Indesit KP900GX User Manual

Operating Instructions
Contents
GB
Installation, 2-5
English,2
KP900GX
Description of the appliance, 6
Overall view Control panel
Start-up and use, 7-11
Using the hob Setting the time Using the oven Cooking modes for Multi-function (1rst Oven) Cooking modes for conventional-function (2nd Oven) Practical cooking advice Oven cooking advice table
COOKER AND OVEN
GB
Precautions and tips, 12
General safety Disposal Respecting and conserving the environment
Care and maintenance, 13
Switching the appliance off Cleaning the appliance Replacing the oven light bulb Gas tap maintenance Assistance
Installation
GB
! Before operating your new appliance please read this instruction booklet carefully. It contains important information concerning the safe installation and operation of the appliance.
! Please keep these operating instructions for future reference. Make sure that the instructions are kept with the appliance if it is sold, given away or moved.
! The appliance must be installed by a qualified professional according to the instructions provided.
! Any necessary adjustment or maintenance must be performed after the cooker has been disconnected from the electricity supply.
Room ventilation
The appliance may only be installed in permanently­ventilated rooms, in accordance with current national legislation. The room in which the appliance is installed must be ventilated adequately so as to provide as much air as is needed by the normal gas combustion process (the flow of air must not be lower than 2 m3/h per kW of installed power). The air inlets, protected by grilles, should have a duct with an inner cross section of at least 100 cm2 and should be positioned so that they are not liable to even partial obstruction (see figure A). These inlets should be enlarged by 100% - with a minimum of 200 cm2 - whenever the surface of the hob is not equipped with a flame failure safety device. When the flow of air is provided in an indirect manner from adjacent rooms (see figure B), provided that these are not communal parts of a building, areas with increased fire hazards or bedrooms, the inlets should be fitted with a ventilation duct leading outside as described above.
Adjacent room Room requiring
ventilation
AB
Disposing of combustion fumes
The disposal of combustion fumes should be guaranteed using a hood connected to a safe and efficient natural suction chimney, or using an electric fan that begins to operate automatically every time the appliance is switched on (see figure).
Fumes channeled outside
Fumes channelled through straight a
chimney or a branched flue system
(reserved for cooking appliances)
! The liquefied petroleum gases are heavier than air and collect by the floor, therefore all rooms containing LPG cylinders must have openings leading outside so that any leaked gas can escape easily. LPG cylinders, therefore, whether partially or completely full, must not be installed or stored in rooms or storage areas that are below ground level (cellars, etc.). Only the cylinder being used should be stored in the room; this should also be kept well away from sources of heat (ovens, chimneys, stoves) that may cause the temperature of the cylinder to rise above 50°C.
Positioning and levelling
! It is possible to install the appliance alongside cupboards whose height does not exceed that of the hob surface.
! Make sure that the wall in contact with the back of the appliance is made from a non-flammable, heat­resistant material (T 90°C).
A
Ventilation opening Increase in the gap between for comburent air the door and the flooring
! After prolonged use of the appliance, it is advisable to open a window or increase the speed of any fans used.
2
To install the appliance correctly:
• Place it in the kitchen, the dining room or the bed­sit (not in the bathroom).
• If the top of the hob is higher than the cupboards, the appliance must be installed at least 600 mm away from them.
• If the cooker is installed underneath a wall cabinet, there must be a minimum distance of 420 mm between this cabinet and the top of the hob.
This distance should be increased to 700 mm if the
wall cabinets are flammable (see figure).
mm.
420
Min.
HOOD
Min. mm.
900
• Do not position blinds behind the cooker or less than 200 mm away from its sides.
mm. with hood
mm. without hood
420
• Any hoods must be
650
700
Min. mm.
installed according to
min.
min.
the instructions listed in the relevant operating manual.
Green & Yellow wire to terminal marked “E” or
or coloured Green or Green & Yellow. Brown wire to terminal marked “L” or coloured Red. Blue wire to terminal marked “N” or coloured Black (see fig. B).
l fix the feeding cable in the special cable stop and
close the cover.
N.B.: the power supply cable must have these minimum requirements: Type: H05RR-F Section: 3x2.5 mm
2
GB
Levelling
If it is necessary to level the appliance, screw the adjustable feet into the places provided on each corner of the base of the cooker (see figure).
The legs* fit into the slots on the underside of the base of the cooker.
Electrical connection
WARNING – THIS APPLIANCE MUST BE EARTHED.
Electrical connection Electric cookers come without a power supply cable. The cooker is designed to operate on an electricity supply which conforms to the electrical data shown on the Rating Plate. The cooker can be connected to the mains only after removing the back panel of the cooker itself with a screwdriver. N.B.: the following installation procedure must be carried out by a qualified electrician. The electrical installation must comply with the IEE Regulations, Building & local By-Lays. For the installation of the feeding cable carry out the following operations:
l Using a screwdriver, prise on the side tabs of the
terminal board cover (see fig. A);
l Pull and open the junction blok lid
Important: the wires in the mains lead are coloured in accordance with the following code:
Green & Yellow -Earth Blue -Neutral Brown -Live
As the colours of the wires in the mains lead may not correspond with the coloured markings identifying the terminals in your plug, proceed as follows:
Ensure that the mains cable is routed away from any brackets affixed to the rear panel and is not trapped to the rear wall when pushing the cooker into position between cabinets.
L
2
N
4
Fig. A
Fig. B
Gas connection
Connection to the gas network or to the gas cylinder may be carried out using a flexible rubber or steel hose, in accordance with current national legislation and after making sure that the appliance is suited to the type of gas with which it will be supplied (see the rating sticker on the cover: if this is not the case see below). When using liquid gas from a cylinder, install a pressure regulator which complies with current national regulations. To make connection easier, the gas supply may be turned sideways*: reverse the position of the hose holder with that of the cap and replace the gasket that is supplied with the appliance. ! Check that the pressure of the gas supply is consistent with the values indicated in the Table of burner and nozzle specifications (see below). This will ensure the safe operation and durability of your appliance while maintaining efficient energy consumption. Gas connection using a flexible rubber hose
Make sure that the hose complies with current national legislation. The inter nal diameter of the hose must measure: 8 mm for liquid gas supply; 13 mm for methane gas supply. Once the connection has been performed, make sure
3
GB
that the hose:
• Does not come into contact with any parts that reach temperatures of over 50°C.
• Is not subject to any pulling or twisting forces and that it is not kinked or bent.
• Does not come into contact with blades, sharp corners or moving parts and that it is not compressed.
• Is easy to inspect along its whole length so that its condition may be checked.
• Is shorter than 1500 mm.
• Fits firmly into place at both ends, where it will be fixed using clamps that comply with current regulations.
! If one or more of these conditions is not fulfilled or if the cooker must be installed according to the conditions listed for class 2 - subclass 1 appliances (installed between two cupboards), the flexible steel hose must be used instead (see below).
Connecting a flexible jointless stainless steel pipe to a threaded attachment Make sure that the hose and gaskets comply with current national legislation. To begin using the hose, remove the hose holder on the appliance (the gas supply inlet on the appliance is a cylindrical threaded 1/2 gas male attachment).
! Perform the connection in such a way that the hose length does not exceed a maximum of 2 metres, making sure that the hose is not compressed and does not come into contact with moving parts. Checking the tightness of the connection When the installation process is complete, check the hose fittings for leaks using a soapy solution. Never use a flame. Adapting to different types of gas
It is possible to adapt the appliance to a type of gas other than the default type (this is indicated on the rating label on the cover).
suited to the new type of gas
see Burner and nozzle
(
specifications table
3. Replace all the components by fo llowin g the above instructions in reverse. Adjusting the hob burners’ minimum setting:
1. Turn the tap to the minimum position.
2. Remove the knob and adjust the regulatory screw, which is positioned inside or next to the tap pin, until the flame is small but steady. ! If the appliance is connected to a liquid gas supply, the regulatory screw must be fastened as tightly as possible:
3. While the burner is alight, quickly change the position of the knob from minimum to maximum and vice versa several times, checking that the flame is not extinguished.
! The hob burners do not require primary air adjustment.
! After adjusting the appliance so it may be used with a different type of gas, replace the old rating label with a new one that corresponds to the new type of gas (these labels are available from Authorised Technical Assistance Centres).
! Should the gas pressure used be different (or vary slightly) from the recommended pressure, a suitable pressure regulator must be fitted to the inlet hose in accordance with current national regulations relating to “regulators for channelled gas”.
).
Table of burner and nozzle specifications
Adapting the hob Replacing the nozzles for the hob burners:
1. Remove the hob grids and slide the burners off
their seats.
2. Unscrew the nozzles using a 7 mm socket
spanner (
4
see figure
), and replace them with nozzles
Table 1 Liquid Gas Natural Gas
GB
Burner Diameter
(mm)
Thermal Power
kW (p.c.s.*)
Nomi nal Re duc ed (mm) (mm) *** ** (mm) (mm)
Fast (Large)(R)
Semi Fast (Medium)(S)
Auxiliary (Small)(A)
Tr iple Ring (TC)
Supply Pressures
100 3,00 0,7 41 86 218 214 116 286 143 286
75 1,90 0,4 30 70 138 136 106 181 118 181
55 1,00 0,4 30 50 73 71 79 95 80 95
130 3.25 1.5 63 91 236 232 133 309 150 309
Nominal (mbar)
Minimum (mbar )
Maximum (mbar)
* At 15°C and 1013 mbar - dry gas ** Propane P.C.S. = 50.37 MJ/kg *** Butane P.C.S. = 49.47 MJ/kg
Natural P.C.S. = 37.78 MJ/m³
By-Pass
1/100
Nozzle
1/100
28-30
20 35
Flow*
g/h
37 25 45
Nozzle
1/100
20 17 25
Flow*
l/h
Nozzle
1/100
Flow*
l/h
13
6,5
18
TECHNICAL DATA (1st Oven )
Oven dimensions Volume
Burners Voltage and frequency see data plate
ENERGY LABEL
H:34;W:39;D:41 cm 54 l may be adapted for use with any type of gas shown on the data plate
Directive 2002/40/EC on the label of electric ovens. Regulation EN 50304
Energy consumption for Natural convection – heating mode:
Traditional mode Declared energy consumption
for Forced convection Class – heating mode: Baking.
EC Directive s: 73/23/EEC dated 19/02/73 (Low Voltage) and subsequent amendments ­89/336/EEC dated 03/05/89 (Electromagnetic Compatibility) and subsequent amendments ­90/369/EEC dated 29/06/90 (Gas) and subsequent amendments - 93/68/EEC dated 22/07/93 and subsequent amendments - 2002/96/EC.
TECHNICAL DATA (2nd Oven)
;
Dimensions Volume
Burners Voltage and frequency see data plate
ENERGY LABEL
H:33.8;W:24.5;D:43.8 cm 36 l may be adapted for use with any type of gas shown on the data plate
Directive 2002/40/EC on the label of electric ovens . Regulation EN 50304
Energy consumption for Natural convectio n – heating mode:
;
Traditional mode
EC Directives: 73/23/EEC dated 19/02/73 (Low Vol tage) and subsequent am end m ents ­89/336/EEC dated 03/05/89 (Electromagnetic Compatibility) and subsequent am end m ents ­90/369/EEC dated 29/06/90 (Gas) and subsequent amendments - 93/68/EEC dated 22/07/93 and subsequent amendments - 2002/96/EC.
5
Loading...
+ 10 hidden pages