Incite Fire Sigma CP Operation And Maintenance Manual

SIGMA-CP Issue 1 November 2011
Conventional Fire Control Panel AFP-2516 Operation and Maintenance Manual
Man-1078_Sigma_CP_AUS_12
Page 2 of 29
I
ndex Page
1 Warning ......................................................................................................................... 4
2 Introduction .................................................................................................................... 5
3 Safety and Mounting ........................................................................................................ 5
3.1 Safety .................................................................................................................................... 5
3.2 Mounting ................................................................................................................................ 6
4 Technical specification ..................................................................................................... 7
6 Using intrinsically safe barriers.......................................................................................... 9
7 Control panel fascia ....................................................................................................... 10
8 Connecting to the circuit board ....................................................................................... 11
9 Software revision number .............................................................................................. 11
10 Detection zone wiring .................................................................................................... 12
11 Sounder circuit wiring .................................................................................................... 13
12 Connection to remote control terminals ........................................................................... 13
13 Aux 24V DC supply ........................................................................................................ 14
14 Connection to relay contacts........................................................................................... 14
15 Connection to Accessory modules ................................................................................... 14
16 Panel operation ............................................................................................................. 15
16.1 Normal condition ................................................................................................................... 15
16.2 Fire condition ........................................................................................................................ 15
16.3 Silence/Sound Alarms ............................................................................................................ 15
16.4 Reset ................................................................................................................................... 15
16.5 Zone fault ............................................................................................................................. 15
16.6 Sounder fault ........................................................................................................................ 15
16.7 Power fault ........................................................................................................................... 15
16.8 System fault ......................................................................................................................... 15
16.9 Lamp test ............................................................................................................................. 15
16.10 Buzzer Silence ....................................................................................................................... 15
16.11 Disablements ........................................................................................................................ 16
16.12 Disable zones ........................................................................................................................ 16
16.13 Disable sounders ................................................................................................................... 16
16.14 Activate delays ...................................................................................................................... 16
16.15 Disable fault contact .............................................................................................................. 16
16.16 Test mode ............................................................................................................................ 16
17 Configuration options ..................................................................................................... 16
18 Watchdog reset switch ................................................................................................... 19
Man-1078_Sigma_CP_AUS_12
Page 3 of 29
19 Processor reset switch ................................................................................................... 20
20 Internal indications – troubleshooting .............................................................................. 20
20.1 Mains fail .............................................................................................................................. 20
20.2 Batt fail ................................................................................................................................ 20
20.3 CPU fault .............................................................................................................................. 20
20.4 Aux 24V fault ........................................................................................................................ 20
20.5 Batt low ................................................................................................................................ 20
20.6 Earth fault ............................................................................................................................ 20
20.7 Sys fuse fault ........................................................................................................................ 20
20.8 S1 fault and S2 fault .............................................................................................................. 20
20.9 Comms fault ......................................................................................................................... 21
21 AIM – Australian Interface Module .................................................................................. 21
21.1 ACF – Ancillary Control Function............................................................................................. 22
21.1.1 Outputs ................................................................................................................................................. 22
21.1.2 Configuration: ...................................................................................................................................... 22
21.1.3 Controls – only available at Level 2 ..................................................................................................... 22
21.2 Door Holder Output ............................................................................................................... 23
21.3 ASE Outputs (Alarm Signalling Equipment) ............................................................................. 23
21.4 Installation ........................................................................................................................... 23
21.5 Configuration. ....................................................................................................................... 23
22 Power supply ................................................................................................................ 24
23 Maintenance ................................................................................................................. 25
24 Zone designation label ................................................................................................... 25
25 Record of Configuration ................................................................................................. 26
Man-1078_Sigma_CP_AUS_12
Page 4 of 29
1 Warning
Sounders can only be used on detection circuits if H
ochiki YBO-R/6PA detector bases are
used.
To disable sounders on detector all lines, ensure that configuration mode 25 is not set. To disable sounders on individual detector circuits, set configuration mode 25 and disable individual circuits through the setting of C1 to C8.See Section 17Table 8.
DETECTOR BASES WILL BE DAMAGED IF THE INCORRECT MODEL IS USED ON CIRCUITS WHICH HAVE SOUNDERS ENABLED.
DAMAGE DUE TO INCORRECT CONFIGURATION WILL NOT COVERED UNDER WARRANTY.
Man-1078_Sigma_CP_AUS_12
Page 5 of 29
2 Introduction
The SIGMA CP conventional fire alarm control panel is designed to comply with AS7240-2 and AS7240-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment.
The control panel has an integral, mains powered battery charger and power supply designed in accordance with the requirements of AS7240-4.
In addition to the requirements of AS7240-2 the control panel has the following facilities:
Test condition to allow the automatic resetting of zones in alarm for testing purposes. AS7240-2 Section 11 option with requirements.
Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a premises is evacuated. AS7240-2 Section 7.11 option with requirements.
Fire alarm devices to enable an audible warning to be sounded throughout a premises upon the detection of a fire condition or the operation of a manual call point. AS7240-2 Section 7.8 option with requirements.
Voltage free relay contacts for fire and local fire which operate upon fire condition. These are to be used for local control and signalling.
3 Safety and Mounting
3.1 Safety
Suppliers of articles for use at work are required to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used.
An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’ relating to its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel in accordance with the following:
(i) Local regulations for electrical equipment in buildings
(ii) Codes of practice
(iii) Statutory requirements (iv) Any instructions specifically advised by the manufacturer
You are therefore requested to take such steps as are necessary to ensure that you make any appropriate information about this product available to anyone concerned with its use.
This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device which disconnects live and neutral simultaneously shall be incorporated in the fixed wiring.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe.
This control panel is designed for indoor use only and at temperatures between -5
0
C (+/- 3) and +500C (+/-
2) and with a maximum relative humidity of 95%.
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.
Man-1078_Sigma_CP_AUS_12
Page 6 of 29
3.2 Mounting
The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level position such that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all four mounting points.
It should be positioned in an accessible position as agreed with the end user.
Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not liable to move once fixed.
The control panel should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to the panel.
Man-1078_Sigma_CP_AUS_12
Page 7 of 29
4 Technical specification
Table 1
Electrical Specifications
Mains supply
230V AC +10%
- 15% (100 Watts maximum)
Mains supply fuse
1.6Amp (F1.6A L250V)
Replace only with similar type
Power supply rating
3 Amps total including battery charge 28V +/ 2V
Maximum ripple current
1.5 Volts
Output voltage
18.5 to 29
V DC +/- 2% Imax a
400 milliamps
Imax b
2.3 Amps
Imin 0.065A
Battery type (Yuasa NP)
Two 12 Volt sealed lead acid (7Ah maximum)
See
Table
2
for capacities
Battery charge voltage
27.6VDC nominal (temperature compensated)
See
Table
3 Battery charge current
0.7A maximum
Battery lead fuse
20mm, 3.15A glass
Replace only with the same type
Battery high impedance warning
(Rimax)
1.35 ohms
max
Low battery voltage indication
21V +/
- 2%
Low battery shut off voltage
18.5V +/
- 2%
Maximum current draw from batteries
3 Amps
With main power source disconnected
R0V output
Fused at with electronic fuse
Dedicated sounder outputs
24V Fused at 500mA with electronic fuse
1.6 Amp total load over
all circuits
Zonal sounder outputs
24V
Fused at 500mA with electronic fuse
1.6 Amp total load
over
all circuits
Fault relay contact rating
30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Fire relay contact rating
30VDC 1A Amp maximum for each
Maximum ratings not to be exceede
d Local fire relay contact rating
30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Zone quiescent current
1.6mA maximum
See
Table
4
for detector types
Terminal capacity
0.5mm
2
to 2.5mm
2
solid or stranded wire
Number of detectors per zone
> 20 Dependent on type
Number of sounders per circuit
Dependent on type and curr
ent consumption
See
Table
6
for sounder types
Detection circuit end of line
6K8 5% ½ Watt resistor
Supplied in terminals
Sounder circuit end of line
10K 5% ¼ Watt resistor
Supplied in terminals
No.
of detection circuits
(see
Table
2
for number of zones for each model)
Dependent on model
No.
of
sounder outputs
2 (plus one per zone on T models)
SIL, AL, FLT, RST inputs
Switched
-
ve, max resistance 100 Ohms
Zone normal threshold
8K ohm TO 1K ohm
Detector alarm threshold
999 ohms to 400 ohms
Call point alarm threshold
399 ohms to 100 ohms
Short circuit threshold
99 ohms to 0 ohms
Head removal condition
15.5 to 17.5 volts
Zener clamp detector base to be used
Cabling
To Australian Standards (
maximum capacitance 1uF
maximum inductance 1 millihenry)
Metal cable glands must be used
Table 2
Standby battery capacity required for fully loaded system
Panel model
24 hours
standby
48 hours standby
72 hours
standby
Standby current
Max panel alarm
current
T11080
M3 (8 Zones)
3.75Ah
5.95Ah
8.2Ah 0.093A
0.63A
Table 3
Battery charge voltage versus temperature
Temperature
0
C
Battery charge voltage
0
29.2 10 28.56
20 27.99
30 27.55
40
27.13
Man-1078_Sigma_CP_AUS_12
Page 8 of 29
Table 4
Compatible Detectors
Model Type Manufacturer Maximum Number per zone
SLV-AS OPTICAL HOCHIKI 40 DCD-A HEAT HOCHIKI 40 DCD-C HEAT HOCHIKI 35 DFJ-60B HEAT HOCHIKI 40 DFJ-90D HEAT HOCHIKI 35 DFG-60BLKJ HEAT HOCHIKI 40 DRD-AS FLAME HOCHIKI 25 SPC-AS BEAM HOCHIKI 6
Table 5
Compatible detector bases and call points
Model Type Manufacturer Comments
YBN-R/4C PLAIN BASE HOCHIKI YBO-R/4A LED BASE HOCHIKI YBO-R/6PA LED BASE HOCHIKI
MUS1A-R470SG-01 CALL POINT KAC MUS1A-R470SF-01 CALL POINT KAC
Table 6
Compatible sounders
Model Type Manufacturer Comments
ROSHNI FULLEON SQUASHNI FULLEON SQUASHNI MICRO FULLEON
Table 7
Compatible I.S. barriers
Note: To use detectors and sounders within an intrinsically safe area, the detectors and sounders must be of an intrinsically safe type and approved for use within the risk category.
Model
Type Manufac
turer
MTL5061
DETECTION ZONE GALVANIC ISOLATOR
MTL MTL778ac
SOUNDER CIRCUITS SI AND S2 ONLY
MTL
Man-1078_Sigma_CP_AUS_12
Page 9 of 29
6 Using intrinsically safe barriers
SIGMA CP control panels support the use of I.S. barriers for connecting to equipment in hazardous areas.
Only certified detectors, call points and sounders may be used in hazardous areas and these must be connected to the control panel via a compatible I.S. barrier as listed in Table 7.
Connection of the I.S. barrier changes the characteristics of the detection circuit, therefore zones that have I.S. barriers connected, must be adjusted to work with them. Programmable options C61 to C68 allow each zone to operate with I.S. barriers.
The amount of detectors and call points that can be connected to a zone is limited by the I.S. approval system diagram which should be supplied by the detector manufacturer. The power rating of the end of line resistor will be dependent upon the Zone classification rating (Gas class) this will be specified on the system diagram.
Figure 1. Detection zone wiring through an MTL5061 I.S .barrier
+ -
SOUNDER
OUTPUT
I.S .
POLARISED
SOUNDER
10K END OF LINE RESISTOR
MTL778ac
MAXIMUM OF TWO SOUNDERS PER SOUNDER CIRCUIT
I.S .
EARTH
POWER WILL DEPEND UPON I.S. ZONE CLASSIFICATION
HAZARDOUS AREASAFE AREA
+ IN+
OUT
-IN-
OUT
I.S .
POLARISED
SOUNDER
+ IN+
OUT
-IN-
OUT
Figure 2. Sounder circuit wiring through an MTL778ac I.S. barrier
+
IN
+
OUT
-
IN
-
OUT
I.S. DETECTOR
I.S . CALL POINT
MTL5061
6K8 END OF LINE RESISTOR
SAFE AREA HAZARDOUS AREA
POWER RATING WILL DEPEND UPON I.S. ZONE
CLASSIFICATION
MAXIMUM NU MBER OF DEVICES ON ZONE
SPECIFIED IN SYSTEM DI AGRAM
Man-1078_Sigma_CP_AUS_12
Page 10 of 29
7 Control panel fascia
In addition to the mandatory controls and indications required by the AS7240-2 standard, two seven­segment LED displays and MODE, SELECT and ENTER buttons are provided to allow easy entry and storage of codes to configure the control panel to suit the requirements of the installation.
Opening the fascia
The fascia of the control panel is held in place by a screw on the right hand side. Undo the screw and lift the plate from the right hand side.
Opening the fascia allows more room when mounting the cabinet and fitting cables.
Man-1078_Sigma_CP_AUS_12
Page 11 of 29
8 Connecting to the circuit board
All connections for field wiring are to a single row of terminals along the top of the circuit board. The connections for the power cables are to a pluggable terminal block which may be pulled off of the board to remove power from the PCB assembly. Remove this pluggable terminal only with Mains Power OFF. Cabling must comply with the relevant Australian Standards. The resistance of any core of any cable must not exceed 25 ohms. Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the appropriate terminals leaving only enough wire to ensure that there is no strain on the PCB. Terminals are capable of accepting wires of up to 2.5mm2.
Terminal designations
Wiring must not go across the front of the circuit board plate or between the plate and the circuit board. If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and well away from the surface of the circuit board. The space at the bottom of the enclosure is largely occupied by the standby batteries so this must be borne in mind when considering cable entries.
9 Software revision number
New features may be added to Sigma CP fire control panels from time to time and when this is done the operating software of the unit is updated. The software revision can be located on the main processor by removing the plate holding the PCB from the enclosure and turning it over. The software version will have a number such as “Sig27.hex” and it is this number which will determine which features the panel has installed and its compatibility with Sigma CP ancillary board, sounders boards, repeaters etc.
CORRECT
INCORRECT INCORRECT
SW1
SW2
SW4
SERIAL NUMBER
+
+
+
+
+
+
+
+
+
D 1008 ISSUE 06
C1
R1
R2
R
3
R
5
R
6
R7
R
8
R
9
C
3
0
C
3
1
R
1
1
R
1
2
R13
R
1
4
R
1
5
R
1
7
R
1
8
R19
R21
R51
R52
R53
R54
R55
R56
R57
R58
R60
R61
R62
R63
R64
R65 R66
R67
R69
R71
R72
R73
R74
R78
R80
R81
R85 R86
R87
R88
R90
R98
R99
R102
R103
R104
R109
R1
10
R111
R112
C2 C3 C4 C5 C7
C19
C20 C21 C22 C 23
C27
C37 C38 C39 C40
C43
C44
C55
C60 C61
R113
R114
R116
R117
C96
C33
R128
C73 C74
C75
C76
C34
C35 C 36
R130 R131 R132 R133
R134
R135
R137
R129
C42
C41
R89
R107
C81
R126
C83
C94
C95
R118
R4A R4B
R4C
R4D
R4E
R4F
R10A
R10B
R1
0C
R10D
R10E
R10F
R16A
R16B
R16C
R16D
R16E
R16F
R22A
C92
C93 C97
C98
C99
C100
C101
C102
C103
R155
R156
R157
C104
C105 R158
C106
C107
C108
C109
D1 D2 D3
D4
D9 D10
D11
D12
D13
D14
D15
D16
D22
D23
Z11
Z14
D30
F1
F2
F4
F9
F10
F11
TR1
TR2
TR3
TR9
TR26
TR19
TR24
TR28 TR25
IC4
IC5
IC10
IC1
IC2
D32 D33 D34
D35
IC6
REG1
J1
C24
C25
C65 C 66 C 67 C 68
C56
C82
D41
D20
F12
C51
RL2
RL3
RL1 RL 9
RL10
XTL1
LED3 LED4 LED5 LED6 LED7 LED17 LED35
VR1
TH1
TR23
L1
T3
REG3
FB5 FB6
FB7
FB
8
FB1
FB2
FB3
FB4
FB9
FB10
R70
R75 R76
X2X1
C45
VDR4
VDR3
VDR2
VDR1
FB20FB21
C128C127
LED8 LED11
LED15 LED12 LED10
LED16LED34LED9LED13LED14
C6
F3
R168
TR47
R167R166
Sig27.hex
Jason
SOFTWARE VERSION LABEL
Man-1078_Sigma_CP_AUS_12
Page 12 of 29
+
IN
+
OUT
-
IN
-
OUT
DETECTOR
CALL POINT
6K8 END OF LINE RESISTOR
+
IN
+
OUT
-
IN
-
OUT
DETECTOR
CALL POINT
6K8 END OF LINE RESISTOR
POLARISED
SOUNDER
IN OUT
+
IN+OUT
_ _
NOTE: SOUNDER WIRED IN
REVERSE POLARITY
USE ONLY SA-WIRE BASES
ON “T” SERIES PANELS
Figure 4. – K Series detection zone wiring
Figure 5. - T series detection zone wiring
10 Detection zone wiring
The detection zones provide a nominal 24V DC to power compatible conventional detectors and call points.
The wiring is monitored for open and short circuit fault conditions. The 6K8 end of line monitoring resistors that are factory fitted to the control panel’s terminals must be removed and placed across the last device that is wired to the zone circuit.
Wiring can be conventional using standard detector bases (K series), or by the use of special detector bases it is possible to wire the system such that detection devices and sounders are fitted to the same pair of wires. (T series)
Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit to work correctly.
Polarised sounders may also be wired across the detection zone but in reverse polarity to that shown by the zone terminals (see figure 5 below). Each zone can be configured individually as a 2-wire type zone or a non 2-wire type zone using configuration options C1 to C8.
Man-1078_Sigma_CP_AUS_12
Page 13 of 29
11 Sounder circuit wiring
All sounders must be of the polarised type. If non-polarised sounders are used the control panel will permanently show a fault condition. Sounder circuits are monitored for open and short circuit faults by placing a 10K end of line monitoring resistor across the last device on the circuit.
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit to work correctly. A maximum of 1.6 Amps is available for powering sounders with a maximum load of 0.41 Amps on any one circuit.
12 Connection to remote control terminals
Some functions of the control panel can be controlled externally from the panel if required. Operation of these inputs must be restricted by an access level 2 control as defined in AS7240-2.These are abbreviated at the terminals block as follows:
a) Remote 0V supply – R0V b) Silence Alarm – SIL c) Sound Alarm – AL d) Fault – FLT e) Reset – RST
To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch or contact and via a resistance of no greater than 100 ohms. All of the remote control inputs are non-latching.
+
-
S1
Figure 6. - Sounder circuit wiring
10K end of line
resistor
POLARISED
SOUNDER
IN OUT
+IN+
OUT
_ _
POLARISED
SOUNDER
IN OUT
+
IN+OUT
_ _
Man-1078_Sigma_CP_AUS_12
Page 14 of 29
13 Aux 24V DC supply
An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door release controllers. The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative terminal and is the same terminal that should be used to switch the remote control terminals. It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote volt­free contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another system for example to give an alert. See programming code 24. The supply is fitted with an electronic self-resetting fuse to protect the control panel’s 24V supply in the event of a wiring fault. Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times as standby time will be significantly affected by even modest standing loads. It is recommended that the Aux24V output is not used to power standing loads and not used to supply loads of greater than 300 milliamps. Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the generation of high voltage transients back to the control panels power supply. The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply should be used for these.
14 Connection to relay contacts
Volt free changeover relay contacts are provided for local control and signalling if required. These contacts are rated for switching signalling circuits only and the maximum ratings listed in Table 1should not be exceeded under any circumstances.
Fault relay
The Fault Relay is normally energised and will de-energise upon any fault condition including total loss of power.
Local fire relay
The Local Fire Relay will energise upon activation of a fire condition on any of the zones or pressing of the Sound Alarm Button on the front panel. The relay will remain activated until the alarm is silenced or the
panel is reset. This relay will not operate upon activation of the remote AL input or when a fire condition is triggered on a zone that is in test mode.
Fire relay
The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain activated until the control panel is reset. This relay will NOT operate upon activation of the remote AL input. Individual zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.
15 Connection to Accessory modules
Accessory modules include a Gas Module, Ancillary Relay Module, or an Australian Interface Module. Accessory modules connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel PCB. Up to a total of 7 Accessory modules may be connected and each has terminals for the incoming cables and outgoing cables. All except the last accessory module connected to the cable must have the jumper links J2 removed. The address of any accessory modules used within the system must have their address set using the DIP switch on the module, ensuring that no two modules of the same type share the same address. NOTE: The Australian Interface Module is fixed at Output unit address 7 and cannot be changed.
Apply power to main panel first and then all accessory modules. Turn ON the Enable Control keyswitch and set the Write Enable switch to ON then briefly press the Processor Reset button on the main panel. Wait for a few seconds and the main panel will show the addresses of the modules that were found on the display for instance “r1” indicates that a module at address 1 has been found. Turn the Write Enable switch OFF, then ON again and then press the Enter button to accept each module that has been found. When all modules have been added, set the main panel Write Enable switch to OFF. Press the Watchdog Reset switch on the main panel. All modules are now configured and the main control panel will report a fault if any module, that has been accepted, becomes faulty or goes off-line.
Man-1078_Sigma_CP_AUS_12
Page 15 of 29
16 Panel operation
16.1 Normal condition
Under normal conditions, control panels will have only the green, Power On LED lit.
16.2 Fire condition
Upon receipt of a fire condition by activation of a detector or call point, the Common Fire indicator will light and the Fire in Zone indicators will flash at around 2Hz. The Fire and Local Fire relays will also operate and signal any systems to which they are connected. Any sounders connected to the sounder circuits will operate in common, zonal or 2-stage mode as selected
by configuration options 10 to 12 (see Table 8).
16.3 Silence/Sound Alarms
The Silence/Sound alarm button can only be operated at access level two which means that the Enable Control keyswitch must be activated.
To silence the sounders, activate the Enable Control keyswitch and press the Silence/Sound Alarm button. When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state. Pressing the Silence/Sound Alarm whilst the control panel is in this silenced condition will cause the sounders to operate again. The sounders can be toggled on and off with the Silence/Sound Alarm button as required.
16.4 Reset
To reset the panel, activate the Enable Control keyswitch then press the Reset button.
16.5 Zone fault
Removal of a detector from its base or a fault on any of the zone wiring will cause the Fault LED and Zone Fault LEDs to light indicating the zone in which the fault has occurred. Zone fault is non-latching and will
automatically reset once the fault has been rectified.
16.6 Sounder fault
A fault on the wiring to sounder circuits will cause the Fault and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits. Sounder fault is non-latching and will automatically reset once the fault has been rectified.
16.7 Power fault
Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit will cause the Fault and Power Fault LEDs to light indicating an abnormality in the power supply to the control panel. Power fault is non-latching and will automatically reset once the fault has been rectified.
16.8 System fault
The System Fault LED will light if the configuration memory has not been set or has become corrupt. System fault is non-latching and will automatically reset once the configuration has been rectified.
16.9 Lamp test
All LED indicators can be tested at any time by pressing the Lamp Test button. The Enable Control keyswitch does not need to be activated to test the indicators.
16.10 Buzzer Silence
The buzzer can be silenced at any time by pressing the Alarm/Fault Warning Silence button. The Enable Control keyswitch does not need to be activated to silence the buzzer.
Man-1078_Sigma_CP_AUS_12
Page 16 of 29
16.11 Disablements
It is possible to disable parts of the system. This may be required if there are works going on in a building which may cause the fire alarm system to operate in error.
16.12 Disable zones
To disable zones, the Enable Control keyswitch should be activated and the Mode button pressed until “d” appears in the first of the two seven-segment LED displays. The Select button should then be pressed to select the number of the zone which is to be disabled in the second of the two seven-segment displays. Once the desired zone is displayed, the Enter button should be pressed to confirm the disablement. The Disable LED will light and the Zone Fault LED will light for each disabled zone.
16.13 Disable sounders
To disable sounder outputs, press the Mode button to select “db” on the seven-segment display. Pressing Enter will disable all sounders and cause the Disable and Sounder Fault LEDs to light.
16.14 Activate delays
To activate delays on zones as set in configuration options 31 to 48, press the Mode button until “Ad’ appears on the seven-segment LED display. When the Enter button is pressed any zones that are set as delayed will have their alarm outputs delayed by the time set in configuration options 00 to 09.
16.15 Disable fault contact
The fault relay can be disabled by selecting configuration option 22.
16.16 Test mode
Fire alarm systems must be tested regularly to ensure that they are functioning correctly. The Sigma CP range of panels enable the system to be tested single handed by using a test mode. When in test mode, activation of a fire alarm will be automatically reset after a few seconds to eliminate the need to return to the control panel to reset after every activation. Test mode is entered in a similar way to disablements. With the Enable Control keyswitch activated, press the Mode button until “t” appears in the first of the seven-segment displays. Then press the Select button until the required zone number appears. Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode. Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db" function (for example) toggles between sounders disabled and sounders enabled.
17 Configuration options
The Sigma CP range of control panels has many configuration options which can be set at the time of commissioning to suit the requirements of the installation. These options are normally set once and will rarely need to change. The configuration options are only available at access level 3. To access level 3, CAREFULLY slide the Write Enable switch (located behind the aperture in the panel plate) to the right position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will “pip” three times every few seconds as an indication that it is at this access level.
Man-1078_Sigma_CP_AUS_12
Page 17 of 29
Configuration options are simple to enter using the codes in Table 8below. When the control panel is at access level 3, the sub-text of the Mode and Select buttons is used to enter a number using tens (+10) and units (+1).
When the required code number is displayed, pressing the Enter button will cause the dot on the units, seven-segment display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8, C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
DOT
FLASHING
NO DOT
ZONE 1 I.S. BARRIER
OPTION SET
ZONE 1 I.S. BARRIER
OPTION NOT SET
Figure 9
– Example display showing option set and not set.
Man-1078_Sigma_CP_AUS_12
Page 18 of 29
Table 8
Configuration Codes
CODE
FUNCTION
COMMENTS
00
SOUNDER DELAY TIME = 30 SECONDS
Sets the time delay before sounders
operate in combination with
configuration codes 31 to 48 and access level 2 function AD.
01 SOUNDER DELAY TIME = 1 MINUTE
02
SOUNDER DELAY TIME = 2 MINUTES
03
SOUNDER DELAY TIME = 3 MINUTES
04
SOUNDER DELAY TIME = 4 MINUTES
05
SOUNDER DELAY TIME
= 5 MINUTES
06
SOUNDER DELAY TIME = 6 MINUTES
07
SOUNDER DELAY TIME = 7 MINUTES
08
SOUNDER DELAY TIME = 8 MINUTES
09
SOUNDER DELAY TIME = 9 MINUTES
10
COMMON ALARM MODE (default)
All sounders operate upon any fire condition
11 TWO-STAGE ALARM
MODE
Continuous sounders in activated zone, pulsing elsewhere
12
ZONED ALARM MODE
Only sounders connected to zone in alarm operate
21* DISABLE FIRE BUZZER
Buzzer will not operate on fire condition
22* DISABLE FAULT OUTPUT
Fault relay will not
operate except upon total power failure
23
DISABLE EARTH FAULT MONITORING
Connection of fire alarm wiring will not announce a fault
24
PULSED REMOTE CONTROL OUTPUT
Aux 24V supply pulses 1 sec on/1 sec off
25
ENABLE SOUNDERS ON DETECTION CIRCUITS
Set as
default if panel is two wire “T” series (detectors and call
points on same cables)
26 DISABLE FIRE OUTPUT
Fire relay will not operate upon any alarm
27
REMOVE AUX 24 UPON PANEL RESET
DO NOT SET
24V supply switches off for about 5 seconds when panel is
reset 28 I
NDICATE CALL POINT ACTIVATION
Activation of a call point
with a 270R resistance fitted
is
indicated by a flashing zone indicator and “Pu” on the 7 segment display. Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display.
29 DO NOT RE
-
SOUND ALARMS FROM ANOTHER ZONE
Silenced sounders will not re
-
sound upon further zone
activations
31
ZONE 1 ALARM FROM DETECTOR DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only. Note: Access level 2 function Ad must be set for this to take effect.
32 ZONE 2 ALARM FROM DETECTOR DELAYED
33 ZONE 3 ALARM FROM DETECTOR DELAYED
34 ZONE 4 ALARM FROM DETECTOR DELAYED
35 ZONE 5 ALARM FROM DETECTOR
DELAYED
36 ZONE 6 ALARM FROM DETECTOR DELAYED
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED
41
ZONE 1 ALARM FROM CALL POINT DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only. Note access level 2 function Ad must be set for this to take effect.
42 ZONE 2 ALARM FROM CALL POINT DELAYED
43 ZONE 3 ALARM FROM CALL POINT DELAYED
44 ZONE 4 ALARM FROM CALL POINT DELAYED
45 ZONE 5 ALARM FROM CALL
POINT DELAYED
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED
51
COINCIDENCE ZONE 1
Zone contributes to ancillary board coincidence O/P
.
Any
number of zones can be selected to contribute.
52 COINCIDENCE ZONE 2
53
COINCIDENCE ZONE 3
54
COINCIDENCE ZONE 4
55
COINCIDENCE ZONE 5
56
COINCIDENCE ZONE 6
57
COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8
61 CONFIGURE Z1 FOR I.S BARRIER
Detection threshold changed
for use with IS barrier
62
CONFIGURE Z2 FOR I.S BARRIER
63
CONFIGURE Z3 FOR I.S BARRIER
64
CONFIGURE Z4 FOR I.S BARRIER
65 CONFIGURE Z5 FOR I.S BARRIER
66
CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68
CONFIGURE Z8 FOR I.S
BARRIER
Man-1078_Sigma_CP_AUS_12
Page 19 of 29
CODE
FUNCTION
COMMENTS
71* ZONE 1 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of
the zone
so that the control
panel can be used on older systems that had no short-circuit monitoring.
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM
77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM
81* ZONE 1 NON
-
LATCHING
Renders the zone self
-
resetting so
that it can be used to receive
signals from other systems and will reset when the input is removed. Note: It can take up to 20 seconds for zone to reset itself when sounders are operating
82* ZONE 2 NON
-
LATCHING
83* ZONE 3 NON
-
LATCHING
84* ZONE 4 NON
-
LATCHING
85* ZONE 5 NON
-
LATCHING
86* ZONE 6 NON
-
LATCHING
87* ZONE 7 NON
-
LATCHING
88* ZONE 8 NON
-
LATCHING
91 ZONE 1 DOES NOT SOUND ALARMS
Prevents the zone from operating the
two common sounder
outputs.
92 ZONE 2 DOES NOT SOUND ALARMS
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT
SOUND ALARMS
A1* ZONE 1 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds
continuously before
an alarm is generated.
A2* ZONE 2 ANY ALARM DELAYED
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM
DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED
C1 ZONE 1 SOUNDERS INHIBITED
Enables individual zones to be configured not to operate zonal
sounders. On 2 wire “T” series panels this enables individual zones to be configured for use with conventional (non 2-wire) detector bases.
C2 ZONE 2 SOUNDERS INHIBITED
C3 ZONE 3 SOUNDERS INHIBITED
C4 ZONE 4 SOUNDERS INHIBITED
C5 ZONE 5 SOUNDERS INHIBITED
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE
7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED
E1* ZONE 1 WILL NOT OPER
ATE FIRE RELAY
Enables individual zones to be selected to not operate the fire
relay. This is sometimes combined with the non-latching function to prevent ring around on interconnected panels.
E2* ZONE 2 WILL NOT OPERATE FIRE RELAY
E3* ZONE 3 WILL NOT OPERATE FIRE RELAY
E4* ZONE 4 WILL NOT OPERATE FIRE RELAY
E5* ZONE 5 WILL NOT OPERATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERATE FIRE RELAY
E7* ZONE 7 WILL NOT
OPERATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERATE FIRE RELAY
NOTE: Setting the options marked with asterisks does not comply with AS7240-2
Once the required configuration options have been set, the Write Enable switch must be returned to its normal position to the left. The General Fault indicator will remain lit if the Write Enable switch is not turned OFF.
18 Watchdog reset switch
If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate these events. If a watchdog event occurs, the control panel will show the Fault and System Faultless on the front panel, the CPU Faulted inside the panel.
Man-1078_Sigma_CP_AUS_12
Page 20 of 29
This fault can only be cleared by pressing the Watchdog Reset button on the PCB inside the control panel. The control panel buzzer cannot be silenced and will continue to sound until the watchdog activation is reset.
19 Processor reset switch
Once started, the microprocessor controlling the panel should continue to run continuously without interruption. If the microprocessor fails to run correctly it can be reset by pressing the Processor Reset button on the PCB inside the control panel. This should not normally be necessary but should be done as a matter of course if the system is behaving abnormally. The system should resume normal operation within a couple of seconds of pressing the Processor Reset button. Note: A Watchdog Reset should always be performed following a Processor Reset.
20 Internal indications – troubleshooting
To assist in identifying fault conditions which are not detailed on the front of the control panel, a number of internal indicators are visible with the front cover removed as follows:
20.1 Mains fail
Indicates that the 230V AC supply is not present and the system is running on standby batteries. If there is not a power cut, check the panels mains fuse.
20.2 Batt fail
Indicates that the standby battery has become disconnected, or that the charging circuit of the control panel has a high resistance or has failed. Check that both batteries are connected and linked together. Test the battery. Disconnect the battery and ensure that 28 Volts can be measured on battery charger leads.
20.3 CPU fault
Indicates that the central processor unit has failed to correctly execute code and has been re-started by the system watchdog. The Watchdog Reset switch must be pressed to clear the CPU Fault condition. If system does not return to normal after the Watchdog Reset switch is pressed then the panel is probably damaged and the circuit board needs replacing.
20.4 Aux 24V fault
The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire alarm ancillary equipment. This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded. The fuse is a self-resetting type and the supply will resume when the fault condition is removed.
20.5 Batt low
Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the minimum battery voltage).
20.6 Earth fault
Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present on.
20.7 Sys fuse fault
Indicates that the total power rating of the power supply has been exceeded and that the system fuse has come into operation. Remove and review all loads and re-connect one at a time until over rated circuit trips fuse to identify troublesome circuit.
20.8 S1 fault and S2 fault
Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors. Check sounder circuit wiring.
Man-1078_Sigma_CP_AUS_12
Page 21 of 29
20.9 Comms fault
Indicates that communication has been lost with a repeater panel or ancillary board. Check for comms fault at all repeaters and ancillary boards to identify the source of the problem.
21 AIM – Australian Interface Module
The AIM module is optional on the Sigma range of panels and can be utilised to provide:
ACF Output Door Holder Output ASE Outputs
Only one AIM is permitted on each control panel and has a fixed addressed at “o7”, output unit 7.
Man-1078_Sigma_CP_AUS_12
Page 22 of 29
21.1 ACF – Ancillary Control Function
21.1.1 Outputs
The ACF has a 24V DC monitored output suitable for operating a remote, polarised and suppressed relay. Monitoring is via an end of line resistor. This output is designated ACF O/P +/-
A clean contact relay rated at 30VDC 1Amp follows the monitored output.
The ACF outputs are activated by a non-silenceable fire signal from the Sigma control panel section. A red LED indicator is lit when the output is active.
A fault on the ACF outputs is signalled at the Sigma panels as a General fault and on the AIM as ACF fault.
21.1.2 Configuration:
The ACF can be configured as latching by setting the LATCH dipswitch to the On position. The ACF can be configured as failsafe (Normally Energised) by setting the FAIL S. dipswitch to the ON position.
21.1.3 Controls – only available at Level 2
When the ACF is set to “latching” the Reset switch on the AIM module, in order to reset the ACF, firstly, the Alarm must be reset, and then the ACF can be reset using the Reset switch on the AIM.
When the ACF is set to “non-latching” the ACF output is deactivated when the alarm is reset or disabled.
Man-1078_Sigma_CP_AUS_12
Page 23 of 29
The Isolate switch on the AIM module allows the ACF output to be disabled and not operate on an alarm condition. A yellow ACF Isolated LED indicates when the ACF is isolated, and signals a General Disablement to the Sigma control panel section.
21.2 Door Holder Output
The door holder circuit allows magnetic fire doors to be automatically closed in the event of a fire, thus limiting smoke and fire egress in an emergency situation. Four terminals are provided:
DH 24V In A 24V supply to power the magnetic door holders. Door Holders The 24V from the “DH 24V In” circuit appears at this output under
“Normal” condition. When an alarm occurs, power is disconnected from the “Door Holder” output.
The maximum output of the Door Holder circuit must be less than 1A.
The status of the door holder output follows that of the ACF output as described in section 21.1 and is isolated via the ACF Isolate facility. The only exception is when the DOOR D. dipswitch is ON, the Door Holder Output activates after a 30 seconds delay.
21.3 ASE Outputs (Alarm Signalling Equipment)
Clean contact relay outputs, rated at 30VDC 1Amp, are provided to facilitate connection of the Sigma fire panel to a variety of ASE depending on the installation. It is the responsibility of the installer to ensure that the ASE being installed is compatible with the local fire station to which it is being connected.
ALARM normally de-energisedactivates on a non-disabled Alarm FAULT normally de-energisedactivates on a non-disabled Fault ISOLATED normally de-energisedactivates on a non-disabled Disable POWER FLT normally energised, de-activates when there is an abnormality with the power
supply.
COINC. normally de-energised activates on multiple alarms. This output will activate when
an alarm occurs any of the zones specified as being coincident zones. See options 51 to 58 in Section 0.
ENABLE normally de-energised activates when the Enable Control keyswitch is activated.
i.e. The panel enters the Level 2 state.
ACF O/P this output follows the state of the ACF monitored output.
21.4 Installation
See Section 15 for full installation instructions.
21.5 Configuration.
The AIM only has 3 configurable parameters which are set via dip-switches.
LATCH sets the ACF output to latching FAIL S. sets the ACF output to normally energised. DOOR D. sets the Door Holder Output to trip 30 seconds after the ACF output activates.
Man-1078_Sigma_CP_AUS_12
Page 24 of 29
22 Power supply
The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the fused terminal block labelled “230V”. The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar type. The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum
0.7A for battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse rated at 4 Amps. The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at least 50mm. Mains wiring should include an earth conductor which is securely bonded to the building earth and should enter the enclosure as close as possible to the mains terminal block. Mains wires should be kept very short inside the enclosure and secured together close to the mains terminal block with a cable tie. The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see Table 2 for battery size required for each model). The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps. Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit which must only be replaced with one of the same type. It is most important that the polarity of the batteries is carefully observed when connecting.
When the batteries are discharged to a level at which a low battery indication is given, the Batt Fail indicator will also be lit.
WRONGLY CONNECTED BATTERIES COULD CAUSE DAMAGE TO THE CONTROL PANEL.
Figure 9 – Mains and battery connections
N N
L L
E
+ - + -
GREY LINK
BLACK BATTERY LEAD TO
-
TERMINAL
RED BATTERY
LEAD TO
+
TERMINAL
MAINS
TERMINAL
KEEP MAINS WIRES AS SHORT AS POSSIBLE
AND SECURE ALL THREE WIRES CLOSE TO
THE TERMINAL BLOCK WITH A CABLE TIE
Man-1078_Sigma_CP_AUS_12
Page 25 of 29
23 Maintenance
Sigma CP control panels do not require any specific maintenance but should the control panel become dirty it can be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or solvents should not be used to clean the panel and care must be taken that water does not enter the enclosure.
The control panel contains sealed lead acid batteries to provide standby power in the event of a mains failure. These batteries have a life expectancy of around 2 years. It is recommended that these batteries be tested in accordance with the battery manufacturer’s recommendations annually to determine their suitability for continued standby applications.
Routine testing of the fire alarm system in accordance with local standards will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately.
Should the control panel become faulty the complete electronic assembly can be replaced.
To do this, any configured options should be noted then both mains and battery power should be removed before the work is started. The field wiring should be carefully labelled and removed from the terminals. The PCB can now be taken out of the panel by removing the screw and hinge pins holding the plate in position.
Fitting the new PCB is the reverse of the procedure for removing the board.
24 Zone designation label
All Sigma CP control panels are supplied with a zone designation label onto which zone designations can be written. This enables each zone to be given a text description allowing easier identification of any zones showing an abnormal condition.
Man-1078_Sigma_CP_AUS_12
Page 26 of 29
25 Record of Configuration
Use the Table below to record the configuration codes that have been set on the control panel for future reference. Place a tick in the grey band for any configuration options that are set. It is recommended that a copy of this Table is left with the control panel under the supervision of the person responsible for the fire detection system.
CODE
FUNCTION
COMMENTS
SET 00 SOUNDER DELAY TIME = 30 SECONDS
Sets the time delay before sounders operate in combination with
configuration codes 31 to 48 and access level 2 function AD.
01
SOUNDER DELAY TIME = 1 MINUTE
02 SOUNDER DELAY TIME = 2
MINUTES
03 SOUNDER DELAY TIME = 3 MINUTES
04 SOUNDER DELAY TIME = 4 MINUTES
05 SOUNDER DELAY TIME = 5 MINUTES
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME =
9 MINUTES
10 COMMON ALARM MODE
All sounders operate upon any fire condition
11 TWO-STAGE ALARM MODE
Continuous sounders in activated zone, pulsing elsewhere
12 ZONED ALARM MODE
Only sounders connected to zone in alarm operate
21* DISABLE FIRE
BUZZER
Buzzer will not operate on fire condition
22* DISABLE FAULT OUTPUT
Fault relay will not operate except upon total power failure
23 DISABLE EARTH FAULT MONITORING
Connection of fire alarm wiring will not announce a fault
24 PULSED REMOTE
CONTROL OUTPUT
Aux 24V supply pulses 1 sec on/1 sec off
25 ENABLE SOUNDERS ON DETECTION CIRCUITS
Set as default if panel is two wire “T” series (detectors and call
points on same cables)
26
DISABLE FIRE OUTPUT
Fire relay will not operate upon any alarm
27 REMOVE AUX 24 UPON PANEL RESET
24V supply switches off for about 5 seconds when panel is reset
28 INDICATE CALL POINT ACTIVATION
Activation of a call point with a 270R resistance fitted is indicated
by a flashing zone indicator and “Pu” on the 7 segment display. Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display
29 DO NOT RE
-
SOUND ALARMS FROM ANOTHER
ZONE
Silenced sounders will not re
-
sound upon further zone activations
31 ZONE 1 ALARM
FROM DETECTOR DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only. Note access level 2 function Ad must be set for this to take effect.
32
ZONE 2 ALARM FROM DETECTOR DELAYED
33
ZONE 3
ALARM FROM DETECTOR DELAYED
34 ZONE 4 ALARM FROM DETECTOR DELAYED
35
ZONE 5 ALARM FROM DETECTOR DELAYED
36
ZONE 6 ALARM FROM DETECTOR DELAYED
37
ZONE 7 ALARM FROM DETECTOR DELAYED
38
ZONE 8 ALARM FROM DETECTOR DELAYED
41
ZONE 1 ALARM FROM
CALL POINT DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only. Note access level 2 function Ad must be set for this to take effect.
42
ZONE 2 ALARM FROM CALL POINT DELAYED
43
ZONE 3
ALARM FROM CALL POINT DELAYED
44
ZONE 4 ALARM FROM CALL POINT DELAYED
45
ZONE 5 ALARM FROM CALL POINT DELAYED
46
ZONE 6 ALARM FROM CALL POINT DELAYED
47
ZONE 7 ALARM FROM CALL POINT DELAYED
48
ZONE 8 ALARM FROM CALL POINT DELAYED
51
COINCIDENCE ZONE 1
Zone contributes to ancillary board coincidence O/P
.
Any number
of zones can be selected to contribute.
52
COINCIDENCE ZONE 2
53 COINCIDENCE ZONE 3
54 COINCIDENCE ZONE 4
55 COINCIDENCE ZONE 5
56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8
61 CONFIGURE Z1 FOR I.S BARRIER
Detection threshold changed for use with IS barrier
62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER
65 CONFIGURE Z5
FOR I.S BARRIER
66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER
Man-1078_Sigma_CP_AUS_12
Page 27 of 29
CODE
FUNCTION
COMMENTS
SET 71* ZONE 1 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of
the zone
so that the control
panel can be used on older systems that had no short-circuit monitoring.
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM
75* ZONE 5 SHORT CIRCUIT
INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM
77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM
81* ZONE 1 NON
-
LATCHING
Renders the zone self
-
resetting so
that it
can be used to receive
signals from other systems and will reset when the input is removed. Note: It can take up to 20 seconds for zone to reset itself when sounders are operating
82* ZONE 2 NON
-
LATCHING
83* ZONE 3 NON
-
LATCHING
84* ZONE 4
NON-LATCHING
85* ZONE 5 NON
-
LATCHING
86* ZONE 6 NON
-
LATCHING
87* ZONE 7 NON
-
LATCHING
88* ZONE 8 NON
-
LATCHING
91 ZONE 1 DOES NOT SOUND ALARMS
Prevents the zone from operating the two common sounder
outputs
92
ZONE 2 DOES NOT SOUND
ALARMS
93
ZONE 3 DOES NOT SOUND ALARMS
94
ZONE 4 DOES NOT SOUND ALARMS
95
ZONE 5 DOES NOT SOUND ALARMS
96
ZONE 6 DOES NOT SOUND ALARMS
97
ZONE 7 DOES NOT SOUND ALARMS
98
ZONE 8 DOES NOT SOUND ALARMS
99 A1* ZONE 1 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds
continuously before
an alarm is generated.
A2* ZONE 2 ANY ALARM DELAYED
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED
C1 ZONE 1 SOUNDERS INHIBITED
Enables individual zones to be configured not to operate zonal
sounders. On 2 wire “T” series panels this enables individual zones to be configured for use with conventional (non-savwire) detector bases.
C2
ZONE 2 SOUNDERS INHIBITED
C3
ZONE 3 SOUNDERS INHIBITED
C4 ZONE 4 SOUNDERS INHIBITED
C5
ZONE 5 SOUNDERS INHIBITED
C6
ZONE 6 SOUNDERS INHIBITED
C7
ZONE 7 SOUNDERS INHIBITED
C8
ZONE 8
SOUNDERS INHIBITED
E1* ZONE 1 WILL NOT OPER
ATE FIRE RELAY
Enables individual zones to be selected to not operate the fire
relay. This is sometimes combined with the non-latching function to prevent ring around on interconnected panels.
E2* ZONE 2 WILL NOT OPERATE FIRE RELAY
E3* ZONE 3 WILL NOT OPERATE FIRE RELAY
E4* ZONE 4 WILL NOT OPERATE FIRE RELAY
E5* ZONE 5 WILL NOT OPERATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERATE FIRE RELAY
NOTE: Setting the options marked with asterisks does not comply with AS7240-2
Man-1078_Sigma_CP_AUS_12
Page 28 of 29
This page intentionally left blank.
Man-1078_Sigma_CP_AUS_12
Page 29 of 29
Loading...