 2–wire start generators
ASCO Series 165 Automatic Transfer Switches are Listed
under the Underwriter’s Laboratories Standard for Transfer
Switch Equipment, UL–1008. They are intended for use
only in optional standby systems in accordance with the
National Electrical Code, NEC/NFPA 70, Article 702. This
ATS is for use with 2–wire automatic start generators only.
Refer to Application Information 381339–219 to confirm
that you have selected the appropriate product for the
intended installation.
Rating Label
Each Automatic Transf er Switch (ATS) has rating labels to
define the loads and fault current withstand/ closi ng ratings.
Refer to those label on the Transfer Switch for specific values.
!
Installation should be performed by a licensed electrician
and in accordance with the National Electrical Code (NEC)
and all local electrical code requirements. Read and
understand all instructions before installing, servicing, or
operating. Failuretodosocouldresultinserious
personal injuries or property damage.
INJURY or SWITCH DAMAGE
Do not exceed the rating label
values; it can cause personal in-
jury or serious switch damage.
Nameplate
TheT ransferSwitch
nameplate includes data
for each specific ASCO
Series 165 ATS. Use the
switch only within the
limitsshownonthis
nameplate.Atypical
Catalog Number is also
shown below with its
elements explained:
Catalog number
product
designation
neutral
A=solidneutral
165A2200F3C
poles
2=2lines
ampere rating
100, 200, or 230 amps
Series
165
Automatic Transfer Switch
for use on Standby Systems
Cat No 165A2200F3C
Ser No 123456
200 A BOM 999999
240 V 60 Hz
enclosure
C=Type1
F=Type3R
control group code
3 = automatic
voltage code
F = 240 V AC
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
Load transfer to alternate (generator) source15 sec....
Load retransfer to preferred (utility) source5 min.......
Generator cooldown period (after load retransfer) 1 min.
Automatic Generator Exerciser
Repeat timeevery 14 days......................
Duration20 minutes...........................
INTRODUCTION
INTRODUCTION
ASCO Series 165 Automatic Transfer Switches are Listed
under the Underwriter’s Laboratories Standard for Transfer
Switch Equipment, UL–1008. They are intended for use only
in optionalstandby systems in accordance with the National
Electrical Code, NEC/NFPA 70, Article 702.
This automatic transfer switch is intended for standby power
applications in residential or light commercial use only .
!
The Series 165 Automatic Transfer
Switch is not for emergency or
life–support systems.
This product is not intended for emergency or
life–support systems.
If you have more stringent application requirements contact
ASCO for other products suitable for critical applications.
The automatic transfer switchhelps provide safe
connection of the alternate source (generator) to the
electrical load after disconnecting the preferred source
(utility). It contains a double–throw, electromechanical
switching device for inherent isolation of the preferred and
alternate sources. This isolation prevents the danger of
connecting the utility to the generator which could cause
damage or personal injury. The automatic transfer switch’s
digital controller provides continuous monitoring of both
power sources and a start/stop signal to the generator.
3
INSTALLATION
Installation of the ASCO Series 165 automatic transfer
switch must be performed by a licensed electrician. It must
be installed according to the National Electrical Code and
all local electrical code requirements. Refer to the
installation drawing and wiring diagram.
!
MALFUNCTION or SHORTENED LIFE
Protect the unit from construction grit and metal
chips to prevent malfunction or shortened life.
Remove the enclosure cover and inspect the unit for ship–
ping damage. If damage is evident do not
install the unit. Type
1 enclosure is for indoor use only (refer to local codes for Type
4 use). Mount the automatic transfer switch vertically to a rigid
supporting structure. Level all mounting points with flat
washers behind the holes to avoid distortion of enclosure.
ELECTRICAL LINE CONNECTIONS
Installation wiring must be performed by a licensed
electrician in accordance with the National Electrical Code
(NEC) and all local electrical code requirements.
The automatic transfer switch must be protected by suitably
sized circuit breakers feeding the preferred and alternate
source terminals. The ratings of the circuit breakers must be
based on the requirements of the National Electrical Code
for its nameplate ampere and short circuit withstand ratings.
See the wiring diagram provided with the unit.
ELECTROCUTION HAZARD
Turn off utility power and turn off the
generator to prevent electrocution
when wiring the transfer switch.
!
CABLE L OOSENING DUE TO SHORT–CIRCUIT. Install
3 cable spacers 1½ in. from termi n al lugs to prevent
cables from loosenin g in a short–circuit condition.
CABLE CONNECTIONS (see wiring diagram)
Prepare the wires for connection as follows: strip the
insulation; avoid nicking or ringing the conductors when
stripping thecable.Remove surface oxides from
conductors by cleaning with a wire brush. Apply electrical
joint compound and wipe away excess. Insert prepared
cable into lug and tighten the lug to the torque specified on
the rating label on the transfer switch.
Connect the preferred source (utility) line 1 and 2 wires to
the terminal lugs marked L1 and L5 at the bottom. Connect
the alternate source (generator) line 1 and 2 wires to the
terminal lugs marked L2 and L6 at the upper middle.
Connect the load line 1 and 2 wires to the terminal lugs
marked L3 and L7 at the top of the transfer switch. Neutral
and ground terminals are provided.
GENERATOR STARTING CONTACTS
Before wiring the generator starting contacts refer to the
generator manufacturer’s installation manual for requirements. Make all connections to the controller with the generator battery disconnected. Verify that the ignition switch
is in the OFF position. Connect the generator starting contacts to the appropriate terminals on terminal block TB7 on
the Controller (CP). See the wiring diagram provided with
the unit.
For wiring convenience terminal block TB7 has a removable
plug. Reconnect the plug with terminal screws facing inward.
CABLE SPACERS (200 and 230 amp. units)
Three cable spacers are included with 200 and 230 ampere
size transfer switches. Run the power cables through the
cable spacers as shown here and position the cable
spacers approximately 1½ inches from the terminal lugs.
Use copper cables for 200 and 230 amp. transfer switches.
L7
L3
load
L2
L6
L1
L5
preferred source (utility)
4
cable spacers
1 ½ inch approximate
from terminal lugs
alternate source (generator)
200 & 230 amp. transfer
switches require cable
spacers and copper cables
cable spacer
!
CONTROLLER DAMAGE. Observe polarity when
connecting the generator battery to the controller.
Refer to wiring diagram. Be sure to reinstall the
TB7 block with terminal screws facing inward.
removable
terminal
block TB7
Be sure to
reinstall
with
terminal
digital
controller
screws
facing
inward.
FUNCTIONAL TEST (after installation)
After installing the Series 165 automatic transfer switch
perform the following three–part functional test.
1–MANUALOPERATION
ELECTROCUTION – FLASH HAZARD
Do not manually operate the transfer
switch until utility and generator are
disconnected; open circuit breakers.
1. Put both the preferred source circuit breaker and the
alternate source circuit breaker feeding the automatic
transfer switch in the OFF position. Verify that ALLPOWER IS OFF ! (Seepage2forhandlelocation.)
2. Grasp the maintenance handle and turn it quickly with
your thumb and fingers to manually operate the transfer
switch. The switch should operate smoothly without
binding. If it does not, check for shipping damage or
construction debris.
maintenance handle
With ALL POWER OFF
grasp maintenance
handle and turn it
quickly with your
thumb and fingers.
weight marked P (preferred) and A (alternate)
3. After checking the manual operation operate the handle
again quickly to return the transfer switch to the preferred
position (letter P on the round weight facing you).
2–VOLTAGECHECKS
The Series 165 automatic transfer s w itch is rated for
nominal 240 V ac at 60 Hz (as stated on the nameplate).
Verify that both your preferred and alternate sources are
also 240 V ac nominal, 60 Hz. See the wiring diagram.
3 – ELECTRICAL OPERATION
This procedure checks t he electrical operation of the
automatic transfer switch. If the actual operation does not
follow this procedure, consult the Troubleshooting section.
!
PERSONAL INJURY HAZARD
Install front cover before operation.
An electrical system fault could
cause a flash and cause injury.
1. Install the enclosure cover and tighten the screws.
2.Verify that the generator battery is connected and that the
generator’s starting control s are set for automatic.
source acceptable lights
test button
transfer switch on utility
(preferred source) light
3.T urn on the preferred source (utility) circuit breaker.
4.T urn on the alternate source (generator) circuit breaker.
5.Verify that UTILITY (preferred source) acceptable light is on.
6. Verify that the TRANSFER SWITCH on utility (preferred
source) light is on.
7. This step will start the generator. Press and hold
Push to Test button until the GENERATOR (alternate
source) acceptable light comes on and stays on.Then
release the button.
This light indicates that the generator is running and
that its output voltage and frequency are acceptable.
Under typical conditions, the light should come on after
about 5 to 10 seconds. If the generator is running and
fails to produce the proper voltage and frequency after
60 seconds then a malfunction has occurred (consult
the Troubleshooting section).
8. About 15 seconds after the GENERATOR (alternate
source) acceptable light comes on, the automatic
transfer switch transfers the load from the utility to the
generator. The TRANSFER SWITCH on generator
(alternate source) light comes on.
9. The transfer switch stays connected to the generator for
5 minutes. Then the load is transferred back to the utility.
To bypass time delay, press and release
button again.
10. After load retransfer to utility, the generator runs 1 minute
(without load), then shuts down. The GENERATO R
acceptable light goes off indicating that generator is off.
This completes the Functional T est. Proceed to next page.
transfer switch on generator
(alternate source) light
the
the Push to Te st
5
OPERATION
utility (preferred source)
acceptable light
generator (alternate source)
acceptable light
exerciser
light
transfer switch on utility
(preferred source) light
transfer switch on generator
(alternate source) light
INDICATOR LIGHTS
On the front control display are five lights that indicate the
status of the sources and the automatic transfer switch.
Utility (preferred source) acceptable
❍
(light at the top left of the display)
● When on, this light indicates that the utility voltage is
acceptable for connection to the load.
Generator (alternate source) acceptable
❍
(light at the top right of the display)
● When on, this light indicates that the generator voltage
and frequency are acceptable for connection to the load.
❍
Transfer Sw itch on utility (preferred so u r ce)
(light at the center left of display)
● When on, this light indicates that the load is connected to
the utility (preferred source).
T ransfer Switch on generator (alt. source)
❍
(light at the center right of display)
● When on, this light indicates that the load is connected to
the generator (alternate source).
Automatic Generator Exerciser
❍
(light above button at the right of display)
● When the utility is acceptable and the load is on the utility,
this light flashes the number of days until the next exercise
period. When it is off, no exerciser period is set. The light is
also off any time the generator is running.
PUSH BUTTONS
On the front control display are two push buttons that
control the operation of t he generator and the automatic
transfer switch.
● Push to Test (buttonontheleftside)
● This button is used t o test the system. See the Manual
Generator Testing sectiononthenextpage.
● This button can be used to cancel any active
Press and release
● This button can be used to clear displayed error codes.
See Troubleshooting section, Problem 8.
the button to bypass the time delay.
time delay.
● Automatic Generator Exerciser (right button)
● This button is used to set the a utomatic generator
exerciser. See the next page.
UTILITY FAILURE
The load is normally connected to the preferred source
(utility) if that source is acceptable. If the preferred source
(utility) fails, the following sequence occurs:
1. The UTILITY source acceptable light goes off.
2. The automatic transfer switch waits three seconds to prevent nuisance starting of the generator from momentary
dips of the utility voltage. If the utility is restored during the
three seconds, the UTILITY source acceptable light
comes on and no further action is taken.
3. If the utili ty remains unacceptable for three seconds, the
automatic transfer switch cranks and starts the generator.
4. Once the generator starts, the automatic transfer switch
waits until the generator voltage and frequency are
acceptable. Then the GENERATOR source acceptable
light comes on.
5.When the generator is acceptable, the automatic transfer
switch waits 15 seconds to allow the generator to warm up.
Then it transfers the load to the generator. The TRANSFERSWITCH on generator (alternate source) light comes on.
6. The automatic transfer switch waits for the utility source to
be restored. When the utility again becomes acceptable
the UTILITY source acceptable light comes on.
7. The automatic transfer switch then waits 5 minutes to
allow the utility to stabilize. Then it retransfers the load
back to the utility. The TRANSFER SWITCH on utility
(preferred source) light comes on.
8. After load retransfer the generator will continue to run
unloaded for one minute for engine cooldown. Then it is
stopped. The GENERATOR acceptable light goes off.
6
AUTOMA TIC GENERATOR EXERCISER
The automatic generator exerciser automatically exercises
the generator for 20 minutes once every 14 days.
TO SET EXERCISER
Press and release the Automatic Generator Exerciser button. After about 8 seconds the exerciser light flashes 14 times
to indicate that the exerciser has been set. The number of
flashes indicates the number of days until the next exercise period (at approximately
TO DISABLE EXERCISER
Press a nd hold the Automatic Generator Exerciser button
until the light above the button goes off (light flashes t hen
goes off). The exerciser is now disabled and the light is off.
TO ENABLE EXERCISER
Press a nd hold the Automatic Generator Exerciser button
until the light goes off (light flashes then goes off). Exerciser
is now enabled. After about 8 seconds exerciser light flashes 14
times to indicate that the exerciser has been re–enabled.
Note: With a total power failure (utility failure and generator
fails to start) the exerciser must be reset after power is
restored.
thesametimethebuttonwaspressed).
automatic generator exerciser light
set exerciser button
MANUAL GENERATOR TESTING
GENERATOR TEST WITH LOAD TRANSFER
During this test a utility failure is simulated. The generator
starts and the load transfers to the generator. Then the load
retransfers back to the utility and generator stops.
1. Press and hold the
GENERATOR acceptable light comes on and stays on
(the generator cranks and starts).
2.The automatic transfer switch waits 15 seconds to allow the
generator to warm up. Then it transfers the load to the
generator . The TRANSFERSWITCHongenerator
(alternatesource)l ight
comes on.
3.After 5 minutes the auto–
matic transfer switch re–
transfers the load back to
the utility. To bypass the
time delay, press and
release the Push to Test
button again. The TRANS–FER SWITCH on utility
(preferredsource)light
comes on.
4. Afterloadretransferthe
generator will continue to
run unloaded for one minute for engine cooldown.
Then it is stopped. The
GENERA TOR acceptable
light goes off.
Push to Test button until the
source acceptable lights
load transfer
test button
transfer switch on utility
(preferred source) light
GENERA TOR TEST WITHOUT LOA D TRANSFER
During the test the generator cranks and starts and the
GENERATOR light comes on (if it is acceptable). After
running for 20 minutes it stops. Throughout the test the load
remains connected to the utility (the automatic transfer
switch does not
1. Press and release
The generator cranks and starts, and the GENERATO R
acceptable light comes on and stays on.
transfer switch on generator
(alternate source) light
transfer the load to the generator).
(do not hold) the Push to Test button.
2. The generator runs for 20
minutes. The automatic
transfer switch does not
transfer the load to the
generator. The TRANS-FER SWITCH on utility
(preferred source) light
stays on.
3. To bypass the time delay or
cancel the test, press and
release the Push to Te st
button again.
4. The generator stops and
the GENERATOR acceptable light goes off.
7
TROUBLESHOOTING
This troubleshooting guide describes some of the simple
causes of problems with the installation of the automatic
transfer switch. Tr ou ble shooting beyond the scope of thisguide should not be attempted by the installer. Alicensed
electrician must perform all internal troubleshooting. ASCO
can be contacted at 800–937–ASCO or www.asco.com.
ELECTROCUTION – FLASH HAZARD
Do not work on the transfer switch
until both the utility and generator are
off. Turn OFF both circu i t breakers .
Problem 1
The UTILITY acceptable light does not come on when utility
power is connected to the automatic transfer switch.
● Verify that the utility feed is 240 V ac nominal and 60 Hz.
● Verify that the utility feed is wired to the terminal lugs on
the bottom of the transfer switch marked L1 and L5.
● Verify that the utility feed is connected and t hat its circuit
breaker is ON.
● With ALL POWER OFF, verify that the transfer switch
harness is connected properly to the controller (plug at
the bottom).
Problem 2
Power is connected (UTILITY acceptable light and/or
GENERATORacceptable lightsareon) butboth
TRANSFER SWITCH position lights are off.
● With ALL POWER OFF, verify that the transfer switch
harness is connected properly to the controller (plug at
the bottom).
Problem 3
Generator does not crank when the utility source fails or
when the Push to Test button is pressed.
● Verify that the generator starting controls are set for
automatic operation.
● Verify engine start low voltage wiring between controller
terminal block TB7 (plug on the left) and the generator .
Check that TB7 plug is properly seated in TB7 receptacle.
● Verify that the generator battery is connected and that the
battery voltage meets the generator manufacturer’s
recommendation.
● Verify that the correct contact (normally open or normally
closed) is being utilized (see the generator manual).
Problem 4
Generator cranks but does not start when the utility source
fails or when the Push to Test button is pressed.
● Verify engine start low voltage wiring between controller
terminal block TB7 (plug on the left) and the generator .
Check that TB7 plug is properly seated in TB7 receptacle.
● Verify proper generator operation (see generator manual).
Problem 5
The automatic transfer switch does not transfer the load to
the generator (TRANSFER SWITCH on generator light does
not come on).
● Verify that the GENERATOR source acceptable light is on.
The transfer switch will not retransfer the load to the generator until the generator output is acceptable. If the light is off
verify that the circuit breaker for the generator feed is ON.
● Wait 15 seconds. There is a 15 second delay after the
generator output becomes acceptable to permit the
generator to warm up.
● If the GENERATOR source acceptable light still does not
come on, see Problems 3 and 4.
Problem 6
The automatic transfer switch does not transfer the load
back to the utility (TRANSFER SWITCH on utility light does
not come on).
● Verify that the UTILITY source acceptable light is on. The
transfer switch will not retransfer the load to the utility until
the utility source is acceptable and the light is on. If light is
off, verify that the circuit breaker from the utility feed is ON.
● Wait 5 minutes. There is a 5 minute delay on retransfer to
the util ity.
Problem 7
The GENERATOR source acceptable light does not go off
after the automatic transfer switch retransfers the load back
to the utility.
● Wait 1 minute. After load retransfer to the utility, there is a
1 minute delay for generator cooldown before shut down.
● Verify proper operation of the generator (see the
generator manual).
Problem 8
Both TRANSFER SWITCH position lights are flashing (this
indicates an error condition). *
● Count the number of times the Automatic Generator
Exercise r light flashes (repeats after pause). This number
is the error code.
● Error codes:
2 Generator failed to start.See Problems 3 and 4.
3 Generator failed after starting. See generator manual.
4 Generator over frequency.See generator manual.
5 Transfer Switch did not transfer the load
to the generator . Service required.
6 Transfer Switch did not transfer the load
to the utility.Service required.
7 Controller error.Service required.
● T o clear error code, press and release
* NOTE: These lights will flash only when controller power
is available from either of the two power sources.
Push to T e st button.
8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.