INSTALLATION, OPERATING AND
MAINTENANCE INSTRUCTIONS FOR
INDEECO ELECTRIC DUCT HEATERS
APPLICATION INFORMATION
1. Follow the procedure given on the reverse side of this sheet
to find the minimum air velocity for safe operation. At least this
minimum velocity must be provided at all points over the heater
face area. Failure to meet this requirement may result in serious
damage or nuisance thermal cutout tripping.
2. The maximum air inlet temperature for open coil heaters is
100F (37.8C), and for finned tubular heaters, 80F (26.7C).
3. The heater must be located at least 4’ (1220mm) from any
grills, registers, filters, abrupt duct size changes, humidifiers, air
conditioning or air handling units, or any other change or
obstructions in the duct which may result in nonuniform airflow,
and not less than 30” (762mm) from the end of the warm air duct.
Duct elbows or turns must be located at least 4’ (1220mm) from
the inlet of the heater and 2’ (610mm) from the outlet of the heater.
Sufficient working space must be provided per paragraph 2-308 of
the Canadian Electrical Code.
4. These duct heaters are not intended for installation in series
in the airstream; the heaters are designed for use only as a single
unit within a duct with the exception of Series ZCA, XCA, ZCBA,
XCBA, TFZCA, TFXCA which are designed for stacked installation
for use as a single unit within a duct. (See Fig. No. 3)
MECHANICAL INSTALLATION
1. Heater terminal outlet box should not be enclosed. Heaters
with expanded metal terminal box covers must be installed in a
position where air passing out of the terminal box does not enter
into confined areas of the building structure (such as a space
behind a false ceiling, a hollow space in a wall, etc.)
2. All heaters are suitable for installation with zero spacing
between the duct and combustible surfaces.
3. The heater must be installed in the correct position as shown
by the arrows in the terminal box.
4. Sufficient clearance for convection cooling must be allowed
for all heaters with built-in SCR Power Controllers. Provide at least
5” (127mm) of free air space above and below cooling fins
extending from heater terminal box.
5. For proper operation of heaters equipped with a built-in
airflow switch, a minimum of .07” (1.8mm) WC of static pressure is
required in the duct system, and the velocity pickup tube for the
airflow switch must be pointed in the proper direction. When the
heater is installed on the downstream or positive pressure side of
the air moving fan, the arrow on the mounting flange of the pickup
tube must point in the same direction as the airflow. When the
heater is installed on the upstream or negative pressure side of the
air moving fan, the arrow must point in the direction opposite to the
airflow. If incorrectly installed, remove the two screws holding the
pickup tube in place, rotate 180 and reinstall. See separate
instruction sheet for installation of heaters supplied with a remote
pickup tube.
FOR FLANGE TYPE HEATERS ONLY: (See Fig. No. 1)
6. Provide flanges on the duct to match the heater flanges, both
on the entering and leaving air sides.
7. Attach the duct flanges to the heater flanges with bolts, sheet
metal screws or slip and drive connectors when the heater has
matching connectors for this purpose.
FOR SLIP-IN TYPE HEATERS ONLY: (See Fig. No. 2)
8. Cut a hole in the side of the duct to accommodate the body of
the heater (excluding terminal box). This hole should be 1/8”
(3.175mm) larger than the heater frame.
9. Slip the heater into the duct and attach the back of the terminal box to
the duct with sheet metal screws.
10. If heater has built-in PE switches they must be calibrated to field
control system. Calibrate the PE switch marked No. 1 to come on first.
FOR STACKED TYPE HEATERS ONLY: (See Fig. No. 3)
11. The heaters with catalog prefix ZCA, XCA, ZCBA, XCBA, TFZCA and
TFXCA must be stacked as indicated in Fig. No. 3.
FOR HEATERS TO BE INSTALLED IN FIBERGLASS DUCTS:
12. Write factory for special instructions. Note that the fiberglass duct
material itself must be CSA approved.
FOR HEATERS TO BE INSTALLED IN INTERIOR INSULATED DUCTS:
13. All slip-in type heaters are suitable for installation in ducts with up to
1” (25.4mm) of interior insulation as long as they have been sized for the
dimensions inside the insulation. The heaters are not suitable for
insulation depths of greater than 1” (25.4mm) unless a special construction
has been ordered. Flange type heaters are only suitable for installation in
insulated ducts if specially ordered for this application.
ELECTRICAL INSTALLATION
14. Follow the wiring diagram on the inside of the terminal box.
15. Supply connections must be made with copper wiring rated 90C
minimum. Use aluminum wire only when specifically called for on
accompanying wiring diagram.
16. All wiring in the terminal box must be insulated for 600 volts.
17. When making line connections to heater element terminals FOR
FINNED TUBULAR DUCT HEATERS ONLY, apply a ¼” wrench to flat
section of terminal or nut immediately below threads. Otherwise damage
to terminal may result.
18. Line connection should be based upon the line current and the
requirements of the Canadian Electrical Code. The line current for either a
single or three phase load is calculated as follows: