Indeeco process Installation, Operating, & Maintenance Instructions

INSTALLATION, OPERATING
&
MAINTENANCE INSTRUCTIONS FOR
CAUTION
CAUTION
WARNING
ELECTRIC PROCESS AIR HEATERS
INDEECO Process Air Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.
GENERAL
element is directly related to its surface temperature. Follow the limitations of Table 1 for maximum watt densities and minimum airflows. The watt density is shown on the heater nameplate.
INDEECO process air heaters are designed and intended for installations in plenums or ducts to heat forced air in industrial equipment and systems. A variety of designs and sizes are available with outlet air temperatures up to 1200°F. Due to these high temperatures, the heater design features must be closely matched to the application.
There are three types of heating elements:
Open Coil - a bare (electrically hot) resistance wire coil
Finned Tubular - a spiral finned metal sheathed element
Tubular – a tubular metal sheathed element.
Open coil elements require clean, uniform airflow and can only be mounted with the coils horizontal. They should not be used where there could be contact with the coils by personnel or electrically conductive material. Finned tubular elements can tolerate moisture and a degree of non-uniform airflow. Finned tubular elements should not be used where contaminants are likely to build up between the fins. Tubular elements are universally applicable. Tubular and finned tubular process air heaters can be mounted with the elements either vertical or horizontal.
The heating elements are available in various watt density ratings. Outlet temperature, watt density and airflow velocity determine the surface temperature of the open coil, tubular or finned tubular elements. Life of the heating
INSTALLATION
There are two types of heater frames:
A sheet metal frame for slip-in duct mounting is standard for 250°F rated units (Figure 1).
A plug-type design with mounting plate is standard for 400°F through 1200°F rated units (Figures 2 & 3).
All open coil process air heaters, and the 250°F finned tubular process air heaters, have top and bottom frames that restrict the airflow to either horizontal or vertical, while all other process air heaters can be used with any perpendicular air flow direction.
Instructions for Industrial Control Panels are provided in 87-2000-83. A section on control methods is included.
Failure to follow INDEECO recommendations could result in premature failure and/or serious equipment damage.
Temperature regulating devices, temperature limiting controls, and low flow controls are recommended for use with process air heaters to control the heating process and safeguard the heater from excessive temperatures that can cause damage.
Mechanical Instructions
INDEECO recommends installation be performed by qualified personnel familiar with the National Electrical Code and all local codes and standards. It is the responsibility of the installer to verify the safety and suitability of the installation
WARNING
Hazardous voltages are present in this equipment. Lock out and tag the branch circuit disconnect switch before working on this heater.
Handling and Storage Care must be taken to avoid damage to the heater during
storage and handling. Protect the heater from weather damage during storage if shipping packaging is not sealed.
It is recommended to store the heater in a cool dry area to help prevent the heating elements or ceramic spacers from drawing moisture.
Site Selection Review the NEMA Type rating of the heater provided. Do
not install a heater in an area not consistent with its rating.
DO NOT mount heaters in an atmosphere containing combustible gases, vapors, dusts, or fibers.
Allow at least three feet in front of the heater terminal box for heater maintenance. Consideration should also be given for heater removal clearance to allow heater replacement.
Electric heaters are capable of developing high temperatures. Therefore, extreme care should be taken to avoid mounting heaters in an atmosphere containing combustible gases, vapors, dusts, or fibers unless properly marked as suitable for the condition.
If the duct or plenum is insulated, be sure that insulation does not block airflow across the heating elements. Insure that the airflow is uniform across the face of the heater to
2
avoid hot spots. Typical causes for uneven airflow are
WARNING
structural components blocking air or mounting the heater too close to elbows, transitions or the fan. A pressure plate on the heater inlet should be considered if uneven airflow is expected.
The heater should be mounted plumb horizontally and vertically to assure proper operation. If the heater is installed horizontally and weighs over 25 pounds, support rails or hangers must be provided in the duct or plenum for support.
WARNING
Do not cover the heater terminal box or install the heater so that part of the terminal box is within the duct or plenum. Dangerous over-heating of the wiring could result.
Slip-In Duct Mounted Construction (Figure 1)
1. Determine proper mounting for airflow direction.
2. Cut a hole into the duct or plenum to accommodate the body of the heater (excluding the terminal box). The hole should be at least 1/8” larger than the frame.
3. Slip the heater into the opening, center and attach the back of the terminal box to the duct or plenum using sheet metal screws.
4. Do not mount an open coil heater with the coils in a vertical position.
Plug-Type with Mounting Plate Construction (Figures 2 & 3)
1. Determine proper mounting for airflow direction.
2. Cut hole into the duct or plenum to accommodate the body of the heater (excluding the mounting flange). This hole should be at least 1/8” larger than the frame.
3. Supply a mating flange, weld studs or bolt holes to match the mounting flange.
4. Supply a gasket between the mounting and mating flanges.
5. Do not mount an open coil heater with the coils in a vertical position.
Electrical Instructions
Field supplied conductors must be sized for at least 125% of the circuit current.
To calculate the circuit current (in amps):
KW x 1000Single phase
Line current Line Voltage
KW x 1000Three phase
Line current 1.732 x Line Voltage
Wiring to the heater should be permanently installed in metallic or non-metallic electrical grade conduit in accordance with all applicable electrical codes, and should include a grounding conductor if non-metallic conduit is used.
Field supply wiring must be rated for 600Vac. Use copper conductors. 450oC wire may be required on high temperature heaters. If the wire is not available locally,
please contact INDEECO. The electrical installation should include a service
disconnect switch in sight of the heater as well as branch circuit over-current protection and over-temperature protection (if not provided with the heater).
For wiring recommendations refer to the wiring diagram. An additional copy is provided inside the heater terminal box.
INDEECO strongly recommends the use of an outlet air over-temperature control device located near the heater outlet. A thermostat or thermocouple (with remote controller) set approximately 50°F above the normal operating temperature may be used. Additionally, a differential pressure switch or a fan interlock relay may be used to detect air pressure or fan motor operation. This will prevent the heater from operating without airflow.
Where thermocouple extension wire is required between the heater and control panel, verify it is connected with proper polarity as shown on the wiring diagram. Failure to do so may result in an uncontrolled heater. Refer to the wiring diagram for the required wire type. Shielded wire is recommended to reduce signal interference.
The potentially high operating and ambient temperatures of process air heaters require field wiring to the heater to be carefully matched to the application to avoid serious injury or damage to the equipment. The wiring must be de-rated for the expected terminal box temperature.
The size and type of incoming field wiring will depend upon the heater terminal box temperature, heater current draw per conductor, number of conductors per conduit, and wire
insulation rating. Refer to the National Electrical Code. The terminal box temperature is directly related to the
heater outlet air temperature. Insulated terminal boxes are provided on high temperature heaters to allow moisture seals on tubular and finned tubular heating elements, and to avoid costly high temperature wire. Refer to Table 2 for the INDEECO estimated terminal box temperature.
Retighten all electrical connections that may have loosened during shipment. Failure to do so may result in damage to the heater or risk of fire.
When making connections directly to the element terminals on tubular or finned tubular elements, apply a ¼” wrench to flat sections of the element terminal immediately below the threads. Otherwise, damage to the terminal may result.
Confirm all unused conduit holes in the terminal box are sealed with plugs suitable for the heater environment.
Attach a ground conductor to the ground lug located in the heater terminal box or by other appropriate means per NEC Article 250.
Loading...
+ 2 hidden pages