InFocus 165 User Manual

Owner’s
rated 100, 200, & 230 amps , single phase, 240 V ac
Manual
DANGER is used in this manual
to warn of risk of electrical shock
from high voltages capable of
causing shock, burns, or death.
!
WARNING is used in this
manual to warn of possible
personal injury.
!
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
Series 165 Automatic Transfer Switches
for automatic 2–wire start generators
ASCO Series 165 Automatic Transfer Switches are Listed under the Underwriter’s Laboratories Standard for Transfer Switch Equipment, UL–1008. They are intended for use only in optional standby systems in accordance with the National Electrical Code, NEC/NFPA 70, Article 702. This ATS is for use with 2–wire automatic start generators only.
Refer to Application Information 381339–219 to confirm that you have selected the appropriate product for the intended installation.
Rating Label
Each Automatic Transf er Switch (ATS) has rating labels to define the loads and fault current withstand/ closi ng ratings. Refer to those label on the Transfer Switch for specific values.
!
Installation should be performed by a licensed electrician and in accordance with the National Electrical Code (NEC) and all local electrical code requirements. Read and understand all instructions before installing, servicing, or operating. Failuretodosocouldresultinserious
personal injuries or property damage.
INJURY or SWITCH DAMAGE
Do not exceed the rating label
values; it can cause personal in-
jury or serious switch damage.
Nameplate
The T ransfer Switch nameplate includes data for each specific ASCO Series 165 ATS. Use the switch only within the limits shown on this nameplate. A typical Catalog Number is also shown below with its elements explained:
Catalog number
product designation
neutral
A=solidneutral
165 A 2 200 F 3 C
poles
2=2lines
ampere rating
100, 200, or 230 amps
Series
165
Automatic Transfer Switch for use on Standby Systems Cat No 165A2200F3C Ser No 123456 200 A BOM 999999 240 V 60 Hz
enclosure C=Type1 F=Type3R
control group code
3 = automatic
voltage code
F = 240 V AC
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA 1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
TABLE OF CONTENTS
Specifications 3.....................................
Introduction 3......................................
Installation 4.......................................
Electrical Line Connections 4.........................
Cable Spacers (200 amp. unit) 4......................
Cable Connections 4................................
Generator Starting Contacts 4........................
Functional Test (after installation) 5....................
Operation 6........................................
load power
connections
alternate source
(generator)
power
connections
neutral
terminal
Indicator Lights 6...................................
Push Buttons 6.....................................
Utility Failure 6......................................
Automatic Generator Exerciser 7......................
Manual Generator Testing 7..........................
Generator Test with Load Transfer 7...................
Generator Test without Load Transfer 7................
Troubleshooting 8...................................
digital controller
with control display
maintenance
handle next to
wheel weight
(see DANGER
under Manual
Operation)
ground
terminal
transfer switch
cable spacers
preferred
source
(utility) power
connections
Series 165 Automatic Transfer Switch in Type 1 enclosure (cover removed)
2
SPECIFICATIONS
ENCLOSED AUTOMATIC TRANSFER SWITCH
Enclosure Size
Type 1 24” H x 14¼” W x 8” D..................
(610 mm H x 362 mm W x 203 mm D)
Type 3R 25” H x 14¾” W x 8½” D...............
(635 mm H x 375 mm W x 216 mm D)
Weight Type 1 enclosure 67 lb......................
Type 3 R e n c l o s ure 82 l b.....................
Tem pe r a t u r e
Operating –4˚ F to +122˚ F(–20˚ Cto+50˚ C)...
Storage –67˚ F to +149˚ F(–55˚ Cto+65˚ C)....
TRANSFER SWITCH
Poles 2............................................
Voltage (nominal) 220–240 V ac single phase..........
Frequency (nominal) 60 Hz...........................
Current (depending upon the unit) 100, 200, or 230 a mps
Withstand / Close–On Current 10,000 amps............
RMS Symmetrical amps 240 V ac max.
for any circuit breaker, manufacturer, or Type
per National Electrical Code, NEC/NFPA 70
100 amp. Transfer Switch power terminals accept wire sizes
one #14 to 4/0 AWG AL or CU
200 amp. Transfer Switch power terminals accept wire sizes
one #14 to 4/0 AWG CU (copper only)
230 amp. Transfer Switch power terminals accept wire sizes
one #14 to 4/0 AWG CU (copper only)
CONTROLLER
Voltage (nominal) 220–240 V ac......................
Pickup (source acceptable) 204 V ac............
Dropout (source unacceptable) 180 V ac........
Frequency (nominal) alternate (generator) source 60 Hz.
Pickup (source acceptable) 57 Hz...............
Dropout (source unacceptable) 54 Hz...........
Generator control contacts
Start / Stop spdt 5 A max / 300 mA min at 30 V dc max.
terminals accept #22 to #14 AWG
stranded copper wire per terminal
Time Delays
Ignore preferred (utility) source outages 3 sec.........
Ignore alternate (generator) source outages 15 sec.....
Load transfer to alternate (generator) source 15 sec....
Load retransfer to preferred (utility) source 5 min.......
Generator cooldown period (after load retransfer) 1 min.
Automatic Generator Exerciser
Repeat time every 14 days......................
Duration 20 minutes...........................
INTRODUCTION
INTRODUCTION
ASCO Series 165 Automatic Transfer Switches are Listed under the Underwriter’s Laboratories Standard for Transfer Switch Equipment, UL–1008. They are intended for use only in optionalstandby systems in accordance with the National Electrical Code, NEC/NFPA 70, Article 702.
This automatic transfer switch is intended for standby power applications in residential or light commercial use only .
!
The Series 165 Automatic Transfer
Switch is not for emergency or
life–support systems.
This product is not intended for emergency or life–support systems.
If you have more stringent application requirements contact ASCO for other products suitable for critical applications.
The automatic transfer switch helps provide safe connection of the alternate source (generator) to the electrical load after disconnecting the preferred source (utility). It contains a double–throw, electromechanical switching device for inherent isolation of the preferred and alternate sources. This isolation prevents the danger of connecting the utility to the generator which could cause damage or personal injury. The automatic transfer switch’s digital controller provides continuous monitoring of both power sources and a start/stop signal to the generator.
3
INSTALLATION
Installation of the ASCO Series 165 automatic transfer switch must be performed by a licensed electrician. It must be installed according to the National Electrical Code and all local electrical code requirements. Refer to the installation drawing and wiring diagram.
!
MALFUNCTION or SHORTENED LIFE
Protect the unit from construction grit and metal
chips to prevent malfunction or shortened life.
Remove the enclosure cover and inspect the unit for ship– ping damage. If damage is evident do not
install the unit. Type 1 enclosure is for indoor use only (refer to local codes for Type 4 use). Mount the automatic transfer switch vertically to a rigid supporting structure. Level all mounting points with flat washers behind the holes to avoid distortion of enclosure.
ELECTRICAL LINE CONNECTIONS
Installation wiring must be performed by a licensed electrician in accordance with the National Electrical Code (NEC) and all local electrical code requirements.
The automatic transfer switch must be protected by suitably sized circuit breakers feeding the preferred and alternate source terminals. The ratings of the circuit breakers must be based on the requirements of the National Electrical Code for its nameplate ampere and short circuit withstand ratings. See the wiring diagram provided with the unit.
ELECTROCUTION HAZARD
Turn off utility power and turn off the
generator to prevent electrocution
when wiring the transfer switch.
!
CABLE L OOSENING DUE TO SHORT–CIRCUIT. Install
3 cable spacers 1½ in. from termi n al lugs to prevent
cables from loosenin g in a short–circuit condition.
CABLE CONNECTIONS (see wiring diagram)
Prepare the wires for connection as follows: strip the insulation; avoid nicking or ringing the conductors when stripping the cable. Remove surface oxides from conductors by cleaning with a wire brush. Apply electrical joint compound and wipe away excess. Insert prepared cable into lug and tighten the lug to the torque specified on the rating label on the transfer switch.
Connect the preferred source (utility) line 1 and 2 wires to the terminal lugs marked L1 and L5 at the bottom. Connect the alternate source (generator) line 1 and 2 wires to the terminal lugs marked L2 and L6 at the upper middle. Connect the load line 1 and 2 wires to the terminal lugs marked L3 and L7 at the top of the transfer switch. Neutral and ground terminals are provided.
GENERATOR STARTING CONTACTS
Before wiring the generator starting contacts refer to the generator manufacturer’s installation manual for require­ments. Make all connections to the controller with the gen­erator battery disconnected. Verify that the ignition switch is in the OFF position. Connect the generator starting con­tacts to the appropriate terminals on terminal block TB7 on the Controller (CP). See the wiring diagram provided with the unit.
For wiring convenience terminal block TB7 has a removable plug. Reconnect the plug with terminal screws facing inward.
CABLE SPACERS (200 and 230 amp. units)
Three cable spacers are included with 200 and 230 ampere size transfer switches. Run the power cables through the cable spacers as shown here and position the cable spacers approximately 1½ inches from the terminal lugs. Use copper cables for 200 and 230 amp. transfer switches.
L7
L3
load
L2
L6
L1
L5
preferred source (utility)
4
cable spacers
1 ½ inch approximate
from terminal lugs
alternate source (generator)
200 & 230 amp. transfer
switches require cable
spacers and copper cables
cable spacer
!
CONTROLLER DAMAGE. Observe polarity when
connecting the generator battery to the controller.
Refer to wiring diagram. Be sure to reinstall the
TB7 block with terminal screws facing inward.
removable
terminal
block TB7
Be sure to
reinstall
with
terminal
digital
controller
screws
facing
inward.
FUNCTIONAL TEST (after installation)
After installing the Series 165 automatic transfer switch perform the following three–part functional test.
1–MANUALOPERATION
ELECTROCUTION – FLASH HAZARD
Do not manually operate the transfer
switch until utility and generator are
disconnected; open circuit breakers.
1. Put both the preferred source circuit breaker and the alternate source circuit breaker feeding the automatic transfer switch in the OFF position. Verify that ALL POWER IS OFF ! (Seepage2forhandlelocation.)
2. Grasp the maintenance handle and turn it quickly with your thumb and fingers to manually operate the transfer switch. The switch should operate smoothly without binding. If it does not, check for shipping damage or construction debris.
maintenance handle
With ALL POWER OFF grasp maintenance handle and turn it quickly with your thumb and fingers.
weight marked P (preferred) and A (alternate)
3. After checking the manual operation operate the handle again quickly to return the transfer switch to the preferred position (letter P on the round weight facing you).
2–VOLTAGECHECKS
The Series 165 automatic transfer s w itch is rated for nominal 240 V ac at 60 Hz (as stated on the nameplate). Verify that both your preferred and alternate sources are also 240 V ac nominal, 60 Hz. See the wiring diagram.
3 – ELECTRICAL OPERATION
This procedure checks t he electrical operation of the automatic transfer switch. If the actual operation does not follow this procedure, consult the Troubleshooting section.
!
PERSONAL INJURY HAZARD
Install front cover before operation.
An electrical system fault could
cause a flash and cause injury.
1. Install the enclosure cover and tighten the screws.
2. Verify that the generator battery is connected and that the generator’s starting control s are set for automatic.
source acceptable lights
test button
transfer switch on utility (preferred source) light
3. T urn on the preferred source (utility) circuit breaker.
4. T urn on the alternate source (generator) circuit breaker.
5. Verify that UTILITY (preferred source) acceptable light is on.
6. Verify that the TRANSFER SWITCH on utility (preferred source) light is on.
7. This step will start the generator. Press and hold Push to Test button until the GENERATOR (alternate source) acceptable light comes on and stays on.Then release the button.
This light indicates that the generator is running and that its output voltage and frequency are acceptable. Under typical conditions, the light should come on after about 5 to 10 seconds. If the generator is running and fails to produce the proper voltage and frequency after 60 seconds then a malfunction has occurred (consult the Troubleshooting section).
8. About 15 seconds after the GENERATOR (alternate source) acceptable light comes on, the automatic transfer switch transfers the load from the utility to the generator. The TRANSFER SWITCH on generator (alternate source) light comes on.
9. The transfer switch stays connected to the generator for 5 minutes. Then the load is transferred back to the utility. To bypass time delay, press and release button again.
10. After load retransfer to utility, the generator runs 1 minute (without load), then shuts down. The GENERATO R acceptable light goes off indicating that generator is off.
This completes the Functional T est. Proceed to next page.
transfer switch on generator
(alternate source) light
the
the Push to Te st
5
OPERATION
utility (preferred source) acceptable light
generator (alternate source)
acceptable light
exerciser light
transfer switch on utility
(preferred source) light
transfer switch on generator
(alternate source) light
INDICATOR LIGHTS
On the front control display are five lights that indicate the status of the sources and the automatic transfer switch.
Utility (preferred source) acceptable
(light at the top left of the display)
When on, this light indicates that the utility voltage is
acceptable for connection to the load.
Generator (alternate source) acceptable
(light at the top right of the display)
When on, this light indicates that the generator voltage
and frequency are acceptable for connection to the load.
Transfer Sw itch on utility (preferred so u r ce)
(light at the center left of display)
When on, this light indicates that the load is connected to
the utility (preferred source).
T ransfer Switch on generator (alt. source)
(light at the center right of display)
When on, this light indicates that the load is connected to
the generator (alternate source).
Automatic Generator Exerciser
(light above button at the right of display)
When the utility is acceptable and the load is on the utility,
this light flashes the number of days until the next exercise period. When it is off, no exerciser period is set. The light is also off any time the generator is running.
PUSH BUTTONS
On the front control display are two push buttons that control the operation of t he generator and the automatic transfer switch.
Push to Test (buttonontheleftside)
This button is used t o test the system. See the Manual
Generator Testing sectiononthenextpage.
This button can be used to cancel any active
Press and release
This button can be used to clear displayed error codes.
See Troubleshooting section, Problem 8.
the button to bypass the time delay.
time delay.
Automatic Generator Exerciser (right button)
This button is used to set the a utomatic generator
exerciser. See the next page.
UTILITY FAILURE
The load is normally connected to the preferred source (utility) if that source is acceptable. If the preferred source (utility) fails, the following sequence occurs:
1. The UTILITY source acceptable light goes off.
2. The automatic transfer switch waits three seconds to pre­vent nuisance starting of the generator from momentary dips of the utility voltage. If the utility is restored during the three seconds, the UTILITY source acceptable light comes on and no further action is taken.
3. If the utili ty remains unacceptable for three seconds, the automatic transfer switch cranks and starts the generator.
4. Once the generator starts, the automatic transfer switch waits until the generator voltage and frequency are acceptable. Then the GENERATOR source acceptable light comes on.
5. When the generator is acceptable, the automatic transfer switch waits 15 seconds to allow the generator to warm up. Then it transfers the load to the generator. The TRANSFER SWITCH on generator (alternate source) light comes on.
6. The automatic transfer switch waits for the utility source to be restored. When the utility again becomes acceptable the UTILITY source acceptable light comes on.
7. The automatic transfer switch then waits 5 minutes to allow the utility to stabilize. Then it retransfers the load back to the utility. The TRANSFER SWITCH on utility (preferred source) light comes on.
8. After load retransfer the generator will continue to run unloaded for one minute for engine cooldown. Then it is stopped. The GENERATOR acceptable light goes off.
6
AUTOMA TIC GENERATOR EXERCISER
The automatic generator exerciser automatically exercises the generator for 20 minutes once every 14 days.
TO SET EXERCISER
Press and release the Automatic Generator Exerciser but­ton. After about 8 seconds the exerciser light flashes 14 times to indicate that the exerciser has been set. The number of flashes indicates the number of days until the next exercise pe­riod (at approximately
TO DISABLE EXERCISER
Press a nd hold the Automatic Generator Exerciser button until the light above the button goes off (light flashes t hen goes off). The exerciser is now disabled and the light is off.
TO ENABLE EXERCISER
Press a nd hold the Automatic Generator Exerciser button until the light goes off (light flashes then goes off). Exerciser is now enabled. After about 8 seconds exerciser light flashes 14 times to indicate that the exerciser has been re–enabled.
Note: With a total power failure (utility failure and generator fails to start) the exerciser must be reset after power is restored.
thesametimethebuttonwaspressed).
automatic generator exerciser light
set exerciser button
MANUAL GENERATOR TESTING
GENERATOR TEST WITH LOAD TRANSFER
During this test a utility failure is simulated. The generator starts and the load transfers to the generator. Then the load retransfers back to the utility and generator stops.
1. Press and hold the GENERATOR acceptable light comes on and stays on (the generator cranks and starts).
2. The automatic transfer switch waits 15 seconds to allow the generator to warm up. Then it transfers the load to the generator . The TRANSFER SWITCH on generator (alternate source) l ight comes on.
3. After 5 minutes the auto– matic transfer switch re– transfers the load back to the utility. To bypass the time delay, press and release the Push to Test button again. The TRANS– FER SWITCH on utility (preferred source) light comes on.
4. Afterloadretransferthe generator will continue to run unloaded for one min­ute for engine cooldown. Then it is stopped. The GENERA TOR acceptable light goes off.
Push to Test button until the
source acceptable lights
load transfer
test button
transfer switch on utility
(preferred source) light
GENERA TOR TEST WITHOUT LOA D TRANSFER
During the test the generator cranks and starts and the GENERATOR light comes on (if it is acceptable). After running for 20 minutes it stops. Throughout the test the load remains connected to the utility (the automatic transfer switch does not
1. Press and release The generator cranks and starts, and the GENERATO R acceptable light comes on and stays on.
transfer switch on generator
(alternate source) light
transfer the load to the generator).
(do not hold) the Push to Test button.
2. The generator runs for 20 minutes. The automatic transfer switch does not transfer the load to the generator. The TRANS- FER SWITCH on utility (preferred source) light stays on.
3. To bypass the time delay or cancel the test, press and release the Push to Te st button again.
4. The generator stops and the GENERATOR accept­able light goes off.
7
TROUBLESHOOTING
This troubleshooting guide describes some of the simple causes of problems with the installation of the automatic transfer switch. Tr ou ble shooting beyond the scope of this guide should not be attempted by the installer. Alicensed electrician must perform all internal troubleshooting. ASCO can be contacted at 800–937–ASCO or www.asco.com.
ELECTROCUTION – FLASH HAZARD
Do not work on the transfer switch
until both the utility and generator are
off. Turn OFF both circu i t breakers .
Problem 1
The UTILITY acceptable light does not come on when utility power is connected to the automatic transfer switch.
Verify that the utility feed is 240 V ac nominal and 60 Hz.
Verify that the utility feed is wired to the terminal lugs on
the bottom of the transfer switch marked L1 and L5.
Verify that the utility feed is connected and t hat its circuit
breaker is ON.
With ALL POWER OFF, verify that the transfer switch
harness is connected properly to the controller (plug at the bottom).
Problem 2
Power is connected (UTILITY acceptable light and/or GENERATOR acceptable lights are on) but both TRANSFER SWITCH position lights are off.
With ALL POWER OFF, verify that the transfer switch
harness is connected properly to the controller (plug at the bottom).
Problem 3
Generator does not crank when the utility source fails or when the Push to Test button is pressed.
Verify that the generator starting controls are set for
automatic operation.
Verify engine start low voltage wiring between controller
terminal block TB7 (plug on the left) and the generator . Check that TB7 plug is properly seated in TB7 receptacle.
Verify that the generator battery is connected and that the
battery voltage meets the generator manufacturer’s recommendation.
Verify that the correct contact (normally open or normally
closed) is being utilized (see the generator manual).
Problem 4
Generator cranks but does not start when the utility source fails or when the Push to Test button is pressed.
Verify engine start low voltage wiring between controller
terminal block TB7 (plug on the left) and the generator . Check that TB7 plug is properly seated in TB7 receptacle.
Verify proper generator operation (see generator manual).
Problem 5
The automatic transfer switch does not transfer the load to the generator (TRANSFER SWITCH on generator light does not come on).
Verify that the GENERATOR source acceptable light is on.
The transfer switch will not retransfer the load to the genera­tor until the generator output is acceptable. If the light is off verify that the circuit breaker for the generator feed is ON.
Wait 15 seconds. There is a 15 second delay after the
generator output becomes acceptable to permit the generator to warm up.
If the GENERATOR source acceptable light still does not
come on, see Problems 3 and 4.
Problem 6
The automatic transfer switch does not transfer the load back to the utility (TRANSFER SWITCH on utility light does not come on).
Verify that the UTILITY source acceptable light is on. The
transfer switch will not retransfer the load to the utility until the utility source is acceptable and the light is on. If light is off, verify that the circuit breaker from the utility feed is ON.
Wait 5 minutes. There is a 5 minute delay on retransfer to
the util ity.
Problem 7
The GENERATOR source acceptable light does not go off after the automatic transfer switch retransfers the load back to the utility.
Wait 1 minute. After load retransfer to the utility, there is a
1 minute delay for generator cooldown before shut down.
Verify proper operation of the generator (see the
generator manual).
Problem 8
Both TRANSFER SWITCH position lights are flashing (this indicates an error condition). *
Count the number of times the Automatic Generator
Exercise r light flashes (repeats after pause). This number
is the error code.
Error codes:
2 Generator failed to start. See Problems 3 and 4. 3 Generator failed after starting. See generator manual. 4 Generator over frequency. See generator manual. 5 Transfer Switch did not transfer the load
to the generator . Service required.
6 Transfer Switch did not transfer the load
to the utility. Service required.
7 Controller error. Service required.
T o clear error code, press and release
* NOTE: These lights will flash only when controller power
is available from either of the two power sources.
Push to T e st button.
8
Loading...