Incon TS-LLD 1 Replacement Parts Manual

INTELLIGENT CONTROLS INC http://www.intelcon.com 74 INDUSTRIAL PARK RD SACO ME 04072 U S A
Replacement Parts Instructions 0000231A.DOC
Changing the TS-LLD 1 microfarad Line Filter Capacitor
Parts Required:
1. TS-LLD Installation Manual
Install the 1uF Line Filter Capacitor (INCON PN LSSP-LF) Between L1 & L2
(INCON P/N 000-1359)
2.
Line Filter Cap (LSSP-LF)
Tools Required:
N L1 L2
1. Flat-bladed & Philips head screwdrivers (assorted sizes)
2.
Multimeter with test probes (set to read voltage at 120 VAC)
DANGER Electrical shock hazards! Turn off and lock-out the submersible pump power source (terminated at L1 and L2), and the pump relay power source (terminated at S2, from the dispenser switch) BEFORE working on this equipment. Failure to turn off these power sources will result in severe injury or death.
Old Line Filter – Removal Steps:
1.
DANGER 240 V AC is present ! …disconnect electrical power as described
in the TS-LLD CU Installation & Wiring and in the Safety Chapter of that manual.
2.
Open / remove the submersible pump relay box cover.
3.
Use the multimeter to make sure NO VOLTAGE IS PRESENT from N to any
other terminal inside the relay box.
4.
Remove the old Line Filter Capacitor (INCON P/N 020-0028).
New Line Filter – Installation:
Follow the Safety Instructions, the installation steps for the new CU enclosure
to install the new line filter capacitor, and the After Installation Steps / Testing (as detailed in the TS-LLD Installation Manual).
Discard the old Line Filter Capacitor
Contact INCON Technical Service Department for any additional help. Call toll free at 1-800-984-6266.
E-mail: tech@intelcon.com FAX 1-207-282-9002 TEL 1-800-984-6266 PAGE 1 of 1