Infloor DIGIT-STAT 30120 User Manual

INSTALLATION AND OPERATING INSTRUCTIONS
DIGIT-STAT 30120 UNIVERSAL DIGITAL TEMPERATURE GAUGE
FOR HYDRONIC HEATING/SOLAR HEAING/GEOTHERMAL SYSTEM
DIGITAL TEMPERATURE GAUGES 30120
Infloor Sales & ServiceDigital Temperature gauge replaces two mechanical temperature gauges as it can simultaneously displays the accurate temperature of two locations such as the supply and return piping on a hydronic heating system. When 24VAC is supplied, the lithium battery enable the unit to work in case of power failure. 30120 is also ideal for any application that requires quick and accurate response to temperature change, an easy to read display and a wide temperature range.
FEATURES:
Dual Large LCD (Liquid Crystal Display) to show supply and return temperature. Min/Max memory can be selected for both OUT(Supply) and IN (Return) water temperature since the last time RESET button was pressed Celsius or Fahrenheit switch on the front unit. Dual power input: 24VAC or Lithium Battery. When both inputs are applied, 24VAC has priority over lithium battery. Frequent sample rate dictate any change in temperature instantly Easy installation
SPECIFICATIONS:
Temperature range: -58 to 302 F (-50 to 150 C) Resolution: 0.1 F(0.1 C) Accuracy: ±1 C / ±2 F Sample rate: 3 Secs. Input: 2 x 10K ohm thermistor probe model: P-03 (designed to strap on a pipe or insert into a temperature well) Operating Voltage: 24VAC or Lithium Battery (included, last for over 3 years) Size: 3.5” x 2.0” x 0.9” (88.9mm x 50.8mm x 22.86mm) Enclosure: Flame-retardant plastic Operating Temperature: 32 to 122 F(0 to 50 C) Weight: 0.11lbs (50g)
° °
° °
° °
° °
UNIVERSAL SENSOR PROBE (THERMISTOR) Model: 30121
MODEL DESCRIPTION
30120
30121
INSTALLATION:
INSTALLATION:
Digital temperature gauge with two universal sensor probes
Universal sensor probe (high range)
REMOVING THE FRONT COVER
Push down the plastic tab located on top of the enclosure with finger or small screwdriver to release the lock. Swing the front cover away from the base using the bottom edge as the pivot.
Push the tab to open the cover
MOUNTING THE 30120 ON THE WALL
THE 30120 can be mounted on the wall (or wooden board) using two #6 screws. Insert the screws through the mounting holes on the base and fasten the screws to the wall.
The Infloor Sensor Probe is engineered to ensure long life and rapid response. It is designed to strap on a pipe or insert into a temperature well. 30121 is specially designed for use with 30120 and other controls that require 10K ohm thermistors.
SPECIFICATIONS:
Sheath: Copper Lead: 10” of 20 AWG heat resistence green wire Dimension: 3/8" OD x 13/16" length (9.5mm OD x
20.6mm) Weight: 0.02lb (10g) Operating range: -58 to 302 F (-50 to 150 C) Sensor: 10K ohm @ 77 F (25 C ± 1%) thermistor
° °
° °
Insert #6 screws into these mounting holes
WIRING THE 30120
First of all, decide if the wire is going to run through the bottom or back opening. In case of running the wire through the bottom opening, remove the plastic plug by sliding outward. For hydronic heating system, run a pair of wire (18-20AWG) from each of P-03 sensor to the corresponding terminal blocks: Sensor of Supply Piping to “T1 T1” or “OUT”. Sensor of Return Piping to “T2 T2” or “IN”. For other systems, T1 corresponds to location 1 and T2 corresponds to location 2 of the sensors.
When 24VAC input is applied, the power consumption from the lithium battery will be disabled. Always pull away the plastic tab from the battery to activate the battery power or as backup power.
Note: Do not run sensor wires parallel to other electrical wiring
or telephone wires. In case there is strong source of electromagnetic interference, twisted pair 20AWG wire is recommended.
OPERATION OF THE BUTTONS ON THE FR ONT CO VER:
MAX-MIN
From the normal temperature display mode(no wording such as MAX or MIN on the LCD), press MAX-MIN button once to display the recorded maximum temperature of OUT(supply) and IN(return) piping. MAX appears in the temperature LCD’s.
Press MAX-MIN button again to toggle to the recorded minimum temperature of OUT(supply) and IN(return) piping. MIN appears in the temperature LCD’s.
Press MAX-MIN button again to return to the normal temperature display mode.
RESET
Press RESET button to reset both the maximum and minimum temperatures in the memory.
Printed Circuit Board behind the cover
24VAC
T2 T2
24VAC
RETURN PIPING
IN
OUT
T1 T1
Plastic plug removed
30121 Sensor Probes
SUPPLY PIPING
Switch for setting default display unit in ° °C or F after reset or power up.
INST ALLING THE FRONT COVER
This is the reverse process of removing the front cover. The hinges on the bottom of the front cover can be aligned with the base to provide pivot for the front cover to close. Swing the top part of the front cover all the way until it snaps tightly with the base.
C/ F
° °
Press the C/ F button to toggle between C and F.
INSTALLATION:
O THER OPERATION ISSUES:
° ° ° °
OUT OF RANGE
If the temperature is under -58 F (-50 C), “LLL” will be
displayed
If the temperature is over 302 F (150 C), “HHH” will be
displayed
° °
° °
LOW BA TTER Y INDICATOR
If the battery is low, symbol will be flashing.
Change the battery as soon as possible.
MOUNTING THE SENSOR:
The sensor 30121 is designed to strap on a pipe or
insert onto a temperature immersion well.
Sensors should be strapped to the pipe with cable tie. The flat side of the sensor should be resting on the pipe. In addition, they should be covered with a layer of insulation to minimize the effects of ambient temperature for a more reliable temperature reading.
The sensor 30121 can also be insert onto a 3/8”(10mm) or ½”(12.7mm) ID temperature well.
www.infloor.com