Incon 1250-LTC Installation And Programming Manual

INSTALLATION AND
PROGRAMMING MANUAL
FOR MODEL
1250-LTC
Solid State Indicator for SynchroTransmitter
000-2072 Rev. C
1
INTELLIGENT CONTROLS, INC.
PO Box 638
Saco, Maine 04072 USA
Phone: 207-283-0156 FAX: 207-283-0158
Toll Free: Technical Service & Sales 800-872-3455
Web Site: www.incon.com E-mail: sales@incon.com
This manual applies to all INCON model 1250-LTC monitors
Copyright 2008, Intelligent Controls, Inc. All rights reserved
.
2
TABLE OF CONTENTS
Section: Page:
List of Figures…………………………………………………………………… 4
List of Tables……………..……………………………………………………… 4
Introduction……………………………………………………………………... 5
1.0 Installation……………………………………………………………..…… 5 - 8
2.0 Programming…………………………………………………………..…… 9 – 33
2.1 Front Panel Programming…………………………………………….. 9
2.2 Serial Port Programming – ASCII …………………………………… 13 - 17
2.3 Serial Port Programming – MODBUS……………………………….. 18 – 33
2.3.1 MODBUS Packet Format – Read……………………………….. 19
2.3.2 MODBUS Packet Format – Write………………………………. 20
2.3.3 MODBUS Packet Format – Error Exception Response……….. 21
2.4 Operating Modes………………………………………………………. 34 – 37
2.5 Programming Notes……………………………………………………. 38
3.0 Options…………………………………………………………………..….. 39 – 48
3.1 Analog Output……………………………………………………..…… 39
3.2 High / Low Relay Limits………………………………………..……… 40 – 45
3.2.1 Tap Change Acknowledgement.………………………………… 41
3.2.2 High Tap / Low Tap……………………………………………… 41
3.2.3 Total Tap Change Count………………………………………… 42
3.2.4 On-Tap Alarm……………………………………………………. 42
3.2.5 Up-To & Down-To Count………………………………….…….. 44
3.2.6 Pass-Through-Neutral Alarm…………………………….……… 44
3.2.7 One-Direction Change Count…………………………….……… 45
3.2.8 FA 25 & FA 27 Error Alarm…………………….…………….… 45
3.3 Serial RS-232…………………………………………………...……….. 46
3.4 Serial RS-485 .……………………………………...………………….... 47
3.5 Input Isolation…………………………………………………...……… 48
4.0 Field Calibration and Test………………………………………...…….…. 48 – 49
5.0 Error Codes…………………………………………………………….……. 50
6.0 Specifications…………………………………………………………….….. 51
3
LIST OF FIGURES
Figure: Page:
1.1 Mechanical Dimensions…………………………………………………………… 6
1.2 Field Wiring Diagram…………………………………………………………….. 6
1.3 Field Wiring Diagram with 4-20mA Option.…………………………………….. 7
2.1 Simplified Programming Flowchart…...…………………………………………. 12
2.2 Serial Data Dump Example……………………………………………………….. 17
2.3 Base 1 Uni-Polar Mode Analog Output………………………………………….. 35
2.4 Base 0 Uni-Polar Mode Analog Output………………………………………….. 36
2.5 Bi-Polar Mode Analog Output…………………………………………………… 37
3.1 Relay Field Wiring Diagram……………………………………………………... 40
3.2 On-Tap Example………………………………………………………………….. 43
4.1 Analog Output Adjustment Pots…………………………………………………. 49
LIST OF TABLES
Table: Page:
1.1 Terminal Functions……………………………………………………………… 7
1.2 DIP Switch Functions…………………………………………………………... 7
1.3 Analog Output Configuration Jumpers…………………………………………. 8
2.1 Numeric and Alpha-numeric Menu Items……………………………………… 9-12
2.2 Serial Programming ASCII Commands……………………………………….. 13-15
2.3 Read Registers Command Format..……………………………………………. 19
2.4 Read Registers Response Format.…………………………..………………….. 19
2.5 Write Registers Command Format……………………………………………... 20
2.6 Write Registers Response Format……………………………………………… 20
2.7 Error Exception Response Format……………………………………….…….. 21
2.8 RS-485 MODBUS Register Definitions...……………………………………… 22-33
3.1 Analog Output Load Limits……………………………………………………. 39
3.8 Wiring: Digital Connector Pin-Out……………………………………….…….. 47
5.1 Error Codes …………………………………………………………….….……. 50
4
INTRODUCTION
The Model 1250-LTC Programmable Position Monitor is a highly advanced solid­state instrument, which measures the absolute position of a synchro transmitter. It provides both a user definable visual panel indication and optional analog and digital signal outputs suitable for a variety of monitoring and control applications.
The INCON 1250-LTC series is unique in its capability to monitor up to 40 user­definable position segments. It is specifically designed for monitoring power transformer load tap changer position, where the desired readout is in whole tap numbers. Its transmitter can be attached to any operating shaft on the LTC and the 1250 programmed to read out in tap positions. The display and all outputs follow a “stair step” function defined in the program. The INCON 1250 has become the industry standard for LTC position monitoring.
In addition to basic LTC tap position, the 1250-LTC can provide useful information about the movement of the LTC. Beginning with a momentary (optional) relay closure after each successful tap change, the 1250-LTC keeps records on seven important issues relating to LTC movement, including: total number of tap changes; number of days since last “pass through neutral”; number of changes “up to” and “down to” each tap; and more.
Most LTC’s rotate about 9 to 11 degrees with each tap change. The 1250-LTC can measure in increments of 1/10th of a degree. A special feature of the 1250-LTC is its ability to monitor small discrepancies in tap position. A programmable limit can be set to give an alarm when the discrepancy in tap position reaches the limit. Inaccurate tap position can be an early indicator of wear in the LTC mechanism or possible impending failure.
The 1250-LTC may be wired in parallel with existing synchro transmitter/receiver pairs or wired directly to the synchro transmitter. Additional 1250’s may be wired to the same transmitter without compromising the accuracy or reliability of the system.
1.0 INSTALLATION
The Model 1250-LTC is designed for use in any 50/60 Hz, five-wire synchro system compatible with electrical specifications given in Section 6.0, page 51. These devices include CX, TX, CDX, and TDX function synchros, as well as Self-Synchronous Indicator devices. (INCON’s model 1292 Synchro is a highly specified robust transmitter with a history of proven performance.)
The panel-mount case is designed to snap-fit into a standard 1/8 DIN rectangular cut-out of 44mm (1.73 in.) by 92mm (3.62 in.)
Wiring is done to the rear of the case. #16 AWG (min.) type THHN, THWN, TFFN, or equivalent wire is recommended for the five AC synchro lines. #20 AWG (min.) shielded twisted pair wire is recommended for analog output wiring. Use appropriate spade lugs (provided) when connecting to the case terminals.
Contact INCON Technical Service (1-800-872-3455) for application assistance if the synchro transmitter and the 1250-LTC monitor are separated by a wire run of more than 1200 feet.
5
Figure 1.1 Mechanical Dimensions
Figure 1.2 Field Wiring Diagram
6
Figure 1.3 Field Wiring Diagram with 4-20mA Output
Table 1.1 Terminal Functions
Terminal Function Terminal Function
A S1 1 Analog Output + B S2 2 Analog Output – C S3 3 Program Mode Inhibit D (Spare) 4 Inhibit Return E R1 * 5 Line L1 * F R2 * 6 Line L2 * 7 Chassis Ground * Terminals E & F are 8 Relay Low Contact N.O. jumpered to 5 & 6 9 Relay Common respectively 10 Relay High Contact N.O.
A DIP switch tells the firmware which hardware options are installed, so their function can be enabled. It is located on the top PCB, above the power transformer and is accessible through a slot in the left side of the case, towards the rear of the instrument.
Table 1.2 DIP Switch Functions
Switch # Function
1 Serial Communications Option Enable 2 MODBUS Protocol Enable 3 Spare 4 High / Low Relay Limit Option Enable 5 Analog Output Option Enable 6 Spare 7 Spare 8 In-Factory Test & Calibration Menu Enable
7
Installation Notes:
1) A resistor may be wired remotely across the analog output terminals to convert analog output milliamp current to a voltage. Use Ohm’s Law to calculate the proper resistance for the desired voltage based upon the 1250-LTC’s rated output current.
2) Maximum analog output load resistance: 0-1mA = 10K ohms; +/-1mA = 10K ohms; 0-2mA = 5K ohms; 4-20mA = 500 ohms.
3) Models with 4-20 mA analog output options must have an EXTERNAL LOOP POWER SOURCE of 10.0 VDC minimum, 24.0 VDC maximum, in series with the current loop. The INCON Model 1945 Power Supply is recommended for these installations, (See Figure 1.3, page 7).
4) When additional remote indication is needed, several 1250-LTC’s may be wired in parallel to the same transmitter. The 1250-LTC can also be connected via its serial port to the INCON model RD-4 Remote Display unit.
5) The 1250-LTC and the synchro transmitter MUST BE WIRED TO THE SAME AC SOURCE. Do not remove the jumpers from terminals E and F.
6) A wire jumper or keyswitch may be installed between terminals 3 & 4 to prevent the program from being changed. When these terminals are jumpered the menu will read “EP-x” instead of “OP-x”, which indicates that you can Examine each Parameter, but not change them.
7) After installation and programming, install the rear terminal guard with screws provided.
8) For models with serial options, plug the cable onto the card edge with the red stripe towards the outside of the case.
Application Bulletins:
1) If there is a large component of AC “ripple” present on the 1250 analog output, check the isolation of all wiring with respect to earth ground. R1, R2, S1, S2, and S3 should measure infinite resistance to earth ground. In applications where external isolation is not sufficient, the Input Isolation Option (-I) is required to break the ground path that causes this ripple. See Application Bulletin #000-1150 for more detailed information.
2) Analog outputs of 0-1mA, +/-1mA, and 0-2mA can be changed in the field to any one of the other two (see Table 1.3). The configuration jumpers are located on the bottom PCB. See Application Bulletin #000-1151 for more detailed information.
Table 1.3 Analog Output Configuration Jumpers
Output Signal: J8 J10 J12 J13
0-1mA Jumped Jumped Jumped
+/-1mA Jumped Jumped Jumped
0-2mA Jumped Jumped
8
2.0 PROGRAMMING
The Model 1250-LTC has three methods of programming: numeric menu (traditional
1250); alphanumeric menu; and serial port programming commands. The 1250-LTC can be
ordered with either RS-232 or RS-485 serial port hardware. The serial programming commands can be in the form of ASCII characters or MODBUS packets, depending upon the position of DIP switch #2. See Tables 2.1, 2.2 & 2.3 for a full listing of all programming menu items, commands, and syntax. See the simplified programming flowchart for tap position on page 12, Figure 2.1.
2.1 Front Panel Programming
To access the numeric or alphanumeric programming menu, press the MENU key for several seconds until the display goes blank, then press the SELECT/ENTER key. The display should read “OP 0”. The default menu is the numeric menu. To choose the alphanumeric menu, press the DOWN key to select OP 99. Press the SELECT/ENTER key, the display should read “to OP”. Press the UP key. The display should read “run”. You are now in the alphanumeric menu mode.
To change a parameter using the numeric or alphanumeric menus, select the parameter to be changed from the menu, press the SELECT/ENTER key. The parameter’s present setting will now be displayed. You can change the setting by pressing the UP or DOWN key. To store the new setting, press the SELECT/ENTER key, the display will return to the menu.
Table 2.1 Numeric and Alphanumeric Menu Items:
Num­eric
OP 0 run Press the SELECT/ENTER key to exit the
OP 2 Func Select Operating Mode (see pages 34-37) 21 16, 17, 18, 19, 20,
OP 3 tCrLY Selects which relay will assert
OP 4 tCrdL Sets the delay time before Tap Change
OP 5 tCrLt Sets duration of time the Tap Change
OP 6 dHF-L Selects which visit to the Draghand
OP 10 LtCLr Low Tap Alarm Clear CL OP 11 HtCLr High Tap Alarm Clear CL OP 15 rL Lt Sets low relay limit tap -16 Any valid tap
OP 16
OP 17 rL Ht Sets high relay limit tap +16 Any valid tap
OP 18
Alpha-numeric Protocol
LtrLY
HtrLY
Function: Default
Value:
Program mode
OFF OFF, LO, HI
momentarily, after each tap change
0.0 0.0 to 9.9
Acknowledge Relay turns on (Seconds)
0.0 0.0 to 9.9
Acknowledge Relay stays on (Seconds)
LASt “FirSt”, “LASt” positions (first the day counters
Selects which relay will assert when the “Low Tap” alarm limit is reached
Selects which relay will assert when the “High Tap” alarm limit is reached
time or last time) will begin
OFF OFF, LO, HI
OFF OFF, LO, HI
Programmable Range:
21
number
number
9
Num­eric
OP 19
OP 20 OP 21 OP 22 nEu Number of neutral taps 1 0 to 8 OP 23 n St Sets lowest neutral tap 0-1 Any valid tap
OP 27 S Pt Sets present tap position 0 Any valid tap
OP 28 L Pt Loads present tap position into memory Ld OP 29 dSPrL Enables display of “r” or “L” in Function
OP 30 CAL E Enables analog output Calibration Mode OFF On or OFF OP 31 L CAL Forces the analog output to its lowest
OP 32 H CAL Forces the analog output to its high scale
OP 33 d CAL Forces the analog output to its mid scale
OP 34 t CAL Forces the analog output to alternate
OP 39 dOG t Forces a Watchdog Reset (Factory use
OP 40 LED t Display LED Test: Turns on all LED’s -8.8.8.8.8. OP 41 rS t RS-232 Echo Test: Re-transmits characters
OP 42 InCAL Calibrates synchro input circuitry CAL OP 43 rLY t Relay Test: UP and DOWN keys toggle
OP 50 dSPbL Causes the display to go blank after 60 sec. OFF On or OFF OP 51 SEr Serial Communication Mode:
OP 53 Aut25 Auto-Reset after “FA 25” Loss of Synchro
OP 54
OP 55 ttCLt Sets Total Tap Change counter alarm limit
OP 56 ttrLY Selects which relay will assert when the
OP 57 ttPrE Presets the Total Tap Change counter in
OP 58 ttdtE Total Tap Change counter reference date
OP 59 ttCdS Displays Total Tap Change Count and
Alpha-numeric Protocol
dEGrE
tAPS d SEG
25rLY
Function: Default
Value:
Displays absolute synchro position in degrees with one decimal place resolution Number of taps 33 2 to 40 Degrees per tap 10.000 -99999 to +99999
Modes 20 and 21
signal output
signal output
signal outputs
between high and low scale signal outputs
only)
received through the RS-232 serial port
between LO and HI relays
0=Serial Disabled, 1=Data Logger Mode, 2=Polled Mode, 3=Sampled Mode, 4=Serial Command Mode, 5=Reserved, 6= MODBUS Mode, 7=Remote Display Driver Mode
Signal Error (page 50) Selects which relay will assert when the “FA 25” error is active
in THOUSANDS
Total Tap Change counter limit is reached
THOUSANDS
Enter day, month, year
reference date Press ENTER to exit
OFF On or OFF
LO
HI
- -
LO then HI
<<Press ENTER>>
rS
LO then HI
0 0 to 4, and 6
OFF On or OFF
OFF OFF, LO, HI
000.01 000.01 to 999.99
OFF OFF, LO, HI
000.00 000.00 to 999.99
01–01–00
Programmable Range:
number
number
10
Num­eric
OP 60 Aut27 Auto-Reset after “FA 27” Unstable
OP 61
OP 62 OtGLt Sets On-Tap guard band limit (Degrees) 0.1 0.1 to 9999.9 OP 63 OtrLY Selects which relay will assert when the
OP 64 OtdtE On-Tap reference date
OP 65 OtdIS Scrolls through the list of taps, to select,
OP 66 Otdtd Scrolls through the list of taps which have
OP 67 OtCLr Clears the On-Tap alarm CL OP 68 OtrSt Resets all On-Tap logs & alarm rESEt OP 70 udCLt Sets the alarm limit for the number of
OP 71 udrLY Selects which relay will assert when the
OP 72 uddtE UP TO & DOWN TO Change counter
OP 73 uddIS Scrolls through the list of taps to select,
OP 74 udCLr Clears an active Up-To and Down-To
OP 75 udrSt Resets all Change Up-To and Down-To
OP 80 POrt Sets serial port parameters: (press the UP
OP 85 PtnLt Sets the limit for number of days without a
OP 86 PtrLY Selects which relay will assert when the
OP 87 PtdIS Displays the number of days since the last
Alpha-numeric Protocol
27rLY
Function: Default
Value:
OFF On or OFF Synchro Signal Error (page 50) Selects which relay will assert when the “FA 27” error is active
On-Tap guard band limit is reached
Enter day, month, year
Press ENTER to display the highest measured deviation, for that tap Press MENU to escape back to the menu
exceeded the On-Tap alarm limit to select, Press ENTER to display the highest measured deviation, for that tap Press MENU to escape back to the menu
changes UP TO any tap in THOUSANDS
“UP TO” change alarm limit is reached
reference date Enter day, month, year
Press ENTER to display the Change Up­To count Press ENTER to display the Change Down-To count, for that tap Press MENU to escape back to the menu
Change alarm
counters and alarm
or Down key to select a value, press the enter key to move to the next parameter)
Baud rate
Word length
Parity (n=none, E=even, O=odd)
Stop bits
Address (for RS-485 Multi-drop)
“Pass Thru Neutral”
“Pass Thru Neutral” time limit is reached
“Pass-Through-Neutral”
OFF OFF, LO, HI
OFF OFF, LO, HI
01–01–00
Any valid tap
Any valid tap
000.01 000.01 to 999.99
OFF OFF, LO, HI
01–01–00
0 Any valid tap
CL
rESEt
9600
8
n
1
128
OFF Off, 0.1 to 365.0
OFF OFF, LO, HI
Programmable Range:
number
number
number
2400, 4800, 9600, 14400, 19200, 28800,38400, 57600, 76800
7 or 8 n, E, O 1 or 2 0 to 255
11
Num­eric
OP 88 PtrSt Resets the “Pass-Through-Neutral”
OP 90 1dCLt Sets the limit for number of consecutive
OP 91 1drLY Selects which relay will assert when the
OP 92 1ddIS Displays the number of days since the
OP 93 1dCLr Clears “One Direction Change” alarm CL OP 99 tO OP Toggles between Numeric and
Alpha-numeric Protocol
Function: Default
Value:
rESEt counter & alarm
2 2 to 30 tap changes in One Direction
OFF OFF, LO, HI “One Direction Change” limit is reached
“One Direction Alarm” was asserted
tO OP Alphanumeric menus
Programmable Range:
Figure 2.1 Simplified Programming Flowchart
12
2.2 Serial Port Programming - ASCII:
These commands require either the RS-232 (-S) or RS-485 (-M) hardware option. To use the serial port programming commands, connect a computer terminal to the serial port cable. The terminal must have the proper Comm port settings to communicate to the 1250-LTC (see Sections
3.3 and 3.4, pages 46 - 47). See Table 2.2 for a full listing of all Serial Programming Commands and syntax. At the command prompt, type a command followed by the new parameter setting, using proper syntax as shown in Table 2.2. Typing the command only, without a new para-
meter setting, will cause the 1250-LTC to transmit the present setting for that parameter.
Table 2.2 Serial Programming ASCII Commands:
=space ª=enter
Command Syntax: Function: Explanation:
SETUPª Enter the Setup Mode This command must be entered before
any other commands can be made.
EXITª Re-starts the serial connection Changes to comm. port settings will take
effect
RUNª Return to the Run Mode Changes to settings will take effect DISPª Displays all setup parameters Each setup parameter command is dis-
played with the current value following it
DUMPª Displays all measured LTC
information
(See Figure 2.2, page 17)
POSª Displays present Tap #, synchro
position (in degrees) and current On-Tap deviation degrees
MODE◊nnª ACKRLY◊LOª
ACKDLYnn.nª
ACKHOLDnn.nª
DHCOUNTFIRSTª
DHLRST Low Draghand Reset Draghand value becomes present tap DHHRST High Draghand Reset Draghand value becomes present tap LTLMTnnª LTRLYLOª
LTCLRª Clears Low Tap Alarm Also resets “Days Since Alarm” counter HTLMTnnª HTRLYLOª
HTCLRª Clears High Tap Alarm Also resets “Days Since Alarm” counter TAPSnnª
Segmented modes See Section 2.4, page 34-37 for details Selects which relay will assert
momentarily after each tap change Sets the delay time, in seconds, before the ACK relay asserts Sets the duration, in seconds, that the ACK relay remains on Selects which visit to the Draghand position to begins the day counter
Set Low Tap alarm limit n= an integer, any valid tap number Selects which relay is associated
with the Low Tap alarm
Set High Tap alarm limit n= an integer, any valid tap number Selects which relay is associated
with the High Tap alarm
Set number of taps n= an integer from 2 to 40
Lists: Total tap change count, Days since Pass-Through-Neutral, High & Low Draghand positions, Change Up-To and Down-To counts for each tap, Maximum On-Tap deviations for each tap, etc… Reads Tap #, 0.0 to 359.9 degrees, with one decimal place of resolution Press ª (enter) to exit
Choose “OFF”, “LO” or “HI” relay to assert momentarily after each tap change
n= a number from 0.1 to 9.9 with one decimal place resolution n= a number from 0.1 to 9.9 with one decimal place resolution Choose “FIRST” or “LAST” visit. The number of days since the LTC visited that extreme position the first or last time
Choose “OFF”, “LO” or “HI” relay to assert when the alarm limit is reached
Choose “OFF”, “LO” or “HI” relay to assert when the alarm limit is reached
13
Command Syntax: Function: Explanation:
DEGSEGn.nnnnª
NEUTRALSnª NSTARTnnª SETTAPnnª LDTAPª DISPRLONª
ANACALª
WDOGTESTª LEDTESTª Turns on all display segments Press the enter key to stop the LED test INCALª Self-calibrates the input circuitry Outputs “Pass” or “Fail” calibration
RLYTESTª Forces Hi / Lo relay output to
DSPBLONª
SERIALnª
AUTO25ONª
FA25RLYLOª
RESET25ª Manually clears the “FA 25”
TTCLMTnnn.nnª
TTCRLYLOª
TTCPREnnn.nnª
TTCDATEmm-dd-yyyyª
AUTO27ONª
FA27RLYLOª
RESET27ª Manually clears the “FA 27”
Set degrees per segment n= a floating point number, 5 digits max,
average number of degrees between taps Set number of neutral taps n= an integer from 0 to 8 Set lowest neutral tap number n= an integer, any valid tap number Set present tap position n= an integer, any valid tap number
Load present tap pos. into memory Enables the display of “r” (raised)
and “L” (lowered) tap numbers
Must be done for SETTAP to take effect
ON” or “OFF” When enabled causes
the display to show “r” and “L” in
function modes 20 and 21 only
Enter analog calibration mode, the 1250 analog output will be forced to Low / Mid / High signal output Forces a Watchdog Reset This command is for factory use only.
Press the space bar to toggle between
Low / Mid / High analog output. Press the
enter key to stop calibration
result
Press the Space Bar to toggle between close Enables the display blanking feature
Lo or Hi relay Press ª (enter) to exit
ON” or “OFF” When enabled causes
the display to go blank after 60 sec. Set serial communication mode 0=Serial Disabled, 1=Data Logger
Mode, 2=Polled Mode,
3=Sampled Mode,
4=Serial Command Mode, 5= Reserved,
6=MODBUS Mode, 7=Remote Display
Driver
Enables automatic reset of the “FA 25” Loss of Synchro Signal Error (page 50) Selects which relay is associated with the “FA 25” Error
“ON” or “OFF” When “ON”, the
“FA 25” alarm will automatically reset
when the condition clears
Choose “OFF”, “LO” or “HI” relay to
assert when the FA 25 Error is active
When AUTO25 is “OFF”, manually alarm Sets the Total Tap Change count alarm limit in THOUSANDS Selects which relay is associated with the Total Tap Change count
clears the alarm and opens the relay
n= a number from 0.00 to 999.99 with
two decimal place resolution
Choose “OFF”, “LO” or “HI” relay to
assert when the alarm limit is reached alarm
Presets the Total Tap Change counter
and clears the alarm
Sets the Total Tap Change
counter reference date
in THOUSANDS
Enables automatic reset of the “FA 27” Unstable Synchro Signal Error (page 50) Selects which relay is associated with the “FA 27” Error
n= a number from 0.00 to 999.99 with
two decimal place resolution
mm-dd-yyyy = Month <hyphen> Day
<hyphen>Year (4 digits)
“ON” or “OFF” When “ON”, the
“FA 27” alarm will automatically reset
when the condition clears
Choose “OFF”, “LO” or “HI” relay to
assert when the FA 27 Error is active
When AUTO27 is “OFF”, manually alarm
clears the alarm and opens the relay
14
Command Syntax: Function: Explanation:
OTGDLMTnn.nª
Sets the On-Tap guard band limit in DEGREES
OTRLYLOª
Selects which relay is associated with the On-Tap alarm
OTDVTNª Displays the tap with the greatest
On-Tap Deviation
OTDATEmm-dd-yyyyª
Sets the On-Tap reference date
OTCLRª Clears the On-Tap alarm Data is retained, the alarm is cleared OTRSTª Resets all On-Tap logs & alarm All On-Tap data is erased, alarm cleared UPDNLMTnnn.nnª
Sets the alarm limit for the number of changes “Up-To” and “Down-To” any tap
in THOUSANDS
UPDNRLYLOª
Selects which relay is associated with the “Up-To / Down-To” Change alarm
UPDNDATEmm-dd-yyyyª
Sets the Up To / Down To
Change counter reference date
UPDNCLRª Clears an active Up-To or
Down-To Change alarm
UPDNRSTª Resets all Change Up-To and
Down-To counters and alarm
PORTbbbbwp
◊s◊aª
Set comm. port settings: baud rate, word length, parity, stop bits, and address
SITEIDAbcd-Xyz & 123ª
Identifies installation site on the “DUMP” header
PTNLMTnnnª
Sets the alarm limit for the number of DAYS without a “Pass Through Neutral”
PTNRLYLOª
Selects which relay is associated with the “Pass-Through-Neutral” alarm
PTNRSTª Resets the “Pass-Through-
Neutral” counter & alarm
1DTCLMTnnª
Sets the alarm limit for the number of consecutive tap changes in One Direction
1DTCRLYLOª
Selects which relay is associated with the “One Direction” alarm
1DTCCLRª Clears a “One Direction” alarm MENU◊1ª
Set the keyboard button menu type
n= a number of degrees from 0.0 to 99.9
with one tenth degree resolution
Choose “OFF”, “LO” or “HI” relay to
assert when the alarm limit is reached
Displays Tap Number and Deviation
mm-dd-
yyyy = Month <hyphen> Day
<hyphen>Year (4 digits)
n= a number from 0.00 to 999.99 with
two decimal place resolution
Choose “OFF”, “LO” or “HI” relay to
assert when the alarm limit is reached
mm-dd-yyyy = Month <hyphen> Day
<hyphen>Year (4 digits)
If a tap with an Up-To or Down-To Change
counter exceeding the programmed limit is
re-visited, the alarm will re-activate
All Up-To and Down-To counters are reset
to zero and an active alarm is turned off
b=
2400, 4800, 9600, 14400, 19200,
28800, 38400, 57600, 76800 baud
w= 7 or 8 bit word
p= n, E, O
s= 1 or 2 stop bits
a= 0 to 255
40 ASCII Characters – Upper / lower case
letters, numbers, punctuation marks
n= a number from 0.0 to 365.0 with one
decimal place resolution
Choose “OFF”, “LO” or “HI” relay to
assert when the alarm limit is reached
n= an integer from 2 to 30, OFF
Choose “OFF”, “LO” or “HI” relay to
assert when the alarm limit is reached
“1” = Numeric “OP” menu or
“2” = Alpha-numeric menu
15
HELP(command) ª
Provides on-line help on the specific command entered or lists all available commands
An explanation of a command and the
proper entry syntax is given. If no
command is entered, all commands will
be listed with syntax but no explanations
To prevent accidental or unwanted changes to the program parameters, a jumper wire may be installed across terminals 3 & 4. With this jumper installed, the numeric menu will read “EP nn” instead of “OP nn”. All parameters can be viewed but no changes can be made.
16
Loading...
+ 36 hidden pages