INFLUX MEASUREMENTS FIRESURE FIREGROOVE, FIRESURE FIREFLANGE Manual To The Installation, Operation And Maintenance

Cert No.
464a/01
-10
M e a s u r e m e n t s L t d
T
YPE
- F
IREFLANGE
MANAGEMENT
SYSTEMS
Tel: +44 (0)1962 736736 Fax: +44 (0)1962 736737 Email: sales@influxmeasurements.com
1a Bennett House, The Dean, Alresford, Hampshire, UK. SO24 9BQ.
Quality Systems Certificate No. 464
A GUIDE TO THE INSTALLATION, OPERATION AND MAINTENANCE OF
FIRESURE
Assessed to ISO 9001:2008
T
T
YPE - FIREGROOVE
F
IRESURE FLOWMETER TYPES – APPROVED BY
YPE - FIREFLANGE
LPCB
Contents: Page
1 Specification and Principle of Operation
1.1 I
1.2 C
1.3 P
2 Installation
2.1 P
2.2 M
2.3 C
2.4 I
3 Operation
3.1 F
3.2 F
3.3 F
4 Maintenance
4.1 C
4.2 R
NTRODUCTION
ONSTRUCTION AND SPECIFICATION
RINCIPLE OF OPERATION
IPE LINE CONFIGURATION
AIN ORIFICE CARRIER PREPARATION
ONNECTING THE BYPASS INDICATOR
NSTALLATION IN-LINE
LOW TEST RANGES
LOW TESTING AND READING
AULT CHECKING
HANGING GLASS INDICATOR
ECOMMENDED SPARES
....................................................................................................................................... 2
....................................................................................................................... 2
..................................................................................................................... 3
........................................................................................................................... 6
............................................................................................................................... 7
................................................................................................................ 7
................................................................................................................................... 7
................................................................................................................ 8
........................................................................................................................ 8
...................................................................................................... 2
................................................................................................... 4
................................................................................................... 5
LPS 1045.1
IOM FS Iss 9; April 2012; ECR1269 Page 1 of 8
1 Specification and Principle of Operation
Carrier
Indicator
Firegroove and Fireflange Type
1.1 Introduction
The Firesure flowmeter is a direct reading flowmeter, approved for use under the LPCB rules for automatic sprinkler installations.
These meters have been approved for installation with gauge glass in the vertical position. There must be at least five diameters of straight pipe upstream and downstream of the orifice plate. The isolating valve on the pressure tappings must be kept closed when the meter is not being used. A spare gauge glass must be provided and located in the cabinet containing the stock of replacement sprinklers.
1.2 Construction and Specification
Main Orifice Carrier - 316 stainless steel flow orifice mounted in a polyester coated mild steel carrier
Bypass Flow Indicator - Nickel-plated copper tubing and brass connections Stainless steel filter element, restrictor rodding and float indicator Boroscilicate glass indicator tube Viton and polyurethane seals
Max Operating Pressure - 16 bar
Max Operating Temperature - 90°C maximum
Connection - Fireflange - Wafer style bolted between flanges Firegroove – Cut groove pipe ends using approved pipe couplings
1.3 Principle of Operation
Water flow through the main orifice, creates a pressure difference between the two pressure tapping ports. These pressure ports are connected across the bypass flow indicator, causing a small bypass flow through the indicator, directly related to the flow through the main orifice. An indicating float positioned within the glass tube can be read against scale markings, which show the flow rate delivery of the installation.
Main Orifice
Bypass Flow
Pressure Tapping Ports
IOM FS Iss 9; April 2012; ECR1269 Page 2 of 8
2 Installation
A A
2.1 Pipe Line Configuration
Optional Full Bore Isolation Valve
From Pump
464a/01, 464a/06 F3/1, F3/6 50 250 BS1387 464a/02, 464a/07 F3/2, F3/7 80 400 BS1387 464a/03, 464a/08 F3/3, F38 100 500 BS1387 464a/04, 464a/09 F3/4, F3/9 150 750 BS1387 464a/05, 464a/10 F3/5, F3/10 200 1000 BS3600
LPCB Ref. No. Type Nom. Size mm A mm Pipe Spec.
Recommended pipeline configuration for automatic sprinkler installation of Firesure Flowmeter.
Firegroove
90mm
Sizes 50-150
40mm
Fireflange
Firegroove
100mm
Size 200
Control Valve
Return
IOM FS Iss 9; April 2012; ECR1269 Page 3 of 8
2.2 Main Orifice Carrier Preparation
a) For Horizontal Pipe Work Mounting – Connect joggled connection pipes as shown
Red
White
or
Flow Direction Left to Right
White
Red
b) For Vertical Pipe Work Mounting – Connect joggled connection pipes as shown
Red
Red
Flow Direction
Up
White
Flow Direction
Down
c) Rotate Pipes to Position Shown in a) or b) Check pipes for horizontal alignment.
Ensure that the pipes spacing matches the rear bypass indicator connections. Tighten pressure tapping nuts.
Tighten
Flow Direction Right to Left
White
IOM FS Iss 9; April 2012; ECR1269 Page 4 of 8
2.3 Connecting the Bypass Indicator
indicator vertical.
Red
White
Rear view of indicator piping as supplied suitable for connection to
main orifice carrier for horizontal flow right to left or vertical flow upward.
Remove red plastic stop and retaining rod from top block. Remove retaining screw and assemble restrictor and bleed assembly to indicator top block with retaining screw in place.
Rear view of indicator adjusted and suitable for connection to main orifice carrier for horizontal flow left to right or vertical flow downwards. To adjust loosen nuts, rotate arms to position shown and retighten nuts.
nut
Connect Bypass unit to main orifice carrier ensuring that ‘white’ marked pressure point connects with ‘white’ handled tap and ‘red’ pressure point connects with ‘red’ handled tap. Tighten connecting nuts, keeping
Red
White
IOM FS Iss 9; April 2012; ECR1269 Page 5 of 8
2.4 Installation In-Line
Red
White
a) Ensure direction arrow is consistent with viewed direction of flow and position Fireflange between pipeline
flanges concentrically. Concentricity can be achieved by ensuring the carrier outside diameter is central to the fixing bolts.
b) Firegroove type should be fitted with approved couplings suitable for groove cut joints.
c) When fitting Fireflange type, ensure that any sealing gaskets do not obstruct the pipe line or carrier bore.
Size/model Min ID Gasket Permissible
50 53mm
80 79mm 100 103mm 150 155mm 200 204mm
IOM FS Iss 9; April 2012; ECR1269 Page 6 of 8
3 Operation
3.1 Flow Test Ranges
The Firesure flowmeter is designed to test that the automatic sprinkler installation meets the required flow rate needs. Each size of flowmeter meets a particular duty as shown below.
Size Flow Range
50 150-700
80 300-1600 100 500-3500 150 900-7900 200 2000-15000
3.2 Flow Testing and Reading
1. With bypass taps in closed position direct flow through
meter pipe line.
2. Open bypass indicator taps.
Red Tap
3. Bleed air from bypass by opening bleed assembly one
revolution.
Closed
4. Close bleed assembly when air is bled.
5. Press restrictor button full home and release.
6. Flow rate is shown by aligning the top of the float with scale
White
Tap
markings. Test flows are highlighted on the scale.
7. When test is completed, close bypass taps and drain by
opening drain assembly and bleed assembly one turn.
8. Visually check filter bowl. If dirty, remove by unscrewing
fully and clean filter element.
9. After draining close filter and bleed assemblies.
3.3 Fault Checking
Observation Possible Causes Remedy No Flow Indication. Bypass taps closed.
Restrictor clogged.
Connections reversed to flow.
Flow Indication Low. Restrictor clogged.
Filter heavily clogged.
Air trapped in bypass.
Orifice carrier reverse installed
Open Taps.
Press & release restrictor button or remove and visually check restrictor.
Check procedure. As above.
Remove and clean filter.
Bleed air from bypass.
Check flow direction against carrier label arrow.
Open
Filter and Drain Assembly
Open
IOM FS Iss 9; April 2012; ECR1269 Page 7 of 8
4 Maintenance
4.1 Changing Glass Indicator
In case of breakage a glass tube indicator would be required. Refer first to the black printed Firesure model number F3/- on the carrier label or tube before ordering a replacement. NOTE: This model uses BLACK scaled tubes. These should not be replaced with RED scaled tubes which are used for the extended indicator model (Firesure X).
1. Remove Cover
2. Remove Wedges
3. Push inserts back into end blocks
4. Tilt glass out of backplate
5. Assembly is in reverse order.
4.2 Recommended Spares
If the installation and operating procedures are followed there should be no need for maintenance. In the event of accidental damage or loss the following spare parts are available:
Restrictor and bleed assembly
Filter element and drain
Glass Tube Indicator
Seals Kit
Part No.
S1000
S1001
F3/-
S1002
IOM FS Iss 9; April 2012; ECR1269 Page 8 of 8