This manual is written for the OPTImizer2 Circuit Breaker Monitor with rmware revision 1.0.1.
LIABILITY DISCLAIMER
INCON (Intelligent Controls) reserves the right to change this document and specications at any time without
notice. INCON makes no express or implied warranty with regard to the content of this manual. INCON assumes no
liability for errors or omissions, or for any damages, direct or consequential, that may result from the use of this
document or the equipment that it describes. This manual specically pertains to the OPTImizer2 with rmware
version 1.0.1.
Intellectual Property
This document contains proprietary information and is protected by copyright. All rights reserved. This document may
be reproduced so long as it remains in the custody of the original purchaser, and is used only by the original purchaser’s
personnel for informational purposes. OPTImizer® is a registered trademark of Intelligent Controls.
Warning
Return Shipping Charges
INCON will not accept shipments of returned products without a Return Goods Authorization (RGA) number. RGAs are
obtained by contacting INCON’s Technical Service Division – NO RGAs will be given without the unit’s serial number. Return
material remains the property of the buyer until replaced or repaired.
Only qualied personnel should undertake application, installation, and use of the OPTImizer² on
power systems. While applying this device on the power system, there is always the possibility of
faulty equipment operation and electrical shock. Any of these situations may result in injury or death.
Under Warranty: INCON will pay all freight and insurance charges for RGAs.
Non-Warranty: It is the buyer’s responsibility to prepay all freight and insurance charges for RGAs. Refer to INCON
Warranty Policy document #000-1397
CONTACT INFORMATION
Expect this OPTImizer2 User’s Guide to be revised as new information is available and feedback is gathered from the
eld. We welcome and appreciate any comments. Should any questions develop during application, please contact us for
assistance.
COMMENTSASSISTANCE
INCON - Power Reliability SystemsINCON - Power Reliability Systems
Product ManagerTechnical Service Division
34 Spring Hill RoadTel: 800-872-3455
PO Box 638www.incon.com / contact.aspx
Saco, ME 04072
e-mail: JWebber@incon.com
Tel: 207-283-0156Fax: 207-283-0158
2
Page 3
Contents
List of Tables ........................................................................................................................... 6
The OPTImizer2 is an On-Line Circuit Breaker
Performance and SF6 Gas Density Monitor that is used
for implementing predictive maintenance, maintenance
deferral, just-in-time (JIT) maintenance and environmental
protection. This intelligent electronic device (IED) monitors
the condition of the main contacts, mechanism and
dielectric; and logs the following information during CB
operation:
• Trip Time (mS) (also known as Opening Time)
• Arc duration (mS) (phase segregated)
• Clearing Time (mS) (also known as Interrupting Time)
2
• Cumulative I
segregated) from arcing
• Restrike Occurrence (phase segregated)
• Mechanism opening travel time (mS)
• Mechanism closing travel time (mS)
• Operation Counts
The OPTI
hexauoride) gas density and temperature, and then
calculates gas pressure, density and pressure trend rates
and changes in mass. The present density, pressure,
mass, density and pressure trend rates, and temperature
are recorded in the history log at regular intervals. There
are alarms for low density and high density or pressure
trend rate.
In addition to alarming of anomalies by LEDs and contact
alarms, digital information is available for retrieval through
a DNP3.0 network or a web browser. The ability to provide
historical data, in addition to alarming at setpoints, makes
the OPTImizer2 ideal for reliability centered maintenance
(RCM) programs.
The OPTImizer2 has passed rigorous standards for
survivability in the electric utility substation environment. It
may be mounted directly in the circuit breaker cabinet, or
in the control house.
A minimal interface to the breaker control and secondary
current circuits is used, employing snap-on CT pickup coils
and two parallel wiring connections. This minimal interface
to the power circuit breaker makes the OPTImizer2 ideal
for both retrot and new applications. One, two or three
SF6 gas density sensors may be used.
The OPTImizer2 is specically designed for use on gas
(SF6) circuit breakers, but can be used on oil and vacuum
breakers.
The wear models used in the OPTImizer2 are valid for any
voltage class and correspond to ANSI / IEEE C37.06-1989.
x T or I x T on the main contacts (phase-
2
mizer
continuously monitors SF6 (Sulfur
1.2 Operation Overview
CONDITION and WEAR LOGGING
• SF6 Density (g / L), Pressure (PSIG, BAR, Kilopascals)
Mass (Pounds, Kilograms)
Trend Rate (units / day) Mass Loss (Pounds,
• SF
6
Kilograms, Pounds CO2, Metric Tonnes CO2)
• Trip Time (mS)
• Duration of the arcs (by phase) during tripping (mS)
• Clearing Time (mS)
2
• Cumulative I
segregated) from the arcs during tripping
• Restrike Occurrence (by phase)
• Mechanism opening travel time (mS)
• Mechanism closing travel time (mS)
• Operation Counts (Time and Date Stamping is provided
for each trip operation.)
Alarm set-points may be entered against these items.
SENSING INPUTS
AC Current Input Channels
Three signals (one per phase) from split-core CT pickup
coils placed around the secondary of each circuit breaker
primary phase CT. The signal is proportional to 0-(Max) A
in the primary CT’s secondary circuit (where “Max”= 20,
30, 50, 100,160, 250, 400 or 800 Amps depending upon
the CT range chosen).
System frequency may be at 50 or 60 Hz. These signals
are used to record the arc duration and cumulative I
I x T contact duty. I2 x T or I x T calculations are accurate in
the presence of DC offset and sinusoidal harmonics up to
the 16th.
Split-Core CTs
The OPTImizer2 is designed to be used with INCON Split-Core pickup coils only. Models CT-20, CT-30,
CT-50, CT-100, CT-160, CT-250, CT-400 and CT-800
are custom designed for the accuracy required by the
OPTImizer2. Range is 1.4-20A, 2.1-30A, 3.5-50A, 7.0-
100A, 11.2-160A, 17.5-250A, 28.0-400A and 56.0-800A
respectively. Three CT’s (one per phase) are provided in a
CT kit. These split-core CT pickup coils snap-on for easy,
non-intrusive installation to the circuit breaker secondary
current circuits. Burden is 0.05VA @ 5 amp.
SF6 Input Channels
Two types of SF6 gas density sensors may be used:
2-wire 4-20mA “analog” or INCON Model DSSP “digital”
type sensor. This input is user-congurable for up to
three sensors. For analog sensors, the density units
(grams / liter) are scalable over all or a portion of the
4-20mA signal range. Sensor power of 20VDC is provided
for each channel. SF6 gas temperature can also be
measured if the “digital” sensor is used.
x T or I x T on the contacts (phase
2
x T or
7
Page 8
DC Input Channels
Two discrete voltage signals, 48-250 VDC. The “Aux A”
input is used to initiate the trip time log, the mechanism
time log, the arc duration time log, and the cumulative
I2 T or I T duty log. The “Aux B” input is used to stop the
mechanism time log.
A continuous interrogation process detects Aux input logic
failure when both inputs are asserted or de-asserted at
the same time for longer than 3 seconds. This conicting
input would indicate a serious problem with the circuit, DC
power has been lost, a wire is broken, etc. This condition
causes an “A-B Logic” alarm.
EVENT TRIGGERING
•TRIP TIME (opening time log) – (Available in
INPUT MODEs 2 & 4 only.) The start is triggered by
a positive assertion (rising edge) to the Aux A input.
The stop is triggered by the de-assertion (falling
edge) of the Aux A input, with the actual buffer stop
time adjusted by the software setting A INPUT DELAY, which accounts for the time difference
between the Aux A de-assertion and the actual
parting of the main contacts.
•ARC TIME (arc duration log) – maximum duration
is 10 cycles per trip operation; the start time is
indexed by an assertion of the Aux A input, with the
actual buffer start time adjusted by the software
setting A INPUT DELAY, which accounts for
the time difference between the Aux A assertion
and the actual parting of the main contacts. A
proprietary algorithm that detects the end of arc
current in all three phases triggers the stop. See
Figure 6.
•CLEARING TIME (interrupting time log) –
(Available in INPUT MODEs 2 & 4 only.) The start
is triggered by the assertion (rising edge) of the Aux
A input. A proprietary algorithm that detects the end
of arc current in all three phases triggers the stop.
•TRAVEL TIME (mechanism time log) – (Available
in INPUT MODEs 1 & 4 only.) maximum duration is
10 cycles per trip operation; the start is triggered by
a change in state of the Aux A input. An assertion to
the Aux B input triggers the stop.
•CLOSING TIME (mechanism time log) – (Available
in INPUT MODE 1 only.) maximum duration is 10
cycles per trip operation; the start is triggered by
an assertion to the Aux B input. An assertion to the
Aux A input triggers the stop.
•MAIN CONTACT ARCING DUTY LIFE (phase
segregated I2 T or I T per trip operation and phase
cumulativeI2 T or I T data log); A mathematically
calculated value representative of the destructive
arc energy.
8
FIELD OUTPUTS
Visual Display
On-board LEDs will illuminate and latch when reaching an
alarm setpoint or detecting a failure mode. These may be
reset by software command.
The circuit breaker OPEN / CLOSED status is also
shown by green and red LEDs on the OPTImizer2. This
OPEN / CLOSED status indicator should only be used as a
secondary indication and to verify correct programming of
A INPUT POLARITY and B INPUT POLARITY assertion
states.
An LED bar graph alternates every 10 seconds between
indicating the remaining contact life and the SF6 gas level.
In both cases, the condition of the worst phase is displayed.
When more than one LED is lit, the contact life is being
displayed. When a single LED is lit, the SF6 level is being
displayed.
The scale is -50% to +100% for contact life. The scale for SF6
gas level is based upon the programmed SF6 Fill (density
or pressure), the Low Gas Warning Limit and the low Gas
Alarm Limit.
When displaying remaining contact life, the green zone is
scaled from 100% remaining life to the Warning Limit. The
yellow zone is scaled from the Warning Limit to the Danger
Limit (0% life). The red zone is scaled from the Danger Limit
to 50% below the Limit.
When displaying
SF6 gas level, the green zone is scaled from
the Fill (density or pressure) value to the Low Gas Warning
Limit. The yellow zone is scaled from the Low Gas Warning
Limit to the Low Gas Alarm Limit. The red zone is scaled from
the Low Gas Alarm Limit to zero (pressure or density).
When the display is in the green zone, the LED(s) will be
lit continuously. When the display is in the yellow zone, the
LED(s) will ash slowly to indicate an approaching alarm
condition. When the display is in the red zone, the LED(s) will
ash rapidly to indicate an alarm condition exists.
A slowly
ashing green heartbeat LED indicates that the OPTImizer²
system is functioning normally.
Relay Contacts
Two Form C relays and one Form A relay are provided
for alarms. The dry contacts are rated for 3A at 250 VAC
or 1 / 2A at 125VDC. These contacts are not intended
for breaking DC inductive loads. (For Alarm / relay
assignments, see Figure 8):
• The “RED” relay asserts when a Restrike or excess arc
duration is detected, or when the Contact Life Danger
limit is reached.
• The “YELLOW” relay asserts when a failed CT pickup
coil is detected, the Contact Life Warning limit is
reached, the Operations Count limit is reached, the
open or close mechanism time limit is reached, the Trip
Time limit is reached, the Clearing Time limit is reached,
the No Operations time limit is reached, or an A-B Logic
Alarm condition occurs.
• The SF
relay asserts when a Low Gas Alarm limit or
6
Trend Alarm limit is reached or if there is a malfunction
of the SF6 sensor.
Page 9
POWER INPUT
The OPTImizer2 operates from station battery DC or from
AC station service power. Input Range: 110 to 250VDC, 90
to 264VAC. Power Consumption: 15 VA maximum.
COMMUNICATION PORTS
These ports are for setting, alarm acknowledgment, history
reset, and data viewing / dumping using the DNP3.0 protocol.
RS-232:
Connection: RS-232C, 9-pin female, DCE. A “straight
through” cable should be used for connection to a DTE
device, such as a PC. (Note:The ASCII protocol is no
longer supported on this port.)
Factory preprogrammed settings for RS-232 and RS485 communication:
Data bits: 8
Stop bits: 1
Parity: None
Baud rate: 9600 bps
Flow control: None
DATA STORAGE
Data is stored in non-volatile memory. The memory holds
the most recent 5000 records in a database. A “record” will
be made of events that include: program settings changes,
CB opening, CB closing, alarm occurrences and scheduled
data logs.
SELF DIAGNOSTICS
A blinking green “power on” LED indicates satisfactory
operation of the microprocessor system. An "Input Signal"
LED indicates the malfunction of a CT Pickup Coil or
SF
6
sensor.
PHYSICAL
Size: 8.69W x 5.63H x 2.75D, Inches Nominal
Weight: 4 Lbs. 8 Oz.
PERFORMANCE
• Temperature: -20 to +150° F
• Surge Withstand: ANSI C37.90.1, SWC Test
• Electrostatic Dissipation: IEC 810-2
• Environmental: ANSI C37.1
RS-485:
The port is full-duplex and un-terminated. The port can
be congured for half-duplex by adding jumpers from Tx+
to Rx+ and from Tx- to Rx-. If the OPTImizer² is the last
device in a network, the Transmit and Receive lines need
to be properly terminated with a 120 ohm resistor.
Ethernet:
This port is can be used with DNP 3.0 and TCP / IP
protocols simultaneously (in multi-sessions). When
connected to a secure local area network (LAN) the
OPTImizer² can be accessed remotely with a web browser,
providing the correct IP address is given. Firmware
upgrades can also be performed through this port using a
special upgrade tool (contact INCON Technical Services).
USB COMMUNICATION PORT
This port is for data dumping (BIN les and ASCII text
les), alarm acknowledgement or rmware upgrades. It
will Interface only to a USB memory stick. A memory stick
with a special software tool can be used to acknowledge
alarms. This software tool can be downloaded from the
OPTImizer2 Product CD. A memory stick containing a
special upgrade script and les can be used to upgrade
the rmware (contact INCON Technical Services). (See
section 6)
COMMUNICATIONS SOFTWARE
The OPTImizer² is equipped as a web server. A common
web browser is all that is needed to communicate to the
OPTImizer² using the TCP / IP protocol. If DNP3.0 protocol
is used, the DNP Master device will have the proper
software for network communication. The OPTImizer²
will respond to properly addressed and validated DNP
commands.
9
Page 10
2 I N S TA L L A T I O N
2.1 External Connections (Termination)
110-250 VDC (Twisted Pair Recommended)
90-264 VAC 50/60Hz
Contact Rating: 3A @ 250 VAC or
1/2A @ 125VDC
Terminal Screw
maximum torque
12 inch-Lbs
Use Twisted Pair Cable
Figure 1: OPTImizer² Field Wiring
Density Sensors
SF
6
2
The OPTImizer
should be installed
as close to the CT Pickup Coils as
possible. Cut any excess cable from the
Pickup Coils. It is not recommended to
extend the Pickup Coil cables.
10
Page 11
2.2 Mounting Dimensions
Figure 2: OPTImizer² Mounting Dimensions (Not actual size)
11
Page 12
12
Figure 3: OPTImizer² General Dimensions
Page 13
2.3 SF6 Sensor Mounting
Pipe Thread
INCON offers an SF6 density sensor as an accessory to
the OPTI
signal. This sensor uses a G 3 / 8” British Standard parallel
pipe thread with an O-ring seal. An appropriate adaptor
tting will be required when installing one of these sensors
into a manifold or vessel with a different thread.
Other brands of SF6 density sensor are available
with many other pipe thread options. Be sure you are
combining the appropriate sensor threads with the
appropriate adaptor tting threads.
Location
It is always preferable that the
mounted as close to the gas vessel as possible, so that the
sensor can be close to the same temperature as the vessel.
The INCON DSDP is a “true density” sensor, not a
temperature-compensated pressure sensor. For this
reason, it is less critical that it be mounted as close as
possible to the SF
is not as affected by temperature.
Other brands of SF6 density sensor may be used. Virtually
all other brands are temperature-compensated-pressuretype sensors. It is more critical to mount this type of sensor
mizer²: The Model DSDP with digital output
SF6
density sensor be
gas vessel. The density measurement
6
as close as possible to the SF
gas vessel, so that the
6
temperature of the SF6 gas can properly affect the sensor.
A difference in temperature between the SF6 gas in the
vessel and a sensor of this type will cause an error in the
density output signal.
The SF6 density sensor may be installed alongside an
existing SF6 density switch or gauge. If only one opening
is available, a “T” tting may be used to create a second
opening for the sensor.
Any air in the piping to the sensor can delay accurate
density measurement for up to two weeks. The sensor
should be installed with the gas port facing upward if
possible. A SMALL amount of SF6 can be bled past the
sensor threads before tightening the sensor to purge
trapped air.
Extreme care must be taken when
Caution
installing sensors. A gas-tight seal
must be achieved on all pipe tting and
sensor threads.
Vacuum
If a vacuum is used to extract air before lling a breaker
with SF6 gas, do not expose the density sensor to vacuum
greater than one atmosphere.
SF6 Sensor Connections
Pin 1: Connect to Optimizer² + Terminal (Red Wire)
Pin 2: Connect to Optimizer
² — Terminal (Black Wire)
Pins 3 & 4: No Connection
G ⅜" Thread
1.06" Dia.
(27 mm)
0.454"
(11.5 mm)
3.24"
(82.3 mm)
4
12
3
Viewed from end
2.00"
(50.8 mm)
1.135"
(28.8 mm)
Figure 4: DSDP Sensor Connections
13
Page 14
2.4 Planning for Installation and Programming, Required Field Documentation
The OPTImizer2 application should be planned, much like the application of other IEDs, such as a protective relay, fault
recorder, or monitor. Actual programming and installation can be accomplished in a few hours (typically 2 hours) after the
setpoints are calculated and determined. The required information is tabulated below:
InformationSource(s)
CT Primary Coil Ratio
Logic and Assertion Levels of
Aux A and Aux B inputs
Time Difference Between Aux
A input Assertion and Parting
of Main Contacts
One Line Diagram, Visual Inspection of
Applied CT Ratio
Circuit Breaker Elementary Diagram
Trip Trace, ANSI Standards (C37.06)
•Bushing CT Ratio
•Input Mode
•A Input Polarity
•B Input Polarity
•A Input Delay
(Time Difference between Aux A input and
the main contacts parting)
AffecTed SeTTINgS / USe
•Contact Life Mode
2
x T or I x T)
(I
•Contact Life Danger Limit
•Contact Life Warning Limit (%)
•Operations Count Limit
•SF6 Gas Fill Weight
Breaker Nameplate Data
Breaker Manufacturer’s Data Sheets,
Breaker Nameplate, ANSI Standards
(C37.06)
•SF6 Gas Fill Pressure
•SF6 Gas Fill Temperature
•Breaker Volume
Breaker Trip History
Type of Breaker for employing
Restrike Detection
Operations Logs, Relay Fault Records,
Digital Fault Recorders, Oscillographs,
Estimation
Generally used on SF
Gas Breakers•Restrike Alarm (Enable / Disable)
6
•Preset Remaining Contact Life
(% for each phase)
System Frequency•Power System Frequency
Date•DATE
Time•TIME
Site IdenticationSystem Topology, Mapping•Site Name
Baud Rate, Parity, Flow
Control, Stop Bits
Pre-programmed Setting, Interfaced
Communication Equipment if Networked
Table 1: Required Information for Application
•Port Settings
14
Page 15
General Planning Considerations
A
B
C
Aux B Interface
Aux A Interface
Phase A, Snap-on CT
Phase B, Snap-on CT
Phase C, Snap-on CT
Phase A, Snap-on CT
Phase B, Snap-on CT
Phase C, Snap-on CT
R
G
Aux A Interface
Aux B Interface
Bushing CT (Typ.)
Phase Relay (Typ.)
Ground Relay
(Typ.)
BREAKER CABINET
CONTROL HOUSE
orTI
TI
b
a
or
The OPTImizer2 may be installed in a control house or breaker cabinet. The required interfaces can be obtained at either
location. The SF6 sensors must be installed on the circuit breaker itself. Sensor accuracy is best when installed nearest to
the interrupter vessel.
The OPTImizer2 should be installed as close to the CT Pickup Coils as possible. Cut any excess cable from the Pickup
Coils. It is not recommended to extend the Pickup Coil cables.
Phase A, CT Pickup Coil
Phase B, CT Pickup Coil
Phase C, CT Pickup Coil
Phase A, CT Pickup Coil
Phase B, CT Pickup Coil
Phase C, CT Pickup Coil
Figure 5: Breaker Cabinet and Control House Interface
15
Page 16
The actual installation location may be determined after review of many factors, some of which are outlined below:
Circuit Breaker Cabinet Mounting
ProsCons
Trip initiate signal may not be available should
Readily accessible to Maintenance personnel.
A 52 / a contact (in the actual trip circuit or
individually wetted) for asserting the Aux A input,
and a 52 / b contact (in the actual green light circuit
or individually wetted) signal for asserting the Aux
B input are readily available. A trip initiate signal
may also be available for the Aux A input assertion if
desired.
it be the desired interface for the Aux A input
assertion.
May be environmentally unfriendly (temperature,
humidity, electrical noise, transients) for both the
equipment and personnel.
Secondary current circuit interface is readily
available (from bushing CTs).
Centralized location for multiple unit installations.
Trip Initiates (red light) signal for asserting the Aux
A input, and an end of mechanism travel (green
light) signal for asserting the Aux B interfaces are
readily available. A 52 / a contact signal may also
be available for the Aux A input assertion if desired.
Secondary current circuit interface is readily
available (from relays).
Usually easier to integrate (short physical wiring
runs in close proximity to an RTU, PLC, substation
computer, modem, port switcher, etc.).
Environmentally friendly (temperature, humidity,
electrical noise, transients) for both the equipment
and personnel.
Integration may be more difcult (long distances,
electrical noise, step potential).
May lie within an area not readily accessible to
Maintenance personnel.
The 52/a and 52/b may not be available if they
are the desired interface for the Aux A and Aux
B input assertion.
Not near SF
ports on circuit breaker, long cable
6
runs from sensors may increase noise.
Table 2B: Control House Installation Considerations
16
Page 17
3 APPLICATION GUIDE
3.1 Breaker Wear Symptoms
Breaker Wear Symptoms
Power circuit breakers exhibit symptoms of wear from
the stresses of operation. The wearing of a breaker may
adversely affect the mechanism, the dielectric capabilities
for extinguishing an arc, and the main contacts by erosion
due to duty (wear).
Mechanism Condition
The mechanism operation during a trip essentially consists
of three events:
• Trip Latch Operation
• Travel Mechanism Operation
• End of Travel Mechanism (dashpot, including
preparation for closing)
• Closing Mechanism Operation
Samples of issues that may cause problems within the
mechanism are:
• Poor trip coil action due to high impedance or
shorted turns
• Sticking in the latch
• Lack of lubrication
• Binding of components
• Bearing wear or seizure
• Compromise in the stored energy system (spring,
pneumatics)
Any of these may manifest themselves as a decrease
in the breaker travel velocity. Accompanying a slowing
in velocity would be a detectable increase in transit time
from the closed to tripped (open) position. This is due to
the relationship of V T = D, where V is velocity, or rate
(in. / sec.), T is time (secs.), and D is distance (in.).
Solving for T, the equation transforms to T = V / D. Any
decrease in velocity must be accompanied by an increase
in time. In the case of a power circuit breaker, if the time
interval between two signals is monitored, one being
the beginning of travel and the other the end of travel,
increases in transit time can be detected.
2
The OPTI
mechanism travel transit times (open and close) to aid in
determining the condition of the mechanism, and predicting
when maintenance is needed.
mizer
monitors trip response time and
Dielectric Capability
The ability of a circuit breaker to extinguish an arc can
be monitored by examining the amount of time an arc is
present after a trip command to the breaker is given. If the
mechanism transit time remains constant, but an increase
in arc duration is noted from a baseline level, some
“dielectric” compromise can be assumed to have occurred
in the arc chamber. Samples of issues that may cause
problems in the ability of a circuit breaker to extinguish an
arc are:
• Contaminated oil
• Contaminated gas
• Low gas density
• Worn bafes
• Nozzle ablation
2
The OPTI
determining if maintenance is needed to prevent loss of
dielectric and to predict when gas needs to be added.
The OPTImizer2 monitors arc duration time to aid in
determining the condition of the dielectric quality within the
arc chamber, and predicting when maintenance is needed.
The OPTImizer2 monitors phase segregated I2 x T or
I x T values from each operation, and maintains a phase
segregated summation log of the cumulative duty that each
pole has undergone to aid in determining the condition of
the main contacts within the arc chamber.
Main Contacts Erosion Due to Duty
The main contacts of a circuit breaker erode (wear) from
the heat present during the arc interval. The relationship
for breakers with a medium (air, gas, oil) is expressed
in ANSI C37.06, Rating of Power Circuit Breakers on a
Symmetrical Basis, as a dI / dT function, which can be
reduced to an I2 x T expression.
The erosion of the main circuit breaker contacts is directly
proportional to the I2 x T present during each arc. To
effectively measure the I2 x T during the arc interval, steps
must be taken to insure that DC offset is included in the
calculation, and the sampling rate is high enough to insure
that harmonics present within the arc are also accounted
for in the calculation.
mizer
monitors SF6 gas density to aid in
17
Page 18
3.2 Description of Circuit Breaker Monitoring
Typical Trip Trace Example
A typical trip trace is illustrated in Figure 6. The OPTImizer2, by examining signals corresponding the start of the trip (trip
initiate or the 52 / a contact opening), the end of mechanism travel (green light or 52 / b contact closing), and secondary
phase currents can obtain a wealth of information about the power circuit breaker.
Figure 6: Typical Trip Trace, with Arc Duration Information Superimposed
General Comments
Examination of a typical trip trace allows the quantities the
OPTImizer2 records to be visualized. Arc duration (ARC),
although not possible to record during a de-energized trip
test using conventional test equipment, is shown here for
illustration.
The time line corresponding to the parting of the main
contacts (mains) is used to determine the time difference
between this event and either the trip initiate or the 52 / a
contact opening. In each case the A INPUT DELAY time
will be different. The choice to use the trip initiate or the
parting of the 52 / a will depend on where the OPTImizer’s
Aux A input is wired in the circuit. The proper A INPUT DELAY must be programmed accordingly. The ability
to know this time difference allows the OPTImizer2 to
precisely start timing the arc for both the arc duration
record and the wear duty (I2 x T or I x T) calculations.
Reference for the following function descriptions in this
section should be made to Figure 6A, Typical Trip Trace
Diagram.
Interface to Breaker Secondary Current
Secondary Current Interface - The per phase (fA,
fB, fC) interrupting duty information and arc duration
information is ascertained by interfacing to the bushing
CT secondary current circuits using snap-on CT Pickup
Coils. The acquisition of interrupting current information
is therefore non-intrusive, as the CT secondary current
circuits do not have to be cut or otherwise modied. No
shunts are required.
The CT secondary circuits are available at the breaker
cabinet and the control house, (if there is a control house).
The Protective Relay Bushing CT’s secondary circuits
should be used, since Metering CTs may saturate at high
current levels associated with fault duty.
18
Page 19
Interface to the Breaker Control Circuits
Two discrete voltage inputs are used to obtain information
to determine the start of the trip (Aux A) and the end of
mechanism travel (Aux B). These two inputs may be
directly coupled, using parallel wiring connections, to
the breaker control circuit or separately wetted breaker
auxiliary contacts. Additionally, auxiliary relays or diodes
may be used for isolation or to accommodate dual trip
circuits. No shunts are required.
Depending on the application, the voltage state can
change from no-voltage to voltage, or voltage to novoltage. The OPTImizer² is programmed to react to one
of the changes as an assertion to an input. De-bounce
circuitry is employed, and input assertions are dened as
the rst transition point in voltage.
Aux A Input Interface
The Aux A input is the starting trigger for the Trip Time log
and the mechanism time log. With the time adjustment
from the A INPUT DELAY setting, the Aux A starts the arc
duration log and the wear duty logs.
The Aux A input interface is made using a parallel connection
in the actual breaker control circuit: to the trip initiate
(shunting of the red light or the Trip Coil); to the 52 / a
contact (closed to opened), or an individually wetted 52 / a
contact (closed to opened) that is not in the actual trip circuit.
There are other possibilities using additional interface
devices, such as isolating relays and diodes.
There are advantages to using the Trip Coil signal for
assertion of the Aux A input:
• Allows capture of the latch time in the Trip Time log.
As many mechanism problems are in the latch, this
is the most important advantage. Use of the 52 / a
contact for interface will not allow capture of the
latch time in the mechanism time log.
• Repeatable signal with no “slop” issues as can occur
with mechanically linked auxiliary contacts.
The OPTImizer²’s Aux A input is fused, optically isolated
and transient protected. If it fails, it will be open, therefore
it cannot cause a false trip or short circuit when applied in
actual breaker control circuits.
Aux B Input Interface
The Aux B input is the stopping trigger for the mechanism
time log. The Aux B input assertion can be made using
either a green light signal (off to on) or a 52 / b contact
state change (opened to closed). There are other
possibilities using additional interface, such as isolating
relays and diodes.
INPUT MODE
The Aux Input logic mode can be programmed for one of
four conditions:
Mode 1: Use this mode when the Aux A & B Input voltages
remain continuously high or low until a breaker event
occurs (as when wired across the red and green lights),
then change to the opposite state and remain constant
until the breaker is reset. In this mode, TRIP TIME and
CLEARING TIME are not logged and their alarms are
disabled.
Mode 2: Use this mode when the Aux A Input voltage
changes state momentarily, when a breaker event occurs
(as when wired to the trip coil signal), but Aux B is not
wired. In this mode, TRAVEL TIME and CLOSING TIME ,
and A-B LOGIC data are not recorded and their alarms are
disabled. The circuit breaker OPEN and CLOSED states
cannot be indicated in this mode. The red “CLOSED” LED
will be lit continuously.
Mode 3: Use this mode when the Aux A Input voltage is
continuous, as in Mode 1, but Aux B is not wired . (Used
in cases where there is no Aux B switch available) In
this mode, TRIP TIME, CLEARING TIME, TRAVEL TIME,
CLOSING TIME, and A-B LOGIC data are not logged and
their alarms are disabled.
Mode 4: Use this mode when the Aux A Input voltage
changes state momentarily, when a breaker event occurs
(as when wired to the trip coil signal) and the Aux B input
voltage remains continuously high or low until a breaker
event occurs, then changes to the opposite state and
remains constant until the breaker is reset. In this mode,
the OPTImizer² can record TRIP TIME, CLEARING TIME,
TRAVEL TIME and A-B LOGIC data and their alarms can
be active. Closing Time cannot be recorded and its alarm
will be disabled.
TRIP TIME (Trip Mechanism Time Log) (Input Modes 2
& 4 only)
When INPUT MODE 2 or 4 is selected and the "Aux A"
input is wired as shown in Figure 14, the OPTImizer²
will record TRIP TIME. The TRIP TIME log consists of a
timer. The timer starts from an assertion of the “Aux A”
input, and stops with the de-assertion of the “Aux A” input,
adjusted by the A INPUT DELAY value. The assertion
level is dened in software (A INPUT POLARITY), and
is application-dependent. The TRIP TIME measurement
starts with the Trip Initiate voltage application to the Trip
Coil and ends when the 52a contact opens (+ / - A Input Delay value), de-energizing the Trip Coil.
The Aux B input is fused, optically isolated and transient
protected. If it fails, it will be open, therefore it cannot
cause a false indication or short circuit when applied in
actual breaker control circuits.
19
Page 20
TRAVEL TIME (Mechanism Time Log) (Input Modes 1 & 4 only)
When INPUT MODE 1 or 4 is selected, the OPTImizer² will record mechanism TRAVEL TIME. The mechanism time log
consists of a timer. The timer starts from an assertion (or de-assertion in Mode 4) of the “Aux A” input, and stops with an
assertion to the “Aux B” input. The assertion levels are dened in software (A INPUT POLARITY & B INPUT POLARITY),
and are application-dependent.
It is possible to start the mechanism trip transit time log from one of two instances, either the trip initiate signal, or the
opening of the 52 / a contact.
Note: The “Aux A” input is the common start for both the mechanism time log and the arc time log functions.
ARC TIME (Arc Time Log)
The individual, phase-segregated Arc Time logs employ a timer, starting with the main breaker contacts parting and
ending with the cessation of current in each phase.
Starting of the Arc Time Log
The arc time log is indexed to start with an assertion (or de-assertion in Modes 2 & 4) of the “Aux A” input. The assertion
level is dened in software (A INPUT POLARITY), and is application dependent. The actual starting of the log is
dependent on a setting used to adjust the time interval difference between the “Aux A” assertion and the actual parting of
the mains. This adjustment time is referred to as A INPUT DELAY in Figure 6.
The A INPUT DELAY value may be either positive or negative, depending on if the “Aux A” assertion is later or earlier than
the mains parting:
• The adjustment time (A INPUT DELAY) is positive (+), if the mains part later than the “Aux A” assertion
• The adjustment time (A INPUT DELAY) is negative (-), if the mains part earlier than the “Aux A” assertion
Note: The “Aux A” input is the common start for both the mechanism time log and the arc time log functions.
Stopping of the Arc Time Log
The arc time logs stop with the cessation of current in each phase. The cessation of current is determined by a proprietary
software algorithm which does waveform analysis in addition to checking for CT Secondary current falling below 7% of the
Pickup Coil full scale current rating for more than 8 consecutive samples (1 / 4 cycle).
Note: In instances where the CT Secondary phase currents are less than 7% of Pickup Coil full-scale current rating and
the breaker trips, an ARC TIME of 000 mS will be recorded.
20
Page 21
CLEARING TIME (Clearing Time Log) (Input Modes 2 & 4 only)
The individual, phase-segregated CLEARING TIME logs use a timer, with the starting point at the beginning of the Trip
signal and ending with the cessation of current in each phase. Thus the Clearing Time for each phase is the sum of the
measured TRIP TIME and ARC TIME. The programmable A INPUT DELAY value has no effect on the CLEARING TIME.
This time represents the interrupter's overall efciency, both mechanical and dielectric.
The individual, phase-segregated main contact wear duty logs employ a method of recording the destructive energy of
each arc incident that is programmable for I2 x T or I x T. The measured current is (squared for I2 x T and then) multiplied
by the time between measurement samples. The sum of these sample calculations is recorded in the main contact duty
wear logs for each phase, for each arc event. As subsequent arc events occur, the measured I2 x T or I x T is added to the
phase-segregated main contact wear duty accumulation logs.
Note: If the CT Secondary phase currents are less than 7% of the Pickup Coil’s full-scale current rating and the breaker
trips, an ARC TIME of 000mS will be recorded. The values of I2 x T or I x T recorded for such incidents are recorded
as 0 in the wear duty log.
Operations Counter
A counter will increment each time the circuit breaker opens. An Operations Count alarm limit can be programmed. When
the operations count reaches the limit an alarm is asserted.
Restrike Detection
The RESTRIKE setting is used to enable the detection of restrikes. When Restrike detection is activated, the ANSI
C37.100 criterion is used, which states that if an arc is extinguished, and more than ¼ cycle later it re-ignites, that is
considered a restrike (see Figure 22 on page 46). If a re-ignition takes place before the ¼ cycle period elapses, it is not
considered a restrike, but rather a continuance of the original arc. The rst restrike detected will assert the alarm. Each CB
Trip record in the Circuit Breaker Event History will indicate whether a restrike has occurred by phase - true or false.
21
Page 22
Time Line to Trip Trace Correlation (Examples)
The following examples show how the OPTImizer2 logs events.
They include:
• Arc record examples
• Interactions of the Aux A and Aux B inputs
• The phase currents
• The A INPUT DELAY setpoint
• The ARC TIME and TRAVEL TIME setpoints
The setpoints and applied limits for the following examples are given below each time line (Figs. 6A, 6B, 6C and 7).
MECHANISM
TRIP MECHANISM
TIME (TRIP TIME),
(24 mS)
TRAVEL TIME, difference
between Aux A and Aux B
Input state changes
(49 mS)
Figure 6A: Trip Trace, Using Trip Coil Voltage to Start OPTImizer
22
2
Page 23
Figure 6B: Event to Time Correlation of Fig 6A,
Using Trip Coil Voltage to Start OPTImizer
2
Example:
• The Aux A input on the OPTImizer2 is asserted by the Trip Signal voltage measured across the Trip Coil.
• The recorded TRIP TIME is 25mS
• The recorded TRAVEL TIME is 51mS (94mS – 43mS)
• The recorded ARC TIME is 32mS
• The recorded CLEARING TIME is 56mS
• The A INPUT DELAY Setting is -19mS, as the assertion to the Aux A input on the OPTImizer2 is the breaker Aux A
contact, which opens 19mS after the main contacts part (A INPUT DELAY is negative when the assertion to the Aux
A input is later than the main contacts parting)
• The TRIP TIME alarm limit is 30mS
• The ARC TIME alarm limit is 48mS (32mS plus 16mS margin)
• The CLEARING TIME alarm limit is 78mS (56mS plus 22mS margin)
• The TRAVEL TIME alarm limit is 76mS (51mS plus 25mS margin)
This OPTImizer2 would not be in an alarm state after this operation.
23
Page 24
Figure 6C: Event to Time Correlation of Fig 6A
Using a Separately Wetted 52 / a Contact to Start OPTImizer2 Measurements
Example:
• The Aux A input on the OPTImizer2 is asserted by voltage from a separate contact on the 52 / a switch.
• The TRIP TIME cannot be recorded with this wiring method.
• The CLEARING TIME cannot be recorded with this wiring method.
• The recorded TRAVEL TIME is 51ms
• The recorded ARC TIME is 32mS
• The A INPUT DELAY Setting is -19mS, as the assertion to the Aux A input on the OPTImizer2 is the same Aux A
switch, which opens 19mS after the main contacts part (A INPUT DELAY is negative when the assertion to the Aux
A input is later than the main contacts parting)
• The ARC TIME alarm limit is 48mS (32mS plus 16mS margin)
• The TRAVEL TIME alarm limit is 76mS (51mS plus 25mS margin)
This OPTImizer2 would not be in an alarm state after this operation.
24
Page 25
T
ref
=0
Current
"Aux A" input
"Aux B" input
3040506070809020
TIME (mS)
Not Asserted
Asserted
Pre- or Post Trip Event, Asserted
Pre- or Post Trip Event, Not Asserted
Aux A Input asserts at T
ref
= 0
Main Contacts open at T=24mS
Arc Extingushes at T=56mS
Arc Duration 56mS minus 24mS=32mS
Aux B Input asserts at T=94mS
Aux A assertion is 24mS earlier than Mains Parting
AD = +24
10
0
AD = +24
Total Arc Duration =
32mS
100
110
A Input Delay = +24
A Input Delay = +24
Figure 7: Trip Trace, Using Trip Initiate to Start OPTImizer2
Example:
• The Aux A input on the OPTImizer2 is asserted by the trip initiate signal (red light) in the breaker trip circuit
• The recorded TRAVEL TIME is 94ms
• The recorded ARC TIME is 32mS
• The A INPUT DELAY Setting is +24mS, as the assertion to the Aux A input on the OPTImizer2 is the trip initiate
signal, which asserts 24mS before the main contacts part (A INPUT DELAY is positive when the assertion to the
Aux A input is earlier than the main contacts parting)
• The ARC TIME alarm limit is 48mS (32mS plus 16mS margin)
• The TRAVEL TIME alarm limit is 141mS (94mS plus 47mS margin)
This OPTImizer2 would not be in an alarm state after this operation.
25
Page 26
Alarm Set-points
The following recorded parameters have alarm set-points placed against them. Specically, these alarm points are:
ParameterUnitsSeTpOINT ReSOLUTIONRange
Trip TimemS1mS0-999 mS
Arc TimemS1 mS0-165 mS
Clearing TimemS1mS0-265 mS
Travel TimemS1 mS0-265 mS
Contact Life WarningPercent0.1 Percent0.0% to 99.0%
Contact Life DangerAmp (Squared) - Seconds
0.1 • 10x, where x is the
base 10 exponent
0.1 to 9.9 • 10
Operation CountsOccurrences1 Count0-9999 Counts
No Operations TimeDays1 Day0-999 Days
Closing TimemS1 mS0-999 mS
SF6 Low Gas WarningBar; PSI; g / L (Kg / m3); Kilopascals0.10.0 to 25 Bar, 60 g / L
SF6 Low Gas AlarmBar; PSI; g / L (Kg / m3); Kilopascals0.10.0 to 25 Bar, 60 g / L
SF
Gas Trend RateBar; PSI; g/L; Kilopascals per day0.1
6
Table 3: Alarm Set-points
0.0 to 40 Bar, 100 g / L
per day
Note: To disable any function, set the value to “0” (The Contact Wear Danger function cannot be disabled).
Alarm Outputs, Indications & Relay Assertions
Upon reaching an alarm setpoint, output designations are:
99
AlarmLEDReLAy cONTAcT
TRIP TIME
ARC TIME
CLEARING TIME
TRAVEL TIME
Contact Life Warning
Contact Life Danger
Restrike
Operation Counts
NO OPERATION TIME
CLOSING TIME
A-B INPUT LOGIC
Failed CT Pickup
SF6 Low Gas Warning
SF
Low Gas Alarm
6
SF
Density or pressure Trend Rate
6
Loss of SF
SF
Sensor Signal Out of Range
6
Invalid Conguration
Internal Error
Input Invalid
Unknown CB Monitor Activity
Unknown SF
Sensor
6
Monitor Activity
6
Slow SpeedYellow
Excess Arc, FlashingRed
Excess ArcRed
Slow Speed FlashingYellow
Bargraph Slow FlashYellow
Bargraph Fast FlashRed
RestrikeRed
Operations FlashingYellow
OperationsYellow
Slow SpeedYellow
Input SignalYellow
Input SignalYellow
, Bargraph Slow FlashNone
SF
6
, Bargraph Fast FlashBlue (SF6)
SF
6
, Blue (SF6)
SF
6
, Input Signal, No BargraphBlue (SF6)
SF
6
No BargraphBlue (SF6)
SF
6,
Closed & Open Fast FlashingNone
Input Signal Fast FlashYellow
Input Signal Fast FlashYellow
Operation Fast FlashYellow
Fast Flash Blue (SF6)
SF
6
Table 4: Alarm Outputs, LED’s and Relays
26
Page 27
Viewed graphically, the alarm relay assignments are:
I²T Danger
Restrike
Excess Arc Duration
Excess Clearing Time
Excess Trip Time
A-B Input Logic
Excess Travel Time
I²T Warning
Operations Count
No Operations
Excess Closing Time
Failed CT Pickup
Internal Error
Input Invalid
Unknown CB Monitor Activity
Low Gas
SF
6
SF
Trend
6
Loss of SF
SF
6
Unknown SF
Sensor
6
Signal out of Range
Monitor Activity
6
OR
OR
OR
Red
Yellow
Blue
SF
6
Figure 8: Alarm Relay Assignments
27
Page 28
3.3 Description of SF6 Density Monitoring
The OPTImizer2 monitors SF6 gas density to aid in
identifying circuit breakers with potential problems.
Investigation and maintenance can be scheduled sooner,
keeping SF6 gas loss to a minimum.
Density Loss
Power circuit breakers that use SF6 gas as a dielectric can
lose gas from one or a combination of several causes.
Lost gas may adversely affect the dielectric capability for
extinguishing an arc, and consequently, the main contacts
by erosion (wear).
Gas Loss Causes
The following issues may cause problems leading to loss
of SF6 gas:
• Gasket deterioration
• Shaft Seal deterioration
• Tank porosity
• Bushing porosity
• Tubing & pipe ttings
• Heater failure (allowing liquefaction)
Any of these may manifest themselves as a decrease in SF
gas density. Accompanying a loss of SF6 gas density may
be a detectable increase in arc duration.
SF6 Gas Monitoring
SF6 Gas Density Sensors The OPTImizer2 monitors
the signal from two types of SF6 gas density sensors:
Analog (4-20mA) and Digital (INCON DSDP). Both types
are connected to the OPTImizer2 with two wires. The
OPTImizer2 provides DC power to the sensors. The
Digital sensor will provide a temperature signal in addition
to the density signal.
6
SF6 Mass Loss Reporting
Once a day, the OPTImizer2 will calculate the change in
SF6 mass. This value will be logged in the SF6 History,
Daily Summary.
Density or Pressure Trends and Alarms
Once a day, the OPTI
mizer
will compute density or
2
pressure trends for each active SF6 input channel. Each
density or pressure trend is based upon measurements
collected over a 15-day time period. A Condence Level
(%) will be associated with each of these trends, indicating
the number of valid readings each trend is based upon and
the stability of the readings. Fifteen days of valid readings
are required for 100% condence in the computed Density
or Pressure Trend.
If the Density or Pressure Trend Alarm Limit is reached
or exceeded, the SF6 Alarm LED will light, the SF6 Alarm
Relay will close and a time-stamped record of the alarm
will be recorded in the history log.
Low Gas Alarm Forecast
Once a day, the OPTI
mizer
2
computes the number of
days before the SF6 gas will reach the Low Gas Alarm
Limit. This forecast will be based upon the Density or
Pressure Trends just computed.
SF6 Gas Data Logging
Every 2 hours, the OPTImizer2 will log the present SF6
gas density, pressure & temperature readings. Once a
day, the OPTImizer2 will log the average density, average
pressure, density or pressure trend, condence level,
mass, change in mass and accumulated mass loss.
At any time, when a warning or alarm occurs, its
occurrence is recorded in the history log.
The OPTImizer2 measures SF6 gas density and
calculates SF6 gas pressure from the measured
density. Pressure calculations are based upon
entered or calculated SF6 gas volume and temperature
measurements. The Pressure Trend is calculated from the
Density Trend and temperature measurements.
SF6 volume is calculated from entered nameplate gas ll
weight, pressure and temperature, or taken directly from
entered gas volume.
Low Gas Warning and Alarm
If the SF6 gas density or pressure decreases, the
OPTImizer2 will give a warning when a programmable
limit is reached. The SF6 Alarm LED will light and a timestamped record of the warning will be logged in the history.
If the SF6 gas density or pressure decreases further, a Low
Gas Alarm will be activated, closing the SF6 Alarm Relay.
A time-stamped record of the alarm will be recorded in the
history log.
28
Page 29
4 PROGRAMMING
4.1 Initial Communication With the OPTImizer2
To initialize communications with an OPTImizer2, use the provided “crossover” cable to connect the Ethernet port on the
OPTImizer2 to the Ethernet port on a computer. Power-up the OPTImizer2 and computer, then set the computer’s IP
address to “192.12.27.2”
Conguring IP Properties for Communication
Before attempting to modify any computer settings, contact the Information Technologies department of your business, if
available. Some computer accounts may have restricted permissions to overcome before any changes are allowed to be
made to TCP / IP settings. At the PC:
Windows XP™
1. Log into your PC with Windows™ operating system.
2. Click on Start, then select Control Panel.
• In Classic View, click on Network Connections.
4. Right-click on Local Area Connection and select Properties.
• In Classic View, click on Network Connections.
29
Page 30
5. In the Local Area Connection Properties dialog box,
under “This connection uses the following items,”
select Internet Protocol (TCP / IP) and click Properties.
6. Select Use the following IP
address.
7. Enter the IP address “192.12.27.2”
Subnet Mask: Masking is a way to diversify the use of multiple subnets. The mask must match that of the network the
OPTImizer2 is connected to. Masks are used in networking to create ‘sub-networks’ within a whole, like slicing an apple.
You have separate slices that may be in different locations, but they are still from the same apple. Administrators use this
to make separate networks, to maximize bandwidth or capacity of medium resources (cables or ber). Therefore, when
your network uses static IP addressing (assigned by an administrator), this mask must match the Subnet Mask of the
router port that it is attached to. If the network uses a DHCP server (automatically assigns IP addresses) then the mask
should meet the specications set by your administrator.
Default Gateway: The Gateway is the logical address to the nearest router port, commonly the one that is connected to
the console. Consult your administrator for details on this and other network parameters.
8. Leave the DNS information blank. Click “OK” and close the Control Panel.
30
Page 31
Windows 7™
Below is shown one way to congure the connection using Windows 7™.
1. Open Windows™ Explorer and right-click on Network.
2. Select Properties.
3. Select Change Adapter Settings
31
Page 32
4. The screen should show the Local Area Connection. Right click on the connection and select Properties.
5. Select Internet Protocol Version 4 (TCP/IPv4)
6. Select Properties
7. Enter the IP address 192.12.27.2
32
Page 33
Check Status of Connection
1. Check the status of your connection by going to the Network Connections window.
2. If the connection status is disabled, enable it by right-clicking on the Local Area Connection and selecting
Enable. If technical difculties arise, please contact INCON Technical Support before proceeding.
Open the web browser. Type the OPTImizer2’s default IP address (192.12.27.1) in the browser’s address eld. You should
see the OPTImizer2’s STATUS page. Click “Conguration”, at the top left, to move to the CONFIGURATION page. Click
“Edit”, at the top right, to make changes to the OPTImizer2’s conguration.
Figure 9: User Interface, Conguration Page
Initial Set-up
Conguration settings required to initially set-up (commission or test) an OPTI
mizer
are included under the following
2
headings:
• Passwords (The default Administrator’s password is “admin”)
• Date / Time
• DNP3
• Circuit Breaker Information
• Circuit Breaker Monitor
Monitor
• SF
6
Sensor A
• SF
6
Sensor B
• SF
6
Sensor C
• SF
6
33
Page 34
Figure 10: User Interface, Conrming Conguration Update
Following the guidelines listed in this manual, make the appropriate changes to each conguration parameter. When all
changes are entered, click “Yes” to update the conguration. The correct Administrator’s password (initially set to “admin”)
will need to be given for the changes to be saved.
Commissioning the OPTI
mizer
2
involves setting most of the available programming parameters. Note that during initial setup
and programming, alarms may be triggered inadvertently. When all conguration programming is done it is recommended to
"Clear Latched Alarms" on the ACTION page to clear alarms and preset the remaining contact life (if desired).
34
Figure 11: User Interface, Action Page
Page 35
4.2 General
IDENTIFICATION
The OPTImizer2 provides four text elds (ID Line 1
through 4) that can be used to identify the circuit breaker,
substation, etc... Up to 40 text characters of all types can
be entered in each eld. (Site Name, Address, City, State
and Telephone are a few suggestions. Any desired text
can be entered). Note that the text entered in ID Line 1 will
be used in the heading of the user interface.
To change the identication text, select the
CONFIGURATION tab and click "EDIT". Type the desired
text in the eld.
PASSWORD
The OPTImizer2 uses three levels of access rights,
Administrator, User and Guest. Each has a separate
password. The Default password for the Administrator is
“admin”.
The Default password for the User is “user”. There is
no default password for the Guest. It is STRONGLY
recommended that the password for the Administrator be
changed immediately. The password for the User should
also be changed for better security.
A password for the Guest can be also added to prevent
access to viewing all data. Passwords are limited to a
maximum of 40 characters. The password can contain
upper and lower case letters and any keyboard character.
If the Administrator’s password is changed and then
forgotten, program settings will not be able to be changed.
If this occurs call the INCON factory for assistance. An
INCON service technician can use a diagnostic password
to reset the Administrator’s password. Remote internet
access to the OPTImizer2 is required for the technician to
do this.
Guest Level rights include the ability to VIEW all
Status, Alarms, Conguration and Preferences data, and
download reports from the history page.
User Level rights include all of the above plus the ability
to clear all alarms, reset the Operations Count and preset
Contact Life.
Administrator Level rights include all of the above plus
saving changes to passwords and program settings.
IP ADDRESS
The OPTImizer2 is capable of internet communication. A
web browser can be used to “log on” to the OPTImizer2
either locally (with the short cable provided) or remotely
through a network and perform all user interface functions.
To access an OPTImizer2, its IP address is needed. A
new OPTImizer2 is shipped with the default IP address of
“192.12.27.1” As part of a network, the OPTImizer2 will
need a different IP address.
To change the IP address, select the
CONFIGURATION tab and click “EDIT”:
Program:IP Address = “nnn.nnn.nnn.nnn”
To change the passwords, select the
CONFIGURATION tab and click “EDIT”:
The correct (old) Administrator’s password will need
to be given for the changes to be saved.
DATE / TIME
The date and time are needed for reference on the trip
records and event history logging.
To change the date and time, select the CONFIGURATION
tab and click “EDIT”:
Time Zone: The local time zone is selected from a pulldown list.
System Clock: The clock time and date can be manually
entered using the pull-down lists or…
Time Server: The system clock can be set from an NTP
server. The IP address of this server can be entered in the
blank eld.
DIAGNOSTICS
The OPTImizer2 is capable of sending diagnostic
information to an IP address. This is used by INCON
Technical Service to help in troubleshooting. It should
be used only when instructed by an INCON Service
Technician. The Technician will provide the IP address
and further instructions. Always call the INCON Technical
Service Division for assistance when troubleshooting a
problem. This Diagnostics utility may help in nding the
source of your problem.
DNP3.0 SETTINGS
The OPTImizer2 can communicate using the DNP3.0
protocol through its Ethernet port, RS-232 port or RS485 port, but only through one port at a time. Therefore,
the DNP3.0 Mode must be selected. If TCP / IP mode is
selected, the TCP / IP port must be specied. If the RS-232
or RS-485 mode is selected, further serial port settings
must be made.
To set up the DNP3.0 Mode, select the CONFIGURATION
tab and click “EDIT”:
Local & Remote Addresses: The DNP3.0 Local and
Remote Address numbers are manually entered in these
elds.
DNP3.0 Mode: The DNP3.0 Mode is selected from a pulldown list.
TCP / IP Port: The DNP3.0 TCP / IP Port is manually
entered in this eld.
Port Settings: The RS-232 & RS-485 Port Settings (Baud
Rate, Data Bits, Parity, Stop Bits) are selected from pulldown lists.
35
Page 36
CIRCUIT BREAKER INFORMATION
The OPTImizer2 can store information about the
circuit breaker in memory. This information is for
reference only. It has no effect on functionality.
To enter Circuit Breaker Information, select the
CONFIGURATION tab and click “EDIT”:
Program: Manufacturer = “ABCxyz123%^&…”
Program: Voltage Rating (KV) = “12345”
Program: Max. Interrupting Current (Amps) =
“1234567890”
4.3 Circuit Breaker Monitor Settings
The following settings are used by the OPTImizer2
specically for circuit breaker monitoring.
POWER SYSTEM FREQUENCY
The applied power line frequency is entered as 60 or 50 Hz.
Note: When the OPTImizer2 is cold-started, the Power
System Frequency parameter is set to 60Hz.
To set Power System Frequency, select the
CONFIGURATION tab and click “EDIT”:
Power System Frequency: The System Frequency is
selected from a pull-down list.
Program:Max. Operations Count = “1234567890”
BUSHING CT RATIO
Entering the applied CT ratio allows the OPTImizer2 to
reect Duty values to the primary base. Enter the applied CT
ratio to set the OPTImizer2 (Primary current to Secondary
current).
Example:
Given: A CT of 1000:5 is applied for a given breaker.
Calculate: Primary Current / Secondary Current = CT Ratio
1000 / 5 = 200
CT Ratio = 200
To set Bushing CT Ratio, select the CONFIGURATION tab
and click “EDIT”:
Program:Bushing CT Ratio = “200”
PICKUP COIL RATING
Entering the applied Pickup Coil Rating allows the
OPTImizer2 to scale the input signal correctly for the
Pickup Coils being used.
36
Note: When the OPTImizer2 is cold-started, the Pickup
Coil Rating parameter is set to “160 Amps”.
Pickup Coil Rating: The Pickup Coil Rating is selected
from a pull-down list.
Page 37
A INPUT POLARITY
(Aux A Input Assertion Level)
Entering the proper Aux A input assertion level allows the
OPTImizer2 to properly start the mechanism time, arc
time, and duty wear logs. The OPTImizer2 reacts to a
change in voltage state when the breaker is proceeding
from the closed position to the open position. These are
dened to the OPTImizer2 as:
• No-voltage to voltage = “Positive”
• Voltage to no-voltage = “Negative”
2
Note: When the OPTI
Polarity parameter is set to “Positive”.
A Input Polarity: The A Input Polarity is selected from a
pull-down list.
To determine the assertion level, reference is made to the
following diagrams.
mizer
T/2T/1
is cold-started, the A Input
OPTImizer
+
2
Aux A
R
Input
• Trip Command - One of the trip initiate contacts
closes, shunting the red light and the Aux A input.
This causes high current to ow through the trip coil,
which begins to pull the latch. The Aux A input would
sense a transition from voltage to no-voltage.
• Breaker Travel - As the breaker begins to travel, the
52 / a contact opens, effectively causing an open
trip circuit. The Aux A input would still sense a novoltage condition (which will remain even after reset
of the trip initiate contacts).
• Fully Opened - The 52 / a contact remains open,
effectively causing an open trip circuit. The Aux
A input would continue to sense a no-voltage
condition.
2
In summation, the OPTI
with the trip initiates, should be set as:
• A Input Polarity = “Negative”
• INPUT MODE = “1” or “3”
mizer
, when applied in parallel
52/a
A Input Polarity
= Negative
TC
ClosedOpen
Figure 12: Aux A Interface, using Trip Initiate (Red Light)
This is an elementary diagram of a typical trip circuit. The
elements T / 1 and T / 2 are trip-initiating contacts. These
could be from protective relays, manual trip switches,
SCADA contacts, etc. With the OPTImizer2 Aux A input
wired in parallel with the trip initiates, (red light), the
voltage levels sensed by the Aux A input during a trip
operation would be as follows:
• Breaker Closed - The trip initiates are open, the red
light is lit, as the 52 / a contact is closed and a low
current is passing through the trip coil. The Aux A
input would sense voltage.
37
Page 38
T/2T/1
T/2T/1
R
OPTImizer
52/a
+
Aux A
Input
A Input Polarity
TC
Figure 13: Aux A Interface, using 52 / a Contact in Trip Circuit
This is an elementary diagram of a typical trip circuit. The
elements T / 1 and T / 2 are trip-initiating contacts. These
could be from protective relays, manual trip switches,
SCADA contacts, etc. With the OPTImizer2 Aux A input
wired in parallel with the 52 / a contact in the trip circuit,
the voltage levels sensed by the Aux A input during a trip
operation would be as follows:
• Breaker Closed - The 52 / a contact is closed. The
Aux A input would sense a no-voltage condition, as
the voltage to the input is shunted.
• Trip Command - One of the trip initiate contacts
closes. This causes high current to ow through the
trip coil, which begins to pull the latch. The Aux A
input would sense a no-voltage condition, with the
52 / a contact remaining closed, as the breaker has
not yet begun to travel.
• Breaker Travel - As the breaker begins to travel, the
52 / a contact opens. The Aux A input would sense a
transition from no-voltage to voltage.
• Fully Opened - The 52 / a contact remains open, and
the Aux A input would continue to sense a voltage.
In summation, the OPTI
with the 52 / a Contact in the trip circuit, should be set
as:
mizer
= Positive
ClosedOpen
2
, when applied in parallel
2
R
52/a
A Input Polarity
= Positive
Trip
Closed
Figure 14: Aux A Interface, using Trip Coil Excitation Voltage
This is an elementary diagram of a typical trip circuit. The
elements T / 1 and T / 2 are trip-initiating contacts. These
could be from protective relays, manual trip switches,
SCADA contacts, etc. With the OPTImizer2 Aux A input
wired in parallel with the Trip Coil in the trip circuit, the
voltage levels sensed by the Aux A input during a trip
operation would be as follows:
• Breaker Closed - The 52 / a contact is closed. The
Aux A input would sense a low-voltage condition, as
the voltage dropped across the Trip Coil is minimal.
• Trip Command - One of the trip initiate contacts
closes. This causes high current to ow through the
trip coil, which begins to pull the latch. The Aux A
input would sense a high-voltage condition, with the
52 / a contact remaining closed, as the breaker has
not yet begun to travel.
• Breaker Travel - As the breaker begins to travel, the
52 / a contact opens. The Aux A input would sense a
transition from high-voltage to no-voltage.
• Fully Opened - The 52 / a contact remains open, and
the Aux A input would continue to sense no voltage.
In summation, the OPTI
with the Trip Coil in the trip circuit, should be set as:
• A Input Polarity = “Positive”
• INPUT MODE = “2” or “4”.
Open
TC
mizer
2
, when applied in parallel
OPTImizer
+
Aux A
Input
2
• A Input Polarity = “Positive”
• INPUT MODE = “1” or “3”.
38
Page 39
52/a
+
OPTImizer
+
Aux A
Input
B INPUT POLARITY (Aux B Input Assertion Level)
Entering the proper Aux B input assertion level allows the
OPTImizer2 to properly stop the mechanism time log. The
OPTImizer2 reacts to a change in voltage state when the
breaker is proceeding from the closed position to the open
position. These are dened to the OPTImizer2 as:
2
•No-voltage to voltage = “Positive”
•Voltage to no-voltage = “Negative”
Note: When the OPTImizer2 is cold-started, the B Input
Polarity parameter is set to “Positive”.
B Input Polarity: The B Input Polarity is selected from a
pull-down list.
A Input Polarity
= Negative
ClosedOpen
Figure 15: Aux A Interface using Individually Wetted 52 / a
Contact
This is an elementary diagram of a typical trip circuit.
With the OPTImizer2 Aux A input wired in series with an
individually wetted SPARE 52 / a contact, the voltage levels
sensed by the Aux A input during a trip operation would be
as follows:
• Breaker Closed - The trip initiates are open, and
the 52 / a is closed. The Aux A input would sense
voltage.
• Trip Command - One of the trip initiate contacts
closes. This causes high current to ow through
the trip coil, which begins to pull the latch. The Aux
A input would continue to sense a voltage, with the
52 / a contact remaining closed, as the breaker has
not yet begun to travel.
• Breaker Travel - As the breaker begins to travel, the
52 / a contact opens. The Aux A input would sense a
transition from voltage to no-voltage.
• Fully Opened - The 52 / a contact remains open,
and the Aux A input would continue to sense a novoltage condition.
In summation, the OPTImizer2, when applied in
series with an individually wetted 52 / a contact,
should be set as:
• A Input Polarity = “Negative”
• INPUT MODE = “1” or “3”.
To determine the assertion level, refer to the following
diagrams.
+
52/b
OPTImizer
2
+
G
B Input Polarity
= Positive
ClosedOpen
Figure 16: Aux B Interface, using Green Light
This is an elementary diagram of a typical 52 / b
contact / green light circuit. With the OPTImizer2 Aux B
input wired in parallel with the green light, the voltage levels
sensed by the Aux B input during a trip operation would be
as follows:
• Breaker Closed - The 52 / b contact is opened. The
Aux B input would sense a no-voltage condition.
• Trip Command - One of the trip initiate contacts
closes. This causes high current to ow through the
trip coil, which begins to pull the latch. The Aux B
input would sense a no-voltage condition, with the
52 / b contact remaining opened, as the breaker has
not yet begun to travel.
• Breaker Travel - As the breaker nears the end of
travel, the 52 / b contact closes. The Aux B input
would sense a transition from no-voltage to voltage.
• Fully Opened - The 52 / b contact remains closed,
and the Aux B input would continue to sense a
voltage.
Aux B
Input
39
Page 40
In summation, the OPTImizer2, when applied in parallel
with the green light, should be set as:
• B Input Polarity = “Positive”.
+
+
52/b
2
52/b
OPTImizer
+
Aux B
Input
G
B Input Polarity
= Negative
ClosedOpen
Figure 17: Aux B Interface, using 52 / b Contact in Green
Light Circuit
This is an elementary diagram of a typical 52 / b
contact / green light circuit. With the OPTImizer2 Aux B
input wired in parallel with the 52 / b contact in the breaker
control circuit, the voltage levels sensed by the Aux B input
during a trip operation would be as follows:
• Breaker Closed - The 52 / b contact is opened. The
Aux B input would sense a voltage from the low
current circuit through the green light.
• Trip Command - One of the trip initiate contacts
closes. This causes high current to ow through the
trip coil, which begins to pull the latch. The Aux B
input would sense a voltage, with the 52 / b contact
remaining opened, as the breaker has not yet begun
to travel.
• Breaker Travel - As the breaker nears the end of
travel, the 52 / b contact closes. The Aux B input
would sense a transition from voltage to no-voltage,
as the voltage to the Aux B input is shunted.
• Fully Opened - The 52 / b contact remains closed,
and the Aux B input would continue to sense a novoltage condition.
OPTImizer
2
+
Aux B
Input
B Input Polarity
= Positive
Closed Open
Figure 18: Aux B Interface, using Individually Wetted 52 / b
Contact
This is an elementary diagram of an individually wetted
SPARE 52 / b contact. With the OPTImizer2 Aux B input
wired in series with this contact, the voltage levels sensed by
the Aux B input during a trip operation would be as follows:
• Breaker Closed - The 52 / b contact is opened. The
Aux B input would sense a no-voltage condition.
• Trip Command - One of the trip initiate contacts
closes. This causes high current to ow through the
trip coil, which begins to pull the latch. The Aux B
input would sense a no-voltage condition, with the
52 / b contact remaining opened, as the breaker has
not yet begun to travel.
• Breaker Travel - As the breaker nears the end of
travel, the 52 / b contact closes. The Aux B input
would sense a transition from no-voltage to voltage.
• Fully opened - The 52 / b contact remains closed,
and the Aux B input would continue to sense a
voltage.
2
In summation, the OPTI
individually wetted contact, should be set as:
• B Input Polarity = “Positive”.
mizer
, when applied to an
2
In summation, the OPTI
with the 52 / b contact, should be set as:
• B Input Polarity = “Negative”.
40
mizer
, when applied in parallel
Page 41
Input Mode
Entering the Input Mode, in combination with the A Input
Polarity and B Input Polarity, allows The OPTImizer2 to
monitor the circuit breaker control circuit’s logic states
in the closed and open positions. The Input Mode also
governs whether or not Trip Time, Clearing Time, Travel
Time and Closing Time are measured.
If the B Input is not wired, Input Modes 2 or 3 must be
used, depending upon the wiring of the A Input. Mode 3 is
used when the A Input signal is a continuous source, as
shown in Figures 12, 13 and 15. Mode 2 is used when the
A Input signal is a momentary (pulse) source, as shown in
Figure 14.
If the A Input is wired as shown in Figures 12, 13 or 15,
then Input Modes 1 or 3 must be used, depending upon
the wiring of the B Input: Mode 1 is used when the B Input
is wired. Mode 3 is used when the B Input is not wired.
If the A Input is wired across the trip coil, as shown
in Figure 14, then Input Modes 2 or 4 must be used,
depending upon the wiring of the B Input: Mode 2 is used
when the B Input is not wired. Mode 4 is used when the B
Input is wired.
To set the Input Mode, select the CONFIGURATION tab
and click “EDIT”:
The Input Mode is selected from a pull-down list.
Mode 1 = Continuous A Signal with Continuous B
Signal
Mode 2 = Momentary A Signal, No B Signal
Mode 3 = Continuous A Signal, No B Signal
Mode 4 = Momentary A Signal with Continuous B
Signal
A Input Delay
(Time Difference between Aux A Input Assertion and Parting
of Main Contacts)
Entering the A Input Delay setting allows the OPTImizer2 to
accurately time the arcs, and calculate Contact Wear values
during the arcing intervals. This Delay setting impacts the
starting of the arc time log and the Contact Wear logs to
align with the parting of the main contacts.
To set the A Input Delay, select the CONFIGURATION tab
and click “EDIT”:
Program:A Input Delay = “-19”
• To account for an Aux A input assertion that occurs
before the main contacts part, use a positive (+)
value for the A Input Delay setting. Example: Aux
A assertion occurs 24 mS before the main contacts
part, A Input Delay = “+24”
• To account for an Aux A input assertion that occurs
after the main contacts part, use a negative (-)
value for the A Input Delay setting. Example: Aux A
assertion occurs 19 mS after the main contacts part,
A Input Delay = “-19”
Figure 19: Trip Trace illustrating A Input Delay Setting Considerations
41
Page 42
Depending on what is being used to assert the Aux A input, there are multiple methods available to derive the A Input Delay
setting value.
A Input AssertionMethods to Derive A INPUT DELAY Setting
•Use breaker trip trace, A Input Delay setting is the time difference between
Parallel connection to “Red
1
Light” or trip initiate contacts
the trip initiate signal and the parting of the main contacts
•Use ANSI C37.06 to approximate latch release times based on kV level of
breaker if a breaker trip trace is unavailable
•Use breaker trip trace, A Input Delay setting is the time difference between
the opening of the 52 / a contact and the parting of the main contacts
Parallel connection to 52 / a
2
contact in breaker trip circuit
•Use breaker operation time line provided by the manufacturer in Instruction
literature, provided the 52 / a contact has not been adjusted from the
manufacturer
•Use breaker trip trace, A Input Delay setting is the time difference between
the opening of the 52 / a contact and the parting of the main contacts
3Parallel connection to Trip Coil
•Use breaker operation time line provided by the manufacturer in Instruction
literature, provided the 52 / a contact has not been adjusted from the
manufacturer
•Use breaker trip trace, A Input Delay setting is the time difference between
Series connection to wetted
4
52 / a contact not in breaker
trip circuit
the opening of the 52 / a contact and the parting of the main contacts
•Use breaker operation time line provided by the manufacturer in Instruction
literature, provided the 52 / a contact has not been adjusted from the
manufacturer
Use of auxiliary relay in
5
conjunction with method 1
Use of another input that
6
indexes the trip initiate
contacts
•Same as method 1, but the delay in pick-up or drop out of the auxiliary relay
(depending on application) must be added or subtracted from the A Input Delay time setting
•Same as method 1, but the delay in pick-up or drop out of the initiating input
(depending on application) must be added or subtracted from the A Input
Delay time setting
Table 5: Impact of A Input Assertion on the A Input Delay Setting
42
Page 43
Use of ANSI / IEEE C37.06-1989, Rating of Power Circuit
Breakers under a Symmetrical Fault Basis
ANSI / IEEE C37.06-1989 can provide guidance for the
time of latch release and the duration of arcs for power
circuit breakers. The latch release time is approximately
the same time value as the main contacts parting, which
is required for the A Input Delay setting. This standard
addresses power circuit breakers with voltage ratings
from 13 kV to in excess of 500 kV. To be qualied as an
ANSI rated breaker, which most utilities use, the following
performance criteria must be met under symmetrical fault
conditions:
MUST cLeAR TIMe
Breaker Voltage
<230kV
>230kV
Table 6: Must-Clear Times of Breakers, Voltage Dependent
Note: Pre-1989 breakers may not conform to this
standard. Always use manufacturers data or oscillographic
data if available.
(TRIpINITIATeTOARc
exTINgUIShMeNTS)
3 cycles at 60Hz
2 cycles at 60Hz
Contact Wear Mode
The OPTImizer2 can be programmed to use one of
two available Contact Wear modes, Ix T or I 2T. In I 2T
mode, the square of the current measurement is used in
calculating contact wear units.
Note: When the OPTImizer2 is cold-started, the Contact
Wear Mode is set to “I 2T”.
To set the Contact Wear Mode, select the CONFIGURATION
tab and click “EDIT”: The Contact Wear Mode is selected
from a pull-down list.
Contact Life Danger Limit
The Contact Life Danger Limit is the alarm setpoint for
cumulative Ix T or I 2T duty. This limit is usually correlated to
the ultimate wear-out of the contacts. Breaker manufacturers
typically provide nameplate data that supplies enough
information to calculate the Contact Life limit. Some breaker
nameplates do not supply all of the information required,
however, ANSI C37.06-1989 provides guidelines that can
assist in deriving ultimate duty wear estimates. The equation
used is:
Danger Limit = (NF) I (squared for I 2T) • T, where
• NF is the rated number of fault interruptions,
•I is the full rated fault current (Amps RMS symmetrical)
•T is the arc time of the breaker.
Notice that it is only the arc time that is used in the
calculation, and not the total clearing time. The arc time is
used because it is during the arc interval that the heating
takes place, which degrades the breaker. During the current
carrying phase of clearing a fault, no arcing, and therefore
no heating takes place. The current carrying interval from
trip initiate to main contacts parting should not be included
in the wear limit calculation.
Figure 20: Estimated Trip Latch Release Times based on
Nameplate Breaker Voltage
Based on these limits, and using the assumption that
breakers are designed to clear a fault faster as the applied
voltage increases; the following timing graph is based
on ANSI C37.06-1989 for latch release times. These
approximations should be helpful to determine the A INPUT
DELAY setting when a time trace is unavailable, and the
OPTImizer2 is being applied with the trip initiates (red light)
for the Aux A input assertion. These approximations may
also have use if the 52 / a contact of the breaker is being
used for the Aux A assertion, however, the time interval from
the trip initiate signal to the 52 / a contact opening must be
known. The breaker manufactures instruction literature or
original factory trip trace will provide useful information.
The required nameplate data are:
• Full fault (symmetrical) current capability (I). If this
value is not available, or if the breaker is rated in
MVA, see Incomplete Nameplate Data, addressed
later in this section.
• Number of times breaker can interrupt full fault
(symmetrical) current (N
). If this value is not
F
available, see Incomplete Nameplate Data,
addressed later in this section.
• The rated voltage of the breaker.
To arrive at the arc duration time of the breaker, which is
used for T, several methods may be used:
• Viewing of a recent oscillographic record of the
breaker clearing, noting the time from main contacts
parting to arc extinguishments, all phases.
• Using ANSI / IEEE C37.06-1989 as a guideline to
arrive at an arc duration estimate (see ANSI / IEEE
C37.06-1989, Figure 15, and Appendix B).
Note:
When the OPTImizer2 is cold-started, the Danger Limit
parameter is set to 0.1
.
43
Page 44
Arc Duration (mS)
Breaker Voltage (kV)
50100 150 200 250 300 350 400 450 500
4
8
12
16
20
24
28
32
Figure 21: Estimated Arc Time based on Nameplate Breaker
Voltage
Example:
Given:Breaker is rated at 69kV, 30kA fault interrupt
(RMS symmetrical), and it can withstand 5
operations at fault interrupt current.
Note:The answer is expressed in amp2-seconds (A2S),
converted to scientic notation, base 10, rounded to
two signicant digits.
Incomplete Nameplate Data
There are occasions when the breaker nameplate data
does not state how many full-rated faults (symmetrical)
the breaker can withstand. For those instances, to arrive
at an estimate of the full-rated fault operations capability,
use the number of rated load current operations a breaker
can withstand and employ the equation NF = (NL IL) / IF,
where NF is the number of fault current operations, NL is
the number of rated load breaker operations, IL is the rated
load breaker current, and IF is the full-rated fault current.
ANSI / IEEE C37.06-1989 states that all outdoor circuit
breakers, all voltages, must be able to undergo 100 trip
operations at rated load interruption before an inspection of
the contacts is warranted.
Example:
Given:Breaker is rated at 69kV, 20kA fault interrupt
(symmetrical), 1200A rated load break. No
information is given on the number of fault rated
interruptions.
Assume: 69kV breakers have an arc duration T of 24mS
(0.024s). 69kV breaker can withstand 100 rated
load break operations, NL, before an inspection
(ANSI / IEEE C37.06-1989).
Calculate: NF = (N
IL) / IF
L
NF = (100) (1200A) / 20kA
NF = 6
Danger Limit = (NF ) I
2
x T
Danger Limit = (6) (20kA)2 (0.024s)
Danger Limit = 57,600,000 A2s
Danger Limit = 5.76 x 107 A2s
Note: The answer is expressed in amp2-seconds (A2s),
converted to scientic notation, base 10.
To set the Contact Life Danger Limit, select the
CONFIGURATION tab and click “EDIT”:
Program: Contact Life Danger Limit = “5.76e7”
If breaker is Rated in MVA, not kA, or is being Applied at
Voltage other than Nameplate:
There are occasions when the breaker is rated in MVA at
a given voltage. No kA value is available. To arrive at kA
maximum rated fault (symmetrical) current, it is necessary
to convert the MVA to kA on the voltage base. Employ the
equation IL = S3 / √3 (VLL) to derive single phase current,
where IL is the individual phase current in kA, S
is the three
3
phase power in MVA, and VLL is the line-to-line voltage in kV.
Example:
Given:Breaker is rated at 69kV, 2,500 MVA
interrupting duty
Breaker is to be applied at 69kV.
Calculate:IL = S3 / √3 (VLL),
IL = 2,500 MVA / 69kV √3
IL = 20.943kA, or approximately 21kA
Danger Limit = (NF ) I2 x T
Danger Limit = (100) (21kA) 2 (0.024s)
Danger Limit = 10,584,000,000 A2s
Danger Limit = 1.06 x 1010 A2s
Program:Contact Life Danger Limit = “1.06e10”
44
Page 45
If breaker is Rated in MVA, and is being
Applied at Voltage other than Nameplate:
There are occasions when the breaker is rated in MVA
at a given voltage, and the breaker is being applied at a
different voltage. No kA value is available. To calculate kA
maximum rated symmetrical fault current from MVA, use
= S
the equation I
L
current, where IL is the individual phase current in kA, S
is the three phase power in MVA, and VLL is the line-to-line
voltage in kV.
Example:
Given:Breaker is rated at 38kV, 1,200 MVA
interrupting duty.
Breaker is to be applied at 34kV.
/ √3 (VLL) to derive single phase
3
3
Set at One Fault Rated Interruption less than the Danger
Limit
Setting the Warning Limit at one fault interruption operation
allows a Warning alarm to be issued before another
fault takes place and brings the breaker cumulative I2 x T
to the Danger Limit. Use the equation Warning Limit =
1 / NF , where NF is the maximum number of fault rated
interruptions.
Example:
Given: Breaker DANGER setpoint has been determined
6
to be (6.4) 10
A2s and it can withstand 15
operations at fault interrupt current
Calculate: Warning Limit = 1 / N
F
Warning Limit = 1 /15]
Calculate: IL = S3 / √3 (VLL),
IL = 1,200 MVA / 34kV √3
IL = 20.401kA, or approximately 20kA
Danger Limit = (NF ) I2 x T
Danger Limit = (100) (20kA)2 (0.024s)
Danger Limit = 9,600,000,000 A2s
Danger Limit = 9.6 x 109 A2s
Program: Contact Life Danger Limit = “9.6e9”
Contact Life Warning Limit
The Contact Life Warning Limit is the warning setpoint for
cumulative Ix T or I 2T duty. The intent of this setpoint is
to allow the generation of a warning alarm prior to ultimate
contact wear (Danger Limit). Accordingly, when used in this
mode it is set at a fraction of the Danger Limit setpoint.
Note: When the OPTImizer2 is cold-started, the Warning
Limit parameter is set to ZERO, which disables this
alarm.
Set at an Arbitrary Percentage of the Danger Limit
To set the WARNING setpoint at an arbitrary percentage of
the DANGER setpoint simply use the WARNING command
followed by the percentage value.
Example:
Given: Breaker Danger Limit setpoint has been determined
to be (6.4) 106 A2S.
To set the Warning Limit to 30% of the Danger
limit…
Program:Contact Life Warning Limit(%) = “30”
The OPTI
calculate the Warning Limit I2 x T.
mizer
2
will automatically
Warning Limit = 0.067 or 6.7%, round to 7%
To set the Contact Life Warning Limit, select the
CONFIGURATION tab and click “EDIT”:
Program:Contact Life Warning Limit(%) = “7”
(The OPTImizer2 will automatically calculate the Warning
Limit I2 x T.)
There is no guidance from standards on the following
issues, so Alarm Limit selection is for the applying
company to decide.
The correct Administrator’s password is needed for these
settings to be saved.
Trip Time Alarm Limit
The OPTImizer2 will measure the response time
of the trip latch mechanism, if programmed for
Input Modes 2 or 4. A Trip Time Alarm Limit can be
programmed in milliseconds. When the measured
Trip Time reaches or exceeds this Alarm Limit an
alarm will be asserted.
It is recommended that this limit be set for 25% to
35% above the typical trip latch response time to
reduce nuisance alarms.
Note: When the OPTImizer2 is cold-started, the Trip
Time Alarm Limit parameter is set to ZERO, which
disables this alarm.
To set the Trip Time Alarm Limit, select the CONFIGURATION
tab and click “EDIT”:
Program:Trip Time Alarm Limit = “13”
45
Page 46
Arc Time Alarm Limit
The OPTImizer2 will measure the duration of the
fault arcs as the interrupter contacts separate. An Arc
Time Alarm Limit can be programmed in milliseconds.
When the measured Arc Times reach or exceed this
Alarm Limit an alarm will be asserted.
Travel Time Alarm Limit
The OPTImizer2 will measure the time between the
opening of the 52a switch and the closing of the 52b
switch, if programmed for Input Modes 1 or 4. A Travel
Time Alarm Limit can be programmed in milliseconds.
When the measured Travel Time reaches or exceeds this
Alarm Limit an alarm will be asserted.
It is recommended that this limit be set for 25%
to 35% above the typical arc duration time (see
Figure 21 for suggested typical arc times) to reduce
nuisance alarms.
Note: When the OPTImizer2 is cold-started, the Arc
Time Alarm Limit parameter is set to ZERO, which
disables this alarm.
To set the Arc Time Alarm Limit, select the CONFIGURATION
tab and click “EDIT”:
Program:Arc Time Alarm Limit = “42”
Clearing Time Alarm Limit
The OPTImizer2 will measure the combined time
of the trip latch mechanism and arc duration, if
programmed for Input Modes 2 or 4. A Clearing Time
Alarm Limit can be programmed in milliseconds.
When the measured Clearing Times reach or exceed
this Alarm Limit an alarm will be asserted.
Good practice is to set this limit for 25% to 35%
above the typical fault clearing time to reduce
nuisance alarms. We recommend that the sum of the
Trip Time and Arc Time alarm limits be used as the
Clearing Time Alarm Limit.
Note: When the OPTImizer2 is cold-started, the Clearing
Time Alarm Limit parameter is set to ZERO, which
disables this alarm.
To set the Clearing Time Alarm Limit, select the
CONFIGURATION tab and click “EDIT”:
It is recommended that this limit be set for 25% to 35%
above the typical breaker opening time to reduce nuisance
alarms.
Note: When the OPTI
Time Alarm Limit parameter is set to ZERO, which
disables this alarm.
To set the Travel Time Alarm Limit, select the
CONFIGURATION tab and click “EDIT”:
Program:Travel Time Alarm Limit = “75”
mizer
2
is cold-started, the Travel
Closing Time Alarm Limit
The OPTImizer2 will measure the time between the
opening of the 52b switch and the closing of the 52a
switch, if programmed for Input Mode 1 only. A Closing
Time Alarm Limit can be programmed in milliseconds.
When the measured Closing Time reaches or exceeds this
Alarm Limit an alarm will be asserted.
Good practice is to set this limit for 25% to 35% above the
typical breaker closing time to reduce nuisance alarms.
Note: When the OPTImizer2 is cold-started, the Closing
Time Alarm Limit parameter is set to ZERO, which
disables this alarm.
To set the Closing Time Alarm Limit, select the
CONFIGURATION tab and click “EDIT”:
Program: Closing Time Alarm Limit = “105”
Program: Clearing Time Alarm Limit = “55”
46
Page 47
Operations Count Alarm Limit
The OPTImizer2 will increment a counter with each
circuit breaker trip operation. An Operations Count Alarm
Limit may be set to turn on the Operations LED and
close the Yellow relay when the breaker has reached a
certain number of operations. This Alarm Limit is different
than the Operations Number. The Alarm Limit may be
set for a small number of operations and counter may
be reset several times over the life of the breaker (like a
trip odometer in a car), while the Operations Number will
continue to increment for the life of the breaker (like a car’s
main odometer).
The Operations Count Alarm can be used to alert
maintenance staff to perform maintenance that is
recommended after a specic number of operations. Once
the maintenance is done, the Operations Counter can be
reset, and the alarm will recur when the specic number
of operations is reached again. When the OPTImizer2 is
cold started, the Operations Count Alarm Limit parameter
is set to ZERO, which disables this alarm.
Restrike Alarm
The ability to detect restrikes is important, especially for
gas (SF
The following gure illustrates how the OPTImizer2
perceives typical arcs and restrikes. The OPTI
sampling the phase-segregated waveforms at 32 times per
line cycle.
The Restrike Alarm may be enabled or disabled.
If enabled, the rst detection of a restrike will assert the
Restrike Alarm, turning on the Restrike LED and energizing
the Red relay. A time-stamped record of the alarm will
be recorded in the history log. The Restrike Alarm may
be reset, opening the relay and turning off the LED. The
record of the alarm will remain in the history log even if the
alarm is reset.
Note: When the OPTImizer2 is cold-started, the Restrike
) breakers.
6
Alarm parameter is set to “Disabled”.
mizer
2
is
To set the Operations Count Alarm Limit, select the
CONFIGURATION tab and click “EDIT”:
Program: Operations Count Alarm Limit = “75”
No Operations Alarm Limit
The OPTImizer2 will count the number of days since the
last trip operation. A No Operations Alarm Limit can be
programmed in days. When the number of days since the
last trip operation reaches or exceeds this Alarm Limit an
alarm will be asserted.
This limit should be set according to the breaker
manufacturer’s recommendations.
Note: When the OPTImizer2 is cold-started, the No
Operations Alarm Limit parameter is set to ZERO,
which disables this alarm.
To set the No Operations Alarm Limit, select the
CONFIGURATION tab and click “EDIT”:
To set the Restrike Alarm, select the CONFIGURATION
tab and click “EDIT”:
Program: Restrike Alarm = “Enabled”
Program: No Operations Alarm Limit = “90”
47
Page 48
Arc Time = 3 Cycles
Arc begins here
Arc begins here
Arc begins here
Restrike not detected
Possible total arc duration = 10 cycles
Figure 22A: A 3-Cycle Arc, No Restrike
Arc Time = 5.5 Cycles
Restrike not detected
Possible total arc duration = 10 cycles
Figure 22B, A 5½-Cycle Arc, No Restrike
Less than ¼ cycle
Arc Time = 5.5 Cycles
Restrike detected
48
More than ¼ cycle
Possible total arc duration = 10 cycles
Figure 22C, A 5½-Cycle Arc, Restrike Detected
Page 49
4.4 SF6 MONITOR SETTINGS
The following settings are used by the OPTImizer2
specically for SF6 monitoring.
• SF6 Monitoring Units: Density; Pressure
• Pressure Units: PSI; BAR; Kilopascals
• Temperature Units: Celsius; Fahrenheit
• Volume Units: Cubic Feet; Liters; Cubic Meters
• Mass Units: Pounds; Kilograms
2
• Mass Loss Units: Pounds; Kilograms; Pounds CO
Metric Tonnes CO
2
• Breaker Nameplate SF6 Gas Fill Weight (mass), in the
chosen units:________
• Breaker Nameplate SF
Fill Pressure, in the chosen
6
units:________
• Rated Temperature, in the chosen units:________
Volume (optional), in the chosen units:________
• SF
6
Low Gas Warning Limit
As the OPTImizer2 monitors the SF6 density or pressure,
an alarm will be asserted when the density or pressure
reaches or falls below the programmed Low Gas Warning
Limit.
The Low Gas Warning Limit can be set to the circuit
breaker manufacturer’s “Alarm Limit” specication. If
the OPTImizer2 is used in conjunction with an electromechanical SF6 monitoring device, this Warning Limit
can be set higher than the manufacturer’s “Alarm Limit”
specication to provide an “early warning” that SF6 density
or pressure is getting low.
Note: When the OPTImizer2 is cold-started, the Low
Gas Warning Limit parameter is set to ZERO, which
disables this alarm.
To set the Low Gas Warning Limit, select the
CONFIGURATION tab and click “EDIT”:
Program:Low Pressure Warning Limit = “76”
or
Low Density Warning Limit = "39.8"
;
Low Gas Alarm Limit
An alarm will be asserted when the density or pressure
reaches or falls below the programmed Low Gas Alarm
Limit.
The Low Gas Alarm Limit can be set to the circuit
breaker manufacturer’s “Lock-Out Limit” specication. If
the OPTImizer2 is used in conjunction with an electromechanical gas monitoring device, this Alarm Limit can
be set higher than the manufacturer’s “Lock-Out Limit”
specication to provide an “early warning” that a Lock-Out
is imminent.
Note: When the OPTImizer2 is cold-started, the Low
Gas Alarm Limit parameter is set to ZERO, which
disables this alarm.
To set the Low Gas Alarm Limit, select the
CONFIGURATION tab and click “EDIT”:
Program:Low Pressure Alarm Limit = “72”
or
Low Density Alarm Limit = "38.2"
Density or Pressure Trend Limit
The OPTImizer2 will analyze the SF6 density and pressure
uctuations over a 15 day period and calculate the Density
and Pressure Trends once an hour. The magnitude of these
trends indicate whether the SF6 density and pressure are
stable or decreasing. The Density Trend is expressed in
grams-per-liter-per-day (g / L / d). The Pressure Trend is
expressed in the chosen units-per-day. They are shown as
negative numbers in the Status, if there is a loss of gas. The
Trend Limit is programmed as a positive number.
An alarm will be asserted when the magnitude of the trend
is the same or greater than the programmed Trend Limit.
Note: When the OPTImizer2 is cold-started, the Trend
Alarm Limit parameter is set to ZERO, which
disables this alarm.
To set the Trend Alarm Limit, select the CONFIGURATION
tab and click “EDIT”:
Program:Density Trend Alarm Limit = “0.03”
or
Pressure Trend Alarm Limit = "0.3"
49
Page 50
SF6 Sensor Signals
The OPTImizer2 can monitor the signal from two types of
SF6 density sensor:
Analog Sensors with an output current signal within
the range of 4mA and 20mA
Analog Sensor - Signal Low Represents
(Units)
Each SF6 input on the OPTImizer2 can be programmed
to scale the analog Signal Low (programmed above) to a
grams per liter value that may be something other than zero.
Digital Sensors with a special frequency & pulse-
width-modulated signal (INCON DSDP)
Each of the three input channels can be separately
programmed for an Analog or Digital sensor or disabled
(Off). If the SF6 Sensor Signal chosen is “Analog”, four
more parameter elds will appear for that sensor (see
below).
Note: When the sensor signal chosen is "Analog", the
chosen units cannot be "Pressure".
Note: When the OPTImizer2 is cold-started, the SF6
Sensor Signal parameters are all set to “Off”, which
disables the inputs.
To set the SF6 Sensor Signals, select the CONFIGURATION
tab and click “EDIT”:
Under the headings “SF6 Sensor A”, “SF6 Sensor B”, “SF6
Sensor C”:
Program:Signal = “Digital”
or
Signal = “Analog”
Note: When the OPTImizer2 is cold-started, the Signal
Low Represents parameter is set to 0.0 g / L.
To set the Signal Low Represents parameter, select the
CONFIGURATION tab and click “EDIT”:
Under the headings “SF6 Sensor A”, “SF6 Sensor B”, “SF6
Sensor C”:
Program: Signal Low Represents (g / L) = “10.0”
Analog Sensor - Signal High (Milliamps)
Each SF6 input on the OPTImizer2 can be programmed
to monitor an analog signal with a high scale that may be
something other than 20mA.
2
Note: When the OPTI
High parameter is set to 20.0mA.
Note: If the measured sensor signal is higher than the
programmed Signal High value, a “Sensor Signal
Out of Range” alarm will be asserted.
To set the Signal High parameter, select the
CONFIGURATION tab and click “EDIT”:
mizer
is cold-started, the Signal
Analog Sensor - Signal Low (Milliamps)
Each SF6 input on the OPTImizer2 can be programmed
to monitor an analog signal with a low scale that may be
something other than 4mA. For example, some sensors
have a working range of 6.5 to 20mA.
Note: When the OPTImizer2 is cold-started, the Signal
Low parameter is set to 4.0mA.
Note: If the measured sensor signal is lower than the
programmed Signal Low value, a “Sensor Signal
Out of Range” alarm will be asserted.
To set the Signal Low parameter, select the
CONFIGURATION tab and click “EDIT”:
Under the headings “SF6 Sensor A”, “SF6 Sensor B”, “SF6
Sensor C”:
Program:Signal Low (mA) = “6.5”
Under the headings “SF6 Sensor A”, “SF6 Sensor B”, “SF6
Sensor C”:
Program: Signal High (mA) = “16.0”
Analog Sensor - Signal High Represents
(Units)
Each SF6 input on the OPTImizer2 can be programmed
to scale the analog Signal High (programmed above) to a
grams per liter value.
Note: When the OPTImizer2 is cold-started, the Signal
High Represents parameter is set to 400.0 g / L.
To set the Signal High Represents parameter, select the
CONFIGURATION tab and click “EDIT”:
Under the headings “SF6 Sensor A”, “SF6 Sensor B”, “SF6
Sensor C”:
Program:Signal High Represents (g / L) = “70.0”
50
Page 51
4.5 ACTIONS
An “Action” is taken in response to an alarm or
maintenance activity. Actions include clearing active
alarms; resetting data; resetting the operations counter;
pre-setting the remaining contact life percentage and
presetting the operation number. The OPTImizer2 allows
these things to be done from the “ACTION” tab of the user
interface (see Figure 10).
Preset Remaining Contact Life
The ability to preset the remaining contact life as a
percentage of the Danger Limit for each phase allows the
OPTImizer2 to account for any interrupting duty wear that
has occurred prior to installation. This issue may be divided
into two general categories:
• New breakers, or breakers that have been
recently refurbished, have essentially 100 percent
life remaining on one or more of the contacts.
Refurbished is dened here as replaced contacts, oil
and grids (bafes) in OCBs, and replaced contacts
and gas cleaning in SF6 breakers, or contact and
bafe replacement in magblast air breakers.
• Existing breakers that have not had recent
maintenance (refurbishment)
There are two processes for estimating the percentage of
remaining contact life for existing breakers that have not
been recently maintained:
• Experience based on eld engineers / technicians
who can evaluate the condition of contacts and rate
a percent of life lost, or percent of life remaining.
• Calculation from trip duty records from
Oscillographs, relays with Oscillographic capabilities,
relay target logs.
Experience Method of presetting Remaining Contact
Life per phase
A breaker may have been recently inspected by a eld
engineer / technician whose expert knowledge of breaker
wear characteristics may allow declaration of a percent of
life remaining on contacts.
Calculation Method of presetting Remaining Contact
Life
In the calculation method, an attempt is made to
quantify the cumulative currents interrupted since the
last refurbishing of each phase of the breaker. This
quantication would include the summation of fault
operations and load breaks. (No-load breaks would be of
no consequence to the wear duty of the breaker.)
The general method is to add the total I² x T (or I x T) from
all fault operations to the total I² x T (or I x T) from all load
breaks for each phase. The equation used is similar to the
one used to derive the Danger Limit value, except that the
variables represent individual operations.
Use the equation WN = IN² T to determine Duty Wear for
each operation, where “W” is the Duty Wear, “N” is the
operation number, IN is the current interrupted for that
operation (squared if using the I² x T mode), and T is the
arc duration time of the breaker. Determining the time (T)
is discussed in the Danger Limit calculation, addressed
earlier in this section.
The summation of all interrupting duty (WN’s) for a
particular phase is used to arrive at a nal accumulated
Duty Wear value for that phase. Divide this calculated Duty
Wear by the Danger Limit to get the accumulated Duty
Wear percentage. Subtract this percentage value from
100 to get the Remaining Contact Life percentage. This
percentage value is programmed as the Preset Remaining
Contact Life for this phase.
It may be difcult to obtain exact interrupted amps for each
and every operation. In these cases, some assumptions
must be made to arrive at an estimated setting. Possible
information sources may be from protective relay targets.
By examining the settings that relate to the targets,
estimates of the fault current may be obtained.
Lacking precise targets, by separating the operations
into fault operations and load break operations, some
assumptions can be made. One assumption may be
that load breaks equal ½ the maximum load the breaker
is subjected to, and fault operations are some factor of
expected short circuit ground current, or phase-to-phase
current.
As the great majority of fault incidences are phase-toground, some factor relating to the expected ground short
circuit current can be made. The factors applied would
depend on knowledge of the relative fault currents that
have been recorded on the line to the short circuit ground
fault current assuming zero ground fault impedance.
System Protection and Operations personnel are helpful
sources for obtaining data for estimating the accumulated
Duty Wear if hard data is not available.
51
Page 52
Example for Calculating Accumulated Duty Wear
Given:A breaker has operated 8 times since the last
refurbishing. The breaker is a 38 kV breaker. The
Danger Limit is calculated to be 2.5e+07 I2 x T.
Assume: Equation used for accumulated I2 T is:
∑ WN = (IN)2 T
Arc duration time of a 69kV breaker is 24mS
(0.024s), per explanation under Danger Limit
calculation derived earlier in this section.
Clear Latched Alarms
When an alarm occurs, an LED will be lit to give a general
indication of what has caused the alarm. Table 4 gives
a listing of which LED is lit for each alarm. Some of the
LED’s can indicate a number of different alarms. To know
specically what alarm is active when an LED is lit, browse
to the Status page. A complete listing of all alarms is
shown with the status of each. Some "ALARM" indications
are hyper-links to the ACTION tab, where the alarm can be
cleared.
It has been determined by examination of Operations
records that the history was:
Trip #
1Fault5,000600,0006.0 E+05
2Fault4,000384,0003.8 E+05
3Load Break 80015,3601.5 E+04
4Fault15,0005,400,0005.4 E+06
5Load Break 4003,8403.8 E+03
6Fault5,000600,0006.0 E+05
7Fault6,000864,0008.6 E+05
8Load Break 2009609.6 E +02
Table 7: Accumulated Duty Wear Calculation Example based
Divide 7.9 e+06 by 2.5 e+07 to determine Contact Wear
percentage = 31.6
Subtract 31.6 from 100 to determine Preset Remaining
Contact Life percentage = 68.4
To preset the remaining contact life for a phase, select the
ACTION tab and click “Preset Remaining Contact Life Phase (A, B or C)”. A yellow bar will appear at the top of the
window. Type the desired remaining contact life percentage
into the eld (The acceptable range is -50 to +100).
Type of
Clearing
Approx.
Interrupt
Current
on Trip History
I2 x T
(decimal)
I2 x T
(Notation)
Preset Operation Number
The OPTImizer2 will assign an operation number that is
increased by one with each circuit breaker trip operation.
Normally this count will start at “1”. The operation number
may be preset to a number other than “1”. This allows the
OPTImizer2 to indicate the same operation number as the
counter on the circuit breaker. The OPTImizer2 will count
to a maximum of 9999 operations before “rolling over” to
0000. The operation number will continue to increment after
“rolling over”.
On the action page, certain active alarms can be cleared
and others cannot. “Latched Alarms” can be cleared
because they are not tied to accumulated or persistent
data. “Persistent Alarms” cannot be cleared without rst
addressing the cause of the problem, altering the alarm
limit or resetting the data. The No Operations Alarm cannot
be cleared directly. It will automatically clear upon the next
circuit breaker trip operation. Raising the No Operations
Alarm Limit will also clear that alarm.
Latched Alarms include: Trip Time; Travel Time; Closing
Time; Restrike; Excess Arc and Clearing Time. These
alarms can only be cleared by clicking the “Clear Latched
Alarms” button or using the USB Alarm Clearing script.
These alarms can NOT be cleared by altering their alarm
limit.
Persistent Alarms include: A-B LOGIC; No Operations;
Operations Count; Remaining Contact Life Warning;
Remaining Contact Life Danger; Low Density; Density
Trend and Sensor Malfunction. These alarms cannot be
cleared without rst addressing the cause of the problem,
altering the alarm limit or resetting the data.
To Clear Latched Alarms, select the ACTION tab and click
“Clear Latched Alarms”. A yellow bar will appear at the top
of the window. Click "Yes" to conrm.
Reset Operations Counter
When an Operations Count Alarm occurs, it can be cleared
by either increasing the Operations Count Alarm Limit on
the CONFIGURATION tab, or by resetting the counter. This
action will zero the counter.
To reset the operation counter, select the ACTION tab and
click “Reset Operations Counter”. A yellow bar will appear
at the top of the window. Click "Yes" to conrm.
To preset the operation number, select the ACTION tab and
click “Preset Operation Number”. A yellow bar will appear
at the top of the window. Type the desired operation number
into the eld. Click "Yes" to conrm.
52
Page 53
Reset SF6 Density Trend Data
If an SF6 density sensor is found to be faulty, the SF6 Trend
calculation should be re-started after replacing the sensor.
This can be done by resetting the accumulated SF6 data
for that channel. When this action is taken, a new array
of data will be accumulated and a new SF6 Trend will be
calculated for that channel. Until there is a full array of data
to calculate the new Trend, the Condence Level for that
channel will indicate less than 100%.
To reset the SF6 Trend Datafor a channel, select the
ACTION tab and click “Reset Channel A, B or C”. A yellow bar will appear at the top of
the window.
Click “YES” to conrm the action. The correct
Administrator’s password will need to be given for the
change to be saved. Click “Apply” to complete the action.
SF
Trend Data and Alarm
6
53
Page 54
5 User Interface
There are ve general interface activities with the
OPTImizer2:
1. Initial Conguration
2. Post Maintenance Resetting / Presetting
3. Periodic Data dump
4. Alarm Acknowledgment / Cancellation
5. Archiving and Exporting Data to a PC
The following are typical steps for each of the preceding
major interface activities. The order of the tasks have been
arranged to allow a logical approach to these activities.
5.1 Post Maintenance Resetting / Presetting
Typical interface activities performed on an OPTImizer2
after breaker maintenance include:
• PRESET REMAINING CONTACT LIFE (for
changing or presetting the contact life to 100%, for
the appropriate phases of the circuit breaker after
contact inspection, refurbishment, or replacement).
Note that the PRESET settings are entered as a
percentage of the Danger Limit on a phase-by-phase
basis.
• CLEAR LATCHED ALARMS (for resetting any
asserted alarms after maintenance).
• RESET OPERATIONS COUNTER (for resetting the
Operations Count to zero after maintenance.)
• RESET SF
to calculate SF6 density trends after replacing a
SF6 gas sensor). Note that these Trend Data are
automatically reset when gas lling is detected.
5.2 Periodic Data Dump
Typical interface activities to perform a periodic datadump
from an OPTImizer2 include:
• Move to the HISTORY Page.
• Select the type of history report from the Available
Data list.
• Select the Date Range.
• Click “Download", at the upper right.
• A CSV (Comma Separated Values) le will be
created. Choose to Open, Save or Cancel this le.
(Typically, MS™ Excel will be used to open this le).
TREND DATA (for resetting data used
6
• The data can then be viewed, graphed, sorted, as
desired.
• See also page 59 for instructions for downloading
the complete OPTI
mizer
database using a USB
2
Script.
See pages 54 - 58 in this manual for a detailed explanation
of each item in each report.
History Log
The OPTI
mizer
records all alarm events, application
2
events, circuit breaker events and SF6 density measurements
in a large History Log database. Five types of reports can be
downloaded from the History Log:
• Alarm History – Maximum 500 records This report
lists the occurrence of all alarms of any type.
• Application Event History – Maximum 500 records
This report lists the occurrence of all application
events, including: system restarts; conguration
changes;
• Circuit Breaker Event History – Maximum 500
records This report lists the occurrence of all circuit
breaker operations and the data measured during
those operations.
Daily Summary – Maximum 750 records This
• SF
6
report lists all SF6 measurements and calculations
for the past day, including: average density,
temperature, pressure, mass, trends, change in
mass and accumulated mass loss.
Logged History - Maximum 5000 records
• SF
6
This report lists the density, pressure and
temperature measurements taken at the
programmed logging interval.
When the maximum number of records is reached in each
history log, the oldest record will be erased when each new
record is written to that log.
Downloading Reports
To download a report, select the HISTORY tab and choose
a report from the Available Data list on the left. Select the
time frame of the report from the Data Range on the right.
Click “Download” to extract the report from the database. A
comma separated values (CSV) le will be generated. You
can choose to open or save the le. The le can be opened
®
by Microsoft Excel
or an equivalent spreadsheet program.
54
Figure 23: User Interface, History Page
Page 55
Alarm History Report
The Alarm History Report consists of: Code; Category; Device; Data; State; (Date & Time) Occurred and (Date & Time)
Cleared.
Code: The alarm Code is an abbreviation for the description of the alarm seen on the ALARM tab. The prex “al” is used to
indicate that it is an Alarm code. The table below gives a description of each alarm Code:
Code:Description:Cause:How to Clear:
alInvalidConguration
alCongurationDNP3
alWarningLimit
alDangerLimit
Invalid Setup
Conguration
Invalid DNP3
Conguration
Remaining Contact
Life Warning Limit
Remaining Contact
Life Danger Limit
Contact Life has reached
the Warning Limit
Contact Life has reached
the Danger Limit
Excess Arc Time has
been detected
A Restrike has been
detected
Excess Clearing Time
has been detected
Excess Trip Time has
been detected
Excess Travel Time has
been detected
Excess Closing Time has
been detected
Operation Count has
reached the Limit
Time between CB
operations too long
Logic violation on A & B
inputs
CB Monitor settings are
illegal
On ACTION Tab: Preset Remaining
Contact Life below the Warning Limit
On ACTION Tab: Preset Remaining
Contact Life below the Danger Limit
On ACTION Tab: Clear Latched Alarms
On ACTION Tab: Clear Latched Alarms
On ACTION Tab: Clear Latched Alarms
On ACTION Tab: Clear Latched Alarms
On ACTION Tab: Clear Latched Alarms
On ACTION Tab: Clear Latched Alarms
On ACTION Tab: Reset Operations
Counter
Operate the circuit breaker
Self-clears when the A-B Input logic is
OK
Reprogram CB Monitor settings
Low SF6 gas detectedAdd gas to the CB
Very low SF6 gas
detected
Erratic SF6 Sensor
Signal detected
SF6 Trend Limit has been
reached
No SF6 sensor signal
Detected
SF6 sensor signal out of
range
SF6 Monitor settings are
illegal
Add gas to the CB
Self-clears when a signal is stable
Stop loss of SF6; On ACTION Tab:
Reset SF6 Trend Data
Self-clears when a signal is detected
Self-clears when the signal is in range
Reprogram SF6 Monitor settings
alInternalError1Internal Error #1Data OverloadContact Technical Support
alInputInvalid Input Invalid Software MalfunctionContact Technical Support
alCBMonitorUnknownActity CBM Unknown Activity Software MalfunctionContact Technical Support
SF
Unknown
alSF6UnknownActivity
6
Activity
alInternalErrorDNP3Internal DNP3 ErrorSoftware MalfunctionContact Technical Support
Software MalfunctionContact Technical Support
Table 8: Alarm Codes
55
Page 56
Category:
The alarm Category identies what class the
alarm belongs to: System, Circuit Breaker
Monitoring (CBM) or SF6 Monitoring. The prex
“alc” is used to indicate that it is a Category code.
Type: The alarm Type indicates the severity of the
alarm condition: Warning, Alarm or Failure. The
prex “alt” is used to indicate that it is a Type
code
Application Event History Report
The Application Event History Report consists of: Code;
Category; Device; Data; (Date & Time) Occurred
Code: This Code is an abbreviation for the description
of the Application Event. The prex “ae” is used
to indicate that it is an Application Event code.
The table below gives the description of each
Application Event Code:
Device: The alarm Device and Data combine to indicate
the location of the alarm condition. The prex
“ald” is used to indicate that it is a Device code.
Device code “aldChannelCBM” indicates that
the alarm relates to one of the circuit breaker
phases.
Device code “aldChannelSF6” indicates
that the alarm relates to one of the SF6 input
channels.
Device code “aldNone” indicates that the alarm
is a non-phase or non-channel related alarm.
Data:
The Device Data indicates which CB phase or
SF6 input channel caused the alarm; 0 = None; 1 = A; 2 = B; 3 = C.
State: The State code indicates the present state of
the alarm: Active or Inactive. The prex “als” is
used to indicate that it is a State code.
Occurred: The report indicates the date and time the alarm
occurred.
Cleared:
The report indicates the date and time the alarm
was cleared. Alarms that are presently in the
active state will not have a cleared date and
time.
Category: The Application Event Categories are the same
as Alarm Categories.
Device: The Application Event Devices are the same as
Alarm Devices.
Data: The Application Event Data are the same as
Alarm Data.
Occurred: The report indicates the date and time the
Application Event occurred.
Code:Description:Cause:
aeCongurationChangedConguration ChangedOne or more program setting has changed
aeSystemTimeChangedSystem Time ChangedThe system clock time or date has changed
aeCircuitBreakerOpenedCircuit Breaker OpenedThe CB was closed and now is open
aeCircuitBreakerClosedCircuit Breaker ClosedThe CB was open and now is closed
aeSF6DensityIncreaseDensity Increase DetectedSF
56
gas has been added or density sensor malfunction
6
Table 9: Application Event Codes
Page 57
Circuit Breaker Event History Report
The Circuit Breaker Event History Report consists of:
• Report ID
• Time Stamp
• Type
• Operation Number
• Over Trip Time Limit (Input modes 2 & 4 only)
• Over Travel Time Limit (Input modes 1 & 4 only)
• Over Closing Time Limit (Input mode 1 only)
• Over Operation Count Limit
• Travel Time (Input modes 1 & 4 only)
• Trip Time (Input modes 2 & 4 only)
• Closing Time (Input mode 1 only)
Each phase has a record for:
• Restrike Occurred
• Over Warning Limit
• Over Danger Limit
• Over Arc Time Limit
• Arc Time
• Clearing Time (Input modes 2 & 4 only)
• Wear
• Wear Total
• Peak Current
Report ID: This is a number used by the system to identify
the individual events in the report. It is not referenced to
any external or programmable value. Its only purpose is to
keep events in sequential order in the database.
Time Stamp: The date and time each circuit breaker event
was recorded.
Type: The event Type indicates what caused the circuit
breaker event to be recorded: Trip (Opening); Closing;
A-B Logic Failure (Alarm); No Operation (Alarm); Preset
Wear; Preset Operation Number; Reset Operation Count
• Type code “cbTrip” indicates that the event record
was recorded because the circuit breaker has
opened.
• Type code “cbClose” indicates that the event record
was recorded because the circuit breaker has
closed.
• Type code “cbABLogicFailure” indicates that the
event record was recorded because an A-B Logic
Failure Alarm occurred.
• Type code “cbNoOperation” indicates that the event
record was recorded because a No Operations
Alarm occurred.
• Type code “cbPresetWear” indicates that the event
record was recorded because the remaining contact
life was preset on one phase.
• Type code “cbPresetOperationNumber” indicates
that the event record was recorded because the
Operation Number was preset.
• Type code “cbResetOperationCount” indicates
that the event record was recorded because the
Operation Counter was reset.
Operation Number: This number is associated with the
total operations on the circuit breaker and, if correctly
preset, should match the circuit breaker’s mechanical
counter.
Over Trip Time Limit: This indicates (True or False)
whether the Trip Time Limit was reached or exceeded
during this CB event.
Over Travel Time Limit: This indicates (True or False)
whether the Travel Time Limit was reached or exceeded
during this CB event.
Over Closing Time Limit: This indicates (True or False)
whether the Closing Time Limit was reached or exceeded
during this CB event.
Over Operation Count Limit: This indicates (True or
False) whether the Operation Count Limit was reached or
exceeded during this CB event.
Travel Time : This number is the measured Travel Time for
this CB event.
Trip Time : This number is the measured Trip Time for this
CB event.
Closing Time : This number is the measured Closing Time
for this CB event.
Restrike Occurred (A,B,C): This indicates (True or False)
whether a Restrike was detected on this phase (A,B,C)
during this CB event.
Over Warning Limit (A,B,C): This indicates (True or False)
whether the Contact Life Warning Limit was reached or
exceeded on this phase during this CB event.
Over Danger Limit (A,B,C): This indicates (True or False)
whether the Contact Life Danger Limit was reached or
exceeded on this phase during this CB event.
Over Arc Time Limit (A,B,C): This indicates (True or False)
whether the Arc Time Limit was reached or exceeded on
this phase during this CB event.
Over Clearing Time Limit (A,B,C): This indicates (True or
False) whether the Clearing Time Limit was reached or
exceeded on this phase during this CB event.
Wear (A,B,C): This number is the measured contact wear
2
(I T or I
T) for this phase (A,B,C) for this CB event.
Wear Total (A,B,C): This number is the accumulated
contact wear (IT or I 2T) for this phase (A,B,C) up to this
CB event.
Peak Current (A,B,C): This number is the measured peak
current in amps (not RMS) for this phase (A,B,C) for this
CB event.
57
Page 58
SF6 Logged History Report
The SF6 Logged History Report consists of: Record
ID; Time Stamp; Density (A,B,C); Pressure (A,B,C);
Temperature (A,B,C).
Record ID: This is a number used by the system to identify
the individual records in the report. It is not referenced to
any external or programmable value. Its only purpose is to
keep records in sequential order in the database.
Time Stamp: The date and time each SF6 record was
logged.
Density (A,B,C): The measured density (Grams / Liter) for
this input channel (A,B,C) at the time the density record
was logged.
Pressure (A,B,C): The calculated pressure (in the chosen
units) for this input channel (A,B,C) at the time the gas
record was logged.
Temperature (A,B,C): The measured temperature (in the
chosen units) for this input channel (A,B,C) at the time the
density record was logged.
SF6 Daily Summary Report
Date Stamp: The date each SF6 Summary record was
logged.
Average Density (A,B,C): Average density (Grams/Liter)
for the past 24 hours.
Average Pressure (A,B,C): Average pressure (in the
chosen units) for the past 24 hours.
Average Temperature: Average temperature (in the chosen
units) for the past 24 hours.
Density Trend (A,B,C): The calculated SF6 Density Trend
(Grams / Liter / day) for this input channel (A,B,C) at the
time the gas record was logged.
Pressure Trend (A,B,C): The calculated SF6 Pressure
Trend (in the chosen units) for this input channel (A,B,C) at
the time the gas record was logged.
Trend Conf (A,B,C): The calculated SF6 Trend Condence
Level (%), for both density and pressure, for this input
channel (A,B,C) at the time the gas record was logged.
Average Mass: Average mass (in the chosen units) for the
past 24 hours.
Mass Change: The calculated change in mass (in the
chosen units) over the past 24 hours, a negative number
represents mass lost, a positive number represents mass
gained
Accumulated Mass Loss: A running total of mass loss (in
the chosen units), from the beginning of the Date Range
to the date of that record in the report, a negative number
represents mass lost. Accumulated Mass Loss is not
affected by gas lling events.
Data Interpreting
Circuit Breaker Data:
Data from the OPTImizer2 reveals absolute setpoint limit
violation and trends in degradation:
• The phase segregated I
values allow analysis of the duty wear impressed
on the breaker for that particular operation. Fault
type can often be determined by examining which
phase(s) has a higher value than the other phases.
• The phase segregated
per phase allows analysis to determine which
pole(s) are nearing their life limits. Other uses for
this value involve correlation to grid (bafe) wear, oil
contamination, and gas contamination.
• The TRAVEL TIME (Opening Mechanism Time)
allows trending of the mechanical speed of the
breaker. Rapid departures from normal values
suggest a mechanical compromise requiring urgent
attention. Small departures over a long time period
may indicate a minor maintenance item, such as
lubrication.
• The TRIP TIME (Breaker Trip Mechanism Time)
allows trending of the mechanical speed of the
tripping mechanism. Rapid departures from normal
values suggest a mechanical compromise requiring
urgent attention. Small departures over a long time
period may indicate a minor maintenance item, such
as lubrication. Although no “Trip Coil Signature”
data is recorded, the TRIP TIME measurement can
indicate general condition and effectiveness of the
tripping mechanism.
• The ARC TIME (Arc Duration) allows trending of the
dielectric capabilities of the breaker. By examining
the ratio of TRAVEL TIME to ARC TIME, it can be
determined if the ARC TIME is growing in duration
while the TRAVEL TIME remains constant. If this is
observed, a compromise in the dielectric quality of
the breaker is suggested. Rapid departures from
normal values suggest a dielectric compromise
requiring urgent attention. Small departures over a
long time period may indicate a minor maintenance
item, such as gas reconditioning or oil replacement.
• CLEARING TIME (Breaker Interrupting Time) is the
sum of TRIP TIME and ARC TIME. This important
measurement represents the breaker’s ability
to quickly interrupt current ow in reaction to a
fault condition. The CLEARING TIME data allows
trending of the breaker’s overall effectiveness,
mechanical and dielectric.
• CLOSING TIME (Closing Mechanism Time) allows
trending of the mechanical closing speed of the
breaker. Rapid departures from normal values suggest
a mechanical compromise requiring urgent attention.
Small departures over a long time period may indicate
a minor maintenance item, such as lubrication.
2
x T or I x T per trip event
I2 x T or I x T accumulated
58
Page 59
SF6 Data
Data from the OPTImizer2 can call attention to potential
SF6 gas leaks; long before critical gas levels are reached.
• SF6 DENSITY indicates the dielectric strength of
the insulating gas. As density decreases, dielectric
strength decreases.
TREND indicates the rate of gas loss averaged
• SF
6
over a 15 day period. A negative trend value
indicates gas loss. This trend may uctuate positive,
then negative, back and forth a small amount, due
to the effects of temperature changes. If it shows a
consistent negative value, this is a good indication
that the SF6 may be leaking.
• CONFIDENCE LEVELS indicate the statistical
validity of the SF
trends. A combination of two
6
things affects the Condence Level value: the
amount of data collected and the linearity of the SF6
density data.
o It takes one full time period (15 days) to collect
enough SF
data to have a high Condence
6
Level in the trend calculation. Until the full array
of data is collected, the Condence Level will be
lower.
o If the SF6 data has signicant variation, the
Condence Level will be lower. If the SF6 data
is very consistent, the Condence Level will be
higher. Low Condence Levels, after the full
time period has passed, indicate uctuations in
the SF6 measurements. This can be caused by
temperature differences between the SF6 density
sensor and the SF6 vessel itself. Another cause
of uctuations in the SF6 measurements could
be a sensor malfunction.
• The LOW GAS ALARM FORECAST is a prediction
(based upon the most recently calculated SF6 trend)
of how many days before the SF6 reaches the Low
Gas Alarm Limit. This forecast aids in scheduling
and prioritizing of maintenance resources.
59
Page 60
5.3 Alarm Acknowledgement / Cancellation
Figure 24: User Interface, Status Page with Active Alarms
Typical interface activities performed on an OPTImizer2 to
acknowledge and cancel an alarm include:
• Some active alarms appear as red “ALARM”
hyperlinks on the STATUS page (see Figure 22).
Clicking on the red hyperlink will automatically move
you to the ACTION page (see Figure 11).
• CLEAR LATCHED ALARMS (Latched Alarms include:
Trip Time; Travel Time; Closing Time; Restrike;
Excess Arc and Clearing Time. These alarms can be
cleared by clicking the “Clear Latched Alarms” button.)
• Move to the ALARMS Page to view a list of active
alarms.
• Contact Life (I2 T or I T) Warning and Danger alarms
must be cleared by presetting the Contact Life (by
phase, see Figure 11) to a value lower than the alarm
limit. This should only be done after maintenance
to replace or recondition the interrupter contacts is
completed.
• See below for instructions for clearing alarms using a
USB Script.
5.4 USB Scripts
The OPTImizer2 has the special capability to perform
certain operations from script les installed on a USB
memory stick. These operations include: clearing alarms;
downloading the full database; resetting the IP address;
uploading new rmware. INCON Technical Support can
provide these scripts on memory sticks or through e-mail.
Downloading the Database: The full database will be
automatically downloaded to the USB memory stick.
Resetting the IP Address: The OPTI
mizer
’s IP address
2
will be automatically reset to “192.12.27.1”.
Uploading New Firmware: The new rmware will be
automatically uploaded. All conguration settings and
recorded history will be retained.
Transferring a script to a USB memory stick: Insert a USB
memory stick into the USB port on the computer. Copy the
les provided to the memory stick. (Only one script may be
installed at a time on a memory stick). Remove the USB
memory stick from the computer. It is ready to use. Insert it
into the OPTImizer2’s USB port.
While the USB script is running, all LED’s will be lit. If
there is a problem with the USB script or an error occurs
while running the script, the LED’s will ash rapidly. When
a script has completed its operation, the OPTI
ash all its LED’s slowly. When the LED’s are ashing the
USB memory stick can be removed and the OPTImizer
mizer
2
will
2
will return to normal operation. If the USB memory stick is
not removed, after 5 minutes the LED’s will stop ashing
and the OPTImizer2 will return to normal operation.
Clearing Alarms: All latched alarms will be automatically
cleared.
60
Page 61
6 COMMUNICATION DETAILS
6.1 RS-232
The OPTImizer2 uses asynchronous RS-232 communications. It is congured as a DCE device. A 9-pin
female connector is on the OPTImizer2 for cable connection. The end of the cable that connects with
the OPTImizer2 therefore is a 9-pin male.
OPTIMIZER2
DTE Device
DTE Device
9
9
Pin
Pin
STRAIGHT- THROUGH
STRAIGHT- THROUGH
(IN) DCD 1
(IN) DCD 1
(IN) RXD 2
(IN) RXD 2
(OUT) TXD 3
(OUT) TXD 3
(OUT) DTR 4
(OUT) DTR 4
GND 5
GND 5
(OUT) RTS 7
(OUT) RTS 7
(IN) CTS 8
(IN) CTS 8
1 DCD (OUT)
6
6
9
9
1 DCD (OUT)
2 RXD (OUT)
2 RXD (OUT)
3 TXD (IN)
3 TXD (IN)
5 GND
5 GND
6 N/C
6 N/C
7 RTS (IN)
7 RTS (IN)
8 CTS (OUT)
8 CTS (OUT)
9 N/C
9 N/C
9
Pin
(IN) DTR 4
(IN) TXD 3
(OUT) RXD 2
(OUT) DCD 1
(OUT) CTS 8
(IN) RTS 7
GND 5
6
9
4 DTR (IN)
4 DTR (IN)
OPTImizer
1 DCD (OUT)
2 RXD (OUT)
3 TXD (IN)
4 DTR (IN)
5 GND
6 N/C
7 RTS (IN)
8 CTS (OUT)
9 N/C
DCE Device
DCE Device
DCE DeviceDCE Device
9
9
Pin
Pin
2
Pins 1 and 4
are connected
internally
9
Pin
Pins 1 and 4
are connected
internally
“NULL MODEM”
Note: All references are to DTE 9-pin convention.
CABLE
Figure 25: 9-pin to 9-pin Cable Connections
61
Page 62
OPTImizer
0
2
25
Pin
25
Pin
DTE Device
(OUT) DTR 20
(OUT) RTS 4
STRAIGHT- THROUGH
DCE Device
(OUT) DCD 8
(OUT) CTS 5
(IN) DCD 8
(IN) RXD 3
(OUT) TXD 2
GND 7
(IN) CTS 5
(IN) DTR 2
(IN) TXD 2
(OUT) RXD 3
GND 7
(IN) RTS 4
DCE Device
6
9
1 DCD (OUT)
2 RXD (OUT)
3 TXD (IN)
4 DTR (IN)
5 GND
6 N/C
7 RTS (IN)
8 CTS (OUT)
9 N/C
OPTImizer
DCE Device
6
9
1 DCD (OUT)
2 RXD (OUT)
3 TXD (IN)
4 DTR (IN)
5 GND
6 N/C
7 RTS (IN)
8 CTS (OUT)
9 N/C
Pins 1 and 4
are connected
internally
9
Pin
2
9
Pin
Pins 1 and 4
are connected
internally
“NULL MODEM”
Cable
Figure 26: 25-pin to 9-pin Cable Connections
Note:All references are to DTE 25 and 9 pin conventions.
62
Page 63
6.2 Fiber-Optic Interconnection
2814 M
2814 F
TRANSCEIVER
TRANSCEIVER
Male EndFemale End
The OPTImizer2’s serial port is congured to support the use of Schweitzer ber-optic transceivers.
A 9-pin female null modem adaptor must be used between the OPTImizer2 and the transceiver.
The transceiver will be powered directly from the OPTImizer2’s serial port’s CTS line. No other
programming is needed. The ber-optic connection labeled “T” on each transceiver should connect to
the ber-optic connection labeled “R” on the other transceiver.
Figure 27: Schweitzer Fiber-Optic Interface
6.3 RS-485
The OPTImizer2 employs full duplex RS-485 communications, but can be wired for half duplex
communication if needed. The same RS-232 port settings apply to the RS-485 port.
The OPTImizer2 uses a standard 10-Base T / 100-Base T Ethernet connector. A special “crossover
cable” is provided to facilitate connection directly to a computer’s RJ45 port. This cable may not be
suitable for connection to a router or other communication device.
63
Page 64
6.5 XML
The OPTImizer2 will respond to manual XML commands. To access XML command mode, select the
PREFERENCES page. Click on “EDIT” in the upper right.
Figure 30: User Interface, Preferences Page
Check the box next to “Show XML Tool”.
Click “Yes” to update the preferences.
Enter the Administrator’s password if prompted.
Figure 31: User Interface, Editing the Preferences Page
64
Page 65
Figure 32: User Interface, XML Page
Click “Query”. The Command eld can now be pulled down and an XML command selected. Click “Help” to view an
explanation of the command and its proper syntax.
Figure 33: User Interface, XML Command Access
Once selected, a command can be executed by clicking “Send”. The response will be listed in the lower portion of the
window.
65
Page 66
6.6 DNP3.0
The following table provides a “Device Prole Document” in the standard format dened in the
DNP3 Subset Denitions Document. While it is referred to in the DNP3 Subset Denitions as a
“Document,” it is only a component of a total interoperability guide. This table in combination with
the Implementation Table should provide a complete interoperability/conguration guide for the
OPTImizer
6.6.1 Device Prole Document
DNP V3.0
Device Prole Document
(Also see the DNP Implementation Table, beginning on page 68)
Vendor Name: Franklin Fueling Systems, Inc.
INCON Power Reliability Systems
2
.
Device Name: OPTImizer
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Notable objects, functions, and/or qualiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the Implementation Table):
NONE
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Data Link Re-tries:
1 None
1 Fixed
g Congurable from 0 to 255
Requires Data Link Layer Conrmation:
2
Device Function:
1 Master
g Slave
Maximum Application Fragment Size (octets):
Transmitted: Fixed at 4096
Received: Fixed at 4096
Maximum Application Layer Re-tries:
1 None
g Congurable from 0 to 65535
Requires Application Layer Conrmation:
1 Never
1 Always
g Sometimes
1 Congurable
Timeouts while waiting for:Data Link Conrm: 1 None g Fixed at 1 sec. 1 Variable 1 Congurable
Complete Appl. Fragment 1 None g Fixed at 5 sec. 1 Variable 1 CongurableApplication Conrm: 1 None g Fixed at 5 sec. 1 Variable 1 Congurable
Complete Appl. Response: 1 None g Fixed at 5 sec. 1 Variable 1 Congurable
66
1 Never
1 Always
g Sometimes
1 Congurable
Page 67
Sends/Executes Control Operations:
WRITE Binary Outputs: g Never 1 Always 1 Sometimes 1 Congurable
SELECT/OPERATE: 1 Never g Always 1 Sometimes 1 Congurable
DIRECT OPERATE: g Never 1 Always 1 Sometimes 1 Congurable
DIRECT OPERATE – No ACK: g Never 1 Always 1 Sometimes 1 Congurable
Count>1: g Never 1 Always 1 Sometimes 1 Congurable
Pulse On: 1 Never g Always 1 Sometimes 1 Congurable
Pulse Off: g Never 1 Always 1 Sometimes 1 Congurable
Latch On: g Never 1 Always 1 Sometimes 1 Congurable
Latch Off: g Never 1 Always 1 Sometimes 1 Congurable
Queue: g Never 1 Always 1 Sometimes 1 Congurable
Clear Queue: g Never 1 Always 1 Sometimes 1 Congurable
Reports Binary Input Change Events when no
specic variation requested:
Reports Time-Tagged Binary Input Change Events when no
specic variation requested:
1 Never
1 Only Time-Tagged
1 Only Non-Time-Tagged
g Congurable
Sends Unsolicited Responses:
1 Never
1 Congurable
1 Only certain objects
1 Sometimes
g ENABLE/DISABLE UNSOLICITED
Default Counter Object/Variation:
1 No Counter Reported
g Congurable
1 Default Object ____
Default Variation ____
1 Point by Point List Attached
Sends Multi-Fragment Responses:
1 Never
1 Binary Input Change With Time
1 Binary Input Change With Relative Time
g Congurable
Sends Static Data in Unsolicited Responses:
g Never
1 When Device Restarts
1 When Status Flags Change
Counters Roll Over at:
1 No Counter Reported
1 Congurable
g 16 Bits (65,535)
g 32 Bits (4,294,967,295)
1 Other Value ______
1 Point by Point List Attached
g Yes
1 No
67
Page 68
6.6.2 DNP3.0 Implementation Table
The following table identies the variations, function codes, and qualiers supported by the
OPTImizer
Object
Number
121
121
121
201
221
305
325
411
411
411
412
412
412
413
413
2
DNP Slave in both request messages and in response messages.
Variation
Number
11
22
OBJECTREQUESTRESPONSE
DescriptionFunction
Binary Input - Singlebit packed
Binary Input Change
Event - with absolute
time
Pulsed Control control relay output
block
Pulsed Control control relay output
block
Pulsed Control control relay output
block
Counter - 32-bit with
ag
Counter Change
Event - 32-bit with ag
Analog Input - single-
precision, oatingpoint with ag
Analog Input Change
Event - single-
precision, oating-
point without time
Analog Output Block
- 32-bit
Analog Output Block
- 32-bit
Analog Output Block
- 32-bit
Analog Output Block
- 16-bit
Analog Output Block
- 16-bit
Analog Output Block
- 16-bit
Analog Output Block
- single-precision,
oating-point
Analog Output Block
- single-precision,
oating-point
Code (Dec)
1(read)06 (no range, or all)129 (Response)00, 01 (start-stop),
1(read)06 (no range, or all),
3(select)17, 28 (index),
4(operate)17, 28 (index),
5
(direct op.)
1(read)06 (no range, or all)129 (Response)00, 01 (start-stop),
1(read)06 (no range, or all),
1(read)06 (no range, or all)129 (Response)00, 01 (start-stop),
1(read)06 (no range, or all),
3(select)17, 28 (index),
4(operate)17, 28 (index),
5
(direct op.)
3(select)17, 28 (index),
4(operate)17, 28 (index),
5
(direct op.)
3(select)17, 28 (index),
4(operate)17, 28 (index),
Qualier Code
(Hex)
07, 08 (limited qty),
09
39
39
17, 28 (index),
39
07, 08 (limited qty),
09
07, 08 (limited qty),
09
39
39
17, 28 (index),
39
39
39
17, 28 (index),
39
39
39
Function Code
Qualier Code (Hex)
(Dec)
02
129 (Response) 17, 28 (index),
39
129 (Response) echo of request
129 (Response) echo of request
129 (Response) echo of request
02
129 (Response) 17, 28 (index),
39
02
129 (Response) 17, 28 (index),
39
129 (Response) echo of request
129 (Response) echo of request
129 (Response) echo of request
129 (Response) echo of request
129 (Response) echo of request
129 (Response) echo of request
129 (Response) echo of request
129 (Response) echo of request
68
Page 69
6.6.3 DNP3.0 Point List
The following table identies for each data type, the data points available in the device.
Binary Input Points Slave >> Master
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: 1 (Binary Input 2 without status)
Change Event Variation reported when variation 0 requested: 3 (Binary Input Change with Time)
Event
Class
Circuit Breaker Monitor
1022
1122
1222
1322
1422
1522
1622
1722
1822
1922
11022
11122
11222
11322
11422
11522
11622
11722
11822
11922
12022
12122
SF
12222
12322
12422
12522
12622
12722
Point
Index
Default
Group
Default
Variable
Name/Description
Breaker Is Open
A-B Logic Failure Alarm Acve
Contact Life Warning Acve Phase A
Contact Life Warning Acve Phase B
Contact Life Warning Acve Phase C
Contact Life Danger Alarm Acve Phase A
Contact Life Danger Alarm Acve Phase B
Contact Life Danger Alarm Acve Phase C
Trip Time Alarm Acve
Arc Time Alarm Acve Phase A
Arc Time Alarm Acve Phase B
Arc Time Alarm Acve Phase C
Clearing Time Alarm Acve Phase A
Clearing Time Alarm Acve Phase B
Clearing Time Alarm Acve Phase C
Travel Time Alarm Acve
Closing Time Alarm Acve
Operaon Count Alarm Acve
No-Operaons Alarm Acve
Restrike Alarm Acve Phase A
Restrike Alarm Acve Phase B
Restrike Alarm Acve Phase C
Monitor
6
Sensor Malfuncon Alarm Acve
Low Density Alarm Acve
Trend Alarm Acve
CT Failure Alarm Acve Phase A
CT Failure Alarm Acve Phase B
CT Failure Alarm Acve Phase C
305Default Static Analog
325Default Event Analog
201Default Static Counter
221Default Event Counter
12Default Static Binary
22Default Event Counter
69
Page 70
Analog Input Points Slave >> Master
Static (Steady-State) Object Number:(30,1)
Change Event Object Number: (32,1)
Static Variation reported when variation 0 requested: (30,1)
Change Event Variation reported when variation 0 requested: (32,1)
Event
Class
Circuit Breaker Monitor
20325
21325
22325
23325
24325
25325
26325
27325
28325
29305
210305
211305
012305
013305
014305
015305
SF6 Monitor
016305
017305
018305
019305
020305
021305
022305
023305
024305
025305
026305
027305
028305
029305
030305
031305
032305
033305
Point
Index
Default
Group
Default
Variable
Name/DescriptionDead Band
Current Wear Phase A
Current Wear Phase B
Current Wear Phase C
Percent of Warning Limit Phase A
Percent of Warning Limit Phase B
Percent of Warning Limit Phase C
Percent Of Danger Limit Phase A
Percent Of Danger Limit Phase B
Percent Of Danger Limit Phase C
Percent Remaining Contact Life Phase A
Percent Remaining Contact Life Phase B
Percent Remaining Contact Life Phase C
RMS Current Phase A
RMS Current Phase B
RMS Current Phase C
Days since last operaon
Current Density Channel A
Current Density Channel B
Current Density Channel C
Current Temperature Channel A
Current Temperature Channel B
Current Temperature Channel C
Trend Channel A
Trend Channel B
Trend Channel C
Trend Condence Level Channel A
Trend Condence Level Channel B
Trend Condence Level Channel C
Average Mass Channel A
Average Mass Channel B
Average Mass Channel C
Average Pressure Channel A
Average Pressure Channel B
Average Pressure Channel C
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
70
Page 71
Counter Input Points Slave >> Master
Static (Steady-State) Object Number:(20,1)
Change Event Object Number: (22,1)
Static Variation reported when variation 0 requested: (20,1)
Change Event Variation reported when variation 0 requested: (22,1)
Point
Index
10221
11221
Point
Index
Default
Group
Default
Variable
Name/Description
Current Operaon Number
Operaon Count
Control Output Points Master >> Slave
Static (Steady-State) Object Number:(12,1)
Change Event Object Number: NA
Static Variation reported when variation 0 requested: NA
Change Event Variation reported when variation 0 requested: NA
Point
Index
Circuit Breaker Monitor
0
1
2
3
SF
4
5
Name/Description
Clear Circuit Breaker Alarms
Reset Operaon Count
Preset Operaon Number
Preset Contact Life
Monitor
6
Clear SF6 Alarms
Reset Trend Data
Setpoint Output Points Master >> Slave
Static (Steady-State) Object Number:(40,2)
Change Event Object Number: NA
Static Variation reported when variation 0 requested: NA
Change Event Variation reported when variation 0 requested: NA
Circuit Breaker Monitor
0
1
2
3
Preset Operaon Number Value
Preset Contact Life Value Phase A
Preset Contact Life Value Phase B
Preset Contact Life Value Phase C
71
Page 72
7 SPECIFICATIONS
Electrical:
Power Supply Input Voltage 110-250 VDC / 90-264 VAC, 50 / 60 Hz
Aux A & B Input Voltage0 to 48 - 250 VDC
CT (Pickup Coil) Input Signal0 to 5 VAC
Input Sampling Rate32 Samples per line cycle
Input Signal
SF
6
Sensor Power20 VDC @ 25mA Max
SF
6
Relay OutputsDry Contact; 2 ea. Form C, 1 ea. Form A
Relay Contact Rating3 Amps @ 250 VAC or ½ Amps @ 125 VDC
Environmental:
Operating Temperature -40 to 65° C
Storage Temperature -40 to 65° C
Humidity0 to 95% Non-condensing
Communication:RS-485 Full / Half Duplex
Analog: 4 to 20 mA
Digital: Frequency & Pulse-Width Modulated
RS-232
USB Master
Ethernet
User Interface:19 LED’s
Immunity and Emissions Certication:
CISPR 16-2-1 (Conducted Emissions)
CISPR 16-2-3 (Radiated Emissions)
IEC61000-4-2 (ESD)
IEC61000-4-3 (Radiated RF)
IEC61000-4-4 (EFT)
IEC61000-4-5 (Surge)
IEC61000-4-6 (Conducted RF)
IEC 61000-4-11 (Voltage Dips & Interrupts)
IEC 61000-4-12 (Damped Osc. Wave, Power Ports)
FCC Part 15, Subpart B; ICES-003 (Emissions)
Physical:
184 L x 146 W x 76 H Millimeters
Dimensions
7.25 L x 5.75 W x 3.00 H Inches
Shipping Weight5 lbs. (2.25Kg)
Table 10, OPTImizer2 Specications
72
Page 73
DSDP SF6 Density & Temperature Sensor Specications
Principal:Oscillating Quartz Measurement
Density Measuring Range:0 to 60 Grams per Liter (kg/m3) SF
Temperature Measuring Range:-40 to +85 Degrees Celsius
Accuracy:+/- 1% of measured value and +/- 1% of range
Repeatability:+/-0.2% of measured value
Stability:<+/-0.3% per year
Temperature Signal:+/-1ºC @ ambient temperature, +/-3ºC at -40 to 85ºC
Output Signal:Current pulses, frequency & pulse-width modulated